ML090090144

From kanterella
Jump to navigation Jump to search
PINGP Lr -
ML090090144
Person / Time
Site: Prairie Island  
Issue date: 10/22/2008
From:
Office of Nuclear Reactor Regulation
To:
References
Download: ML090090144 (6)


Text

1 PrairieIslandNPEm Resource From:

Richard Plasse Sent:

Wednesday, October 22, 2008 1:20 PM To:

Eckholt, Gene F.

Attachments:

PINGP_LRA_FP_RAI_Rev1.doc draft RAIs

Hearing Identifier:

Prairie_Island_NonPublic Email Number:

272 Mail Envelope Properties (Richard.Plasse@nrc.gov20081022131900)

Subject:

Sent Date:

10/22/2008 1:19:35 PM Received Date:

10/22/2008 1:19:00 PM From:

Richard Plasse Created By:

Richard.Plasse@nrc.gov Recipients:

"Eckholt, Gene F." <Gene.Eckholt@xenuclear.com>

Tracking Status: None Post Office:

Files Size Date & Time MESSAGE 12 10/22/2008 1:19:00 PM PINGP_LRA_FP_RAI_Rev1.doc 79866 Options Priority:

Standard Return Notification:

No Reply Requested:

No Sensitivity:

Normal Expiration Date:

Recipients Received:

October XX, 2008 MEMORANDUM TO: Rani L. Franovich, Chief Projects Branch 2 Division of License Renewal Office of Nuclear Reactor Regulation FROM:

Alexander R. Klein, Chief Fire Protection Branch Division of Risk Assessment Office of Nuclear Reactor Regulation

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION REGARDING THE LICENSE RENEWAL APPLICATION - PRAIRIE ISLAND NUCLEAR GENERATING PLANT UNITS 1 AND 2 - FIRE PROTECTION (TAC NOS. MD8513 AND MD8514)

The Fire Protection Branch reviewed Section 2.3.3.9, Fire Protection System, of the license renewal application submitted by the Nuclear Management Company, LLC, for Prairie Island Nuclear Generating Plant, Units 1 and 2. The staff reviewed the application, methodology, and systems that are within the scope of license renewal in accordance with Title 10 of the Code of Federal Regulations (CFR) 54.4(a) (10 CFR 54.4(a)), and subject to an aging management review in accordance with 10 CFR 54.21(a)(1). As a result of our review, enclosed is a request for additional information (RAI).

Our effort on TAC Nos. MD8513 and MD8514 are being continued. If you have any questions regarding this RAI, please contact us.

Docket Nos.: 50-282 and 50-306 Facility Operating License: DPR-42 and DPR-60

Enclosure:

As stated CONTACT: Naeem Iqbal, DRA/NRR (301) 415-3346

ML NRR-106 OFFICE AFPB:DRA:NRR BC: AFPB:DRA:NRR NAME NIqbal AKlein DATE 10/ /08 10/ /08 REQUEST FOR ADDITIONAL INFORMATION LICENSE RENEWAL APPLICATION PRAIRIE ISLAND NUCLEAR GENERATING PLANT UNITS 1 AND 2 DOCKET NOS.: 50-282 AND 50-306 TAC NOS.: MD8513 AND MD8514 Office of Nuclear Reactor Regulation Division of Risk Assessment Fire Protection Branch For Prairie Island Nuclear Generating Plant, Units 1 and 2 (PINGP), the staff reviewed the license renewal application (LRA); updated final safety analysis report (UFSAR), Section 10.3.1, Plant Fire Protection Program; and the following fire protection current licensing basis (CLB) documents listed in the PINGP Units 1 and 2 Operating License Condition 2.C.4:

Safety Evaluation Reports dated February 14, 1978, September 6, 1979, April 21, 1980,December 29, 1980, July 28, 1981, October 27, 1989, and October 6, 1995.

The staff has identified that fire protection systems and components discussed in the following sections have been excluded from the scope of license renewal and an aging management review (AMR). These systems and components were not included in the license renewal boundaries and appear to have fire protection intended functions required for compliance with Title 10 of the Code of Federal Regulations (CFR) 50.48, Fire protection, as stated in 10 CFR 54.4. Therefore, in order to complete our review, the staff requires responses to the following requests for additional information (RAIs):

RAI 2.3.3.9-1 Section 4.3.1.5 of the ??? for PINGP Units 1 and 2, dated September 6, 1979, discusses various types of wet pipe, deluge, and pre-action dry pipe sprinkler systems provided in the plant areas for fire suppression activities. The sprinkler systems in various areas are:

Fire Sprinkler System Area Wet Pipe Automatic Sprinkler Systems Turbine Building - Turbine Lube Oil and Control Oil Piping Areas Air Compressor and Auxiliary Feedwater Pump Rooms Exit Stairwells Records Storage Area Decontamination Area Water Treatment Area Warehouse Hot Lab Area Deluge Systems Main Auxiliary and Startup Transformers Turbine Generators Bearings Turbine Seal Oil Unit Turbine Lube Oil Reservoir Oil Storage Room Charcoal Filter - Auxiliary Building Special Exhaust

Filter and the Shield Building Exhaust Filters Pre-action Dry Pipe Sprinkler Systems Containment Cable Penetration Areas Screen House Pump Area (Both Levels) Including the Diesel Cooling Water Pumps and the Diesel Driven Fire Pump The staff requests that the applicant verify whether the above sprinkler systems installed in various areas of the plant are in the scope of license renewal in accordance with 10 CFR 54.4(a) and subject to an AMR in accordance with 10 CFR 54.21(a)(1). If they are excluded from the scope of license renewal and not subject to an AMR, the staff requests that the applicant provide justification for the exclusion.

RAI 2.3.3.9-2 LRA Tables 2.3.3-9 and 3.3.2-9 exclude several types of fire protection components that appear on the LRA drawings as within the scope of license renewal or discussed in PINGP CLB documents. These components are listed below:

hose connections interior fire hose stations pipe supports couplings dikes for oil spill confinement floor drains and curbs for fire-fighting water backflow prevention devices trash grids and traveling screens flame retardant coating for cables fire retardant intumescent coating for polyurethane foam insulation turbine building smoke removal system components air compressors for safe-shutdown operations For each, determine whether the component should be included in Tables 2.3.3-9 and 3.3.2-9 as component types subject to an AMR, and if not, justify the exclusion.