ML083170807

From kanterella
Jump to navigation Jump to search
License Amendment Request for Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change (TSC) Number 2007-09, Supplement 7
ML083170807
Person / Time
Site: Oconee  
Issue date: 10/16/2008
From: Baxter D
Duke Energy Carolinas
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
TSC 2007-09, Suppl 7
Download: ML083170807 (27)


Text

Duke DAVE BAXTER Vice President M Energy.

Oconee Nuclear Station Duke Energy Corporation ON01 VP/7800 Rochester Highway Seneca, SC 29672 864-885-4460 864-885-4208 fax dabaxter@dukeenergy. corn October 16, 2008 U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Attention: Document Control Desk

Subject:

Duke Energy Carolinas, LLC Oconee Nuclear Station, Units 1, 2, and 3 Docket Numbers 50-269, 50-270, and 50-287 License Amendment Request for Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change (TSC) Number 2007-09, Supplement 7 On January 31, 2008, Duke Energy Carolinas, LLC (Duke) submitted a License Amendment Request (LAR) to address replacement of the existing Oconee Nuclear Station (ONS) analog based Reactor Protective System (RPS) and Engineered Safeguards Protective System (ESPS) with a digital computer based RPS/ESPS. Duke docketed most of the technical documents listed in Table 1-2 of the LAR in Supplement 1 dated April 3, 2008.

In some cases where the document's date of availability was not known, Duke indicated the date would be determined. During subsequent discussions with NRC Staff, Duke*

agreed to provide factory acceptance test (FAT) procedures (Table 1-2, Item 16.a) by-electronic mail as they become available and then docket within two weeks. The FAT procedures Duke provided by electronic mail on October 13, 2008 and October 14, 2008, are provided in Enclosure 3. identifies test cases that address software integration testing requirements for the RPS Functional FAT. These test cases address testing requirements that could be performed using AREVA NP's simulation validation tool.

The documents included in Enclosure 3 are classified by AREVA NP as proprietary. The appropriate affidavits by AREVA NP are provided in Enclosure 1 in accordance with the provisions of 10 CFR 2.390. to this letter contains proprietary'*.ii nformr-atiOn.

Withhold from public disclosure under.'10 CFR M2 390'--,.

Upon removal of Enclosure 3, this letter is" 666ontroled.-

www. duke-energy. com

U. S. Nuclear Regulatory Commission October 16, 2008 Page 2 If there are any questions regarding this submittal, please contact Boyd Shingleton at (864) 885-4716.

Very truly yours, D)ayBaxter, Vice President Oco ee Nuclear Station

Enclosures:

1.

2.

3.

AREVA NP Affidavits Test Case Identification AREVA NP Documents - Proprietary to this letter contains proprietary information.

Withhold from public disclosure under 10 CFR 2.390.

Upon removal of Enclosure 3, this letter is uncontrolled.

U. S. Nuclear Regulatory Commission October 16, 2008 Page 3 cc:

w/o attachments Mr. L. N. Olshan, Project Manager Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop 0-14 H25 Washington, D. C. 20555 L. A. Reyes, Regional Administrator U. S. Nuclear Regulatory Commission - Region II Atlanta Federal Center 61 Forsyth St., SW, Suite 23T85 Atlanta, Georgia 30303 Mr. G. A. Hutto Senior Resident Inspector Oconee Nuclear Station S. E. Jenkins, Manager Infectious and Radioactive Waste Management Section 2600 Bull Street Columbia, SC 29201 to this letter contains proprietary information.

Withhold from public disclosure under 10 CFR 2.390.

Upon removal of Enclosure 3, this letter is uncontrolled.

U. S. Nuclear Regulatory Commission October 16, 2008 Page 4 Dave Baxter affirms that he is the person who subscribed his name to the foregoing statement, and that all the matters and facts set forth herein are true and correct to the best of his knowledge.

Dave Baxte, Vice President Oconee Nuclear Site Subscribed and sworn to me:

ýDate 14J Notary Public My Commission Expires:

6-1/2---

Date SEAL I to this letter contains proprietary information.

Withhold from public disclosure under 10 CFR 2.390.

Upon removal of Enclosure 3, this letter is uncontrolled.

License Amendment Request No. 2007-09, Supplement 7 October 16, 2008 AREVA NP Affidavit for Enclosure 3 Documents

AFFIDAVI T COMMONWEALTH OF VIRGINIA

) -

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

AREVA NP document 63-9080101-001, FAT Procedure for Diverse High Pressure Injection Actuation System Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this_____

day of 2

, 2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP' Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

AREVA NP document 63-9076528-000, Cyber Security Factory Acceptance Test Procedure Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this__

day of 2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA SHERRY L. MC:FADDEN Noto'y Public Commonwealth of Virginlo 7079129 E

My Commission Expires Oct 31, 20O10

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

AREVA NP document 62-9014399-000, Cyber Security Factory Acceptance Test Specification Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this-1 day of A ~m 2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA SHERRY L. MCFADEN Notary Public Commonwealth of Virginla 7079129 E

O MyCommission Expires Oct 31, 2010

-L--

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

AREVA NP document 63-9018592-000, Oconee Nuclear Station, Unit 1 RPS/ESFAS Controls Upgrade Startup/Shutdown Acceptance Test Procedure Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this 2/6 day of

,2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to

)

ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

AREVA NP document 62-9081518-000, Oconee Nuclear Station, Unit 1 RPS/ESFAS Controls Upgrade FAT Specification for Normal Startup and Shutdown Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

/

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this day of St2ý ý

./

2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, (50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

0 AREVA NP document 63-9009706-000, RPS Functional Test Procedure Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this_

day of

,2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA SHERRY '. MCFADEN Notary Public Commonwealth of Virginia 7079129 My Commission Expires Oct 31, 2010

AFFIDAVIT COMMONWEALTH OF VIRGINIA

)

ss.

CITY OF LYNCHBURG

1.

My name is Mark J. Burzynski. I am Manager, Product Licensing, for AREVA NP Inc. and as such I am authorized to execute this Affidavit.

2.

I am familiar with the criteria applied by AREVA NP to determine whether certain AREVA NP information is proprietary. I am familiar with the policies established by AREVA NP to ensure the proper application of these criteria.

3.

I am familiar with the AREVA NP information provided to the NRC in support of a Duke Power Company LLC License Amendment Request for Oconee Nuclear Station, Units 1, 2, and 3 (Docket Numbers 50-269, 50-270, and 50-287) entitled Reactor Protective System/Engineered Safeguards Protective System Digital Upgrade, Technical Specification Change Number 2007-09. The following AREVA NP document is provided and referred to herein as the "Document."

0 AREVA NP document 62-9066984-000, RPS Functional Test Specification Information contained in this Document has been classified by AREVA NP as proprietary in accordance with the policies established by AREVA NP for the control and protection of proprietary and confidential information.

4.

This Document contains information of a proprietary and confidential nature and is of the type customarily held in confidence by AREVA NP and not made available to the public.

Based on my experience, I am aware that other companies regard information of the kind contained in this Document as proprietary and confidential.

5.

This Document has been made available to the U S. Nuclear Regulatory Commission in confidence with the request that the information contained in this Document be withheld from public disclosure. The request for withholding of proprietary information is made in accordance with 10 CFR 2.390. The information for which withholding from disclosure is requested qualifies under 10 CFR 2.390(a)(4) "Trade secrets and commercial or financial information".

6.

The following criteria are customarily applied by AREVA NP to determine whether information should be classified as proprietary:

(a)

The information reveals details of AREVA NP's research and development plans and programs or their results.

(b)

Use of the information by a competitor would permit the competitor to significantly reduce its expenditures, in time or resources, to design, produce, or market a similar product or service.

(c)

The information includes test data or analytical techniques concerning a process, methodology, or component, the application of which results in a competitive advantage for AREVA NP.

(d)

The information reveals certain distinguishing aspects of a process, methodology, or component, the exclusive use of which provides a competitive advantage for AREVA NP in product optimization or marketability.

(e)

The information is vital to a competitive advantage held by AREVA NP, would be helpful to competitors to AREVA NP, and would likely cause substantial harm to the competitive position of AREVA NP.

The information in this Document is considered proprietary for the reasons set forth in paragraphs 6(b), 6(c) and 6(d) above.

7.

In accordance with AREVA NP's policies governing the protection and control of information, proprietary information contained in this Document has been made available, on a limited basis, to others outside AREVA NP only as required and under suitable agreement providing for nondisclosure and limited use of the information.

8.

AREVA NP policy requires that proprietary information be kept in a secured file or area and distributed on a need-to-know basis.

9.

The foregoing statements are true and correct to the best of my knowledge, information, and belief.

SUBSCRIBED before me on this_____

day of Z, 2008.

NOTARY PUBLIC, COMMONWEALTH OF VIRGINIA SHERRY L. MCFADEN Notary Public Commonwealth of Virginia My Commssio E

Oc Mycommission Expires Oct 31, 2010[

F r-Yý--

License Amendment Request No. 2007-09, Supplement 7 October 16, 2008 The following test cases address Oconee application software integration testing requirements that could be performed during the implementation phase using AREVA NP's simulation validation tool. The specific test cases are described in AREVA NP document 62-9066984-000, Oconee Nuclear Station, Unit 1 RPS/ESFAS Controls Upgrade RPS Factory Acceptance Test Functional Test Specification.

RPS Trip Function Test Cases RPSTrip#1 (Attachment1)

System Test Cases 1 through 9 (Test Specification Section's 2.1.2 - 2.1.10)

RPS Trip #3 (Attachment 2)

System Test Cases 1 through 9 (Test Specification Sections 2.1.2 - 2.1.10)

RPS Trip #4 (Attachment 3)

System Test Cases 1 through 9 (Test Specification Sections 2.1.3 -2.1.11)

RPS Trip #5 (Attachment 4)

System Test Cases 1 through 9 (Test Specification Sections 2.1.2 - 2.1.10)

RPS Trip #6 (Attachment 5)

Systerm Test Cases 1 through 9 (Test Specification Sections 2.1.2 - 2.1.10)

System Test Cases 1 through 9 RPS Trip #7 (Attachment 6)

(Test Specification Sections 2.1.2 -. 2.1.10)

System Test Cases 1 through 9 Trip #8 (Attachment 7)

(Test Specification Sections 2.1.2 - 2.1.10)

System Test Cases 1 through 9 RPS Trip #9 (Attachment 8)

(Test Specification Sections 2.1.2 - 2.1.10)

System Test Cases 1 through 9 RPS Trip #10 (Attachment 9)

(Test Specification Sections 2.1.2 - 2.1.10).

System Test Cases 1 through 9 RPS Trip #11 (Attachment 10)

(Test Specification Sections 2.1.2 - 2.1.10)

RPS Trip #13 (Attachment 11)

Channel Specific Test Case 1 (Test Specification Section 1.1.3)

RPS Trip #14 (Attachment 12)

None Channel[Specific Test Cases 1 and 2 Channel E (Attachment 13)

(Test Specification Sections 1.1.3 - 1.1.4)

RPS Signal Failures (Attachment 14)

None Initial Conditions (Attachment 15)

None