September 4, 2008

Mr. Charles G. Pardee

Chief Nuclear Officer and

Senior Vice President

Exelon Generation Company, LLC

4300 Winfield Road

Warrenville IL 60555

SUBJECT:

LASALLE COUNTY STATION NOTIFICATION OF AN NRC TRIENNIAL

FIRE PROTECTION BASELINE INSPECTION AND REQUEST FOR

INFORMATION 05000373/2008007(DRS); 05000374/2008007(DRS)

Dear Mr. Pardee:

On November 3, 2008, the U.S. Nuclear Regulatory Commission (NRC) will begin a triennial fire

protection baseline inspection at the LaSalle County Station. This inspection will be performed

in accordance with the NRC Baseline Inspection Procedure 71111.05T.

The schedule for the inspection is as follows:

$

Information gathering visit: October 22 - 24, 2008

$

On-site inspection activity: November 3 - 7, 2008, and November 17 - 21, 2008

The purpose of the information gathering visit is: (1) to obtain information and documentation

needed to support the inspection; (2) to become familiar with the LaSalle County Station=s fire

protection programs, fire protection features, post-fire safe shutdown capabilities and plant

layout; and (3) to arrange administrative details such as office space, availability of

knowledgeable office personnel and to ensure unescorted site access privileges.

Experience has shown that the baseline fire protection inspections are extremely resource

intensive both for the NRC inspectors and the licensee staff. In order to minimize the inspection

impact on the site and to ensure a productive inspection for both organizations, we have

enclosed a request for documents needed for the inspection. These documents have been

divided into four groups. The first group lists information necessary to aid the inspection team in

choosing specific focus areas for the inspection. It is requested that this information be

provided to the lead inspector via mail or electronically no later than October 10, 2008. The

second group also list information and areas for discussion necessary to aid the inspection team

in choosing specific focus areas for the inspection and to ensure that the inspection team is

adequately prepared for the inspection. It is requested this information be available during the

information gathering visit (October 22-24, 2008). The third group of requested documents

consists of those items that the team will review, or need access to, during the inspection.

Please have this information available by the first day of the on-site portion of the inspection

(November 3, 2008). The fourth group lists information necessary to aid the inspection team in

tracking issues identified as a result of the inspection.

C. Pardee

-2-

It is requested that this information be provided to the lead inspector as the information is

generated during the inspection. It is important that all of these documents are up to date

and complete in order to minimize the number of additional documents requested during the

preparation and/or the on-site portions of the inspection.

The lead inspector for this inspection is Mr. R. Langstaff. We understand that our regulatory

contact for this inspection is Mr. J. Vergara of your organization. If there are any questions

about the inspection or the material requested, please contact the lead inspector at

(630) 829-9747 or via e-mail at ronald.langstaff@nrc.gov.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and

its enclosure will be available electronically for public inspection in the NRC Public Document

Room or from the Publicly Available Records System (PARS) component of NRC's Agencywide

Documents Access and Management System (ADAMS), accessible from the NRC Web site at

http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Robert C. Daley, Acting Chief

Engineering Branch 3

Division of Reactor Safety

Docket No. 50-373; 50-374

License No. NPF-11; NPF-18

Enclosure:

Fire Protection Inspection Document Request

cc w/encl:

Site Vice President - LaSalle County Station

Plant Manager - LaSalle County Station

Regulatory Assurance Manager - LaSalle County Station

Chief Operating Officer and Senior Vice President

Senior Vice President - Midwest Operations

Senior Vice President - Operations Support

Vice President - Licensing and Regulatory Affairs

Director - Licensing and Regulatory Affairs

Manager Licensing - Braidwood, Byron and LaSalle

Associate General Counsel

Document Control Desk - Licensing

Assistant Attorney General

J. Klinger, State Liaison Officer,

Illinois Emergency Management Agency

Chairman, Illinois Commerce Commission

C. Pardee

-2-

It is requested that this information be provided to the lead inspector as the information is

generated during the inspection. It is important that all of these documents are up to date and

complete in order to minimize the number of additional documents requested during the

preparation and/or the on-site portions of the inspection.

The lead inspector for this inspection is Mr. R. Langstaff. We understand that our regulatory

contact for this inspection is Mr. J. Vergara of your organization. If there are any questions

about the inspection or the material requested, please contact the lead inspector at

(630) 829-9747 or via e-mail at ronald.langstaff@nrc.gov.

In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and

its enclosure will be available electronically for public inspection in the NRC Public Document

Room or from the Publicly Available Records System (PARS) component of NRC's Agencywide

Documents Access and Management System (ADAMS), accessible from the NRC Web site at

http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

Robert C Daley, Chief

Engineering Branch 3

Division of Reactor Safety

Docket No. 50-373; 50-374

License No. NPF-11; NPF-18

Enclosure:

Fire Protection Inspection Document Request

cc w/encl:

Site Vice President - LaSalle County Station

Plant Manager - LaSalle County Station

Regulatory Assurance Manager - LaSalle County Station

Chief Operating Officer and Senior Vice President

Senior Vice President - Midwest Operations

Senior Vice President - Operations Support

Vice President - Licensing and Regulatory Affairs

Director - Licensing and Regulatory Affairs

Manager Licensing - Braidwood, Byron and LaSalle

Associate General Counsel

Document Control Desk - Licensing

Assistant Attorney General

J. Klinger, State Liaison Officer,

Illinois Emergency Management Agency

Chairman, Illinois Commerce Commission

DOCUMENT NAME: G:\\DRS\\WORK IN PROGRESS\\LTR 08__08 FERMI FPBI RFI RAL.doc

G Publicly Available

G Non-Publicly Available

G Sensitive

G Non-Sensitive

To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" = Copy with attach/encl "N" = No copy

OFFICE

RIII

N

RIII

RIII

RIII

NAME

RLangstaff: ls

RDaley

DATE

09/04/08

09/04/08

OFFICIAL RECORD COPY

Letter to Mr. Charles Pardee from Mr. Robert C. Daley dated September 4, 2008.

SUBJECT:

LASALLE COUNTY STATION NOTIFICATION OF AN NRC TRIENNIAL

FIRE PROTECTION BASELINE INSPECTION AND REQUEST FOR

INFORMATION 05000373/2008007(DRS); 05000374/2008007(DRS)

DISTRIBUTION:

Russell Gibbs

Tamara Bloomer

Stephen Sands

RidsNrrDirsIrib Resource

Mark Satorius

Kenneth Obrien

Jared Heck

Carole Ariano

Linda Linn

DRPIII

DRSIII

Patricia Buckley

Tammy Tomczak

ROPreports@nrc.gov

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

1

Inspection Report: 05000373/2008007(DRS); 05000374/2008007(DRS)

Inspection Dates:

October 22 through 24, 2008, Information Gathering Visit

November 3 through 7, 2008, On-site Inspection Activity

November 17 through 21, 2008, On-site Inspection Activity

Inspection Procedures:

IP 71111.05T, AFire Protection (Triennial)@

IP 71152, "Identification and Resolution of Problems"

Inspectors:

Ronald A. Langstaff, Lead Inspector

(630) 829 9747

ronald.langstaff@nrc.gov

Zelig Falevits

(630) 829-9717

zelig.falevits@nrc.gov

Robert C. Winter

(630) 829-9758

robert.winter@nrc.gov

I.

Information Requested Prior to the Information Gathering Visit

The following information is requested by October 10, 2008. If you have any questions

regarding this information, please call the lead inspector as soon as possible. All

information may be sent electronically (to Mr. Ronald Langstaff, e-mail address

ronald.langstaff@nrc.gov) or provided on compact disc (the preferred method). If

compact discs are provided, three sets (one for each inspector) are requested.

1.

The reactor plant's Individual Plant Examination for External Events (IPEEE) for

fire, results of any post-IPEEE reviews for fire, and listings of actions taken,

and/or plant modifications conducted in response to IPEEE information for fire.

Alternatively, probabilistic risk analyses for fire, and associated information, if it

exists and is more recent than the IPEEE.

2.

A list of fire areas requiring alternative shutdown capability, i.e., those areas for

which 10 CFR Part 50, Appendix R, Section III.G requirements are satisfied under

Section III.G.3, or where both safe shutdown trains can be affected.

3.

Plant operating procedures, which would be used, and describe shutdown for a

postulated fire (for both areas requiring alternative shutdown and areas which do

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

2

not require alternative shutdown). Only those procedures with actions specific to

shutdown in the event of a fire need be included.

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

3

II.

Information Requested During the Information Gathering Visit

(October 22-24, 2008)

This information is requested to be available on-site during the information gathering

visit. Unless otherwise specifically requested below, if the requested information is

available electronically, it is requested that the information be provided on three sets of

compact discs (searchable, if possible).

1.

One set of hard-copy documents for facility layout drawings, which identify plant

fire area delineation; areas protected by automatic fire suppression and detection;

and locations of fire protection equipment.

2.

Licensing Information:

a.

The facility license, including the fire protection license condition;

b.

All Nuclear Regulatory Commission (NRC) Safety Evaluation Reports

(SERs) applicable to fire protection (specifically including those SERs

referenced by the plant fire protection license condition) and licensing

correspondence referenced by the SERs;

c.

All licensing correspondence associated with the comparison to Standard

Review Plan (NUREG-0800), Section 9.5.1 or equivalent for licensing

purposes;

d.

Exemptions from 10 CFR 50.48 and 10 CFR Part 50, Appendix R (for

post-1979 plants), and associated licensing correspondence;

e.

A listing of all other associated licensing correspondence applicable to fire

protection; and

f.

The fire protection program and applicable portions of the Updated Safety

Analysis Report, as referenced by the fire protection license condition.

3.

Fire Protection Program:

a.

If not already provided under Request III.2.f above, fire protection program

documents including fire hazards analyses and post-fire safe shutdown

analyses;

b.

A listing of changes made to the fire protection program (including

associated adverse to safe shutdown analyses) since the last triennial fire

protection inspection;

c.

A listing of the protection methodologies identified under 10 CFR Part 50,

Appendix R,Section III.G used to achieve compliance for selected fire

zones/areas (to be determined during information gathering visit). That is,

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

4

please specify whether 3-hour rated fire barriers (Section III.G.2.a),

20-foot separation along with detection and suppression

(Section III.G.2.b), 1-hour rated fire barriers with detection and

suppression (Section III.G.2.c), or alternative shutdown capability

(Section III.G.3) is used as a strategy for each selected fire zone/area;

d.

A list of Generic Letter 86-10 evaluations (i.e., a list of adverse to safe

shutdown evaluations);

e.

A list of applicable codes and standards related to the design of plant fire

protection features for the fire areas selected during the information

gathering trip. The list should include National Fire Protection

Association (NFPA) code versions committed to (i.e., the NFPA codes of

record); and

f.

A list of plant deviations from code commitments and associated

evaluations.

4.

Corrective Actions:

a.

Listing of open and closed fire protection condition reports (i.e., problem

identification forms and their resolution reports) since the date of the last

triennial fire protection inspection; and

b.

Listing of fire impairments since the date of the last triennial fire protection

inspection.

5.

General Information:

a.

A listing of abbreviations and/or designators for plant systems;

b.

Organization charts of site personnel down to the level of fire protection

staff personnel; and

c.

A phone list for on-site licensee personnel.

6.

On-Site Discussions:

In addition, during the information gathering visit, it is requested that licensee staff

be available for the following:

a.

Informal discussion on plant procedures operators would use in the event

of fire and under what conditions would the plant be shutdown using

alternative shutdown methodology;

b.

Informal discussion on the plant=s safe shutdown cable routing database

and the plant-wide cable routing database, as applicable; and

c.

A tour of alternative shutdown and risk significant fire areas.

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

5

III.

Information Requested to be Available on First Day of Inspection

(November 3, 2008)

This information is requested to be available on-site on first day of inspection. If the

requested information is available electronically, it is requested that the information be

provided on three sets of compact discs (searchable, if possible).

1.

Facility Information:

a.

One set of hard copy piping and instrumentation (flow) diagrams showing

the components used to achieve and maintain hot standby and cold

shutdown for fires outside the control room and those components used

for those areas requiring alternative shutdown capability;

b.

One set of hard copy facility layout and equipment drawings which identify

the physical facility locations of hot standby and cold shutdown equipment

for selected fire zones/areas (to be determined during information

gathering visit);

c.

One set of hard copy one-line schematic drawings of the electrical

distribution system for 4160 Volts - alternating current (Vac) down to

480 Vac;

d.

One set of hard copy one-line schematic drawings of the electrical

distribution system for 250 Volts - direct current (Vdc) and 125 Vdc

systems as applicable;

e.

One set of hard copy logic diagrams showing the components used to

achieve and maintain hot standby and cold shutdown; and

f.

Safe shutdown cable routing database (requested electronically such as

on compact disc), if available.

2.

Operations Response for Fire Protection:

a.

Pre-fire plans for selected fire zones/areas (to be determined during

information gathering visit); and

b.

Control room operations response procedure for fire.

3.

Fire protection design basis documentation, if available (if considered proprietary,

hard copy only).

4.

Program Procedures:

a.

List of the fire protection program implementing procedures

(e.g., administrative controls, surveillance testing, fire brigade);

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

6

b.

List of maintenance and surveillance testing procedures for alternative

shutdown capability and fire barriers, detectors, pumps, and suppression

systems;

c.

List of maintenance procedures which routinely verify fuse breaker

coordination in accordance with the post-fire safe shutdown coordination

analysis;

d.

List of procedures and/or instructions that control the configuration of the

reactor plant's fire protection program, features, and post-fire safe

shutdown methodology and system design; and

e.

List of procedures and/or instructions that govern the implementation of

plant modifications, maintenance, and special operations, and their impact

on fire protection.

5.

Design and Equipment Information:

a.

Coordination calculations and/or justifications that verify fuse/breaker

coordination for selected fire zones/areas (to be determined during

information gathering visit) that are fed off of the same electrical buses as

components in the protected safe shutdown train;

b.

Copies of significant fire protection and post-fire safe shutdown related

design change package descriptions (including their associated 10 CFR

50.59 evaluations) and Generic Letter (GL) 86-10 (or adverse to safe

shutdown) evaluations;

c.

Gaseous suppression system pre-operational testing, if applicable, for

selected fire zones/areas (to be determined during information gathering

visit);

d.

Hydraulic calculations and supporting test data which demonstrate

operability for water suppression systems, if applicable, for selected fire

zones/areas (to be determined during information gathering visit);

e.

Alternating current (ac) coordination calculations for 4160 Vac down to

480 Vac electrical systems; and

f.

Vendor manuals and information for fire protection equipment (such as

detection, suppression systems, fire pumps), applicable to selected fire

zones/areas (to be determined during information gathering visit). It is

acceptable to make vendor manuals available to the inspectors in lieu of

providing a copy.

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

Enclosure

7

6.

Assessment and Corrective Actions:

a.

The three most recent fire protection Quality Assurance (QA) audits

and/or fire protection self-assessments; and

b.

Corrective action documents (e.g., condition reports, including status of

corrective actions) generated as a result of the three most recent fire

protection Quality Assurance (QA) audits and/or fire protection

self-assessments.

7.

Any updates to information previously provided.

IV.

Information Requested to Be Provided Throughout the Inspection

1.

Copies of any corrective action documents generated as a result of the team=s

questions or queries during this inspection; and

2.

Copies of the list of questions submitted by the team members and the

status/resolution of the information requested (provide daily during the inspection

to each team member).

If you have questions regarding the information requested, please contact the lead inspector.