ET 08-0032, Submittal of Additional Information Regarding Main Steam and Feedwater Isolation System (Msfis) Controls Modification
| ML081420366 | |
| Person / Time | |
|---|---|
| Site: | Wolf Creek |
| Issue date: | 05/14/2008 |
| From: | Garrett T Wolf Creek |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| ET 08-0032 | |
| Download: ML081420366 (37) | |
Text
'W0LF CREEK NUCLEAR OPERATING CORPORATION Terry J. Garrett May 14, 2008 Vice President, Engineering ET 08-0032 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555
Reference:
- 1)
Letter ET 07-0004, dated March 14, 2007, from T. J. Garrett, WCNOC, to USNRC
- 2)
Letter ET 07-0022, dated June 15, 2007, from T. J. Garrett, WCNOC, to USNRC
- 3)
Letter ET 08-0004, dated January 18, 2008, from T. J. Garrett, WCNOC, to USNRC
Subject:
Docket No. 50-482: Submittal of Additional Information Regarding Main Steam and Feedwater Isolation System (MSFIS) Controls Modification Gentlemen:
Reference 1 provided a license amendment request that proposed revisions to Technical Specification (TS) 3.3.2, "Engineered Safety Feature Actuation System (ESFAS)
Instrumentation," TS 3.7.2, "Main Steam Isolation Valves (MSIVs)," and TS 3.7.3, "Main Feedwater Isolation Valves (MFIVs)." Reference 1 proposed changes to these specifications based on a planned modification to replace the MSIVs and associated actuators, MFIVs and associated actuators, and replacement of the Main Steam and Feedwater Isolation System (MSFIS) controls.
Reference 3 provided a table identifying additional/revised documentation to be submitted associated with the modification to the MSFIS controls by May 15, 2008. The information identified in Reference 3 to be submitted is the post installation test procedure and a synopsis.
of training on the controls. Reference 2 identifies the post installation test procedure as Question 17, item D, and the synopsis of training as Question 22. Enclosure I provides the post installation test procedure. Enclosure II provides the synopsis of training.
P.O. Box 411 / Burlington, KS 66839 / Phone: (620) 364-8831 An Equal Opportunity Employer M/F/HC/VET
ET 08-0032 Page 2 of 3 The documentation provided in the Enclosures does not impact the conclusions of the No Significant Hazards Consideration provided in Reference 1. In accordance with 10 CFR 50.91, a copy of the submittal is being provided to the designated Kansas State official.
Attachment I provides a list of commitments made in this letter. If you have any questions concerning this matter, please contact me at (620) 364-4084, or Mr. Richard D. Flannigan at (620) 364-4117.
Sincerely, Terry J. Garrett TJG/rlt Attachment Enclosure II MSFIS Controls Replacement Post Maintenance Test Advanced Logic System Class 1 E Controls Training Overview cc:
E. E. Collins (NRC), w/a, w/e, T. A. Conley (KDHE), w/a, w/e V. G. Gaddy (NRC), w/a, w/e B. K. Singal (NRC), w/a, w/e Senior Resident Inspector (NRC), w/a, w/e
ET 08-0032 Page 3 of 3 STATE OF KANSAS COUNTY OF COFFEY
)
)
Terry J. Garrett, of lawful age, being first duly sworn upon oath says that he is Vice President Engineering of Wolf Creek Nuclear Operating Corporation; that he has read the foregoing document and knows the contents thereof; that he has executed the same for and on behalf of said Corporation with full power and authority to do so; and that the facts therein stated are true and correct to the best of his knowledge, information and belief.
Vice SUBSCRIBED and sworn to before me thisdayof SRHONDA L. TIEMEYER Notary Public
-OFFICIAL'z MY COMMISSION EXPIRES iI;SEAL.:
S..
.E ptJanuaryo11, 2010 Expiration Date mfoLý
,2008.
rI?
C' 0,112ZQ
~
d6 /I Z
C
Attachment to ET 08-0032 Page 1 of 1 LIST OF COMMITMENTS The following table identifies those actions committed to by Wolf Creek Nuclear Operating Corporation in this document. Any other statements in this letter are provided for information purposes and are not considered regulatory commitments. Please direct questions regarding these commitments to Mr. Richard D. Flannigan, manager Regulatory Affairs at Wolf Creek Generating Station, (620) 364-4117.
REGULATORY COMMITMENT DUE DATE Hold a detailed ALS controls training for a targeted engineering audience 12-16-2008 durinq the second half of 2008.
I
Enclosure I to ET 08-0032
MSFIS Controls: Post Maintenance Test MAIN STEAM & FEEDWATER ISOLTION SYSTEM (MSFIS)
CONTROLS REPLACEMENT V
POST MAINTENANCE TEST REVISION 0 PROJECT MANAGER GREGG CLARKSON MANAGEMENT SPONSOR PATRICK GUEVEL EXECUTIVE SPONSOR TERRY GARRETT Wolf Creek Nuclear Operating Corporation PO Box 411 1550 Oxen Lane, NE Burlington, KS 66839 Revision 0 5/6/2008 Page 1 of 26 Revision 0 5/6/2008 Page I of 26
MSFIS Controls: Post Maintenance Test Revision Control 014 Approval Approval Date 0
GWC 5/6/2008 Dsrpin of hanve(s)
Initial Revision Revision 0 5/6/2008 Page2of26 Revision 0 5/6/2008 Page 2 of 26
MSFIS Controls: Post Maintenance Test Table of Content REVISION 0......................................................................................................................................................................
I 1
Post M aintenance Test.................................................................................................................................................
4 1.1 P u rp o se..............................................................................................................................................................
4 1.2 S co p e.................................................................................................................................................................
4 1.3 Conditions.............................................................................................
4 2
SA075A Testing..........................................................................................................................................................
5 2.1 SA075A Cabinet Power Up................................................................................................................................
5 2.2 SA075A M FIV Rack Generic Testing..........................................................................................................
6 2.3 SA0.75A M SIV Rack Generic Testing................................................................
.... 7 2.4 MFIV portions of the MSFIS Controls for the SA075A cabinet...........................................
8 2.4.1 AE-FV-0039..........................................................................................................................................
8 2.4.2 AE-FV-0040..........................................................................................................................................
9 2.4.3 AE-FV-0041.................................................................................................
10 2.4.4 AE-FV-0042.....................................................................................................................
................... 11 2.4.5 Test ALLCLOSE for all M FIVs (SA075A)..................................................................................
.. 11 2.5 M SIV portions of the M SFIS Controls for the SA075A cabinet...................................................................
12 2.5.1 AB-HV-0014.......................................................................................................................................
12 2.5.2 AB-HV-0017........................................................................................
13 2.5.3 AB-HV-0020............................................................
14 2.5.4 AB-HV-0011.......................................................................................................................................
15 2.5.5 Test ALLCLOSE for all M SIVs (SA075A)....................................................................................
15 3
SA075B Testing........................................................................................................................................................
16 3.1 SA075B Cabinet Power Up.............................................................................................................................
16 3.2 SA075B M FIV Rack Generic Testing...............................................................................................................
17 3.3 SA075B M SIV Rack Generic Testing...............................................................................................................
18 3.4 MFIV portions of the MSFIS Controls for the SA075B cabinet.......
.......................... 19 3.4.1 AE-FV-0039........................................................................................................................................
19 3.4.2 AE-FV-0040...............................................................................................................
........................ 20 3.4.3 AE-FV-0041........................................................................................................................................
21 3.4.4 AE-FV-0042.........................................................................................................................................
22 3.4.5 Test ALLCLOSE for all M FIVs (SA075B)...................................................................................
22 3.5 MSIV portions of the MSFIS Controls for the SA075B cabinet................................
23 3.5.1 AB-HV-0014...................................................................................
...... :................ 23 3.5.2 AB-HV-0017.....................................................................................................................................
24 3.5.3 AB-HV-0020.......................................................................................................................................
25 3.5.4 AB-HV-0011.........................................................
26 3.5.5 Test ALLCLOSE for all M SIVs (SA075B)....................................................................................
26 Revision 0 5/6/2008 Page 3 of 26
MSFIS Controls: Post Maintenance Test LPost Maintenance Test 1.1 Purpose The purpose of the post maintenance test (PMT) is to verify the equipment is installed properly, including verification of all input and outputs to and from the field connections. The PMT relies on the rack specific functional testing performed in both the Factory Acceptance Testing and Site Acceptance Testing.
1.2 Scope The scope of the PMT shall include the scope of work for the MSFIS Controls Replacement Project. The scope of work includes replacement of the existing discrete logic based control system with an Advanced Logic System (ALS).
The MSFIS Controls Replacement Project replaces the existing safety related MSFIS with a hardware-based system to perform the control functions of the MSIVs and MFIVs. The MSFIS controls, both the existing and replacement, has two redundant subsystems located in separate cabinets:
MSFIS Channel 1 (1) located in MSFIS Cabinet SA075A MSFIS Channel IV (4) located in MSFIS Cabinet SA075B The replacement project will retain the existing cabinets, external power supply feeds, and channel separation scheme in the overall plant configuration. The replacement project will include changes to the functions by which the replacement MSFIS controls the replacement MSIVs and MFIVs. These changes account for the differences in the function of the existing and replacement MSIVs and MFIVs, that is, electro-pneumatic-hydraulic actuators replaced by system medium actuators.
The existing and replacement MSFIS are both considered digital in that they deal with ON-OFF inputs and outputs, and there are no analog / magnitude inputs and outputs involved. However, the systems, both the existing and replacement, do not have general digital computer components and characteristics such as a clock-driven central processing unit in continuous operation.
1.3 Conditions The PMT shall be performed after the installation of the ALS Class 1E Controls for MSFIS equipment. The PMT shall be performed while the plant is in cold shutdown, Mode 5, or Mode 4.
Revision 0 5/6/200 8 Page 4 of 26 Revision 0 5/6/2008 Page 4 of 26
MSFIS Controls: Post Maintenance Test 2 SA075A Testing 2.1 SA075A Cabinet Power Up Step Completed Open Fuse(s), F101 and F102 Open Fuse(s), F103 and F104 Close NK5119 Feeder to supply power to SA075A Verify voltage @ TB101 = 133VDC +/- 5VDC Close NK5119 Feeder to supply power to SA075A Revision 0 5/6/2008 PageS of 26 Revision 0 5/6/2008 Page 5 of 26
MSFIS Controls: Post Maintenance Test 2.2 SA075A MFIV Rack Generic Testing Step Completed Close Fuse(s), F101 and F102 Verify green PWR LED on both ALS-905 is lit Verify green READY LED on ALS-201 is lit Verify green VFC LEDs on ALS-301-2 are lit Toggle RESET switch on ALS-101 Verify green PWR LED is lit on ALS-101 Verify green PWR LED is lit on ALS-301-2 Verify green PWR LED is lit on ALS-401-1 Verify green PWR LED is lit on ALS-201 Verify green PWR LED is lit on ALS-41 1-1 Verify green PWR LED is lit on ALS-411-2 Verify green PWR LED is lit on ALS-411-3 Verify green RUN LED is blinking at - 1HZ rate on ALS-101 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-401-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-201 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-3 Verify green C LED lights after -60 sec from toggling reset Depress the upper latch microswitch for the left ALS-905 card Depress the lower latch microswitch for the left ALS-905 card Verify the left ALS-905 card LEDs are not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is not lit Verify red ALARM LED is lit on ALS-101 Verify with Control Room the SA075A Annunciator actuated Reconnect the upper latch microswitch by pressing the latch down until the microswitch changes state Reconnect the upper latch microswitch by pressing the latch up until the microswitch changes state Verify the left ALS-905 card PWR LED is lit and the red FAIL lED is not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is lit Verify red ALARM LED is not lit on ALS-101 Verify with Control Room the SA075A Annunciator not actuated Revision 0 5/6/2008 Page 6 of 26
MSFIS Controls: Post Maintenance Test 2.3 SA075A MSIV Rack Generic Testing Step Completed Close Fuse(s), F103 and F104 Verify green PWR LED on both ALS-905 is lit Verify green READY LED on ALS-201 is lit Verify green VFC LEDs on ALS-301-2 are lit Toggle RESET switch on ALS-101 Verify green PWR LED is lit on ALS-101 Verify green PWR LED is lit on ALS-301-1 Verify green PWR LED is lit on ALS-301-2 Verify green PWR LED is lit on ALS-401-1 Verify green PWR LED is lit on ALS-201 Verify green PWR LED is lit on ALS-41 1-1 Verify green PWR LED is lit on ALS-411-2 Verify green PWR LED is lit on ALS-411-3 Verify green RUN LED is blinking at - 1HZ rate on ALS-101 Vedfy green RUN LED is blinking at - 1HZ rate on ALS-301-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-401-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-201 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-3 Vedfy green C LED lights after -60 sec from toggling reset Depress the upper latch microswitch for the left ALS-905 card Depress the lower latch microswitch for the left ALS-905 card Verify the left ALS-905 card LEDs are not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is not lit Verify red ALARM LED is lit on ALS-101 Verify with Control Room the SA075A Annunciator actuated Reconnect the upper latch microswitch by pressing the latch down until the microswitch changes state Reconnect the upper latch microswitch by pressing the latch up until the microswitch changes state Verify the left ALS-905 card PWR LED is lit and the red FAIL lED is not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is lit Verify red ALARM LED is not lit on ALS-101 Verify with Control Room the SA075A Annunciator not actuated Revision 0 5/6/2008 Page 7 of 26
MSFIS Controls: Post Maintenance Test 2.4 MFIV portions of the MSFIS Controls for the SA075A cabinet.
2.4.1 AE-FV-0039 Step Completed Press AE-HIS-39 (OPEN)
Verify OPEN LED for AE-FV-39 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-39 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-39 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-39 on ALS-401 -1 is not lit Verify the BYPASS LED for AE-FV-39 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-39 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-39 on ALS-401-1 lights Verify the BYPASS LED for AE-FV-39 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-39 (CLOSE)
- Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-39 on ALS-411-3 lights Press AE-HIS-39 (OPEN)
Verify OPEN LED for AE-FV-39 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-39 on ALS-411-3 is not lit Revision 0 5/6/2008 PageS of 26 Revision 0 5/6/2008 Page 8 of 26
MSFIS Controls: Post Maintenance Test 2.4.2 AE-FV-0040 Step Completed Press AE-HIS-40 (OPEN)
Verify OPEN LED for AE-FV-40 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-40 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-40 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-40 on ALS-401 -1 is not lit Verify the BYPASS LED for AE-FV-40 on ALS-401 -1 lights Toggle Operate/Bypass switch for AE-FV-40 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-40 on ALS-401 -1 lights Verify the BYPASS LED for AE-FV-40 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-40 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-40 on ALS-411-3 lights Press AE-HIS-40 (OPEN)
Verify OPEN LED for AE-FV-40 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-40 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 9 of 26 Revision 0 5/6/2008 Page 9 of 26
MSFIS Controls: Post Maintenance Test 2.4.3 AE-FV-0041 Step Completed Press AE-HIS-41 (OPEN)
Verify OPEN LED for AE-FV-41 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-41 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-41 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-41 on ALS-401-1 is not lit Verify the BYPASS LED for AE-FV-41 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-41 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-41 on ALS-401-1 lights Verify the BYPASS LED for AE-FV-41 on ALS-401 -1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-41 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-41 on ALS-411-3 lights Press AE-HIS-41 (OPEN)
Verify OPEN LED for AE-FV-41 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-41 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 10 of 26
MSFIS Controls: Post Maintenance Test 2.4.4 AE-FV-0042 Step Completed Press AE-HIS-42 (OPEN)
Verify OPEN LED for AE-FV-42 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-42 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-42 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-42 on ALS-401-1 is not lit Verify the BYPASS LED for AE-FV-42 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-42 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-42 on ALS-401-1 lights Verify the BYPASS LED for AE-FV-42 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-42 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-42 on ALS-411-3 lights Press AE-HIS-42 (OPEN)
Verify OPEN LED for AE-FV-42 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-42 on ALS-411-3 is not lit 2.4.5 Test ALLCLOSE for all MFIVs (SA075A)
Step Completed Test ALLCLOSE for All MFIV's
- 49) Ensure all green A and B LEDs are lit for each of the valves: AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42
- 50) Press AE-HS-80 (ALLCLOSE)
Verify green A and green B solenoid LEDs for each of the valves, AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42, on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for each of the valves, AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42, on ALS-411-3 lights Revision 0 5/6/2008 Page 11 of26 Revision 0 5/6/2008 Page I11 of 26
MSFIS Controls: Post Maintenance Test 2.5 MSIV portions of the MSFIS Controls for the SA075A cabinet.
2.5.1 AB-HV-0014 Step Completed Press AB-HIS-14 (OPEN)
Verify OPEN LED for AB-HV-14 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-14 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-14 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-14 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-14 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-14 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-14 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-14 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-14 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-14 on ALS-411-3 lights Press AB-HIS-14 (OPEN)
Verify OPEN LED for AB-HV-14 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-14 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 12 of 26
MSFIS Controls: Post Maintenance Test 2.5.2 AB-HV-0017 Step Completed Press AB-HIS-17 (OPEN)
Verify OPEN LED for AB-HV-17 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-17 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-1 7 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-17 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-17 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-1 7 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-17 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-17 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-17 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-41 1-1 and ALS-41 1-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-1 7 on ALS-411-3 lights Press AB-HIS-17 (OPEN)
Verify OPEN LED for AB-HV-17 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-17 on ALS-411-3_is not lit Revision 0 5/6/2008 Page 13 of26 Revision 0 5/6/2008 Page 13 of 26
MSFIS Controls: Post Maintenance Test 2.5.3 AB-HV-0020 Step Completed Press AB-HIS-20 (OPEN)
Verify OPEN LED for AB-HV-20 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-20 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-20 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-20 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-20 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-20 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-20 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-20 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-20 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-20 on ALS-411-3 lights Press AB-HIS-20 (OPEN)
Verify OPEN LED for AB-HV-20 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-20 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 14 of26 Revision 0 5/6/2008 Page 14 of 26
MSFIS Controls: Post Maintenance Test 2.5.4 AB-HV-0011 Step Completed Press AB-HIS-1 1 (OPEN)
Verify OPEN LED for AB-HV-1 1 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-11 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-11 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-1 1 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-11 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-11 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-1 1 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-11 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-11 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-1 1 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-1 1 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-1 1 on ALS-411-3 lights Press AB-HIS-1 1 (OPEN)
Verify OPEN LED for AB-HV-1 1 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-11 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-11 on ALS-411-3 is not lit 2.5.5 Test ALLCLOSE for all MSIVs (SA075A)
Step Completed Ensure all green A and B LEDs are lit for each of the valves: AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-1 1 Press AB-HS-80 (ALLCLOSE)
Verify green A and green B solenoid LEDs for each of the valves, AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-11, on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for each of the valves, AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-11, on ALS-411-3 lights Revision 0 5/6/2008 Page 15 of26 Revision 0 5/6/2008 Page 15 of 26
MSFIS Controls: Post Maintenance Test 3.1 SA075B Cabinet Power Up Step Completed Open Fuse(s), F401 and F402 Open Fuse(s), F403 and F404 Close NK5423 Feeder to supply power to SA075B Verify voltage @ TB101 = 133VDC +/- 5VDC Revision 0 5/6/2008 Page 16of26 Revision 0 5/6/2008 Page 16 of 26
MSFIS Controls: Post Maintenance Test 3.2 SA075B MFIV Rack Generic Testing Step Completed Close Fuse(s), F401 and F402 Verify green PWR LED on both ALS-905 is lit Verify green READY LED on ALS-201 is lit Verify green VFC LEDs on ALS-301-2 are lit Toggle RESET switch on ALS-101 Verify green PWR LED is lit on ALS-101 Verify green PWR LED is lit on ALS-301-1 Vedfy green PWR LED is lit on ALS-301-2 Vedfy green PWR LED is lit on ALS-401-1 Verify green PWR LED is lit on ALS-201 Verify green PWR LED is lit on ALS-41 1-1 Verify green PWR LED is lit on ALS-411-2 Verify green PWR LED is lit on ALS-411-3 Verify green RUN LED is blinking at - 1HZ rate on ALS-101 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-401-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-201 Vedfy green RUN LED is blinking at - 1HZ rate on ALS-411-1 Verify green RUN LED is blinking at - 1HZ.rate on ALS-411-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-3 Verify green C LED lights after -60 sec from toggling reset Depress the upper latch microswitch for the left ALS-905 card Depress the lower latch microswitch for the left ALS-905 card Verify the left ALS-905 card LEDs are not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is not lit Verify red ALARM LED is lit on ALS-101 Verify with Control Room the SA075B Annunciator actuated Reconnect the upper latch microswitch by pressing the latch down until the microswitch changes state Reconnect the upper latch microswitch by pressing the latch up until the microswitch changes state Verify the left ALS-905 card PWR LED is lit and the red FAIL lED is not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is lit Verify red ALARM LED is not lit on ALS-101 Verify with Control Room the SA075B Annunciator not actuated Revision 0 5/6/2008 Page 17 of26 Revision 0 5/6/2008 Page 17 of 26
MSFIS Controls: Post Maintenance Test 3.3 SA075B MSIV Rack Generic Testing Step Completed Close Fuse(s), F403 and F404 Verify green PWR LED on both ALS-905 is lit Verify green READY LED on ALS-201 is lit Verify green VFC LEDs on ALS-301-2 are lit Toggle RESET switch on ALS-101 Verify green PWR LED is lit on ALS-101 Verify green PWR LED is lit on ALS-301-1 Verify green PWR LED is lit on ALS-301-2 Verify green PWR LED is lit on ALS-401-1 Verify green PWR LED is lit on ALS-201 Verify green PWR LED is lit on ALS-41 1-1 Verify green PWR LED is lit on ALS-411-2 Verify green PWR LED is lit on ALS-41 1-3 Verify green RUN LED is blinking at - 1HZ rate on ALS-101 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-301-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-401-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-201 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-1 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-2 Verify green RUN LED is blinking at - 1HZ rate on ALS-411-3 Verify green C LED lights after -60 sec from toggling reset Depress the upper latch microswitch for the left ALS-905 card Depress the lower latch microswitch for the left ALS-905 card Verify the left ALS-905 card LEDs are not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is not lit Verify red ALARM LED is lit on ALS-101 Verify with Control Room the SA075B Annunciator actuated Reconnect the upper latch microswitch by pressing the latch down until the microswitch changes state Reconnect the upper latch microswitch by pressing the latch up until the microswitch changes state Verify the left ALS-905 card PWR LED is lit and the red FAIL lED is not lit Verify the right ALS-905 PWR LED is lit and the red FAIL LED is not lit Verify the PCU HEALTH LED on Als-301-2 is lit Verify red ALARM LED is not lit on ALS-101 Verify with Control Room the SA075B Annunciator not actuated Revision 0 5/6/2008 Page 18 of26 Revision 0 5/6/2008 Page 18 of 26
MSFIS Controls: Post Maintenance Test 3.4 MFIV portions of the MSFIS Controls for the SA075B cabinet.
3.4.1 AE-FV-0039 Step Completed Press AE-HIS-39 (OPEN)
Verify OPEN LED for AE-FV-39 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-39 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-39 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-39 on ALS-401-1 is not lit Verify the BYPASS LED for AE-FV-39 on ALS-401 -1 lights Toggle Operate/Bypass switch for AE-FV-39 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-39 on ALS-401 -1 lights Verify the BYPASS LED for AE-FV-39 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-39 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-39 on ALS-411-3 lights Press AE-HIS-39 (OPEN)
Verify OPEN LED for AE-FV-39 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-39 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-39 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 19 of26 Revision 0 5/6/2008 Page 19 of 26
MSFIS Controls: Post Maintenance Test 3.4.2 AE-FV-0040 Step Completed Press AE-HIS-40 (OPEN)
Verify OPEN LED for AE-FV-40 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-40 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-40 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-40 on ALS-401 -1 is not lit Verify the BYPASS LED for AE-FV-40 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-40 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-40 on ALS-401-1 lights Verify the BYPASS LED for AE-FV-40 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-40 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-411-1 and ALS-411-2'are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-40 on ALS-411-3 lights Press AE-HIS-40 (OPEN)
Verify OPEN LED for AE-FV-40 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-40 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-40 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 20 of 26 Revision 0 5/6/2008 Page 20 of 26
MSFIS Controls: Post Maintenance Test 3.4.3 AE-FV-0041 Step Completed Press AE-HIS-41 (OPEN)
Verify OPEN LED for AE-FV-41 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-41 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-41 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-41 on ALS-401-1 is not lit Verify the BYPASS LED for AE-FV-41 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-41 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-41 on ALS-401-1 lights Verify the BYPASS LED for AE-FV-41 on ALS-401 -1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-41 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-41 on ALS-411-3 lights Press AE-HIS-41 (OPEN)
Verify OPEN LED for AE-FV-41 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-41 on ALS-41 1-1 and ALS-41:1-2 light Verify C solenoid LED for AE-FV-41 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 21 of 26
MSFIS Controls: Post Maintenance Test 3.4.4 AE-FV-0042 Step Completed Press AE-HIS-42 (OPEN)
Verify OPEN LED for AE-FV-42 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-42 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AE-FV-42 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AE-FV-42 on ALS-401-1 is not lit Verify the BYPASS LED for AE-FV-42 on ALS-401-1 lights Toggle Operate/Bypass switch for AE-FV-42 on ALS-201 from Bypass to Operate Verify the STATUS LED for AE-FV-42 on ALS-401 -1 lights Verify the BYPASS LED for AE-FV-42 on ALS-401 -1 is not lit Verify the ESFAS Status alarm is removed Press AE-HIS-42 (CLOSE)
Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AE-FV-42 on ALS-411-3 lights Press AE-HIS-42 (OPEN)
Verify OPEN LED for AE-FV-42 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AE-FV-42 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AE-FV-42 on ALS-411-3 is not lit 3.4.5 Test ALLCLOSE for all MFIVs (SA075B)
Step Completed Test ALLCLOSE for All MFIV's
- 49) Ensure all green A and B LEDs are lit for each of the valves: AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42
- 50) Press AE-HS-81 (ALLCLOSE)
Verify green A and green B solenoid LEDs for each of the valves, AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42, on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for each of the valves, AE-FV-39, AE-FV-40, AE-FV-41, AE-FV-42, on ALS-411-3 lights Revision 0 5/6/2008 Page 22 of 26 Revision 0 5/6/2008 Page 22 of 26
MSFIS Controls: Post Maintenance Test 3.5 MSIV portions of the MSFIS Controls for the SA075B cabinet.
3.5.1 AB--V-0014 Step Completed Press AB-HIS-14 (OPEN)
Verify OPEN LED for AB-HV-14 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-14 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-14 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-14 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-14 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-14 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-14 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-14 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-14 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-14 on ALS-411-3 lights Press AB-HIS-14 (OPEN)
Verify OPEN LED for AB-HV-14 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-14 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-14 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 23 of 26 Revision 0 5/6/2009 Page 23 of 26
MSFIS Controls: Post Maintenance Test 3.5.2 AB-HV-0017 Step Completed AB-HV-17 Press AB-HIS-17 (OPEN)
Verify OPEN LED for AB-HV-17 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-17 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-17 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-17 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-17 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-1 7 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-17 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-17 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-17 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-17 on ALS-411-3 lights Press AB-HIS-17 (OPEN)
Verify OPEN LED for AB-HV-17 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-17 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-17 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 24 of 26
MSFIS Controls: Post Maintenance Test 3.5.3 AB-HV-0020 Step Completed Press AB-HIS-20 (OPEN)
Verify OPEN LED for AB-HV-20 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-20 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-20 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-20 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-20 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-20 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-20 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-20 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-20 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-20 on ALS-411-3 lights Press AB-HIS-20 (OPEN)
Verify OPEN LED for AB-HV-20 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-20 on ALS-41 1-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-20 on ALS-411-3 is not lit Revision 0 5/6/2008 Page 25 of 26
MSFIS Controls: Post Maintenance Test 3.5.4 AB-H-V-0011 Step Completed Press AB-HIS-1 1 (OPEN)
Verify OPEN LED for AB-HV-11 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-11 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-11 on ALS-411-3 is not lit Toggle Operate/Bypass switch for AB-HV-1 1 on ALS-201 from Operate to Bypass Verify with Control Room the ESFAS Status panel annunciated for the valve and train under test Verify the STATUS LED for AB-HV-1 1 on ALS-401-1 is not lit Verify the BYPASS LED for AB-HV-1 1 on ALS-401-1 lights Toggle Operate/Bypass switch for AB-HV-1 1 on ALS-201 from Bypass to Operate Verify the STATUS LED for AB-HV-1 1 on ALS-401-1 lights Verify the BYPASS LED for AB-HV-1 1 on ALS-401-1 is not lit Verify the ESFAS Status alarm is removed Press AB-HIS-1 1 (CLOSE)
Verify green A and green B solenoid LEDs for AB-HV-1 1 on ALS-41 1-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for AB-HV-1 1 on ALS-411-3 lights Press AB-HIS-1 1 (OPEN)
Verify OPEN LED for AB-HV-1 1 on ALS-301-1 lights while switch is pressed Verify green A and green B solenoid LEDs for AB-HV-11 on ALS-411-1 and ALS-411-2 light Verify C solenoid LED for AB-HV-1 1 on ALS-411-3 is not lit 3.5.5 Test ALLCLOSE for all MSIVs (SA075B)
Step Completed
- 49) Ensure all green A and B LEDs are lit for each of the valves: AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-1 1
- 50) Press AB-HS-79 (ALLCLOSE)
Verify green A and green B solenoid LEDs for each of the valves, AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-11, on ALS-411-1 and ALS-411-2 are not lit After a -60 second delay, Verify C solenoid LED for each of the valves, AB-HV-14, AB-HV-14, AB-HV-20, AB-HV-11, on ALS-411-3 lights Revision 0 5/6/2008 Page 26 of 26 Revision 0 5/6/2008 Page 26 of 26
Enclosure II to ET 08-0032
Class IE Controls: ALS Training Overview ADVANCED LOGIC SYSTEM (ALS)
CLASS 1E CONTROLS TRAINING OVERVIEW REVISION 0 PROJECT MANAGER - GREGG CLARKSON MANAGEMENT SPONSOR
- PATRICK GUEVEL EXECUTIVE SPONSOR
- TERRY GARRETT Wolf Creek Nuclear Operating Corporation PO Box 411 1550 Oxen Lane, NE Burlington, KS 66839 Revision 0 5/8/2008 Page 1 of 5
Class 1E Controls: ALS Training Overview Revision Control 0l #18tAppro aae Rvscripisiof anges) 0 GWC 5/8/2008 Initial Revision Revision 0 5/8/2008 Page 2 of 5
Class lE Controls: ALS Training Overview Table of Content REVISION 0................................................................................................................................
1 Training Overview........................................................................................................
4 1.1 CS Innovations Training.....................................................................................................
4 1.1.1 CS Innovations Facility Training..................................................................................
4 1.1.2 CS Innovations at Wolf Creek......................................................................................
4 1.2 WCNOC Training.............................................................................................................
4 1.2.1 Operations Training..................................................................................................
4 1.2.2 Engineering Training................................................................................................
5 1.2.3 I&C Technicians Training..........................................................................................
5 Revision 0 5/8/2008 Page 3 of 5
Class IE Controls: ALS Training Overview This document provides an overview of the training provided for the ALS Class lE Controls.
1.1 CS Innovations Training CS Innovations provided training both at their facility as well as at WCGS. A short summary of the training is discussed below.
1.1.1 CS Innovations Facility Training CS Innovations provided detailed training at their facility in Scottsdale, Arizona. WCNOC sent four I&C Technicians to the CS Innovations facility for this training. One of the four I&C Technicians is also a WCNOC in-house training instructor.
The training was provided in August of 2007 with a week long duration. The training environment for this included both theory of operation discussion as well as lab based hands on.
During the theory of operation discussion the technicians learned about the overall architectural operation of the ALS platform, the functionality of the individual boards, diagnostics capabilities, and the fault tolerant nature of the ALS. The MSFIS specific application was discussed as a reference point for several of the features within the ALS platform.
The lab based setting provided the opportunity for the technicians to get their hands on the equipment. Allowing them to see how the equipment responds to user interface. The CS Innovations personnel injected several sets of faults into the equipment which provided the technicians with a real world troubleshooting effort. By then end of the week the technicians were highly proficient with the ALS platform and specifically the MSFIS Controls implementation.
1.1.2 CS Innovations at Wolf Creek CS Innovations provided training for WCNOC I&C Technicians and System Engineers during the site acceptance testing at WCGS.
The site acceptance testing took place in February 2008. The training included specific information on the testing environment for both the individual cards as well as the complete system. The technicians and engineers were exposed to the robust test suite the system must pass prior to installation in the plant. This exposure provides a good base for the performance of the Post Maintenance Test (PMT) performed after the installation.
1.2 WCNOC Training The WCNOC in-house training group provided training for Operations, Engineering, and I&C Technicians. The sections below provide a summary of the training.
1.2.1 Operations Training Training for operations personnel was provided for all operating crews. This training was created by the WCNOC Operations training group. The training focused on the user interface and overall functions of the ALS MSFIS Controls. Operators were trained on changes to the Main Control Board (MCB) and the user interface of the ALS rack. User case scenarios were provided to the operators to allow them to understand the information which the various indications contain.
The operations training will continue to be offered as refresher material as well as for new operators.
Revision 0 5/8/2008 Page 4 of 5
Class IE Controls: ALS Training Overview 1.2.2 Engineering Training Training was provided by the in-house engineering training group to the general engineering population during Q1 2008 training cycle. The training was high level providing an overview of the ALS and the MSFIS specific controls.
A detailed ALS Controls training for a targeted engineering audience is to be held during second half of 2008.
1.2.3 I&C Technicians Training The I&C training instructor, who attended the CS Innovations training in Scottsdale, Arizona, developed a detailed class based upon the information provided by CS Innovations. The class contains both a classroom and a lab component. The duration of the training is 2 days, the first day and a half is classroom based, while the last half of the second day is lab based.
A run time rack has been provided to I&C for the purposes of training and mock-up development for the ALS architecture. This run time rack was utilized during the initial training and will continue to be utilized for on-going as well as new application training for the ALS. Faults were injected into the run time rack to allow the technicians to apply what they learned in the classroom and to become comfortable interfacing with the equipment.
Revision 0 5/8/2008 Page 5 of 5