Dresden. Units 2 and 3 - Tech Spec Page for Amendments 223 and 215 to Increase the Dresden Safety Valve As-Found Setpoint Tolerance from 1 Percent to 3 Percent
ML071730303
Person / Time
Site: Dresden  
Issue date: 06/21/2007
From:
NRC/NRR/ADRO/DORL/LPLIII-2
To:
Gratton C, NRR/DORL 415-1055
Shared Package
ML071440130 List:
References
TAC MD2166, TAC MD2167
Download: ML071730303 (1)


Text

Safety and Relief Valves 3.4.3 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.4.3.1 Verify the safety function lift setpoints of the safety valves are as follows:

In accordance with the Inservice Testing Program Number of Safety Valves 1

2 2

4 Following testing, within +/- 1%.

Setpoint

( ps i q )

1135 +/- 34.1 1240 +/- 37.2 1250 +/- 37.5 1260 +/- 37.8 lift settings shall be SR 3.4.3.2 Verify each relief valve actuator strokes 24 months when manually actuated.

SR 3.4.3.3


NOTE --------------------

Valve actuation may be excluded.

Verify each relief valve actuates on an 24 months actual or simulated automatic initiation signal.

Dresden 2 and 3 3.4.3-2 Amendment No.223 /215