July 18, 2007 Mr. Randy C. Bunt, Chair BWR Owners Group Southern Nuclear Operating Company 40 Inverness Center Parkway/Bin B057 Birmingham, AL 35242

SUBJECT:

POTENTIAL ADVERSE FLOW EFFECTS IN NUCLEAR POWER PLANTS

Dear Mr. Bunt:

Between 2002 and 2006, the Quad Cities Nuclear Power Station, Units 1 and 2 (Quad Cities),

boiling water reactor (BWR) nuclear power plants experienced severe degradation of the steam dryers and main steam line relief valves during extended power uprate operation. To resolve this problem at Quad Cities, main steam system modifications were necessary to reduce the pressure loading on the steam dryer and vibrations in main steam line piping and components.

Further, Palo Verde Nuclear Generating Station, Unit 1, pressurized water reactor (PWR) nuclear power plant experienced damage from adverse flow effects in a shutdown cooling line resulting from acoustic resonance with subsequent plant modifications performed to address the problem. As a result of these operating experience issues, the nuclear industry and U.S.

Nuclear Regulatory Commission (NRC) staff are evaluating potential adverse flow effects from hydrodynamic loads and acoustic resonance in nuclear power plants in much more detail than in the past.

The acoustic resonance phenomenon that causes adverse flow effects in nuclear power plants is highly complex and requires extensive analyses to evaluate its potential impact on nuclear power plant structures, systems, and components over a wide frequency range. Further, scale model testing (SMT) and analytical tools have not matured sufficiently to allow minimal error and uncertainty values to be used in their application. This has resulted in the need to have significant margin available in stress analyses performed on nuclear power plant components (primarily BWR steam dryers) to account for errors and uncertainties. Consequently, applicants for power uprates, design certifications, construction permits, and operating licenses have a significant challenge in addressing potential adverse flow effects on nuclear power plant structures, systems, and components for their specific applications.

The NRC staff has updated Regulatory Guide 1.20, Comprehensive Vibration Assessment Program for Reactor Internals During Preoperational and Initial Startup Testing, and the Standard Review Plan (SRP) in Sections 3.9.2, Dynamic Testing and Analyses of Systems, Structures, and Components, and 3.9.5, Reactor Pressure Vessel Internals, to incorporate lessons learned from operating experience and the review of power uprate submittals.

However, the NRC staff believes that additional generic communication would be helpful to the nuclear industry in addressing potential adverse flow effects in an adequate manner in power uprate and new reactor applications for BWRs and PWRs. Therefore, the NRC staff is considering the preparation of a Regulatory Issue Summary (RIS) to discuss the evaluation of potential adverse flow effects for power uprates and new reactors.

R. Bunt The NRC staff is considering addressing the following topics in the RIS:

1.

Pressure Fluctuations and Vibration in Plant Systems (including the construction and validation of a small SMT facility, and method and approach for the measurement of plant-specific data to determine pressure fluctuations and vibration that can impact structures, systems, and components) 2.

Design Load Definition for Steam Dryers (including the development of an analytical methodology to calculate fluctuating pressure loads on the steam dryer that is validated against SMT data and plant-specific instrumented steam dryers) 3.

BWR Steam Dryer Stress and Limit Curves (including the performance of a finite element analysis using appropriate damping values, justification of bias error and uncertainty for each category of the stress calculation on a frequency-specific basis, and development of limit curves based on plant data accounting for bias errors and uncertainties as well as concentration and weld size factors) 4.

PWR Steam Generator Stress and Design Margin (including the evaluation of the dynamic response, stress, and design margin of the internal components in steam generators) 5.

Evaluation of Other Plant Components (including the evaluation of potential adverse effects from pressure fluctuations and vibration on piping and components in reactor coolant, steam, feedwater, and condensate systems, such as safety relief valves, power-operated valves, and sampling probes) 6.

Power Ascension Data (including the development of power ascension procedures with limit curves and frequent data collection, walkdowns, and hold points for data evaluation and NRC staff interaction) 7.

Monitoring of Potential Adverse Flow Effects (including the development of proactive methods for identifying acoustic resonance or severe hydrodynamic loading prior to component failure)

If you have any suggestions regarding these considerations, we would appreciate receiving your comments within one month such that the NRC staff can prepare the proposed RIS in a timely manner.

Please contact Kamal Manoly, Chief, Mechanical & Civil Engineering Branch, Division of Engineering, Office of Nuclear Reactor Regulation, at 301-415-2765, for any additional information.

Sincerely,

/RA/

John A. Grobe, Associate Director for Engineering and Safety Systems Office of Nuclear Reactor Regulation Project No. 691 cc: See next page

R. Bunt The NRC staff is considering addressing the following topics in the RIS:

1.

Pressure Fluctuations and Vibration in Plant Systems (including the construction and validation of a small SMT facility, and method and approach for the measurement of plant-specific data to determine pressure fluctuations and vibration that can impact structures, systems, and components) 2.

Design Load Definition for Steam Dryers (including the development of an analytical methodology to calculate fluctuating pressure loads on the steam dryer that is validated against SMT data and plant-specific instrumented steam dryers) 3.

BWR Steam Dryer Stress and Limit Curves (including the performance of a finite element analysis using appropriate damping values, justification of bias error and uncertainty for each category of the stress calculation on a frequency-specific basis, and development of limit curves based on plant data accounting for bias errors and uncertainties as well as concentration and weld size factors) 4.

PWR Steam Generator Stress and Design Margin (including the evaluation of the dynamic response, stress, and design margin of the internal components in steam generators) 5.

Evaluation of Other Plant Components (including the evaluation of potential adverse effects from pressure fluctuations and vibration on piping and components in reactor coolant, steam, feedwater, and condensate systems, such as safety relief valves, power-operated valves, and sampling probes) 6.

Power Ascension Data (including the development of power ascension procedures with limit curves and frequent data collection, walkdowns, and hold points for data evaluation and NRC staff interaction) 7.

Monitoring of Potential Adverse Flow Effects (including the development of proactive methods for identifying acoustic resonance or severe hydrodynamic loading prior to component failure)

If you have any suggestions regarding these considerations, we would appreciate receiving your comments within one month such that the NRC staff can prepare the proposed RIS in a timely manner.

Please contact Kamal Manoly, Chief, Mechanical & Civil Engineering Branch, Division of Engineering, Office of Nuclear Reactor Regulation, at 301-415-2765, for any additional information.

Sincerely,

/RA/

John A. Grobe, Associate Director for Engineering and Safety Systems Office of Nuclear Reactor Regulation Project No. 691 cc: See next page ADAMS ACCESSION NO.: ML071710615 NRR-106 OFFICE PSPB/PM PSPB/LA EMCB/BC CIB2/BC PGCB/BC PSPB/BC NAME MHoncharik DBaxley KManoly KGruss MMurphy SRosenberg DATE 7/5/07 6/22/07 6/22/07 7/2/07 6/27/07 7/5 /07 OFFICE DPR/D DE/D ADES/AD NAME MCase PHiland JGrobe DATE 7/6/07 7/ 9/07 7 /18 /07 OFFICIAL RECORD COPY

Letter to Randy C. Bunt from John A. Grobe dated: July 18, 2007

SUBJECT:

POTENTIAL ADVERSE FLOW EFFECTS IN NUCLEAR POWER PLANTS DISTRIBUTION:

PUBLIC PSPB Reading File RidsNrrDpr RidsNrrDprPspb RidsNrrAdes RidsNrrAdra RidsNrrLADBaxley RidsAcrsAcnwMailCenter RidsNrrPMMHoncharik RidsOgcMailCenter Chakrapani Basavaraju Alexander Tsirigotis Kamal Manoly Thomas Scarborough Kimberly Gruss Martin Murphy Matthew Mitchell John Honcharik SRosenberg (Hardcopy)

BWR Owners Group Project No. 691 Mr. Doug Coleman Vice Chair, BWR Owners Group Energy Northwest Columbia Generating Station Mail Drp PE20 P.O. Box 968 Richland, WA 99352-0968 DWCOLEMAN@energy-northwest.com Mr. Amir Shahkarami Executive Chair, BWR Owners Group Exelon Generation Co., LLC Cornerstone II at Cantera 4300 Winfield Road Warrenville, IL 60555 amir.shahkarami@exeloncorp.com Mr. Richard Libra Executive Vice Chair, BWR Owners Group DTE Energy - Fermi 2 M/C 280 OBA 6400 North Dixie Highway Newport, MI 48166 librar@dteenergy.com Mr. William A. Eaton Entergy Operations Inc.

P.O. Box 31995 Jackson, MS 39286 weaton@entergy.com Mr. Richard Anderson First Energy Nuclear Operating Co Perry Nuclear Power Plant 10 Center Road Perry, OH 44081 randerson@firstenergycorp.com Mr. Scott Oxenford Energy Northwest Columbia Generating Station Mail Drp PE04 P.O. Box 968 Richland, WA 99352-0968 wsoxenford@energy-northwest.com Mr. James F. Klapproth GE Energy M/C A-16 3901 Castle Hayne Road Wilmington, NC 28401 james.klapproth@gene.ge.com Mr. Joseph E. Conen Regulatory Response Group Chair BWR Owners Group DTE Energy-Fermi 2 200 TAC 6400 N. Dixie Highway Newport, MI 48166 conenj@dteenergy.com Mr. J. A. Gray, Jr.

Regulatory Response Group Vice-Chair BWR Owners Group Entergy Nuclear Northeast 440 Hamilton Avenue Mail Stop 12C White Plains, NY 10601-5029 JGray4@entergy.com Mr. Ken A. McCall, Program Manager GE Energy M/C A-16 3901 Castle Hayne Road Wilmington, NC 28401 kenneth.mccall@ge.com Mr. Tim E. Abney GE Energy M/C A-16 3901 Castle Hayne Road Wilmington, NC 28401 tim.abney@ge.com 4/17/07

GHNE Project No. 710 cc:

Mr. George B. Stramback GE-Hitachi Nuclear Energy Americas LLC 1989 Little Orchard Street M/C HME San Jose, CA 95125-1030 george.stramback@ge.com Mr. James F. Harrison GE-Hitachi Nuclear Energy Americas LLC Project Manager - Fuel Licensing P.O. Box 780 M/C A45 Wilmington, NC 28401 james.harrison@ge.com Ms. Patricia L. Campbell Washington Regulatory Affairs Director GE-Hitachi Nuclear Energy Americas LLC 1299 Pennsylvania Avenue, NW 9th Floor Washington, DC 20004 patricia.campbell@ge.com Mr. Andrew A. Lingenfelter Manager, GNF Fuel Engineering P.O. Box 780 M/C F12 Wilmington, NC 28401 andy.lingenfelter@gnf.com Mr. Robert E. Brown Senior Vice President, Regulatory Affairs GE-Hitachi Nuclear Energy Americas LLC P. O. Box 780, M/C A-30 Wilmington, NC 28401 Bob.Brown@ge.com 06/22/07

BWRVIP cc:

Randy Stark, EPRI BWRVIP Integration Manager Raj Pathania, EPRI BWRVIP Mitigation Manager Ken Wolfe, EPRI BWRVIP Repair Manager Larry Steinert, EPRI BWRVIP Electric Power Research Institute P.O. Box 10412 3420 Hillview Ave.

Palo Alto, CA 94303 Paul J. Davison BWRVIP Executive Oversight Committee PSEG Nuclear, LLC Salem/Hope Creek Nuclear Station 11 Yubas Ave.

Burlington, NJ 08016 Bob Geier, Technical Chairman BWRVIP Assessment Committee Exelon Corporation Cornerstone II at Cantera 4300 Winfield Rd.

Warrenville, IL 60555 Denver Atwood, Technical Chairman BWRVIP Repair Focus Group Southern Nuclear Operating Co.

Post Office Box 1295 40 Inverness Center Parkway (M/S B031)

Birmingham, AL 35242-4809 Jeff Goldstein, Technical Chairman BWRVIP Mitigation Committee Entergy Nuclear NE 440 Hamilton Ave. (M/S K-WPO-11c)

White Plains, NY 10601 Charles J. Wirtz, Chairman Technical Chairman BWRVIP Integration Committee FirstEnergy Corp.

Perry Nuclear Power Plant (M/S A250) 10 Center Road Perry, OH 44081 Amir Shahkarami, Executive Chairman BWRVIP Integration Committee Exelon Corporation Cornerstone II at Cantera 4300 Winfield Rd.

Warrenville, IL 60555-4012 Robert Carter, EPRI BWRVIP Assessment Manager Jeff Landrum, EPRI BWRVIP Inspection Manager EPRI NDE Center P.O. Box 217097 1300 W. T. Harris Blvd.

Charlotte, NC 28221 Richard Anderson, Executive Chairman BWRVIP Assessment Committee Vice President, Nuclear FirstEnergy Service Co.

Perry Nuclear Power Plant (M/S A-PY-290) 10 Center Road Perry, OH 44081 Joe Donahue BWRVIP Executive Oversight Committee V. P., Nuclear Engineering & Services Progress Energy, Inc.

410 S. Wilmington St. (M/S PEB6)

Raleigh, NC 27601-1849 Dennis Madison BWRVIP Executive Oversight Committee Site Vice President Southern Nuclear Operating Co.

Edwin I. Hatch Nuclear Plant US Hwy 1 N Baxley, GA 31515-2010