Summary of Category 1 Working-Level Meeting with PPL Susquehanna, LLC (PPL) to Discuss the Licensees Proposed License Amendment Request Regarding Electrical Distribution Systems Dated March 2, 2007
ML071710019
Person / Time
Site: Susquehanna  
Issue date: 06/21/2007
From: Richard Guzman
NRC/NRR/ADRO/DORL/LPLI-1
To:
Guzman R, NRR/DORL, 415-1030
References
Download: ML071710019 (6)


Text

June 21, 2007 LICENSEE:

PPL Susquehanna, LLC (PPL)

FACILITY:

Susquehanna Steam Electric Station, Unit 1 and 2 (SSES 1 and 2)

SUBJECT:

SUMMARY

OF JUNE 13, 2007, CATEGORY 1 WORKING-LEVEL MEETING WITH PPL TO DISCUSS THE LICENSEES PROPOSED LICENSE AMENDMENT REQUEST REGARDING ELECTRICAL DISTRIBUTION SYSTEMS DATED MARCH 2, 2007 (AGENCYWIDE DOCUMENTS ACCESS AND MANAGEMENT SYSTEM (ADAMS)

ACCESSION NO. ML070720545)

On June 13, 2007, a public meeting was held between the U.S. Nuclear Regulatory Commission (NRC), and representatives of PPL at NRC Headquarters, One White Flint North, 11555 Rockville Pike, Rockville, Maryland. The purpose of the meeting was to discuss PPLs March 2, 2007, amendment request to revise the SSES 2 Technical Specifications (TSs).

PPL provided an overview of their proposed amendment request to revise TS 3.8.1, AC (alternating current) Sources Operating, in order to support the 4.16 kilo-volt (kV) bus maintenance during the SSES 1 refueling outage scheduled for spring 2008. PPL presented various configurations of the SSES 1 and 2 electrical distribution system with respect to the proposed note to the SSES 2 TSs. It also discussed the interrelation of SSES 1 and 2 common loads and how maintenance on one unit affects the operation of the other. PPL indicated that the existing SSES 2 TS 3.8.1 requires that when a Unit 1 4.16 kV bus is de-energized for routine maintenance, limiting condition for operation (LCO) 3.8.1 Conditions A, B, and D are entered. Specifically, an offsite circuit (Condition A) and a diesel generator (Condition B) are declared inoperable, and TS 3.8.1 Condition D requires a 12-hour completion time to perform all the maintenance work on the bus. The time required to perform the planned maintenance is between 50 and 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br />. PPL presented its proposed resolution to add a note to SSES 2 TS 3.8.1 which would effectively remove the requirement for entry into TS 3.8.1, but would retain entry into LCO 3.8.7 Condition C during the planned maintenance.

PPL concluded that (1) since LCO 3.8.7 Condition C is the only affected TS LCO condition after application of the proposed note to LCO 3.8.1, the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> completion time is applicable, and sufficient time is provided to perform the necessary 4.16 kV bus maintenance, and (2) adding the proposed note to SSES 2 TS 3.8.1 precludes the need to enter any LCO 3.8.1 conditions for the planned SSES 1 4.16 kV bus configuration.

The Pennsylvania state contact, Brad Fuller, was in attendance. No Public Meeting Feedback forms were received. Enclosure 1 is a list of meeting attendees and Enclosure 2 is a copy of the licensees slides presented at the meeting (ML071710427).

PPL Susquehanna, LLC Please direct any inquiries to me at 301-415-1030, or rvg@nrc.gov.

/RA/

Richard V. Guzman, Senior Project Manager Plant Licensing Branch I-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-387 and 50-388

Enclosures:

1. List of Attendees
2. Licensees Handouts/Slides cc w/encls: See next page

ML071710019 OFFICE LPLI-1/PM LPLI-1/LA LPLI-1/BC NAME RGuzman SLittle MKowal DATE 6/21/07 6/21/07 6/21/07

LIST OF ATTENDEES NUCLEAR REGULATORY COMMISSION (NRC)

NUCLEAR REACTOR REGULATION (NRR) CATEGORY 1 MEETING WITH PPL SUSQUEHANNA, LLC (PPL)

LICENSE AMENDMENT APPLICATION FOR TECHNICAL SPECIFICATION 3.8.1, AC SOURCES OPERATING, SUSQUEHANNA STEAM ELECTRIC STATION, UNIT 1 AND 2 JUNE 13, 2007 NAME ORGANIZATION

1. Richard Guzman NRC/NRR/Plant Licensing Branch I-1
2. Sheila Ray NRC/NRR/Division of Engineering
3. Yoira Diaz NRC/NRR/Division of License Renewal
4. Drew Stuyvenberg NRC/NRR/Division of License Renewal
5. Patrick Boughan NRC/NRR/Division of Engiineering
6. Duane Filchner PPL
7. Todd Creasy PPL
8. Philip Brady PPL
9. Brad Fuller Pennsylvania Bureau of Radiation Protection

MEETING SLIDES

Susquehanna Steam Electric Station, Units 1 and 2 cc:

Britt T. McKinney Sr. Vice President and Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Blvd., NUCSB3 Berwick, PA 18603-0467 Robert A. Saccone General Manager - Nuclear Operations PPL Susquehanna, LLC 769 Salem Blvd., NUCSB3 Berwick, PA 18603-0467 Terry L. Harpster General Manager - Plant Support PPL Susquehanna, LLC 769 Salem Blvd., NUCSA4 Berwick, PA 18603-0467 Rocco R. Sgarro Manager - Nuclear Regulatory Affairs PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Supervisor -

Nuclear Regulatory Affairs PPL Susquehanna, LLC 769 Salem Blvd., NUCSA4 Berwick, PA 18603-0467 Michael H. Crowthers Supervising Engineer Nuclear Regulatory Affairs PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Steven M. Cook Manager - Quality Assurance PPL Susquehanna, LLC 769 Salem Blvd., NUCSB2 Berwick, PA 18603-0467 Luis A. Ramos Community Relations Manager, Susquehanna PPL Susquehanna, LLC 634 Salem Blvd., SSO Berwick, PA 18603-0467 Bryan A. Snapp, Esq Assoc. General Counsel PPL Services Corporation Two North Ninth Street, GENTW3 Allentown, PA 18101-1179 Supervisor - Document Control Services PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Richard W. Osborne Allegheny Electric Cooperative, Inc.

212 Locust Street P.O. Box 1266 Harrisburg, PA 17108-1266 Director - Bureau of Radiation Protection Pennsylvania Department of Environmental Protection P.O. Box 8469 Harrisburg, PA 17105-8469 Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 35, NUCSA4 Berwick, PA 18603-0035 Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Board of Supervisors Salem Township P.O. Box 405 Berwick, PA 18603-0035 Dr. Judith Johnsrud National Energy Committee Sierra Club 443 Orlando Avenue State College, PA 16803