CONTAINMENT SYSTEMS SURVEILLANCE REQUIREMENTS (Continued)

c.

At least once per 18 months, during shutdown, by:

1.

Verifying that each automatic valve in the flow path actuates to its correct position on CSAS and RAS test signals.

2.

Verifying that upon a RAS test signal, the containment sump isolation valves open and that a recirculation mode flow path via an OPERABLE shutdown cooling heat exchanger is established.

3.

Verifying that each spray pump starts automatically on a CSAS test signal.

d.

Verify each spray nozzle is unobstructed following maintenance which could result in nozzle blockage.

ARKANSAS - UNIT 2 3/4 6-.11 Amendment No. 94,245, 272