Text

SOUTHERN CALIFORNIA EDISON An EDISON INTERNATIONAL Company A. Edward Scherer Manager of Nuclear Regulatory Affairs May 25, 2007 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555

Subject:

Docket No. 50-362 Special Report: Inspection of Steam Generator Tubes, Cycle 14 San Onofre Nuclear Generating Station, Unit 3

Dear Sir or Madam:

San Onofre Nuclear Generating Station Unit 3 entered Mode 4 on December 7, 2006 following the completion of an inspection of steam generator tubes during the Cycle 14 Refueling Outage.

Technical Specification (TS) 5.7.2.c states that a "report shall be submitted within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program."

Accordingly we have attached the required report. The report contains no new commitments.

If you require any additional information, please advise.

Sincerely, Attachment cc:

B. S. Mallett, NRC Regional Administrator, Region IV N. Kalyanam, NRC Project Manager, San Onofre Units 2, and 3 C. C. Osterholtz, NRC Senior Resident Inspector, San Onofre Units 2 & 3 P.O. Box 128 San Clemente, CA 92672 949-368-7501 Fax 949-368-7575 AocA

Inspection of Steam Generator Tubes Attachment Special Report Page 1 of 7 SPECIAL REPORT - INSPECTION OF STEAM GENERATOR TUBES Regulatory Reporting Requirements Reporting Requirement 5.7.2.c of Appendix A, Technical Specification to Facility Operating License NPF-1 5 requires a report of steam generator tube inspections to be submitted to the Nuclear Regulatory Commission within 180 days after the initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.2.11, Steam Generator (SG) Program.

The report shall include:

1. The scope of inspections performed on each SG,
2. Active degradation mechanisms found,
3. Nondestructive examination techniques utilized for each degradation mechanism,
4. Location, orientation (if linear), and measured sizes (if available) of service induced indications,
5. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism,
6. Total number and percentage of tubes plugged or repaired to date,
7. The results of condition monitoring, including the results of tube pulls and in-situ testing,
8. The effective plugging percentage for all plugging and tube repairs in each SG, and
9. Repair method utilized and the number of tubes repaired by each repair method.

Inspection Scope Table 1 summarizes the scope of inspections performed on each SG. Also, when indications by the bobbin probe were non-quantifiable or distorted, the inspection scope included inspection with the Plus Point Probe. There were no significant inspection scope expansions in response to inspection results.

Inspection of Steam Generator Tubes Special Report Attachment Page 2 of 7 TABLE 1 - Scope of Inspections Performed: Unit 3 Cycle 14 (U3C14) Refueling Outage Inspection Scope SG E-088 Tubes/Percent SG E-089 Tubes/Percent Full length of tube with the bobbin probe (excluding U-8646/100%

8699/100%

bends for Rows 1-3)

Hot leg expansion transition at the top-of-tubesheet with the Plus Point Probe to an extent of 4 inches 8646/100%

8699/100%

above to 13 inches below the top-of-tubesheet Cold leg expansion transition at the top-of-tubesheet with the Plus Point Probe to an extent of 2 inches 8646/100%

8699/100%

above to 13 inches below the top-of-tubesheet U-bend regions of Rows 1, 2, and 3 with both mid-184/100%

174/100%

frequency and high-frequency Plus Point Probes U-bend regions of Row 4 with the mid-frequency Plus 64/100%

64/100%

Point Probe U-bend regions of Rows 5 through 10 with the mid-74/20%

78/20%

frequency Plus Point Probe Plus Point Probe examination of tube support intersections with dents greater than, or equal to, 2 309/100%

337/100%

volts Plus Point Probe examination of dings greater than, or 319/100%

447/100%

equal to, 4 volts Plus Point Probe examination of all tube support intersections with quantified wear indications by the 816/100%

542/100%

bobbin probe

Inspection of Steam Generator Tubes Special Report Attachment Page 3 of 7 Results of the Inspection of Tubes Table 2 summarizes the active degradation mechanisms found and number of tubes plugged. Each tube is only counted once in this listing, although it may also have an eddy current indication of a type below the point in the listing where it appears. The Appendices provide detail.

TABLE 2 - Active Degradation Mechanisms Found and Number of Tubes Plugged U3C14 Refueling Outage Steam Generator E-088 E-089 Indication Orientation/Location Tubes with circumferentially oriented ID indications near the 2

1 expansion transition at the top of the hot leg tubesheet Tubes with circumferentially oriented OD indications near the 0

1 expansion transition at the top of the hot leg tubesheet Tubes with axially oriented ID indications below the expansion 3

0 transition at the top of the hot leg tubesheet Tubes with indications of wear at tube support locations 23 8

Tubes with Data Quality / ALARA complications 1

1 Total 29 11

Inspection of Steam Generator Tubes Special Report Attachment Page 4 of 7 Examination Techniques Table 3 provides the list of Nondestructive Examination (NDE) techniques utilized for each degradation mechanism found as a result of the inspection. Other mechanisms that were considered in the inspection planning are also included in Table 3.

TABLE 3 - Nondestructive Examination (NDE) Techniques Utilized for Each Degradation Mechanism Indication Orientation/Location Probe Type for Detection Characterization Circumferentially oriented ID (initiated on the inside-diameter of the tubing wall) indications near the expansion transition at the top of the hot leg Plus Point Plus Point tubesheet Circumferentially oriented OD (initiated on the outside-diameter of the tubing wall) indications near the expansion transition at the top of the hot leg Plus Point Plus Point tubesheet Axially oriented ID indications near or below the expansion transition at the Plus Point Plus Point top of the hot leg tubesheet Indications of wear at tube support locations Bobbin Plus Point Miscellaneous preventive plugging Bobbin or Plus Point Plus Point Axially oriented ID indications and Circumferentially oriented ID indications at the Plus Point Plus Point top of the cold leg tubesheet Axially oriented ID indications and Circumferentially oriented ID indications in Plus Point Plus Point explosively expanded tubing within the cold leg tubesheet Circumferentially oriented ID indications below the expansion transition at the Plus Point Plus Point top of the hot leg tubesheet Axially oriented OD indications and Circumferentially oriented OD indications Plus Point Plus Point in the sludge pile region near the top of the hot and cold leg tubesheets Axially oriented OD indications not associated with a tube support (freespan)

Bobbin Plus Point Axially oriented OD indications at tube support locations Bobbin Plus Point Plus Point (Note 1)

Plus Point Bobbin Plus Point Axially oriented ID indications at tube support locations Plus Point (Note 1)

Plus Point Axially oriented ID indications and Circumferentially oriented ID indications in Plus Point Plus Point Low-Row U-bends Circumferentially oriented ID indications at the flanks of tubing bends and Axially Plus Point Plus Point oriented ID indications in similar tubing bends Axially oriented OD indications in Low-Row U-bends Plus Point Plus Point Circumferentially oriented ID indications and Circumferentially oriented OD Plus Point Plus Point indications at dented tube supports (dents Ž2 volts)

Axially oriented OD indications at dings in tubing freespan (dings <5 volts)

Bobbin Plus Point Axially oriented OD indications at dings in tubing freespan Plus Point Plus Point Tube Plug Degradation Visual Visual Cold Leg Thinning at tube supports Bobbin Plus Point Volumetric indications Bobbin or Plus Point Plus Point Note 1: Plus Point technique is used at dents with greater than, or equal to, two volts.

Inspection of Steam Generator Tubes Special Report Attachment Page 5 of 7 Condition Monitoring Condition Monitoring demonstrated that performance criteria in Technical Specifications sections 5.5.2.11.b.1 (structural integrity) and 5.5.2.11.b.2 (accident induced leakage) were met during operation prior to this inspection.

In situ pressure testing was not needed for any eddy current indications. All indications were below screening criteria of the Electric Power Research Institute (EPRI) In Situ Pressure Testing Guidelines.

Table 4 addresses location, orientation and measured sizes of service-induced indications (except wear of tubing at tube supports). Appendices 1 and 2 provide definitions for terms used in Table 4.

Appendices 3 and 4 address location and measured sizes of service-induced indications of wear of tubing at tube supports.

No tubes were removed (pulled) for destructive testing during this outage.

TABLE 4 - Measured Sizes of Service-Induced Indications SG Row Col Elev Inch Ind Origin PP Volts Depth PDA FLDA PP Length CA 88 23 119 TSH -0.11 SCI ID 0.26 88 31 59 TSH -2.11 SAI ID 0.63 39 32.30 0.18 88 32 128 TSH -0.07 MCI ID 0.49 51 1.86 23 88 42 70 TSH

-0.8 SAI ID 0.43 43 24.44 0.18 88 42 70 TSH -2.15 SAI ID 0.46 49 28.77 0.53 88 43 73 TSH -1.26 SAI ID 0.76 40 23.85 0.95 88 43 73 TSH -2.52 SAI ID 0.58 29 18.25 0.32 88 43 73 TSH

-3.1

- SAI ID 0.64 -

26 18.50 0.14 89 24 134 TSH +0.12 SCI OD 0.24 70 3.14 89 30 50 TSH -0.05 MCI ID 0.56 57 4.51 50 Notes:

PP = Plus Point Depth = Percent of Tube Wall Thickness PDA = Percent Degraded Area FLDA = Flaw-Length Degraded Area PP Length (units of measure are inches)

CA = Crack Angle (degrees)

Inspection of Steam Generator Tubes Special Report Attachment Page 6 of 7 Repair Methods, Number of Tubes Repaired by Each Repair Method and Effective Plugging Percentage The repair method of sleeving has not been used for tube repair at Unit 3.

All tube plugging was performed using the design, materials, and installation methods of AREVA. A "roll" method was used for all tube plugs. Table 5 specifies the repair methods used and the effective plugging percentage upon completion of the U3C14 inspection and repairs.

TABLE 5 - Number of Tubes Repaired and Effective Plugging Percentage SG 88 89

  1. Tubes Plugged in 3C14 29 11
  1. Tubes Plugged To Date 733 662 Effective Plugging Percentage 7.9 7.1 L

Inspection of Steam Generator Tubes Attachment Special Report Page 7 of 7 Description of Appendices Appendix 1 -

Steam Generator Reference Information Appendix 2 -

Legend for Appendices 3 and 4 Appendix 3 -

Tube Inspection Summary, Steam Generator E-088 Appendix 4 -

Tube Inspection Summary, Steam Generator E-089

Inspection of Steam Generator Tubes Special Report Appendix 1 Page 1 of 4 Appendix 1 Steam Generator Reference Information

Inspection of Steam Generator Tubes Special Report Appendix 1 Page 2 of 4 Steam Generator CE Model 3410 Tube Support Drawing 10H 09H

)10C0 0

30.75" 09C 30.75' 08C 30.75" 07C 08H 07H 06H 05H 38' 06C i

34.

05C 04H 03H 02H 01H TSH TEH 04-C 38.

03C 36" 02C 35.

01C 27.25" TSC 238 TEC

Inspection of Steam Generator Tubes Special Report Appendix 1 Page 3 of 4 STEAM GENERATOR TUBE SUPPORT INTERSECTIONS ABOVE THE 7 TH (FULL) EGGCRATE SUPPORT SUPPORT INTERSECTIONS ROW STRUCTURES 122-147 08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 120-121*

08H 09H 10H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 10C 09C 08C 115-119 08H 09H DBH VH1 VH2 VH3 VSM VC3 VC2 VC1 DBC 09C 08C 86-114 08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 84-85*

08H 09H DBH VH2 VH3 VSM VC3 VC2 DBC 09C 08C 83 08H DBH VH2 VH3 VSM VC3 VC2 DBC 08C 51-82 08H DBH VH3 VSM VC3 DBC 08C 49-50*

08H DBH VSM DBC 08C 19-48 DBH VSM DBC 1-18 DBH DBC

  • Indicates those rows adjacent to scallop bars

Inspection of Steam Generator Tubes Special Report Appendix 1 Page 4 of 4 SOUTHERN CALIFORNIA EDISON, SAN ONOFRE CE MODEL 3410 STEAM GENERATOR 10 zo so 40 50 Go 70 60 s0 1010 11N 120 130 140 150 160 110 0000 a

at

0. 0000 OO OO O

140 13) 120 Ito 100 s0 80 70 so 0,

0 0

C 0Q 0oo 000° Co 01 00,.0, 0

MnO o~'

O o

~

Q~~~~o;,o 10 00 0o0 0o 00o

)

od.

>o o' ° lo O0 0og 0

Qg 0

0~~o o;06101 1 6^o..o016 IQ%

o~

ooo6 vo°oo o

0-6 0 OR O O 1"

-oo oo o

o oV-ýj o O*Oo 0 ~ ~

~

~

0o' 00-'00o.

I 00

-o**'

6o.

Q 0 o n'==.0 O,

o.

QoO O " *o 08 Q

()Q,:

` l o o Q

100

  • o.NoN,=

"o.

ý,o, 9

o-o.5 149) 131 Ito 60 50

.10 30 20 40 30 20 10 gogo og 13 0 o0

oooogjo, 0"00 0' 0 0'o~o o0.

Q 0%0~

000h 6

I0dQ0 I

Q o Q, q

.06 1i, t

Q C

A

-2:

i

.0

+,

000 1Ao2L8 0nn nn10 0 ~ ~~ ~

~

~

-g

,0

..0IDI.6'

o

-rý

~

-~

0 0-0 0 0

0-,05O 60o0.* 0 0

-0n 00 0 0

0 0 oOo0 0Ro o

".0000 No 0

010'0 0 00,01

0000, IQ-cc.%

p0ý ao.

09,0 10 2)0 30 40 so so 70 80 s0 1to 110 120 150 140 IS0 164) 170

Inspection of Steam Generator Tubes Special Report Appendix 2 Page 1 of 2 Appendix 2 Legend for Appendices 3 and 4

Inspection of Steam Generator Tubes Special Report Appendix 2 Page 2 of 2 List of Abbreviations and Format Used to Describe Indications from Rotating Probe Testing Abbreviations Explanation of the Abbreviations SCI Single Circumferential Indication MCI Multiple Circumferential Indications SAI Single Axial Indication MAI Multiple Axial Indications MMI Mixed Mode Indications SVI Single Volumetric Indication (i.e. no special axial or circumferential aspect)

MVI Multiple Volumetric Indications (i.e. no special axial or circumferential aspect)

TWD Through Wall Depth (an indication of tubing wear used for volumetric wear indicated with a percent value shown in the next column)

Format In Appendices 3 and 4, a single line of data is associated with each individual rotating probe indication. Below is a descriptive example of the format.

1. All "I-Code" indications require a single line entry. The example above displays the form of a Resolution Report line. The VOLTS field contains the Plus Point voltage of the largest, most representative response.

The DEG field contains the corresponding phase angle. The CHN field contains the reporting channel (i.e.

the appropriate 300 kHz Plus Point channel). The IND field contains the appropriate 3-letter code (see list above). The %TW field indicates the percent wall loss for wear indications. The LOCATION field contains the abbreviation for the referenced landmark and the (FROM-TO) distance for the indication. The EXT fields contain the landmarks of the beginning and end of the test extent. The UTIL 1 field contains the 300 kHz pancake voltage of the largest, most representative response. The UTIL 2 field contains notes. The CAL#

field identifies the calibration number associated with the acquired data. The LEG field identifies the Hot or Cold Leg as the location of the probe origination. The PROBE field contains the abbreviated identifier of the probe type used for the inspection. Exceptions to this general guidance are provided in paragraphs 2 through 4 below.

2.

For axial indications of extended length, the location should be ranged (FROM-TO) in the LOCATION field. If the range of such an indication includes any part of a support structure, it should be referenced from that landmark.

3.

For "I-Code" indications which have both axial and circumferential extent (i.e. SVI, MVI, and MMI), the location should be ranged in the LOCATION field (as above) and the UTIL 2 field should contain the circumferential length.

4.

Some data lines contain a note abbreviation in the UTIL 1 and/or UTIL 2 columns. These are the definitions of these abbreviations:

LAR: Lead Analyst Reviewed LOCOK: Location Verification

Inspection of Steam Generator Tubes Special Report Appendix 3 Page 1 of 28 Appendix 3 Tube Inspection Summary Steam Generator E-088

AREVA NP Inc 11/18/06 09:45:08 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 2 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY:

QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 7

1 0.24 78 P3 TWD 17 DBC

+0.94 TEC TEH 29 HOT 600UL 16 2

0.30 59 P2 TWD 14 05H

-0.63 TEC TEH 20 HOT 600UL 43 5

0.49 109 P2 TWD 21 04C

-0.12 TEC TEH 20 HOT 600UL 35 7

0.23 51 P2 TWD 18 VSM

-0.82 TEC TEH 25 HOT 600UL 49 7

0.20 127 P2 TWD 11 06H

-1.16 TEC TEH 24 HOT 600UL 43 9

0.16 157 P2 TWD 12 VSM

-0.84 TEC TEH 25 HOT 600UL 29 13 0.25 72 P3 TWD 11 DBH

+0.98 TEC TEH 24 HOT 600UL 0.05 15 P3 TWD 2 DBH

-2.01 TEC TEH 24 HOT 600UL 43 13 0.30 155 P2 TWD 20 VSM

-0.78 TEC TEH 25 HOT 600UL 66 14 0.19 130 P2 TWD 15 04C

-0.16 TEC TEH 25 HOT 600UL 72 14 0.31 123 P3 TWD 13 DBC

-1.65 TEC TEH 24 HOT 600UL 75 15 0.11 8

P3 TWD 10 DBC

+1.88 TEC TEH 25 HOT 600UL 77 15 0.28 130 P3 TWD 12 DBC

-1.89 TEC TEH 24 HOT 600UL 51 17 0.23 123 P2 TWD 11 VH3

+1.15 TEC TEH 9

HOT 600UL 22 18 0.21 64 P2 TWD 11 VSM

-0.97 TEC TEH 9

HOT 600UL 61 19 0.32 90 P2 TWD 16 VH3

+0.95 TEC TEH 9

HOT 600UL 65 19 0.42 100 P2 TWD 21 VH3

+0.89 TEC TEH 9

HOT 600UL 69 19 0.43 63 P2 TWD 21 VH3

+0.77 TEC TEH 9

HOT 60OUL 0.46 115 P2 TWD 22 VH3

-0.83 TEC TEH 9

HOT 600UL 83 19 0.31 89 P2 TWD 16 VH2

+0.72 TEC TEH 42 HOT 600UL 0.26 92 P2 TWD 13 09C

+1.21 TEC TEH LOCOK 42 HOT 600UL 24 20 0.38 89 P2 TWD 19 VSM

-0.91 TEC TEH 9

HOT 600UL 74 20 0.20 175 P3 TWD 16 DBH

+1.60 TEC TEH 11 HOT 600UL 78 20 0.27 41 P3 TWD 20 DBH

+1.36 TEC TEH 11 HOT 600UL 82 20 0.12 97 P3 TWD 11 DBC

+2.00 TEC TEE 43 HOT 600UL 43 21 0.23 113 P2 TWD 16 VSM

+0.70 TEC TEH 11 HOT 600UL 79 21 0.26 116 P3 TWD 9 DBC

+1.57 TEC TEH 9

HOT 600UL 0.60 106 P3 TWD 21 DBH

+1.71 TEC TEH 9

HOT 600UL 60 22 0.58 62 P2 TWD 26 VH3

-0.87 TEC TEH LAR 9

HOT 600UL 80 22 0.27 74 P3 TWD 9 DBH

+2.13 TEC TEH 9

HOT 600UL 82 22 0.29 123 P3 TWD 11 DBC

+1.75 TEC TEH 42 HOT 60OUL 71 23 0.12 44 P3 TWD 10 DBH

+1.65 TEC TEH 11 HOT 600UL 0.31 121 P2 TWD 21 VH3

-0.75 TEC TEH 11 HOT 600UL 98 24 0.15 144 P2 TWD 8 06C

+0.02 TEC TEH 42 HOT 60OUL 0.26 141 P2 TWD 14 06C

+0.90 TEC TEH 42 HOT 600UL 71 25 0.27 120 P2 TWD 14 04H

-0.83 TEC TEH 9

HOT 600UL 83 25 0.20 57 P3 TWD 8 DBC

-0.52 TEC TEH 42 HOT 600UL 77 27 0.21 12 P3 TWD 7 DBC

+2.13 TEC TEH 9

HOT 60OUL 76 28 0.14 88 P3 TWD 10 DBC

+1.90 TEC TEH 15 HOT 600UL 82 28 0.22 52 P3 TWD 17 DBH

-1.75 TEC TEH 43 HOT 600UL 94 28 0.22 127 P2 TWD 16 VH3

+0.70 TEC TEH 43 HOT 600UL 0.24 107 P2 TWD 18 VH2

-0.98 TEC TEH 43 HOT 60OUL

AREVA NP Inc 11/18/06 09:45:08 Customer Name: SONGS Unit 3 Component: S/G 88 Page 3 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 0.36 111 P2 TWD 23 VSM

-0.80 TEC TEH 43 HOT 60OUL 0.16 145 P2 TWD 12 VH2

+0.08 TEC TEH 43 HOT 600UL 98 28 0.11 38 P3 TWD 9 DBH

-2.00 TEC TEH 43 HOT 600UL 102 28 0.20 153 P2 TWD 15 VH2

+0.84 TEC TEH 43 HOT 600UL 77 29 0.18 110 P3 TWD 12 DBC

-1.81 TEC TEH 19 HOT 60OUL 0.19 153 P2 TWD 13 VC3

-0.82 TEC TEH 19 HOT 60OUL 79 29 0.20 172 P3 TWD 9 DBH

+1.39 TEC TEH 18 HOT 600UL 0.30 77 P2 TWD 14 VC3

-0.87 TEC TEH 18 HOT 600UL 89 29 0.32 116 P2 TWD 22 VH2

+0.06 TEC TEH 43 HOT 60OUL 0.19 147 P2 TWD 14 VH2

+0.94 TEC TEH 43 HOT 600UL 99 29 0.27 131 P3 TWD 11 DBH

+1.69 TEC TEH 42 HOT 600UL 107 29 0.32 153 P2 TWD 16 VH2

-0.62 TEC TEH 42 HOT 600UL 58 30 0.29 98 P2 TWD 19 VH3

-1.03 TEC TEH 19 HOT 600UL 60 30 0.43 112 P2 TWD 19 VH3

-0.88 TEC TEH 18 HOT 600UL 78 30 0.26 156 P2 TWD 18 VH3

-0.83 TEC TEH 19 HOT 60OUL 0.18 35 P2 TWD 13 VH3

-0.26 TEC TEH 19 HOT 600UL 0.32 86 P2 TWD 21 VH3

+0.71 TEC TEH 19 HOT 60OUL 0.23 29 P2 TWD 16 VSM

+0.06 TEC TEH 19 HOT 600UL 0.56 124 P2 TWD 30 VSM

+0.87 TEC TEH 19 HOT 600UL 0.21 81 P3 TWD 14 DBH

+1.23 TEC TEH 19 HOT 600UL 102 30 0.36 98 P2 TWD 17 08C

-1.08 TEC TEH 42 HOT 60OUL 0.19 113 P2 TWD 10 08C

+0.00 TEC TEH 42 HOT 60OUL 73 31 0.21 73 P2 TWD 16 VH3

+0.88 TEC TEH 19 HOT 600UL 75 31 0.21 59 P2 TWD 9 VH3

+0.80 TEC TEH 18 HOT 600UL 0.26 150 P3 TWD 11 DBC

+2.08 TEC TEH 18 HOT 600UL 77 31 0.38 147 P2 TWD.24 VSM

+0.86 TEC TEH 19 HOT 600UL 0.36 139 P3 TWD 23 DBH

+2.01 TEC TEH 19 HOT 600UL 0.19 138 P2 TWD 12 VC3

+0.80 TEC TEH 19 HOT 600UL 107 31 0.27 61 P2 TWD 14 VH2

-0.92 TEC TEH 42 HOT 60OUL 109 31 0.21 46 P3 TWD 9 DBC

-1.80 TEC TEH 42 HOT 60OUL 22 32 0.20 45 P3 TWD 13 DBH

+0.82 TEC TEH 19 HOT 600UL 74 32 0.25 22 P3 TWD 18 DBH

+1.47 TEC TEH 19 HOT 600UL 76 32 0.44 41 P3 TWD 17 DBH

+1.30 TEC TEH 18 HOT 600UL 110 32 0.27 151 P2 TWD 19 02H

-0.92 TEC TEH 43 HOT 600UL 73 33 0.27 144 P2 TWD 14 VH3

+0.74 TEC TEH 18 HOT 60OUL 0.39 124 P3 TWD 15 DBH

+1.42 TEC TEH 18 HOT 60OUL 75 33 0.18 154 P2 TWD 14 VC3

+0.70 TEC TEH 19 HOT 600UL 0.23 33 P3 TWD 17 DBC

-1.67 TEC TEH 19 HOT 600UL 81 33 0.31 150 P2 TWD 21 VSM

-0.86 TEC TEH 43 HOT 600UL 0.24 56 P2 TWD 18 VH3

+0.12 TEC TEH 43 HOT 600UL 0.50 142 P2 TWD 28 VH3

+0.88 TEC TEH 43 HOT 600UL 103 33 0.36 108 P2 TWD 17 VH2

+0.71 TEC TEH 42 HOT 600UL 111 33 0.32 74 P2 TWD 16 VH2

-0.95 TEC TEH 42 HOT 60OUL 72 34 0.42 76 P2 TWD 19 VSM

-0.80 TEC TEH 18 HOT 600UL 74 34 0.26 32 P3 TWD 19 DBH

+1.79 TEC TEH 19 HOT 600UL 76 34 0.22 174 P3 TWD 9 DBC

+1.58 TEC TEH 18 HOT 600UL 0.46 93 P2 TWD 20 VH3

+0.84 TEC TEH 18 HOT 600UL 0.19 171 P3 TWD 8 DBH

+1.44 TEC TEH 18 HOT 600UL

AREVA NP Inc 11/18/06 09:45:08 Customer Name: SONGS Unit 3 Component: S/G 88 Page 4 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 114 34 0.28 59 P3 TWD 11 DBC

+1.86 TEC TEH 42 HOT 600UL 63 35 0.17 45 P3 TWD 11 DBH

-1.97 TEC TEH 19 HOT 600UL 75 35 0.08 149 P3 TWD 3 DBC

-1.75 TEC TEH 19 HOT 600UL 81 35 0.12 41 P3 TWD 10 DBC

-2.13 TEC TEH 43 HOT 600UL 111 35 0.68 113 P2 TWD 27 VH2

-0.97 TEC TEH 42 HOT 600UL 72 36 0.17 93 P2 TWD 9 VH3

-0.38 TEC TEH 18 HOT 600UL 76 36 0.36 124 P2 TWD 17 VH3

-0.18 TEC TEH 18 HOT 600UL 0.51 118 P2 TWD 22 VH3

-0.70 TEC TEH 18 HOT 600UL 0.36 172 P3 TWO 14 DBC

+1.92 TEC TEH 18 HOT 600UL 75 37 0.18 157 P3 TWD 8 DBC

+2.01 TEC TEH 18 HOT 600UL 109 37 0.17 159 P3 TWD 14 DBC

+2.07 TEC TEH 43 HOT 600UL 111 37 0.42 122 P2 TWD 19 VH2

-1.00 TEC TEH 42 HOT 600UL 113 37.

0.23 146 P2 TWD 17 VH2

-0.93 TEC TEH 43 HOT 600UL 119 37 0.18 148 P3 TWD 7 DBC

-1.33 TEC TEH 42 HOT 600UL 40 38 0.39 113 P2 TWD 18 VSM

+0.86 TEC TEH 18 HOT 60OUL 0.24 135 P2 TWD 12 VSM

-0.82 TEC TEH 18 HOT 600UL 56 38 0.41 75 P2 TWD 19 VH3

-0.99 TEC TEH 18 HOT 600UL 74 38 0.18 125 P3 TWD 12 DBH

+1.75 TEC TEH 19 HOT 60OUL 78 38 0.15 47 P3 TWD 10 DBH

+1.89 TEC TEH 19 HOT 600UL 80 38 0.16 81 P2 TWD 9 VC3

+0.76 TEC TEH 18 HOT 600UL 0.27 61 P2 TWD 14 VC3

-0.94 TEC TEH 18 HOT 60OUL 0.70 96 P2 TWD 26 VSM

+0.76 TEC TEH 18 HOT 600UL 0.82 131 P2 TWD 29 VH3

-0.90 TEC TEH 18 HOT 600UL 0.51 117 P3 TWD 19 DBH

+1.46 TEC TEH 18 HOT 600UL 110 38 0.13 139 P3 TWD 5 DBH

+1.69 TEC TEH 42 HOT 600UL 25 39 0.21 129 P2 TWD 15 VSM

+0.82 TEC TEH 21 HOT 600UL 31 39 0.16 75 P2 TWD 8 07H

+0.57 TEC TEH 20 HOT 600UL 73 39 0.18 156 P2 TWD 12 VC3

+0.82 TEC TEH 21 HOT 600UL 81 39 0.21 121 P2 TWD 15 VC3

+0.85 TEC TEH 43 HOT 600UL 0.29 142 P2 TWD 20 VH3

-0.77 TEC TEH 43 HOT 600UL 111 39 0.32 73 P2 TWD 16 VH2

-1.01 TEC TEH 42 HOT 600UL 113 39 0.28 88 P2 TWD 19 VH2

-0.95 TEC TEH 43 HOT 600UL 115 39 0.27 106 P2 TWD 14 VH2

-1.19 TEC TEH 42 HOT 600UL 66 40 0.13 90 P3 TWD 11 DBC

+1.97 TEC TEH 21 HOT 600UL 76 40 0.23 151 P3 TWD 10 DBC

+1.78 TEC TEH 20 HOT 600UL 0.28 46 P2 TWD 14 VH3

+0.67 TEC TEH 20 HOT 600UL 80 40 0.34 86 P2 TWD 14 VH3

-0.06 TEC TEH 20 HOT 600UL 0.22 150 P3 TWD 9 DBC

+1.49 TEC TEH 20 HOT 600UL 0.18 53 P2 TWD 9 VC3

+0.68 TEC TEH 20 HOT 600UL 0.23 74 P2 TWD 11 VC3

-0.04 TEC TEH 20 HOT 600UL 0.19 145 P2 TWD 10 VH3

+0.66 TEC TEH 20 HOT 600UL 94 40 0.65 132 P2 TWD 26 VSM

+0.78 TEC TEH 42 HOT 600UL ii6 40 0.07 144 P3 TWO 3 OBN

+1.41 TEC TEN 42 NOT 600UL 118 40 0.25 150 P3 TWD 10 DBH

-1.51 TEC TEH.

42 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 5 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY:

QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 39 41 0.25 132 P2 TWD 17 VSM

-0.86 TEC TEH 21 HOT 600UL 0.16 129 P2 TWD 12 VSM

+0.91 TEC TEH 21 HOT 60OUL 49 41 0.53 116 P2 TWD 22 08H

+1.53 TEC TEH LOCOK 20 HOT 600UL 81 41 0.18 158 P2 TWO 14 VSM

+0.81 TEC TEE 43 HOT 600UL 0.20 150 P2 TWD 14 VH3

+0.87 TEC TEH 43 HOT 60OUL 0.37 70 P2 TWD 24 VH3

+0.00 TEC TEH 43 HOT 600UL 0.20 148 P2 TWD 15 VH3

-0.93 TEC TEH 43 HOT 60OUL 113 41 0.10 170 P3 TWD 9 DBH

+2.20 TEC TEH 43 HOT 60OUL 32 42 0.27 112 P2 TWO 13 07H

+0.73 TEC TEE 20 HOT 6000L 48 42 0.21 141 P2 TWD 10 07H

-0.73 TEC TEH 20 HOT 600UL 72 42 0.25 132 P2 TWD 12 VS0

-0.83 TEC TEH 20 HOT 600UL 0.36 105 P2 TWD 17 VH3

+0.75 TEC TEH 20 HOT 60OUL 0.30 119 P2 TWD 14 VH3

+0.20 TEC TEH 20 HOT 600UL 0.22 75 P2 TWD 11 VH3

-0.36 TEC TEH 20 HOT 600UL 110 42 0.27 139 P2 TWD 19 VH2

-0.75 TEC TEH 43 HOT 600UL 0.06 169 P2 TWD 5 VH2

+0.85 TEC TEH 43 HOT 600UL 114 42 0.07 160 P3 TWD 6 DBH

+2.02 TEC TEH 43 HOT 600UL 120 42 0.23 79 P3 TWD 9 DBC

+1.75 TEC TEH 42 HOT 600UL 124 42 0.22 84 P2 TWD 12 04C

+0.84 TEC TEH 42 HOT 600UL 33 43 0.14 75 P2 TWD 7 07H

+0.67 TEC TEH 20 HOT 600UL 37 43 0.45 88 P2 TWD 20 VSM

+0.76 TEC TEH 20 HOT 600UL 49 43 0.27 102 P2 TWD 13 08H

+1.89 TEC TEH LOCOK 20 HOT 600UL 0.36 66 P2 TWD 17 08H

-1.65 TEC TEH LOCOK 20 HOT 600UL 97 43 0.23 77 P2 TWD 13 VH2

+0.81 TEC TEH 44 HOT 600UL 111 43 0.33 82 P2 TWD 22 VH2

-0.95 TEC TEH 45 HOT 600UL 117 43 0.19 56 P2 TWD 11 VH2

-0.93 TEC TEH 44 HOT 600UL 123 43 0.19 98 P2 TWD 14 08C

+0.89 TEC TEH 45 HOT 600UL 56 44 0.35 40 P2 TWD 16 08H

+0.83 TEC TEH 20 HOT 60OUL 58 44 0.26 99 P2 TWD 18 08H

-0.58 TEC TEH 21 HOT 600UL 72 44 0.31 132 P3 TWD 12 DBC

+2.11 TEC TEH 20 HOT 600UL 120 44 0.23 95 P2 TWD 17 VHI

-1.00 TEC TEH 45 HOT 600UL 67 45 0.11 78 P2 TWD 8 08H

+0.40 TEC TEH 21 HOT 600UL 73 45 0.35 66 P2 TWD 16 VC3

+0.24 TEC TEH 20 HOT 60OUL 75 45 0.24 118 P2 TWD 17 VSM

+0.86 TEC TEH 21 HOT 600UL 0.23 143 P2 TWD 16 VH3

+0.60 TEC TEH 21 HOT 600UL 0.18 68 P2 TWD 13 VH3

+0.18 TEC TEH 21 HOT 600UL 119 45 0.44 99 P2 TWD 20 VHI

+0.88 TEC TEH 44 HOT 60OUL 36 46 0.29 100 P2 TWD 14 VSM

+0.88 TEC TEH 20 HOT 600UL 0.31 74 P2 TWD 15 VSM

-0.83 TEC TEH 20 HOT 600UL 0.18 117 P2 TWD 9 07H

-0.38 TEC TEH 20 HOT 600UL 56 46 0.53 122 P2 TWD 22 08H

+0.57 TEC TEH 20 HOT 60OUL 128 46 0.24 88 P2 TWD 13 02C

+0.85 TEC TEH 44 HOT 600UL 35 47 0.35 157 P2 TWD 14 VSM

+0.80 TEH TEC 3

COLD 600UL 61 47 0.30 128 P2 TWD 13 08H

+0.65 TEH TEC 3

COLD 600UL 0.21 70 P2 TWD 9 03C

-1.03 TEH TEC 3

COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 6 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 75 47 0.29 112 P2 TWD 12 VH3

+0.10 TEH TEC 3

COLD 600UL 0.46 141 P2 TWD 18 VC3

+0.75 TEH TEC 3

COLD 600UL 0.25 3

P3 TWD 11 DBC

+1.56 TEH TEC 3

COLD 60OUL 79 47 0.29 119 P2 TWD 12 VC3

-0.87 TEH TEC 3

COLD 600UL 109 47 0.23 152 P2 TWD 10 09C

-0.90 TEH TEC 9

COLD 600UL 50 48 0.28 144 P2 TWD 12 08H

+1.38 TEH TEC LOCOK 3

COLD 60OUL 76 48 0.50 130 P2 TWD 23 VSM

-0.87 TEH TEC 4

COLD 600UL 0.47 148 P2 TWD 22 VSM

+0.91 TEH TEC 4

COLD 600UL 0.32 52 P2 TWD 16 VC3

+0.97 TEH TEC 4

COLD 600UL 0.07

.152 P2 TWD 5 VC3

-0.93 TEH TEC 4

COLD 600UL 0.23 138 P2 TWD 12 VH3

+0.26 TEH TEC 4

COLD 600UL 0.26 128 P2 TWD 13 VH3

+0.77 TEH TEC 4

COLD 600UL 102 48 0.44 74 P2 TWD 17 VH2

-1.04 TEH TEC 9

COLD 600UL 106 48 0.46 39 P3 TWD 17 DBH

+1.91 TEH TEC 9

COLD 600UL 118 48 0.37 143 P2 TWD 18 VHI

-0.74 TEH TEC 10 COLD 600UL 122 48 0.26 74 P2 TWD 14 VHI

+0.54 TEH TEC 10 COLD 600UL 49 49 0.26 130 P2 TWD 13 08H

-1.40 TEH TEC LOCOK 4

COLD 600UL 0.33 119 P2 TWD 16 08H

+1.60 TEH TEC LOCOK 4

COLD 600UL 91 49 0.31 150 P2 TWD 13 VH2

-0.72 TEH TEC 9

COLD 600UL 105 49 0.26 90 P2 TWD 14 VH2

-0.74 TEH TEC 10 COLD 600UL 123 49 0.23 54 P2 TWD 12 VHI

-1.10 TEH TEC 10 COLD 600UL 125 49 0.35 110 P2 TWD 14 08C

+0.82 TEH TEC 9

COLD 600UL 36 50 0.30 132 P2 TWD 15 07H

-0.24 TEH TEC 4

COLD 600UL 0.32 78 P2 TWD 16 07H

+0.39 TEH TEC 4

COLD 600UL 0.26 153 P2 TWD 13 07H

+0.98 TEH TEC 4

COLD 60OUL 58 50 0.27 116 P2 TWD 12 VH3

+0.82 TEH TEC 3

COLD 60OUL 70 50 0.31 88 P2 TWD 13 08H

-1.07 TEH TEC 3

COLD 600UL 106 50 0.46 90 P2 TWD 21 VH2

+0.94 TEH TEC 10 COLD 600UL 0.20 141 P2 TWD 11 VH3

+0.90 TEH TEC 10 COLD 600UL 0.34 153 P2 TWD 17 VH2

-0.80 TEH TEC 10 COLD 600UL 114 50 0.26 159 P2 TWD 14.

VH2

-0.88 TEH TEC 10 COLD 600UL 35 51 0.27 38 P2 TWD 12 07H

-0.53 TEH TEC 5

COLD 600UL 37 51 0.37 49 P2 TWD 17 07H

+0.42 TEH TEC 6

COLD 600UL 53 51 0.32 109 P2 TWD 16 08H

-1.01 TEH TEC 6

COLD 600UL 0.21 143 P2 TWD 11 07H

-0.28 TEH TEC 6

COLD 600UL 73 51 0.29 144 P2 TWD 15 VH3

+0.79 TEH TEC 6

COLD 60OUL 0.24 136 P2 TWD 13 VSM

-0.87 TEH TEC 6

COLD 60OUL 0.31 82 P2 TwO 15 VSM

+0.87 TEH TEC 6

COLD 60OUL 0.41 93 P2 TWD 19 VC3

+0.28 TEH TEC 6

COLD 60OUL 0.27 150 P2 TWD 14 VC3

+0.83 TEH TEC 6

COLD 60OUL 0.31 85 P2 TWD 15 VH3

+0.28 TEH TEC 6

COLD 600UL 0.22 43 P2 TWD 11 VSM

+0.28 TEH TEC 6

COLD 600UL 131 51 0.57 126 P3 TWD 19 DBC

+1.93 TEC TEH 56 HOT 60OUL 0.52 115 P2 TWD 23 VH2

+0.69 TEC TEH 56 HOT 600UL 133 51 0.18 91 P2 TWD 15 08C

+0.84 TEC TEH 57 HOT 600UL 36 52 0.32 43 P2 TWD 16 06H

+0.40 TEH TEC 6

COLD 600UL 64 52 0.24 101 P2 TWD 13 05C

+0.87 TEH TEC 6

COLD 60OUL 76 52 0.27 144 P2 TWD 14 VH3

-0.83 TEH TEC 6

COLD 60OUL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 7 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 106 52 0.16 21 P3 TWD 10 DBC

-1.26 TEN TEC 12 COLD 600UL 112 52 0.39 18 P3 TWD 16 DBH

+2.05 TEE TEC 11 COLD 60OUL 122 52 0.31 99 P2 TWD 17 VN1

+0.74 TEE TEC 12 COLD 600UL 126 52 0.41 126 P2 TWD 21 VHI

+0.86 TEN TEC 12 COLD 600UL 17 53 0.24 39 P2 TWD 12 07H

-1.13 TEN TEC 6

COLD 600UL 21 53 0.21 143 P2 TWD 11 07H

-0.98 TER TEC 6

COLD 600UL 35 53 0.24 116 P2 TWD 11 VSM

-0.77 TEN TEC 5

COLD 600UL 43 53 0.76 141 P2 TWD 25 VSM

+0.78 TEE TEC 5

COLD 600UL 0.43 154 P2 TWD 17 VSM

+0.02 TEE TEC 5

COLD 600UL 73 53 0.29 61 P2 TWD 15 VH3

-0.14 TEN TEC 6

COLD 600UL 0.35 85 P2 TWD 17 VC3

+0.20 TER TEC 6

COLD 600UL 0.44 105 P2 TWD 20 VC3

+0.81 TEN TEC 6

COLD 600UL 28 54 0.28 105 P2 TWD 12 06H

+0.12 TEN TEC 5

COLD 600UL 64 54 0.30 45 P2 TWD 15 08H

-0.35 TEN TEC 6

COLD 600UL 116 54 0.27 19 P3 TWD 12 DBH

+1.99 TEN TEC 11 COLD 600UL 124 54 0.29 119 P2 TWD 12 10H

+0.76 TEE TEC 11 COLD 600UL 0.20 135 P2 TWD 9 VHI

-0.90 TEE TEC 11 COLD 600UL 130 54 0.36 130 P3 TWD 14 DBH

-1.81 TEE TEC 11 COLD 600UL 132 54 0.20 134 P3 TWD 8 DBH

-1.54 TEC TEN 56 HOT 600UL 23 55 0.36 149 P2 TWD 17 07H

-1.09 TEN TEC 6

COLD 600UL 39 55 0.18 121 P2 TWD 9 VSM

-0.95 TEE TEC 6

COLD 600UL 73 55 0.20 145 P2 TWD 11 VH3

+0.88 TEE TEC 6

COLD 60OUL 79 55 0.20 169 P3 TWD 8 DBH

+1.81 TEN TEC 5

COLD 600UL 125 55 0.50 11 P3 TWD 18 DBH

+2.13 TEE TEC 11 COLD 600UL 131 55 0.20 19 P3 TWD 8 DBH

+1.78 TEC TEN 56 HOT 600UL 24 56 0.26 135 P2 TWD 13 07H

-1.18 TEN TEC 6

COLD 600UL 36 56 0.16 59 P2 TWD 8 VSM

-0.85 TEE TEC 6

COLD 600UL 68 56 0.25 80 P2 TWO 13 05C

-0.92 TEE TEC 6

COLD 600UL 76 56 0.24 87 P2 TWD 12 05C

+0.92 TEN TEC 6

COLD 600UL 0.26 139 P2 TWD 13 04C

+0.94 TEN TEC 6

COLD 600UL 0.20 130 P2 TWD 11 03C

+0.98 TEE TEC 6

COLD 600UL 120 S6 0.51 140 P2 TWD 11903

+1.49 TEN TEC LOCOK 6

1 COLD 600UL 124 56 0.19 9

P3 TWO 8 OSE

+1.89 TEE TEC 11 COLD 600UL 126 56 0.20 41 P2 TWD 9 V1H

-0.80 TEN TEC 11 COLD 600UL 130 56 0.17 154 P3 TWD 8 DBH

-1.60 TEE TEC 11 COLD 600UL 132 56 0.11 95 P3 TWO 4 USE

-2.05 TEC TEE 56 NOT 600UL 19 57 0.22 72 P2 TWD 11 07H

-0.97 TEE TEC 6

COLD 600UL 47 57 0.19 157 P2 TWD 10 OEH

+0.87 TEE TEC 6

COLD 60OUL 51 57 0.12 107 P2 TWD 7 08H

-0.06 TEE TEC 6

COLD 600UL 55 57 0.31 18 P2 TWD 15 07H

-1.10 TEE TEC 6

COLD 600UL 75 57 0.32 128 P2 TWD 16 VE3

+0.84 TEE TEC 6

COLD 60OUL 0.85 131 P2 TWD 30 VSN

+0.88 TEE TEC 6

COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component:

S/G 88 Page 8 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 0.31 115 P2 TWD 15 VC3

-0.70 TEH TEC 6

COLD 60OUL 0.18 159 P2 TWD 9 VH3

+0.20 TEH TEC 6

COLD 600UL 77 57 0.68 79 P2 TWD 24 VC3

+0.85 TEH TEC 5

COLD 600UL 0.40 100 P2 TWD 16 VC3

+0.18 TEH TEC 5

COLD 600UL 81 57 0.45 97 P2 TWD 22 07H

+0.94 TEH TEC 12 COLD 600UL 85 57 0.72 126 P2 TWD 30 08H

-0.77 TEH TEC 12 COLD 600UL 89 57 0.48 139 P2 TWD 24 09H

+0.54 TEH TEC 12 COLD 600UL 123 57 0.20 22 P3 TWD 12 DBH

+1.72 TEH TEC 12 COLD 600UL 131 57 0.19 98 P3 TWD 7 DBH

+1.76 TEC TEH 56 HOT 600UL 133 57 0.19 28 P3 TWO 16 DBH

-2.13 TEC TEH 57 HOT 600UL 135 57 0.26 15 P3 TWD 10 DBH

+1.48 TEC TEH 56 HOT 600UL 64 58 0.20 162 P2 TWD 11 08H

-0.10 TEH TEC 6

COLD 600UL 72 58 0.37 116 P2 TWD 17 08H

+0.74 TEH TEC 6

COLD 600UL 76 58 0.14 114 P3 TWD 8 DBC

-2.07 TEH TEC 6

COLD 600UL 84 58 0.41 118 P2 TWD 16 09H

-1.25 TEH TEC 11 COLD 600UL 0.74 73 P2 TWD 25 09H

+1.71 TEH TEC LOCOK 11 COLD 600UL 118 58 0.34 11 P3 TWD 19 DBH

+2.16 TEH TEC 12 COLD 600UL 128 58 0.19 36 P2 TWO 12 VH3

+0.30 TEH TEC 12 COLD 60OUL 0.39 123 P2 TWD 20 VH3

+0.94 TEH TEC 12 COLD 600UL 134 58 0.34 80 P2 TWD 18 VC1

-0.95 TEC TEH 56 HOT 600UL 0.32 141 P2 TWD 17 VC2

-0.85 TEC TEH 56 HOT 600UL 0.29 150 P2 TWD 16 VH1

-0.87 TEC TEH 56 HOT 600UL 31 59 0.63 13 2

SAI TSH

-2.11 TSH TSH 0.15 LAR 121 HOT 580PP 53 59 0.37 126 P2 TWO 17 08H

-1.09 TEN TEC 6

COLD 600UL 57 59 0.26 70 P2 TWD 13 08H

-1.08 TEH TEC 6

COLD 600UL 65 59 0.19 94 P2 TWD 10 07H

-1.10 TEH TEC 6

COLD 600UL 0.14 60 P2 TWD 8 08H

-1.05 TEH TEC 6

COLD 600UL 0.14 139 P2 TWD 8 VC3

-0.76 TEH TEC 6

COLD 600UL 69 59 0.16 49 P3 TWD 9 DBC

+1.83 TEH TEC 6

COLD 600UL 79 59 0.44 147 P3 TWO 17 DBH

+2.15 TEH TEC 5

COLD 600UL 81 59 0.37 45 P3 TWD 15 DBH

+1.71 TEH TEC 11 COLD 600UL 0.96 86 P2 TWD 29 VC3

-0.46 TEH TEC 11 COLD 600UL 0.76 121 P2 TWD 25 VC3

-0.58 TEH TEC 11 COLD 600UL 89 59 0.60 121 P2 TWD 21 09H

+0.86 TEH TEC 11 COLD 600UL 121 59 0.16 20 P3 TWD 7 DBC

-1.13 TEH TEC 11 COLD 600UL 137 59 0.22 15 P3 TWD 21 DBH

+1.88 TEC TEH 57 HOT 60OUL 0.33 49 P3 TWO 24 DBC

+2.00 TEC TEH 57 HOT 600UL 8

60 0.19 84 P3 TWD 8 DBH

-0.82 TEC TEH 39 HOT 600UL 18 60 0.46 144 P3 TWD 17 DBH

+2.25 TEH TEC 5

COLD 600UL 24 60 0.19 117 P3 TWD 10 DBH

-1.83 TEH TEC 6

COLD 600UL 84 60 0.39 151 P2 TWD 16 09H

-1.03 TEH TEC 11 COLD 600UL 86 60 0.31 153 P2 TWD 17 08H

-0.81 TEH TEC 12 COLD 600UL 0.22

.40 P2 TWD 13 09H

-0.92 TEH TEC 12 COLD 600UL 90 60 0.32 49 P2 TWD 18 08H

-0.18 TEH TEC 12 COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 9 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 96 60 0.33 69 P2 TWD 18 09H

-0.28 TEH TEC 12 COLD 600UL 100 60 0.73 102 P2 TWD 30 VH2

-0.76 TEH TEC 12 COLD 600UL 126 60 0.67 117 P2 TWD 23 VHI

-0.98 TEH TEC 11 COLD 600UL 134 60 0.40 115 P3 TWD 14 DBH

+1.30 TEC TEH 56 HOT 600UL 136 60 0.43 138 P2 TWD 27 VC3

-0.78 TEC TEH 57 HOT 600UL 0.10 164 P3 TWD 11 DBC

+2.03 TEC TEH 57 HOT 600UL 0.40 108 P3 TWD 27 DBH

+1.42 TEC TEH 57 HOT 600UL 73 61 0.47 111 P2 TWD 21 VSM

+0.84 TEH TEC 6

COLD 60OUL 0.18 141 P2 TWD 10 VH3

-0.88 TEH TEC 6

COLD 600UL 85 61 0.74 111 P2 TWD 25 08H

+0.72 TEH TEC ii COLD 600UL 87 61 0.43 72 P2 TWD 22 08H

+0.78 TEH TEC 12 COLD 600UL 89 61 0.64 126 P2 TWD 22 09H

+0.88 TEH TEC 11 COLD 600UL 93 61 0.82 111 P2 TWD 26 09H

+0.72 TEH TEC 11 COLD 600UL 97 61 0.21 138 P2 TWD 12 04C

-0.96 TEH TEC 12 COLD 600UL 133 61 0.07 31 P3 TWD 7 DBC

-1.49 TEC TEH 57 HOT 60OUL 40 62 0.43 103 P2 TWD 20 VSM

+0.80 TEH TEC 8

COLD 600UL 46 62 0.42 63 P3 TWD 16 DBH

-2.24 TEH TEC 7

COLD 600UL 74 62 0.27 90 P3 TWD 11 DBH

+2.19 TEH TEC 7

COLD 600UL 76 62 0.29 97 P2 TWD 14 04C

+0.85 TEH TEC 8

COLD 600UL 82 62 0.38 76 P2 TWD 20 VH3

+0.84 TEH TEC 12 COLD 600UL 0.20 148 P2 TWD 12 VH3

-0.78 TEH TEC 12 COLD 600UL 84 62 0.43 130 P2 TWD 17 VH2

-1.05 TEH TEC 11 COLD 600UL 94 62 0.29 110 P2 TWD 16 09H

-0.02 TEH TEC 12 COLD 60OUL 110 62 0.34 140 P2 TWO 18 VN2

-0.92 TEN TEC 12 coLD 600UL 126 62 0.31 128 P2 TWD 17 VHI

-1.00 TEH TEC 12 COLD 600UL 0.19 122 P2 TWO 11 VHI

+0.14 TEN TEC 12 COLD 600UL 128 62 0.58 121 P2 TWD 21 VH2

-0.88 TEH TEC 11 COLD 600UL 37 63 0.20 139 P2 TWD 11 VSN

+0.80 TEH TEC 18 COLD 600UL 67 63 0.22 71 P2 TWD 9 VSN

-0.91 TEH TEC 7

COLD 600UL 81 63 0.46 145 P2 TWD 18 VSM

-0.82 TEH TEC 11 COLD 600UL 93 63 0.37 41 P2 TWD 15 091

+0.92 TEH TEC 11 COLD 600UL 95 63 0.30 104 P2 TWD 17 09H

+0.20 TEH TEC 12 COLD 60OUL 141 63 0.23 411 P2 TWD 18 0911

-0.28 TEC TEN 57 NOT 600UL 0.29 140 P2 TWD 21 VNH

-0.84 TEC TEN 57 NOT D 60UL 0.28 87 P3 TWD 22 DBH

-1.88 TEC TEH 57 HOT 600UL 0.20 131 P2 TWD 16 08H1

+0.66 TEC TEH 57 HOT 600UL 94 64 0.23 145 P2 TWD 14 08H

-0.45 TEN TEC 12 COLD 600UL 0.29 72 P2 TWD 16 09H

+0.26 TEN TEC 12 COLD 600UL 98 64 0.34 144 P2 TWD 18 VN2

-0.96 TEH TEC 12 COLD 600UL 106 64 0.42 68 P2 TWO 22 VC2

-0.64 TEN TEC 12 COLD 600UL 0.25 118 P2 TWD 14 VC2

+0.74 TEH TEC 12 COLD 600UL 0.20 129 P2 TWD 12 VC2

-0.08 TEH TEC 12 COLD 600UL 108 64 0.35 32 P3 TWD 14 DEN

+1.88 TEH TEC 11 COLD 600UL 112 64 0.31 12 P3 TWD 12 DBH

+2.09 TEH TEC 11 COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 10 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 116 64 0.18 34 P3 TWO 8 DBH

+1.80 TEH TEC 11 COLD 600UL 9

65 0.15 85 P3 TWD 7 DBH

+0.49 TEC TEH 39 HOT 600UL 39 65 0.50 101 P2 TWO 23 VSM

+0.72 TEH TEC 10 COLD 60OUL 73 65 0.20 44 P2 TWD 11 VSM

-0.96 TEH TEC 8

COLD 600UL 0.22 143 P2 TWD 11 VH3

+0.88 TEH TEC 8

COLD 600UL 0.38 108 P2 TWO 18 VH3

-0.76 TEH TEC 8

COLD 60OUL 81 65 0.65 149 P2 TWD 26 VSM

+0.82 TEH TEC 14 COLD 600UL 95 65 0.35 82 P2 TWO 19

.08H

+0.32 TEH TEC 12 COLD 600UL 0.69 109 P2 TWD 29 09H

-0.16 TEH TEC 12 COLD 600UL 0.19 148 P2 TWD 12, 09H

+0.90 TEH TEC 12 COLD 600UL 97 65 0.17 11 P2 TWD 8 09H

-0.64 TEH TEC 11 COLD 600UL 99 65 0.41 126 P2 TWD 21 08H

+0.54 TEH TEC 12 COLD 600UL 121 65 0.33 155 P2 TWD 14 VHI

+0.96 TEH TEC 11 COLD 600UL 88 66 0.42 128 P2 TWD 20 VH2

-0.80 TEH TEC 14 COLD 600UL 92 66 0.34 139 P2 TWD 16 09H

-0.12 TEH TEC 14 COLD 600UL 0.25 24 P2 TWD 13 09H

+0.98 TEH TEC 14 COLD 600UL 94 66 0.29 113 P2 TWD 12 09H

+0.64 TEH TEC 13 COLD 600UL 0.23 122 P2 TWD 9 VH2

-1.10 TEH TEC 13 COLD 600UL 96 66 0.24 47 P2 TWO 12 08H

-0.08 TEH TEC 14 COLD 600UL 0.33 143 P2 TWD 16 VH2

-0.88 TEH TEC 14 COLD 600UL 98 66 0.49 145 P2 TWO 19 VH2

-0.94 TEH TEC 13 COLD 600UL 0.34 54 P2 TWD 14 09H

+1.00 TEH TEC 13 COLD 600UL 102 66 0.37 106 P2 TWO 15 09H

+1.03 TEH TEC 13 COLD 600UL 0.59 120 P2 TWD 22 VH2

-0.80 TEH TEC 13 COLD 600OL 108 66 0.21 67 P3 TWD 13 DBH

+2.25 TEH TEC 14 COLD 600UL 110 66 0.45 141 P2 TWD 18 VH2

-0.84 TEH TEC 13 COLD 600UL 126 66 0.63 117 P2 TWO 23 VH1

-0.70 TEH TEC 13 COLD 600UL 0.30 103 P2 TWD 13 VHl

+0.90 TEH TEC 13 COLD 600UL 128 66 0.54 148 P2 TWO 20 VH1

-0.94 TEH TEC 13 COLD 600OUL 140 66 0.18 30 P3 TWD 16 DBH

-1.62 TEC TEH 57 HOT 600UL 17 67 0.25 32 P3 TWO 14 DBH

+1.61 TEH TEC 10 COLD 600UL 27 67 0.37 114 P2 TWD 18 VSM

+0.97 TEH TEC 10 COLD 600UL 39 67 0.50 130 P2 TWD 19 VSM

-0.86 TEH TEC 9

COLD 600UL 0.40 150 P2 TWD 16 VSM

+0.70 TEH TEC 9

COLD 600UL 65 67 0.20 86 P3 TWO 12 DBH

-1.75 TEH TEC 10 COLD 600UL 95 67 0.43 128 P2 TWD 17 09H

+0.61 TEH TEC 16 COLD 600UL 101 67 0.52 78 P2 TWO 23 09H

+0.86 TEH TEC 14 COLD 600UL 125 67 0.38 61 P2 TWD 16 VH1

+0.97 TEH TEC 15 COLD 600UL 137 67 0.30 12 P3 TWD 23 DBH

+1.75 TEC TEH 57 HOT 600UL 141 67 0.27 83 P3 TWD 21 DBH

+1.76 TEC TEH 57 HOT 600UL 48 68 0.45 144 P2 TWD 17 VSM

+0.86 TEH TEC 9

COLD 600UL 0.31 38 P2 TWD 13 VSM

-0.87 TEH TEC 9

COLD 600UL 76 68 0.48 58 P2 TWD 18 07H

+1.02 TEH TEC 9

COLD 600UL 82 68 0.36 141 P2 TWO 17 VH3

-0.82 TEH TEC 14 COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 11 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 0.35 95 P2 TWD 17 VSM

-0.20 TEH TEC 14 COLD 600UL 0.30 41 P2 TWD 16 08C

-0.16.

TEH TEC 14 COLD 600UL 88 68 0.38 66 P2 TWD 16 08H

-1.02 TEH TEC 15 COLD 600UL 92 68 0.87 134 P2 TWD 28 09H

-0.20 TEH TEC 15 COLD 600UL 94 68 0.42 146 P2 TWO 19 VN2

-0.93 TEN TEC 14 COLD 600UL 0 40 151 P2 TWD 19 VH2

+0.83 TEH TEC 14 COLD 600UL 96 68 0.35 144 P2 TWD 15 VH2

-0.89 TEH TEC 15 COLD 600UL 0.33 98 P2 TWD 15 09H

+0.83 TEH TEC 15 COLD 600UL 0.20 35 P2 TWD 10 09H

-0.75 TEH TEC 15 COLD 600UL 98 68 0.26 26 P3 TWD 14 DBH

+2.06 TEH TEC 14 COLD 600UL 112 68 0.41 142 P2 TWO 17 VE2

-0.94 TEE TEC 16 COLD 600UL 130 68 0.45 107 P2 TWD 18 VH2

-0.97 TEH TEC 16 COLD 600UL 138 68 0.20 115 P3 TWO 8 DBE

+1.77 TEC TEE 56 NOT 600UL 37 69 0.32 79 P2 TWD 13 VSN

-0.61 TEH TEC 9

COLD 600UL 0.32 143 P2 TWO 13 VSM

+1.21 TEN TEC 9

COLD 600UL 81 69 0.20 134 P3 TWD 9 DBH

+1.32 TEE TEC 16 COLD 600UL 0.12 140 P3 TWO 5 DON

+1.08 TEE TEC 16 COLD EQOUL 0.44 30 P2 TWO 18 VN3

+0.00 TEE TEC 16 COLD 600UL 0.29 104 P2 TWD 13 VSM

-0.59 TEH TEC 16 COLD 600UL 0.26 127 P2 TWO 11 VC3

-0.96 TEN TEC 16 COLD 600UL 0.49 135 P2 TWD 19 VC3

+0.90 TEH TEC 16 COLD 60OUL 91 69 0.52

.116 P2 TWD 23 08H

+0.86 TEH TEC 14 COLD 600UL 0.42 134 P2 TWD 20 09H

-0.14 TEH TEC 14 COLD 60OUL 93 69 0.33 111 P2 TWD 14 09H

+0.71 TEH TEC 16 COLD 600UL 95 69 0.28 128 P2 TWD 14 08M

+0.28 TEH TEC 14 COLD 600UL 97 69 0.23 50 P2 TWD 10 07E

+0.99 TEH TEC 16 COLD 600UL 137 69 0.16 152 P2 TWD 14 VCl

+0.82 TEC TEN 57 COT 600UL 0.17 67 P2 TWO 14 VHl

-0.98*

TEC TEN 57 EDT 600UL 141 69 0.21 61 P3 TWD 8 DBH

+1.56 TEC TEN 56 NOT 600UL 0.22 51 P3 TWO 8 OBC

+1.97 TEC TEN 56 NOT 600UL 42 70 0.46 11 2

SAt TSN

-2.15 TSE TSH 0.56 LAIR 125 NOT 580PP 0.43 16 2

SAl TSH

-0.80 TSE TSE 0.18 LAIR 125 HOT 580PP 96 70 0.84 136 P2 TWD 28 07H

+0.84 TEH TEC 16 COLD 600UL 0.15 148 P2 TWD 7 09H

-0.06 TEH TEC 16 COLD 600UL 132 70 0.62 103 P2 TWO 26 VHl

+0.65.

TEC TEN 56 NOT 600UL 0.18 65 P2 TWO 10 VHl

+0.14 TEC TEE 56 HOT 600UL 136 70 0.44 39 P2 TWO 27 VHI

+0.72 TEC TEN 57 NOT 600UL 138 70 0.19

60. P3 TWO 7 DOE

+1.90 TEC TEN 56 NOT 600UL 95 71 0.23 154 P2 TWD 10 07H

-0.87 TEH TEC 16 COLD 600UL 101 71 0.18 154 P2 TWO 9 09N

+0.88 TEE TEC 14 COLD 600UL 0.21 99 P3 TWO 13 DON

-1.33 TEN TEC 14 COLD 600UL 103 71 0.39 117 P2 TWD 16 09H

+0.99 TEH TEC 16 COLD 600UL 141 71 0.16 81 P3 TWD 15 DHE

+1.16 TEC TEH 57 HOT 600UL 143 71 0.39 138 P3 TWD 27 DBH

+1.65 TEC TEH 57 HOT 600UL 0.35 45 P3 TWD 25 DBH

-2.07 TEC TEH 57 HOT 600UL 76 72 0.28 60 P2 TWD 12 VH3

-0.97 TEN TEC 9

COLD 600UL 90 72 0.38 94 P2 TWD 19 08H

-0.42 TEH TEC 14 COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 12 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW'LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 92 72 0.37 134 P2 TWD 16 05H

+0.83 TEE TEC 16 COLD 600UL 0.49 116 P2 TWD 19 09H

-0.02 TEE TEC 16 COLD 600UL 0.28 49 P2 TWD 12 09H

+0.59 TEE TEC 16 COLD 600UL 94 72 0.25 137 P2 TWD 13 07H

+0.40 TEE TEC 14 COLD 600UL 96 72 0.17 150 P2 TWD 8 09H

-0.98 TEE TEC 16 COLD 600UL 0.27 65 P2 TWD 12 09H

+0.20 TEE TEC 16 COLD 600UL 98 72 0.65 82 P2 TWD 26 07H

+0.91 TEE TEC 14 COLD 600UL 106 72 0.45 136 P2 TWD 20 VC2

-0.76 TEE TEC 14 COLD 600UL 130 72 0.25 162 P2 TWD 11 VHI

-0.83 TEE TEC 16 COLD 600UL 140 72 0.31 12 P3 TWD 11 DBH

+1.51 TEC TEE 56 HOT 600UL 142 72 0.35 154 P2 TWD 24 V1I

+0.76 TEC TEE 57 HOT 600UL 0.26 65 P3 TWD 21 DBH

+1.72 TEC TEE 57 HOT 600UL 0.18 139 P3 TWD 16 DBH

-1.82 TEC TEE 57 HOT 600UL 41 73 0.32 114 P3 TWD 17 DBH

-1.64 TEE TEC 10 COLD 60OUL 0.46 130 P3 TWD 22 DBH

+2.10 TEE TEC 10 COLD 600UL 43 73 0.24 154 P2 TWD 10 VSM

+0.95 TEE TEC 9

COLD 600UL 0.45 82 P2 TWD 17 VSM

-0.92 TEE TEC 9

COLD 600UL 0.76 10 2

SAI TSH

-1.26 TSH TSH 0.95 LAR 125 HOT 580PP 0.64 9

2 SAI TSH

-3.10 TSH TSH 0.25 LAR 125 HOT 580PP 0.58 10 2

SAI TSH

-2.52 TSH TSH 0.37 LAR 125 HOT 580PP 47 73 0.63 98 P3 TWD 22 DBC

-1.99 TEE TEC 9

COLD 600UL 73 73 0.24 55 P2 TWD 13 VSM

+0.94 TEE TEC 10 COLD 600UL 0.29 149 P2 TWD 16 VC3

-0.72 TEE TEC 10 COLD 600UL 77 73 0.27 127 P2 TWD 14 VH3

+0.84 TEE TEC 10 COLD 600UL 91 73 0.74 146 P2 TWD 28 09H

-0.32' TEE TEC 14 COLD 600UL 0.40 128 P2 TWD 19 08H

+0.86 TEE TEC 14 COLD 600UL 93 73 0.39 160 P2 TWD 16 09H

+0.85 TEE TEC 16 COLD 600UL 95 73 0.42 45 P2 TWD 19 VC2

+0.04 TEE TEC 14 COLD 600UL 0.36 154 P2 TWD 17 VSM

+0.84 TEE TEC 14 COLD 600UL 0.33 104 P2 TWD 16 VH3

+0.82 TEE TEC 14 COLD 600UL 0.16 152 P2 TWD 8 VH3

+0.14 TEE TEC 14 COLD 600UL 0.62 75 P2 TWD 26 09H

+0.58 TEE TEC 14 COLD 600UL 0.33 32 P2 TWD 17 07H

+0.71 TEE TEC 14 COLD 60OUL 0.40 139 P2 TWD 19 VC3

+0.72 TEE TEC 14 COLD 600UL 0.13 13 P2 TWD 8 07H

-0.92 TEE TEC 14 COLD 600UL 97 73 0.29 147 P2 TWD 12 08H

-0.60 TEE TEC 16 COLD 60OUL 0.56 136 P2 TWD 21 09H

+0.65 TEN TEC 116 COLD 600UL 0.47 110 P2 TWD 19 08H

+0.79 TEE TEC 16 COLD 600UL 145 73 0.22 108 P3 TWD 18 DBH

+1.76 TEC TEE 57 HOT 600UL 42 74 0.55 70 P3 TWD 25 DBH

-1.99 TEE TEC 10 COLD 60OUL 44 74 0.38 57 P3 TWD 15 DEH

-1.77 TEE TEC 9

COLD 600UL 0.21 152 P3 TWD 9 DBC

+1.75 TEE TEC 9

COLD 600UL 66 74 0.31 101 P3 TWO 17 DEN

+1.88 TEN TEC 10 COLD 600UL 82 74 0.34 15 P3 TWD 18 DBH

+1.87 TEE TEC 14 COLD 600UL 88 74 0.40 132 P2 TWO 16 VN2

-0.75 "TEE TEC 16 COLD 600UL 92 74 0.55 114 P2 TWD 21 07E

+0.88 TEE TEC 16 COLD 600UL 0.33 24 P2 TWO 14 OSE

+0.87 TEE TEC 16 COLD 600UL 94 74 0.33 59 P2 TWD 14 09H

-0.34 TEE TEC 16 COLD 600UL 100 74 0.33 90 P2 TWD 14 09H

-0.08 TEN TEC 16 COLD 600UL 0.29 156 P2 TWD 13 09H

+0.91 TEE TEC 16 COLD 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 13 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[lJ ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 102 74 0.18 90 P2 TWD 10 09H

+0.71 TEH TEC 14 COLD 60OUL 130 74 0.50 141 P2 TWD 20 VHl

-0.93 TEH TEC 17 COLD 600UL 134 74 0.37 112 P2 TWD 19 VH1

-0.83 TEC TEH 56 HOT 60OUL 138 74 0.62 125 P2 TWD 33 VHI

-0.92 TEC TEH 57 HOT 600UL 0.15 164 P2 TWD 12 VH2

+0.78 TEC TEH 57 HOT 600UL 0.23 47 P3 TWD 19 DBH

+1.96 TEC TEH 57 HOT 60OUL 142 74 0.23 50 P3 TWD 19 DBH

+1.16 TEC TEH 57 HOT 600UL 45 75 0.30 123 P3 TWD 16 DEC

-1.84 TEH TEC 10 COLD 600UL 47 75 0.33 112 P3 TWD 14 DBC

-1.99 TEH TEC 9

COLD 60OUL 49 75 0.24 59 P3 TWO 13 DEC

-0.82 TEE TEC 10 COLD 6000L 75 75 0.37 154 P2 TWD 15 VSE

+0.99 TEH TEC 9

COLD 60OUL 0.57 129 P2 TWO 21 VSE

-0.91 TEH TEC 9

COLD 600UL 93 75 0.90 93 P2 TWD 29 O9H

-0.26 TEH TEC 17 COLD 600UL 103 75 0.47 115 P2 TWD 21 09H

-0.86 TEH TEC 18 COLD 600UL 0.22 129 P2 TWD 12 09H

+0.46 TEH TEC 18 COLD 600UL 0.33 101 P2 TWD 16 09H

+0.72 TEH TEC 18 COLD 600UL 0.31 78 P2 TWD 15 09H

+1.02 TEH TEC 18 COLD 60OUL 0.41 64 P2 TWD 19 VH2

+0.80 TEH TEC 18 COLD 600UL 119 75 0.44 118 P3 TWD 19 DEH

-1.00 TEH TEC 18 COLD 600UL 129 75 0.39 130 P2 TWD 16 V0H

+0.81 TEH TEC 17 COLD 600UL 133 75 0.33 70 P2 TWD 23 H101

+0.76 TEC TEE 57 HOT 600UL 141 75 0.18 123 P3 TWD 16 DBH

-1.69 TEC TEH 57 HOT 600UL 0.15 35 P3 TWO 14 DEE

+1.65 TEC TEE 57 HOT 600UL 143 75 0.29 98 P3 TWD 11 DBH

+1.62 TEC TEE 56 HOT 600UL 46 76 0.43 91 P3 TwO 23 DEE

-1.98 TEC TEH 31 HOT 600UL 92 76 0.20 56 P2 TWO 15 0911

-0.28 TEC TEE 45 HOT E00UL 124 76 0.22 122 P3 TWO 9 DEE

+1.37 TEC TEH 44 HOT 600UL 130 76 0.42 130 P2 TWD 26 VH1

+0.96 TEC TEH 45 HOT 600UL 136 76 0.26 148 P2 TWO 19 VHI

+0.62 TEC TEE 57 HOT 600UL 0.29*

101 P2 TWO 21 VHI

-0.90 TEC TEH 57 HOT 600UL 0.27 56 P2 TWO 20 VE2

-1.11i TEC TEH 57 HOT 600UL 138 76 0.47 112 P2 TWO 21 VH2

-0.89 TEC TEE 56 HOT 600UL 0.32 116 P2 TWO 16 VHI

-0.22 TEC TEE 56 HOT 600UL 0.18 162 P2 TWO 9 VHI

+0.79 TEC TEN 56 HOT 600UL 140 76 0.48 127 P2 TWO 29 VH1

-0.94 TEC TEH 57 HOT 600UL 0.31 152 P2 TWO 22 VE2

-0.92 TEC TEE 57 HOT 600UL 47 77 0.40 131 P3 TWD 17 DBC

-1.93 TEC TEH 30 HOT 600UL 49 77 0.25 67 P2 TWD 14 06H

-0.87 TEC TEH 31 HOT 600UL 93 77 0.29 36 P2 TWO 15 09H1

-0.32 TEC TEE 44 HOT 600UL 95 77 0.19 105 P2 TWD 14 08H

+0.42 TEC TEH 45 HOT 600UL 101 77 0.59 107 P2 TWO 25 09H1

+0.63 TEC TEE 44 HOT 600UL

  • 0.24 148 P2 TWO 13 09H

-0.67 TEC TEE 44 HOT 600UL

/ 66 78 0.25 122 P2 TWO 14 02H

-0.26 TEC TEE 30 NOT 600UL 90 78 0.17 151 P2 TWD 13 09H

+0.66 TEC TEH 45 HOT 600UL 0.24 116 P2 TWD 17 09H

-0.04 TEC TEH 45 HOT 600UL 94 78 0.26 113 P2 TWD 18 09H

-0.14 TEC TEH 45 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 14 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 0.20 123 P2 TWD 15 09H

+0.54 TEC TEH 45 HOT 600UL 102 78 0.41 131 P2 TWD 25 09H

+0.86 TEC TEH 45 HOT 600UL 104 78 0.25 122 P2 TWD 13 09H

+0.71 TEC TEH 44 HOT 600UL 128 78 0.38 133 P2 TWD 18 VH1

-0.79 TEC TEH 44 HOT 600UL 130 78 0.24 140 P2 TWD 17 VHI

-0.94 TEC TEH 45 HOT 600UL 136 78 0.46 128 P2 TWD 22 VHI

-0.99 TEC TEH 56 HOT 60OUL 142 78 0.69 121 P2 TWD 35 VHI

-0.97 TEC TEH 57 HOT 600UL 0.38 147 P2 TWD 25 VH2

-0.89 TEC TEH 57 HOT 600UL 0.26 28 P3 TWD 21 DBH

+2.22 TEC TEH 57 HOT 60OUL 57 79 0.30 50 P3 TWD 18 DBC

-1.96 TEC TEH 31 HOT 600UL 61 79 0.60 86 P2 TWD 26 VSM

+0.85 TEC TEH 31 HOT 600UL 89 79 0.39 81 P2 TWD 25 09H

-0.08 TEC TEH 45 HOT 600UL 91 79 0.17 75 P2 TWD 10 07H

+0.26 TEC TEH 44 HOT 600UL 0.27 104 P2 TWD 14 09H

+0.34 TEC TEH 44 HOT 600UL 93 79 0.22 38 P2 TWD 16 09H

+0.08 TEC TEH 45 HOT 600UL 99 79 0.31 117 P2 TWD 16 07H

+0.70 TEC TEH 44 HOT 600UL 101 79 0.46 76 P2 TWD 27 09H

+0.98 TEC TEH 45 HOT 600UL 103 79 0.29 122 P2 TWD 15 09H

-0.91 TEC TEH 44 HOT 60OUL 0.29 108 P2 TWD 15 09H

+0.18 TEC TEH 44 HOT 600UL 0.28 121 P2 TWD 15 09H

+0.67 TEC TEH 44 HOT 600UL 119 79 0.15 128 P3 TWD 5 DBH

-0.28 TEC TEH 48 HOT 600UL 143 79 0.41 97 P3 TWD 27 DBH

+1.84 TEC TEH 57 HOT 600UL 66 80 0.30 81 P3 TWD 13 DBH

-1.44 TEC TEH 30 HOT 600UL 80 80 0.58 104 P2 TWD 24 VSM

+0.77 TEC TEH 30 HOT 60OUL 126 80 0.29 132 P2 TWD 19 VH1

-0.96 TEC TEH 49 HOT 600UL 140 80 0.60 116 P2 TWD 32 VHI

-0.88 TEC TEH 57 HOT 600UL 0.24 118 P3 TWD 20 DBH

-2.22 TEC TEH 57 HOT 600UL 144 80 0.27 134 P3 TWD 21 DBC

+2.06 TEC TEH 57 HOT 600UL 53 81 0.24 153 P3 TWD 11 DBC

+2.00 TEC TEH 30 HOT 600UL 0.34 91 P3 TWD 15 DBH

+1.41 TEC TEH 30 HOT 600UL 55 81 0.24 73 P3 TWD 15 DBH

+1.66 TEC TEH 31 HOT 600UL 61 81 0.24 7

P3 TWD 11 DBH

+1.36 TEC TEH 30 HOT 600UL 81 81 0.64 115 P2 TWD 26 VC3

-0.83 TEC TEH 48 HOT 600UL 0.48 67 P2 TWD 21 VC3

+0.79 TEC TEH 48 HOT 60OUL 0.28 97 P2 TWD 14 VSM

+0.85 TEC TEH 48 HOT 600UL 0.38 143 P2 TWD 18 VH3

+0.83 TEC TEH 48 HOT 600UL 0.22 104 P2 TWD 12 VC3

-0.10 TEC TEH 48 HOT 600UL 0.35 143 P2 TWD 17 VH3

-0.85 TEC TEH 48 HOT 60OUL 99 81 0.37 145 P2 TWD 23 09H

+0.54 TEC TEH 49 HOT 600UL 101 81 0.61 123 P2 TWD 25 09H

-0.70 TEC TEH 48 HOT 600UL 103 81 0.43 112 P2 TWD 25 09H

+0.86 TEC TEH 49 HOT 600UL 113 81 0.22 81 P3 TWD 9 DBH

+1.68 TEC TEH 48 HOT 60OUL 121 81 0.36 75 P2 TWD 17 VHI

+0.55 TEC TEH 48 HOT 600UL 141 81 0.17 46 P3 TWD 15 DBH

-2.22 TEC TEH 57 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 15 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND.%TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 52 82 0.80 85 P3 TWD 28 DBH

-1.78 TEC TEN 30 HOT 600UL 56 82 0.71 119 P3 TWD 26 DBH

-1.63 TEC TEN 30 HOT 600UL 62 82 0.40 151 P3 TWD 17 DBH

-1.53 TEC TEN 30 HOT 600UL 94 82 0.32 151 P2 TWD 20 09H

-0.26 TEC TEN 49 HOT 600UL 102 82 0.30 116 P2 TWD 15 09H

+0.50 TEC TEN 48 HOT 600UL 0.22 72 P3 TWD 9 DBH

+1.96 TEC TEN 48 HOT 600UL 136 82 0.21 151 P2 TWD 16 VH1

-1.16 TEC TEN 57 HOT 600UL 142 82 0.62 113 P2 TWD 26 VH2

-0.89 TEC TEN 56 HOT 600UL 144 82 0.12 27 P3 TWD 12 DBC

+2.02 TEC TEH 57 HOT 600UL 0.16 120 P3 TWD 14 DBH

+1.38 TEC TEN 57 HOT 600UL 51 83 0.53 69 P3 TWD 21 DBC

-1.73 TEC TEN 30 HOT 600UL 0.40 93 P3 TWD 17 DBH

-1.40 TEC TEN 30 HOT 60OUL 57 83 0.20 66 P3 TWD 9 DBC

-2.10 TEC TEN 30 HOT 600UL 0.16.

70 P3 TWD 7 DBC

+1.49 TEC TEN 30 HOT 600UL 61 83 0.38 121 P3 TWD 21 DBC

+1.99 TEC TEN 31 HOT 600UL 63 83 0.38 62 P3 TwD 16 DBC

+1.51 TEC TEN 30 HOT 600UL 85 83 0.23 138 P2 TWD 12 06H

+0.88 TEC TEN 48 HOT 600UL 101 83 0.51 138 P2 TWD 22 09H

-0.51 TEC TEN 48 HOT 600UL 131 83 0.34 104 P2 TWD 17 VHI

-0.99 TEC TEN 56 HOT 600UL 141 83 0.44 113 P2 TWD 27 VC1

+0.88 TEC TEN 57 HOT 600UL 143 83 0.28 102 P3 TWD 11 DBC

+2.07 TEC TEN 56 HOT 600UL 145 83 0.35 75 P3 TWD 25 DBC

+2.01 TEC TEN 57 HOT 600UL 54 84 0.17 51 P3 TWD 9 DBC

-1.38 TEC TEN 30 HOT 600UL 60 84 0.29 13 P3 TWD 14 DBH

+1.57 TEC TEN 30 HOT 600UL 74 84 0.48 153 P3 TWD 20 DBC

-1.44 TEC TEN 30 HOT 600UL 78 84 0.30 23 P3 TWD 13 DBH

+1.55 TEC TEN 30 HOT 600UL 94 84 0.35 85 P2 TWD 17 08H

-0.40 TEC TEN 48 HOT 600UL 102 84 0.26 118 P3 TWD 11 DBH

+1.15 TEC TEN 48 HOT 60OUL 114 84 0.23 78 P3 TWD 10 DBH

+1.84 TEC TER 48 HOT 600UL 128 84 0.34 142 P2 TWD 16 VHI

+0.77 TEC TEN 48 HOT 600UL 130 84 0.42 113 P2 TWD 25 VHI

-0.90 TEC TEN 49 HOT 600UL 0.17 152 P2 TWD 13 VHI

+0.74 TEC TEN 49 HOT 600UL 134 84 0.57 147 P2 TWD 32 VH1

-0.86 TEC TEN 57 HOT 60OUL 136 84 0.35 119 P2 TWD 17 VH1

+0.49 TEC TEN 56 HOT 600UL 0.36 70 P2 TWD 18 VHI

-0.93 TEC TEN "56 HOT 600UL 57 85 0.46 51 P3 TWD 20 DBH

+1.60 TEC TEN 30 HOT 600UL 61 85 0.44 21 P3 TWD 18 DBH

+1.58 TEC TEN 30 HOT 600UL 65 85 0.30 12 P3 TWD 18 DBH

+1.76 TEC TEN 31 HOT 600UL 73 85 0.17 69 P3 TWD 12 DBC

+2.02 TEC TEN 31 HOT 600UL 75 85 0.22 61 P3 TWD 11 DBC

-1.90 TEC TEN 30 HOT 600UL 95 85 0.22 126 P2 TWD 16 09H

+0.72 TEC TEN 49 HOT 60OUL 0.25 133 P2 TWD 17 08H

+0.78 TEC TEN 49 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 16 of 28

MAI, MCI, MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 97 85 0.28 136 P2 TWD 14 09H

-0.14 TEC TEN 48 HOT 600UL 101 85 0.42 123 P2 TWD 19 09H

-0.53 TEC TEN 48 HOT 600UL 103 85 0.23 105 P2 TWD 16 09H

+0.22 TEC TEN 49 HOT 600UL 137 85 0.19 113 P2 TWD 16 09H

+0.88 TEC TEN 57 HOT 60OUL 0.06 165 P2 TWD 6

09H

-1.04 TEC TEN 57 HOT 600UL 60 86 0.73 83 P3 TWD 26 DBH

-1.14 TEC TEN 30 HOT 600UL 106 86 0.55 96 P2 TWD 23 VH3

-0.87 TEC TEN 48 HOT 60OUL 112 86 0.10 29 P2 TWD 8 08H

+1.00 TEC TEN 49 HOT 600UL 122 86 0.35 107 P3 TWD 13 DBH

+1.75 TEC TEN 48 HOT 600UL 124 86 0.10 61 P3 TWD 9

DBH

+2.05 TEC TEN 49 HOT 600UL 0.09 126 P3 TWD 8 DBH

+0.10 TEC TEN 49 HOT 600UL 53 87 0.24 141 P3 TWD 15 DBH

-1.58 TEC TEN 31 HOT 600UL 55 87 0.66 84 P3 TWD 25 DBH

-1.61 TEC TEN 30 NOT 600UL 103 87 0.29 78 P2 TWD 19 09H

-0.04 TEC TEN 49 HOT 600UL 119 87 0.16 34 P3 TWD 13 DBH

+1.10 TEC TEN 49 HOT 600UL 133 87 0.51 128 P2 TWD 30 VH1

-0.80 TEC TEN 57 HOT 600UL 54 88 0.53 12 P3 TWD 21 DBH

+1.57 TEC TEN 30 HOT 60OUL 0.43 76 P3 TWD 18 DBH

-1.18 TEC TEN 30 HOT 600UL

/------------------------------------------------------------------------------------------------------------------------------------------

58.88 0.34 67 P3 TWD 16 DBH

-1.30 TEC TEN 30 HOT 600UL 62 88 0.27 126 P3 TWD 13 DBH

-1.12 TEC TEN 30 HOT 600UL 68 88 0.28 127 P3 TWD 17 DBH

-1.55 TEC TEN 31 HOT 600UL 94 88 0.43 116 P2 TWD 20 09H

-0.85 TEC TEN 48 HOT 60OUL 96 88 0.21 106 P2 TWD 10 07H

+0.22 TEC TEN 48 HOT 600UL 104 88 0.36 135 P2 TWD 17 08H

+0.50 TEC TEN 48 NOT 600UL 130 88 0.13 151 P2 TWD 10 VH1

+0.60 TEC TEN 49 HOT 600UL 0.23 81 P2 TWD 16 VH1

+0.10 TEC TEN 49 HOT 60OUL 134 88 0.56 113 P2 TWD 25 VH1

-0.87 TEC TEN 56 HOT 600UL 138 88 0.23 26 P2 TWD 13 VH1

+0.57 TEC TEN 56 HOT 600UL 0.79 132 P2 TWD 31 VHI

-0.91 TEC' TEH 56 HOT 600UL 63 89 0.34 80 P3 TWD 15 DBC

+1.67 TEC TEN 30 HOT 600UL 71 89 0.37 36 P3 TWD 16 DBC

-1.35 TEC TEN 30 HOT 600UL 73 89 0.20 142 P3 TWD 13 DBH

+1.64 TEC TEN 31 HOT 600UL 79 89 0.21 135 P3 TWD 10 DBH

+1.52 TEC TEN 30 HOT 60OUL 0.56 141 P2 TWD 24 VH3

+0.71 TEC TEN 30 HOT 600UL 95 89 0.28 128 P2 TWD 14 09H

+0.55 TEC TEN 48 HOT 600UL 99 89 0.59 112 P2 TWD 24 09H

+0.69 TEC TEN.

48 HOT 600UL 121 89 0.14 101 P3 TWD 12 DBH

-1.37 TEC TEE 49 HOT 600UL 0.11 86 P3 TWD 9 DBH

+0.44 TEC TEE 49 HOT 600UL 131 89 0.20 108 P2 TWD 12 VH1

-0.93 TEC TEN 56 HOT 600UL 137 89 0.24 147 P2 TWD 18 VH1

+0.74 TEC TEE 57 HOT 600UL 0.15 138 P2 TWD 12 VH1

-0.96 TEC TER 57 HOT 600UL 143 89 0.20 94 P2 TWD 12 08C

+0.89 TEC TEN 56 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 17 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 58 90 0.34 66 P3 TWD 15 DBH

-1.62 TEC TEH 30 HOT 600UL 72 90 0.15 17 P3 TWD 11 DBC

+2.03 TEC TEH 31 HOT 600UL 76 90 0.32 55 P2 TWD 17 08C

-0.20 TEC TEH 31 HOT 60OUL 112 90 0.40 121 P2 TWD 19 VH2

-0.85 TEC TEH 48 HOT 600UL 114 90 0.32 116 P2 TWD 20 VH2

-0.90 TEC TEH 49 HOT 600UL 116 90 0.20 136 P3 TWD 8 DBH

+1.31 TEC TEH 48 HOT 600UL 134 90 0.23 151 P2 TWD 12 VH1

+0.83 TEC TEH 56 HOT 600UL 144 90 0.18 94 P2 TWD 15 06C

+0.95 TEC TEH 57 HOT 60OUL 0.11 88 P2 TWD 10 06C

-0.89 TEC TEH 57 HOT 600UL 0.29 20 P3 TWD 22 DBC

+2.10 TEC TEH LAR 57 HOT 60OUL 57 91 0.54 117 P3 TWD 22 DBH

-1.59 TEC TEH 30 HOT 600UL 0.38 124 P3 TWD 16 DBC

-2.00 TEC TEH 30 HOT 600UL 0.49 37 P3 TWD 20 DBC

+2.04 TEC TEH 30 HOT 600UL 63 91 0.25 131 P3 TWD 11 DBC

-1.57 TEC TEH 30 HOT 60OUL 65 91 0.19 24 P3 TWD 13 DBC

-1.63 TEC TEH 31 HOT 600UL 119 91 0.42 105 P3 TWD 16 DBH

+1.98 TEC TEH 48 HOT 600UL 121 91 0.16 78 P3 TWD 13 DBH

+2.10 TEC TEH 49 HOT 600UL 123 91 0.16 38 P3 TWD 7 DBH

+1.51 TEC TEH 48 HOT 600UL 133 91 0.19 111 P2 TWD 15 VH1

+0.94 TEC TEH 57 HOT 600UL 0.10 39 P2 TWD 9 VHI

-0.86 TEC TEH 57 HOT 600UL 137 91 0.11 22 P3 TWD 9 DBC

+1.68 TEC TEH 63 HOT 600UL 143 91 0.38 24 P2 TWD 17 VC1

-0.89 TEC TEH 62 HOT 60OUL 145 91 0.07 120 P3 TWD 6 DBH

+1.55 TEC TEH 63 HOT 600UL 0.32 108 P2 TWD 20 VC1

-0.83 TEC TEH 63 HOT 600UL 147 91 0.46 116 P2 TWD 26 VC1

-0.90 TEC TEH 63 HOT 60OUL 0.44 110 P2 TWD 25 VC1

+0.59 TEC TEH 63 HOT 600UL 58 92 0.25 94 P3 TWD 16 DBH

-1.25 TEC TEH 31 HOT 600UL 60 92 0.34 16 P3 TWD 15 DBH

+1.64 TEC TEH 30 HOT 600UL 102 92 0.10 151 P3 TWD 9 DBH

+1.83 TEC TEH 49 HOT 600UL 114 92 0.31 73 P3 TWO 21 OEM

+1.87 TEC TEN 49 NOT 600UL 118 92 0.33 64 P3 TWD 22 DBH

+1.97 TEC TEH 49 HOT 600UL 142 92 0.26 120 P2 TWD 13 VH1

-0.91 TEC TEH 62 HOT 600UL 144 92 0.20 32 P2 TWD 14 10C

-1.08 TEC TEH 63 HOT 600UL 146 92 0.22 69 P2 TWD 16 VC1

+1.12 TEC TEH 63 HOT 600UL 0.27 125 P2 TWD 18 10C

+0.56 TEC TEH 63 HOT 60OUL 0.18 27 P3 TWD 14 DBC

+1.65 TEC TEH 63 HOT 60OUL 59 93 0.52 83 P3 TWD 21 DBH

-1.62 TEC TEH 30 HOT 600UL 99 93 0.22 116 P2 TWD 17 09H

+0.50 TEC TEH 55 HOT 600UL 125 93 0.38 54 P3 TWD 14 DBH

+1.80 TEC TEH 54 HOT 600UL 137 93 0.22 86 P2 TWD 16 VH1

-0.92 TEC TEH 63 HOT 600UL 139 93 0.25 53 P2 TWD 13 VC1

+0.87 TEC TEH 62 HOT 600UL 141 93 0.17 147 P2 TWD 12 VC1

+0.86 TEC TEH 63 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 18 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 145 93 0.25 60 P3 TWD 18 DBC

+1.59 TEC TEH 63 HOT 60OUL 0.22 86 P2 TWD 15 VCI

-0.70 TEC TEH 63 HOT 600UL 147 93 0.37 147 P2 TWD 23 VH2

-0.64 TEC TEH 63 HOT 600UL 74 94 0.28 119 P3 TWD 17 DBH

-1.78 TEC TEH 31 HOT 600UL 86 94 0.16 36 P2 TWD 13 01C

-0.96 TEC TEH 55 HOT 60OUL 94 94 0.13 126 P2 TWD 11 07H

+0.88 TEC TEH 55 HOT 600UL 106 94 0.27 141 P2 TWD 20 VH2

-0.87 TEC TEH 55 HOT 600UL 114 94 0.20 21 P3 TWD 16 DBH

-0.60 TEC TEH 55 HOT 600UL 134 94 0.13 129 P2 TWD 10 VH1

+0.78 TEC TEH 63 HOT 600UL 0.22 152 P2 TWD 15 VHX

-0.98 TEC TEH 63 HOT 600UL 138 94 0.31 51 P2 TWD 15 VHI

+0.87 TEC TEH

62.

HOT 600UL 142 94 0.12 38 P2 TWD 9 VHN

+0.86 TEC TEH 63 HOT 600UL 53 95 0.33 49 P3 TWD 17 DBC

-1.48 TEC TEH 35 HOT 600UL 123 95 0.46 145 P2 TWD 28 VHI

+0.89 TEC TEH 55 HOT 60OUL 145 95 0.10 18 P3 TWD 8 DBC

-1.45 TEC TEH 63 HOT 600UL 56 96 0.23 18 P3 TWD 13 DBC

+2.10 TEC TEH 35 HOT 60OUL 58 96 0.17 129 P3 TWD 11 DBH

-2.05 TEC TEH 36 HOT 600UL 0.19 36 P3 TWD 12 DBC

+1.92 TEC TEH 36 HOT 600UL 94 96 0.21 52 P2 TWD 17 08H

-0.48 TEC TEH 55 HOT 600UL 0.09 20 P2 TWD 8 09H

+1.21 TEC TEH 55 HOT 600UL 114 96 0.19 146 P3 TWD 16 DBH

+2.13 TEC TEH 55 HOT 600UL 124 96 0.46 65 P3 TWD 16 DBH

+1.87 TEC TEH 54 HOT 600UL 0.13 69 P3 TWD 5 DBH

+0.73 TEC TEH 54 HOT 60OUL 126 96 0.34 110 P2 TWD 23 VHI

-1.01 TEC TEH 55 HOT 600UL 132 96 0.37 108 P2 TWD 18 VHI

-0.85 TEC TEH 62 HOT 60OUL 0.08 14 P2 TWD 4 VH1

+0.55 TEC TEH 62 HOT 60OUL 134 96 0.29 131 P2 TWD 14 VHI

-0.87 TEC TEH 62 HOT 600UL 144 96 0.22 39 P2 TWD 15 VH1

+0.22 TEC TEH 63 HOT 600UL 0.55 100 P2 TWD 29 VHI

+0.84 TEC TEH 63 HOT 600UL 0.19 108 P3 TWD 15 DBH

+1.80 TEC TEH 63 HOT 600UL 93 97 0.17 124 P2 TWD 9 09H

+0.79 TEC TEH 54 HOT 600UL 0.38 123 P2 TWD 19 09H

-0.18 TEC TEH 54 HOT 600UL 95 97 0.19 95 P2 TWD 16 09H

-0.28 TEC TEH 55 HOT 600UL 101 97 0.62 114 P2 TWD 26 09H

-0.93 TEC TEH 54 HOT 600UL 0.20 59 P2 TWD 11 09H

+0.24 TEC TEH 54 HOT 600UL 103 97 0.23 48 P2 TWD 18 09H

-1.05 TEC TEH 55 HOT 600UL 0.14 145 P2 TWD 12 09H

+0.83 TEC TEH 55 HOT 600UL 123 97 0.32 83 P3 TWD 23 DBH

+1.49 TEC TEH 55 HOT 600UL 125 97 0.25 53 P3 TWD 10 DBH

+1.53 TEC TEH 54 HOT 600UL 131 97 0.22 15 P2 TWD 11 VH1

+0.75 TEC TEH 62 HOT 60OUL 0.13 10 P2 TWD 7 VHX

-0.79 TEC TEH 62 HOT 60OUL 135 97 0.39 57 P2 TWD 18 VHI

-0.87 TEC TEH 62 HOT 600UL 141 97 0.21 115 P2 TWD 15 VH2

+1.04 TEC TEH 63 HOT 600UL 56 98 0.48 138 P3 TWD 24 DBH

-1.51 TEC TEH 36 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 19 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 58 98 0.24 48 P3 TWD 13 DBH

-1.75 TEC TEH 35 HOT 60OUL 60 98 0.24 10 P3 TWD 15 DBH

+1.86 TEC TEH 36 HOT 600UL 84 98 0.21 115 P2 TWD 12 09H

-1.40 TEC TEH LOCOK 54 HOT 600UL 86 98 0.13 62 P2 TWD 11 06H

+0.78 TEC TEH 55 HOT 600UL 92 98 0.35 37 P2 TWD 16 08H

-0.73 TEC TEH 54 HOT 600UL 96 98 0.41 128 P2 TWD 19 09H

+0.59 TEC TEH 54 HOT 600UL 142 98 0.21 145 P2 TWD 15 VHl

+0.76 TEC TEH 63 HOT 600UL 51 99 0.39 59 P3 TWD 19 DBH

-1.43 TEC TEH 35 HOT 600UL 0.37 6

P3 TWD 18 DBH

+1.45 TEC TEH 35 HOT 600UL 55 99 0.37 94 P3 TWD 19 DBH

-1.28 TEC TEH 35 HOT 600UL 59 99 0.18 76 P3 TWD 10 DBH

-1.22 TEC TEH 35 HOT 600UL 87 99 0.14 143 P2 TWO 12 OSH

+0.90 TEC TEE 55 HOT 6000L 0.18 147 P2 TWD 15 08H

-0.48 TEC TEH 55 HOT 600UL 0.15 164 P2 TWD 13 07H

+0.88 TEC TEH 55 HOT 60OUL 91 99 0.18 111 P2 TWD 15 08H

+0.82 TEC TEH 55 HOT 600UL 0.29 84 P2 TWD 21 08H

-0.82 TEC TEH 55 HOT 600UL 99 99 0.30 121 P2 TWD 22 09H

-0.16 TEC TEH 55 HOT 600UL 125 99 0.32 69 P3 TWD 12 DBH

+1.52 TEC TEH 54 HOT 600UL 0.31 101 P3 TWD 12 DBH

+0.51 TEC TEH 54 HOT 600UL 129 99 0.50 109 P2 TWD 22 10H

-0.22 TEC TEH 54 HOT 600UL 143 99 0.11 33 P3 TWD 9 DBC

+1.61 TEC TEH 63 HOT 60OUL 46 100 0.62 21 P3 TWD 26 DBH

+1.51 TEC TEH 35 HOT 600UL 82 100 0.31 67 P2 TWD 16 VH3

+0.81 TEC TEH 54 HOT 60OUL 0.37 78 P2 TWD 18 VH3

-0.79 TEC TEH 54 HOT 600UL 84 100 0.42 60 P2 TWD 20 09H

+1.29 TEC TEH LOCOK 54 HOT.

600UL 0.84 135 P2 TWD 31 09H

-1.54 TEC TEH LOCOK 54 HOT 60OUL 100 100 0.35 138 P2 TWD 24 09H

+0.82 TEC TEH 55 HOT 600UL 106 100 0.44 141 P2 TWD 20 09H

-0.83 TEC TEH 54 HOT 600UL 126 100 0.25 94 P2 TWD 19 VH1

-0.89 TEC TEH 55 HOT 60OUL 132 100 0.43 133 P2 TWO 19 VH1

-0.85 TEC TEH 62 HOT 600UL 136 100 0.30 113 P2 TWD 15 VH1

-0.91 TEC TEH 62 HOT 600UL 0.21 139 P2 TWD 11 VH1

+0.73 TEC TEH 62 HOT 600UL 146 100 0.23.

65 P2 TWD 16 08C

-0.20 TEC TEH 63 HOT 600UL 0.20 98 P2 TWD 14 VC2

-0.89 TEC TEH 63 HOT 600UL 0.63 49 P2 TWD 31 10C

-0.08 TO+0.79 TEC TEH LAR 63 HOT 600UL 45 101 0.31 58 P3 TWD 16 DBC

-1.67 TEC TEH 35 HOT 600UL 0.55 22 P3 TWD 24 DBH

+1.19 TEC TEH 35 HOT 600UL 0.11 139 P3 TWD 6

DBH

-1.77 TEC TEH 35 HOT 60OUL 49 101 0.43 108 P3 TWD 20 DBH

-1.50 TEC TEH 35 HOT 600UL 83 101 0.18 117 P2 TWD 15 07H

-0.68 TEC TEH 55 HOT 600UL 87 101 0.20 136 P2 TWD 16 07H

+0.20 TEC TEH 55 HOT 600UL 89 101 0.34 154 P2 TWD 17 07H

+0.90 TEC TEH 54 HOT 600UL 95 101 0.10 29 P2 TWD 9 09H

+0.72 TEC TEH 55 HOT 600UL 0.42 88 P2 TWD 27 09H

-0.58 TEC TEH 55 HOT 600UL 99 101 0.22 97 P2 TWD 17 09H

+0.70 TEC TEH 55 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 20 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 0.21 11 P3 TWD 17 DBH

+0.94 TEC TEH 55 HOT 600UL 0.25 116 P2 TWD 19 08H

-0.20 TEC TEH 55 HOT 600UL 101 101 0.30 67 P2 TWD 13 09H

-0.28 TEC TEH 54 HOT 600UL 105 101 0.22 135 P2 TWD 12 VH2

+0.26 TEC TEH 54 HOT 600UL 133 101 0.17 153 P2 TWD 12 VHE

-0.94 TEC TEH 63 HOT 600OUL 143 101 0.08 20 P3 TWD 7 DBC

+1.56 TEC TEH 63 HOT 60OUL 0.20 100 P2 TWD 14 VC1

-0.86 TEC TEH 63 HOT 600UL 44 102 0.39 94 P3 TWD 16 DBC

+2.15 TEH TEC 17 COLD 60OUL 48 102 0.32 74 P3 TWD 16 DBH

-1.71 TEH TEC 18 COLD 600UL 78 102 0.35 17 P3 TWD 14 DBH

+2.07 TEH TEC 17 COLD 600UL 80 102 0.78 74 P2 TWD 27 VC3

-0.85 TEH TEC 17 COLD 600UL 84 102 0.30 142 P2 TWD 15 07H

-0.87 TEC TEH 47 HOT 600UL 0.21 101 P2 TWD 11 09H

+1.55 TEC TEH LOCOK 47 HOT 600UL 0.40 90 P2 TWD 19 09H

-1.47 TEC TEH LOCOK 47 HOT 600UL 86 102 0.26 159 P2 TWO 16 09E

+0.57 TEC TEN 46 HOT 6000L 90 102 0.19 149 P2 TWD 13 09H

+0.89 TEC TEH 46 HOT 600UL 0.35 94 P2 TWO 20 08H

-0.08 TEC TEE 46 HOT 600UL 0.19 36 P2 TWD 13 09H

-0.22 TEC TEH 46 HOT 600UL 92 102 0.49 93 P2 TWD 25 09H

+0.97 TEC TEH 46 HOT 600UL 0.41 145 P2 TWD 13 09H

-1.04 TEC TEH 46 HOT 600UL 94 102 0.33 112 P2 TWD 16 09H

-0.42 TEC TEH 47 HOT 600UL 100 102 0.30 125 P2 TWD 18 09H

-0.24 TEC TEH 46 HOT 600UL 134 102 0.35 151 P2 TWO 17 VH2

+0.80 TEC TEH 59 HOT 60OUL 144 102 0.22 62 P3 TWD 14 ONH

+1.72 TEC TEH 59 HOT 600UL 0.37 78 P2 TWD 18 VC3

+0.78 TEC TEH 59 HOT 600UL 41 103 0.41 77 P3 TWO 16 ONE

-1.59 TEE TEC 17 COLD 600UL 0.52 68 P3 TWO 20 ONE

+1.83 TEN TEC 17 COLD 600UL 91 103 0.32 100 P2 TWD 16 08H

+0.78 TEC TEH 47' HOT 600UL 0.12 129 P2 TWO 6 08H

-0.89 TEC TEE 47 HOT 600UL 95 103 0.35 94 P2 TWD 17 09E

+0.75 TEC TEH 47 HOT 600UL 97 103 0.53 125 P2 TWO 27 09H

+0.24 TEC TEN 46 HOT 600UL 99 103 0.23 101 P2 TWD 12 09H

+0.64 TEC TEE 47 HOT 600UL 0.49 94 P2 TWD 22 09H

+0.87 TEC TEE 47 NOT 600UL 127 103 0.68 99 P2 TWD 27 V0H

+0.97 TEC TEH 47 HOT 60OUL 0.28 147 P2 TWD 14 V0H

-0.81 TEC TEH 47 HOT 600UL 137 103 0.59 65 P2 TWO 24 VHIi

-0.8S TEC TE-58 NOT 600UL 0.36 43 P2 TWD 17 V0H

+0.65 TEC TEH 58 HOT 600UL 38 104 0.29 78 P3 TWO 14 ONE

-1.55 TEE TEC 18 COLD 600UL 40 104 0.88 143 P2 TWO 29 VSM

+0.81 TEE TEC 17 COLD 600UL 0.16 48 P2 TWO 6 VSM

-0.08 TEN TEC 17 COLD 600UL 0.27 141 P2 TWO 12 VSM

-1.00 TEE TEC 17 COLD 600UL 48 104 0.64 109 P2 TWO 24 VSM

+0.87 TEN TEC 17 COLD 600UL 92 104 0.28 20 P2 TWD 14 09H

+0.28 TEC TEH 47 HOT 600UL 94 104 0.15 43 P3 TWD 10 0BH

+1.26 TEC TEH 46 HOT 600UL 126 104 0.34 143 P2 TWD 17 VHl

-0.77 TEC TEH 47 HOT 600UL 142 104 0.30 137 P3 TWD 18 OHE

+2.01 TEC TEH 59 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 21 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 37 105 0.60 61 P3 TWD 22 DBH

+1.87 TEH TEC 17 COLD 600UL 91 105 0.31 76 P2 TWD 16 09H

-0.18 TEC TEH 47 HOT 60OUL 93 105 0.24 96 P2 TWD 15 08H

-0.47 TEC TEH 46 HOT 600UL 95 105 0.50 139 P2 TWD 22 09H

+0.80 TEC TEH 47 HOT 600UL 0.19 28 P3 TWD 12 DBH

+0.70 TEC TEH 47 HOT 600UL 105 105 0.21 106 P2 TWD 14 VH2

-0.61 TEC TEH 46 HOT 600UL 143 105 0.40 123 P3 TWD 22 DBC

+1.61 TEC TEH 59 HOT 600UL 0.34 62 P3 TWD 20 DBH

-1.65 TEC TEH 59 HOT 600UL 0.33 17 P3 TWD 19 DBH

+1.71 TEC TEH 59 HOT 600UL 32 106 0.40 128 P2 TWD 17 04C

+0.89 TEH TEC 17 COLD 60OUL 38 106 0.30

.114 P2 TWD 15 VSM

+1.01 TEH TEC 18 COLD 60OUL 0.17 100 P2 TWD 9 VSM

+0.04 TEH TEC 18 COLD 600UL 48 106 0.44 89 P2 TWD 18 VSM

-0.73 TEH TEC 17 COLD 60OUL 0.68 92 P2 TWD 25 VSM

-0.10 TEH TEC 17 COLD 60OUL 0.64 131 P2 TWD 24 VSM

+0.90 TEH TEC 17 COLD 600UL 84 106 0.61 125 P2 TWD 29 09H

+1.57 TEC TEH LOCOK 46 HOT 600UL 0.37 142 P2 TWD 21 09H

-1.69 TEC TEH LOCOK 46 HOT 60OUL 98 106 0.36 147 P2 TWD 17 09H

+0.90 TEC TEH 47 HOT 600UL 0.26 79 P2 TWD 13 09H

-0.18 TEC TEH 47 HOT 600UL 102 106 0.17 55 P2 TWD 9

04C

.+0.91 TEC TEH 47 HOT 600UL 126 106 0.40 120 P2 TWD 19 VHI

-0.54 TEC TEH 47 HOT 600UL 128 106 0.46 152 P2 TWD 24 VHI

-0.89 TEC TEH 46 HOT 600UL 130 106 0.24 70 P2 TWD 12 VHI

-0.22 TEC TEH 47 HOT 60OUL 0.43 142 P2 TWD 20 VHI

-0.83 TEC TEH 47 HOT 600UL 140 106 0.21 80 P3 TWD 13 DBH

+1.75 TEC TEH 59 HOT 60OUL 29 107 0.42 119 P3 TWD 17 DBH

-1.76 TEH TEC 17 COLD 600UL 35 107 0.34 140 P2 TWD 17 VSM

+0.00 TEH TEC 18 COLD 600UL 0.35 143 P2 TWD 17 VSM

-0.89 TEH TEC 18 COLD 600UL 39 107 0.30 99 P2 TWD 15 07H

+0.02 TEH TEC 18 COLD 600UL 73 107 0.19 153 P2 TWD 10 VH3

-0.79 TEH TEC 18 COLD 600UL 0.77 140 P2 TWD 28 VH3

+0.77 TEH TEC 18 COLD 600UL 97 107 0.36 37 P2 TWD 21 09H

-0.04 TEC TEH 46 HOT 600UL 0.52 76 P2 TWD 26 09H

-0.71 TEC TEH 46 HOT 60OUL 111 107 0.50 122 P2 TWD 22 VH2

-0.81 TEC TEH 51 HOT 60OUL 115 107 0.24 10 P3 TWD 14 DBH

+2.06 TEC TEH 51 HOT 600UL 24 108 0.59 128 P2 TWO 24 VSN

-0.71 TEE TEC 18 COLD E00UL 36 108 0.45 111 P2 TWD 20 VSM

-0.89 TEH TEC 18 COLD 600UL 0.46 121 P2 TWD 21 VSM

-0.12 TEH TEC 18 COLD 600UL 44 108 0.75 131 P2 TWD 28 VSM

-0.83 TEH TEC 18 COLD 60OUL 0.70 113 P2 TWD 27 VSM

-0.23 TEH TEC 18 COLD 60OUL 48 108 0.39 121 P2 TWD 18 VSM

-0.32 TEH TEC 18 COLD 600UL 84 108 0.36 134 P2 TWO 18 09E

+1.65 TEC TEE LOCOK 50 HOT 600UL 0.36 144 P2 TWD 18 09H

-1.63 TEC TEH LOCOK 50 HOT 60OUL 86 108 0.33 67 P2 TWD 16 09H

+0.54 TEC TEH 51 HOT 600UL 102 108 0.40 99 P2 TWD 19 VH2

-0.84 TEC TEH 51 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 22 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 126 108 0.24 113 P2 TWD 12 VHI

+0.14 TEC TEH 51 HOT 600UL 0.47 139 P2 TWD 21 VHI

-1.23 TEC TEH 51 HOT 600UL 136 108 0.44 122 P2 TWD 20 VHN

-0.79 TEC TEH 58 NOT 600UL 0.30 96 P2 TWD 15 VHN

+0.73 TEC TEH 58 HOT 600UL 142 108 0.25 125 P2 TWD 13 VH3

+0.82 TEC TEH 59 HOT 600UL 17 109 0.25 61 P3 TWD 13 DBC

-2.00 TEH TEC 18 COLD 600UL 23 109 0.32 61 P2 TWD 14 07H

+0.00 TEH TEC 17 COLD 600UL 47 109 0.38 69 P2 TWD 16 VSM

-0.12 TEH TEC 17 COLD 600UL 81 109 0.27 51 P2 TWD 14 VSM

.- 0.06 TEC TEH 50 HOT 600UL 89 109 0.20 102 P2 TWD 12 09H

+0.57 TEC TEH 50 HOT 600UL 0.26 48 P2 TWD 14 08H

-0.37 TEC TEH 50 HOT 600UL 95 109 0.26 98 P2 TWO 13 09N

+0.88 TEC TEN 51 NOT 600UL 99 109 0.24 34 P2 TWD 13 09H

+0.64 TEC TEH 51 HOT 600UL 44 110 0.63 132 P2 TWD 23 VSM

+0.81 TEH TEC 17 COLD 60OUL 0.24 79 P3 TWD 10 DBC

+1.34 TEH TEC 17 COLD 600UL 82 110 0.38 94 P2 TWD 19 VH3

+0.73 TEC TEH 50 HOT 600UL 84 110 0.28 28 P2 TWD 15 08H

-0.02 TEC TEH 50 HOT 600UL 0.65 96 P2 TWD 27 09H

+1.40 TEC TEH LOCOK 50 HOT 600UL 0.29 137 P2 TWD 15 09H

-1.42 TEC TEH LOCOK 50 HOT 600UL 96 110 0.18 51 P2 TWD 11 09H

+0.12 TEC TEH 50 HOT 600UL 122 110 0.32 153 P2 TWD 16 VH1

-0.83 TEC TEH 50 HOT 600UL 124 110 0.53 102 P2 TWD 23 VH1

-0.16 TEC TEH 51 HOT 60OUL 130 110 0.28 139 P2 TWD 14 VH2

-0.92 TEC TEH 51 HOT 600UL 134 110 0.51 145 P2 TWD 23 VH1

-0.86 TEC TEH 59 HOT 600UL 142 110 0.18 84 P3 TWD 12 DBH

+1.88 TEC TEH 59 HOT 600UL 47 111 0.38 159 P2 TWD 16 VSM

-0.73 TEH TEC 17 COLD 60OUL 0.63 106 P2 TWD 23 VSM

+0.00 TEH TEC 17 COLD 600UL 73 111 0.21 142 P2 TWD 12 VSM

-0.58 TEH TEC 18 COLD 600UL 0.29 142 P2 TWD 15 VSM

+0.73 TEH TEC 18 COLD 600UL 87 111 0.21 120 P2 TWD 11 08H

-0.47 TEC TEH 50 HOT 600UL 91 111 0.42 64 P2 TWD 20 09H

-0.26 TEC TEH 50 HOT 60OUL 93 111 0.36 131 P2 TWD 18 08H

+0.22 TEC TEH 51 HOT 600UL 95 111 0.38 124 P2 TWD 18 09H

+0.99 TEC TEH 50 HOT 60OUL 127 11 0.35 149 P2 TWD 18 VHN

-0.75 TEC TEH 50 HOT 600UL 139 11 0.29 71 P3 TWD 12 DBH

+1.68 TEC TEH 58 HOT 600UL 34 112 0.28 109 P2 TWD 13. VSM

+0.79 TEH TEC 19 COLD 600UL 36 112 '0.65 161 P2 TWD 27 VSM

+0.79 TEH TEC 20 COLD 600UL 0.34 153 P2 TWD 17 VSM

-0.81 TEH TEC 20 COLD 60OUL 86 112 0.33 68 P2 TWD 17 08H

-0.26 TEC TEH 50 HOT 600UL 92 112 0.55 97 P2 TWD 24 09H

+0.24 TEC TEH 50 HOT 600UL 0.22 40 P2 TWD 12 09H

+0.81 TEC TEH 50 HOT 600UL 0.12 156 P2 TWD 6

09H

-1.18 TEC TEH 50 HOT 600UL 106 112 0.18 129 P3 TWD 11 DBC

-1.71 TEC TEH 51 HOT 600UL 114 112 0.34 90 P2 TWD 17 VH2

-0.92 TEC TEH 51 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 23 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 124 112 0.62 89 P2 TWD 26 VH1

+0.63 TEC TEH 50 HOT 600UL 1

113 0.37 130 P2 TWD 19 04H

+0.77 07H TEH 4

HOT 600UL 77 113 0.19 152 P2 TWD 11 VC3

-0.85 TEH TEC 20 COLD 60OUL 0.24 112 P2 TWD 13 VSM

+0.89 TEH TEC 20 COLD 600UL 0.47 127 P2 TWD 22 VH3

+0.85 TEH TEC 20 COLD 600UL 0.24 123 P2 TWD 13 VSM

-0.02 TEH TEC 20 COLD 600UL 0.10 134 P3 TWD 6

DBC

+1.80 TEH TEC 20 COLD 600UL 0.18 140 P2 TWD 10 VH3

-0.67 TEH TEC 20 COLD 600UL 0.27 27 P2 TWD 14 VH3

+0.02 TEH TEC 20 COLD 600UL 89 113 0.39 106 P2 TWD 19 09H

+0.46 TEC TEH 51 HOT 600UL 91 113 0.49 70 P2 TWD 22 09H

+0.33 TEC TEH 50 HOT 600UL 0.29 48 P2 TWD 15 09H

-0.43 TEC TEH 50 HOT 600UL 93 113 0.35 59 P2 TWD 17 09H

+0.56 TEC TEH 51 HOT 600UL 95 113 0.18 160 P2 TWD 10 VH2

-0.83 TEC TEH 50 HOT 600UL 101 113 0.38 14 P3 TWD 21 DBH

+1.51 TEC TEH 51 HOT 600UL 105 113 0.26 128 P2 TWD 13 VH2

-0.08 TEC TEH 51 HOT 600UL 141 113 0.33 146 P2 TWD 16 09C

+0.83 TEC TEH 59 HOT 60OUL 0.20 35 P3 TWD 13 DBH

+2.07 TEC TEH 59 HOT 600UL 70 114 0.25 130 P2 TWD 13 07H

-0.78 TEH TEC 20 COLD 600UL 76 114 0.61 117 P2 TWD 24 VH3

+0.65 TEH TEC 19 COLD 600UL 0.30 124 P2 TWD 13 VSM

-0.53 TEH TEC 19 COLD 600UL 0.40 136 P2 TWD 17 VC3

+0.89 TEH TEC 19 COLD 600UL 84

.114 0.37 109 P2 TWD 18 09H

+1.40 TEC TEH LOCOK 50 HOT 600UL 0.59 130 P2 TWD 25 09H

-1.32 TEC TEH LOCOK 50 HOT 600UL 120 114 0.22 82 P3 TwO 12 DBH

+0.59 TEC TEH 50 HOT 600UL 122 114 0.24 118 P2 TWD 12 VH1

+0.66 TEC TEH 51 HOT 600UL 126 114 0.27 99 P2 TWD 14 VHI

+0.00 TEC TEH 51 HOT 600UL 31 115 0.46 117 P2 TWD 19 07H

-0.06 TEH TEC 19 COLD 600UL 43 115 0.59 126 P2 TWD 23 VSM

+0.89 TEH TEC 19 COLD 600UL 49 115 0.33 141 P2 TWD 17 08H

+1.50 TEH TEC LOCOK 20 COLD 60OUL 79 115 0.37 158 P2 TWD 16 VH3

+0.75 TEH TEC 19 COLD 600UL 0.26 148 P2 TWD 12 VSM

-0.06 TEH TEC 19 COLD 600UL 0.48 115 P2 TWD 20 VC3

-0.77 TEH TEC 19 COLD 600UL 89 115 0.21 141 P3 TWD 11 DBH

-1.38 TEC TEH 50 HOT 600UL 91 115 0.34 112 P2 TWD 17 09H

+0.28 TEC TEH 51 NOT 600UL 113 115 0.30 146 P3 TWD 15 DBH

-2.15 TEC TEH 50 HOT 600UL 125 115 0.35 148 P2 TWD 17 VH1

+0.83 TEC TEH 50 HOT 600UL 127 115 0.43 106 P2 TWD 20 VH1

+0.88 TEC TEH 51 HOT 600UL 84 116 0.37 66 P2 TWD 18 09H

-1.38 TEC TEH LOCOK 50 HOT 600UL 0.56 149 P2 TWD 24 09H

+1.26 TEC TEH LOCOK 50 HOT 600UL 90 116 0.44 145 P2 TWD 20 VH2

-0.92 TEC TEH 51 HOT 600UL 124 116 0.68 148 P2 TWD 27 VHI

-0.77 TEC TEH 50 HOT 600UL 79 117 0.76 109 P2 TWO 27 VC3

-0.91 TEN TEC 19 COLD 600UL 0.78 139 P2 TWD 28 VC3

+0.81 TEH TEC 19 COLD 600UL 0.29 79 P2 TWD 13 07H

-0.78 TEH TEC 19 COLD 600UL 83 117 0.27 136 P2 TWD 14 05C

+0.53 TEC TEH 51 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 24 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 87 117 0.32 123 P2 TWD 16 09H

+0.26 TEC TEH 51 HOT 600UL 113 117 0.16 133 P3 TWD 9 DBH

+2.03 TEC TEH 50 HOT 60OUL 121 117 0.30 140 P2 TWD 15 VH2

-0.87 TEC TEH 50 HOT 600UL 46 118 0.19 91 P2 TWD 8 07H

+0.39 TEH TEC 19 COLD 600UL 74 118 0.47 107 P2 TWD 20 08H

+0.95 TEH TEC 19 COLD 600UL 84 118 0.38 108 P2 TWD 18 09H

-0.54 TEC TEH 51 HOT 600UL 126 118 0.30 155 P2 TWD 15 VHl

+0.88 TEC TEH 51 HOT 60OUL 132 118 0.09 151 P3 TWD 5 DBH

+1.74 TEC TEH 58 NOT 600UL 1-36 118 0.21 20 P3 TWD 13 DBH

+1.60 TEC TEH 59 HOT 600UL 23 119 0.26 16 P1 SCI TSH

-0.11 TSH TSH 0.13 LAR 141 HOT 580PP 85 119 0.47 135 P2 TWD 22 09H

+0.12 TEC TEH 50 HOT 600UL 127 119 0.25 122 P2 TWD 13 VHI

-1.01 TEC TEH 53 HOT 600UL 106 120 0.19 79 P3 TWD 9 DBC

+1.73 TEC TEH 52 HOT 600UL 120 120 0.34 159 P2 TWD 17 VH2

-0.88 TEC TEH 53 HOT 600UL 0.44 113 P2 TWD 21 10H

-2.05 TEC TEH LOCOK 53 HOT 600UL 124 120 0.46 126 P2 TWD 21 VH2

-0.86 TEC TEH 53 HOT 60OUL 0.41 120 P2 TWD 20 VHI

-1.02 TEC TEH 53 HOT 60OUL 35 121 0.32 116 P2 TWD 14 05H

+0.71 TEH TEC 19 COLD 600UL 75 121 0.23 153 P2 TWD 10 VH3

-0.89 TEH TEC 19 COLD 600UL 81 121 0.64 114 P2 TWD 26 VH3

-0.85 TEC TEH 52 HOT 600UL 0.46 157 P2 TWD 21 VH3

+0.77 TEC TEH 52 HOT 600UL 121 121 0.10 117 P2 TWD 5 10H

+1.09 TEC TEH 53 HOT 600UL 40 122 0.24 133 P2 TWD 12 07H

-0.44 TEN TEC 22 COLD 600UL 84 122 0.26 138 P2 TWD 13 09H

-1.54 TEC TEH LOCOK 52 HOT 600UL 112 122 0.52 71 P2 TWD 23 04C

-0.91 TEC TEH 52 HOT 60OUL 23 123 0.36 106 P2 TWD 15 07H

+0.39 TEH TEC 21 COLD 60OUL 43 123 0.41 94 P2 TWD 17 07H

-0.39 TEH TEC 21 COLD 600UL 59 123 0.28 67 P2 TWD 13 07H

-0.33 TEH TEC 21 COLD 60OUL 32 124 0.63 137 P2 TWD 24 VSM

-0.70 TEH TEC 21 COLD 600UL 78 124 0.22 146 P2 TWD 11 VH3

+0.00 TEH TEC 22 COLD 600UL 0.51 85 P2 TWD 21 VH3

+0.93 TEH TEC 22 COLD 60OUL 0.30 71 P2 TWD 15 VC3

-0.71 TEH TEC 22 COLD 60OUL 0.46 109 P2 TWD 20 VC3

+0.93 TEH TEC 22 COLD 600UL 120 124 0.35 79 P2 TWD 17 10H

+1.14 TEC TEH 52 HOT 600UL 23 125 0.32 48 P2 TWD 16 07H

-0.50 TEC TEH 27 HOT 600UL 35 125 0.28 100 P2 TWO 15 VSM

+0.87 TEC TEE 27 NOT 600UL 0.28 107 P2 TWD 15 VSM

-0.76 TEC TEH 27 HOT 600UL 47 125 0.32 158 P2 TWD 17 VSM

+0.73 TEC TEH 26 HOT 600UL 49 125 0.32 117 P2 TWD 17 08H

-1.24 TEC TEH 27 HOT 600UL 0.42 73 P2 TWD 20 08H

+1.45 TEC TEH LOCOK 27 HOT 60OUL 79 125 0.26 99 P2 TWD 14 VC3

-0.87 TEC TEH 26 HOT 60OUL 0.34 131 P2 TWD 18 VC3

+0.83 TEC TEH 26 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 25 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2(l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 127 125 0.35 99 P2 TWD 18 VH2

+0.91 TEC TEH 52 HOT 600UL 24 126 0.33 78 P2 TWD 16 07H

+0.77 TEC TEH 27 HOT 600UL 48 126 0.47 153 P2 TWD 22 VSM

+0.79 TEC TEH 26 HOT 600UL 76 126 0.24 65 P2 TWD 13 VSM

-0.84 TEC TEH 26 HOT 600UL 114 126 0.31 114 P2 TWO 16 VC2

-0.91 TEC TEN 53 NOT 600UL 0.37 148 P2 TWD 18 VN2

-0.91 TEC TEH 53 HOT 600UL 23 127 0.30 129 P2 TWD 16 06H

+0.38 TEC TEH 26 HOT 600UL 37 127 0.29 108 P2 TWD 15 VSM

-0.90 TEC TEH 27 HOT 600UL 0.20 146 P2 TWD 10 VSM

-0.14 TEC TEH 27 HOT 60OUL 0.18 111 P2 TWD 10 VSM

+0.75 TEC TEH 27 HOT 600UL 85 127 0.36 47 P2 TWD 17 VH2

+1.03 TEC TEH 52 HOT 600UL 32 128 0.49 27 P1 MCI TSH

-0.07 TSH TSH 0.36 LAR 137 HOT 580PP 34 128 0.32 70 P2 TWD 17 01H

+0.85 TEC TEH 26 HOT 600UL 0.19 111 P2 TWD 11 VSM

+0.86 TEC TEH 26 HOT 600UL 60 128 0.27 49 P2 TWD 15 08H

+0.26 TEC TEH 26 HOT 60OUL 64 128 0.28 116 P2 TWD 15 02H

-1.23 TEC TEH 26 HOT 60OUL 0.31 117 P2 TWD 17 08H

+0.39 TEC TEH 26 HOT 600UL 41 129 0.39 18 P3 TWD 22 DBH

+1.13 TEC TEH 31 HOT 600UL 61 129 0.45 94 P2 TWD 22 08H

+0.38 TEC TEH 31 HOT 600UL 81 129 0.82 105 P2 TWD 30 VC3

+0.69 TEC TEH 52 HOT 600UL 0.39 94 P2 TWD 18 VH3

+0.89 TEC TEH 52 HOT 600UL 0.21 94 P2 TWD 11 VH3

-0.08 TEC TEH 52 HOT 600UL 0.17 80 P2 TWD 9 VC3

+0.20 TEC TEH 52 HOT 600UL 129 129 0.37 121 P3 TWD 17 DBH

+2.08 TEC TEH 52 HOT 600UL 82 130 0.29 89 P2 TWD 17 VC3

-0.85 TEC TEH 40 HOT 600UL 0.54 142 P2 TWD 26 VH3

-0.91 TEC TEH 40 HOT 600UL 128 130 0.25 81 P2 TWD 14 08C

-0.95 TEC TEH 41 HOT 600UL 49 131 0.21 37 P3 TWD 13 DBH

-0.83 TEC TEH 8

HOT 600UL 77 131 0.32 134 P2 TWD 17 VH3

-0.91 TEC TEH 8

HOT 600UL 79 131 0.26 43 P2 TWD 14 VSM

-0.61 TEC TEH 7

HOT 600UL 76 132 0.32 139 P2 TWD 17 VH3

+0.75 TEC TEH 8

HOT 600UL 0.24 135 P2 TWD 13 VH3

-0.85 TEC TEH 8

HOT 600UL 0.12 76 P3 TWD 8 DBC

-1.80 TEC TEH 8

HOT 600UL 80 132 0.17 142 P3 TWD 8 DBC

+1.99 TEC TEH 7

HOT 600UL 82 132 0.28 137 P2 TWD 17 VH3

-0.88 TEC TEH 40 HOT 60OUL 0.32 147 P2 TWD 18 VH3

+0.86 TEC TEH 40 HOT 600UL 112 132 0.35 70 P2 TWD 18 VC2

-0.95 TEC TEH 41 HOT 600UL 0.39 36 P2 TWD 19 VC3

+0.59 TEC TEH 41 HOT 600UL 114 132 0.33 135 P2 TWD 19 VH2

-0.90 TEC TEH 40 HOT 600UL 115 133 0.42 71 P2 TWD 21 VH1

+0.91 TEC TEH 41 HOT 600UL 8

134 0.28 62 P3 TWD 16 DBC

-1.13 TEC TEH 38 HOT 600UL 76 134 0.14 44 P3 TWD 10 DBC

+2.15 TEC TEH 8

HOT 600UL 94 134 0.10 9

P3 TWD 5 DBC

+1.98 TEC TEH 40 HOT 600UL 100 134 0.13 133 P3 TWD 9 DBC

+2.21 TEC TEH 41 HOT 600UL 106 134 0.66 130 P2 TWD 29 VH2

-0.91 TEC TEH 40 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name:

SONGS Unit 3 Component: S/G 88 Page 26 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 124 134 0.11 32 P3 TWD 7 DBH

+1.65 TEC TEN 41 HOT 600UL 76 136 0.35 120 P2 TWD 19 VSM

-0.79 TEC TEN 13 HOT 600UL 0.58 112 P2 TWD 26 VH3

+0.95 TEC TEN 13 HOT 60OUL 47 137 0.36 77 P2 TWD 18 VSM

+0.17 TEC TEH 12 HOT 600UL 70 138 0.37 102 P2 TWD 18 VC3

-0.89 TEC TEN 12 HOT 600UL 114 138 0.43 121 P2 TWD 23 VH2

-0.93 TEC TEN 40 HOT 600UL 83 139 0.29 155 P2 TWD 16 VH2

+0.87 TEC TEN 41 HOT 600UL 110 140 0.27 103 P2 TWD 15 VH2

+0.62 TEC TEN 41 HOT 600UL 61 141 0.31 96 P2 TWD 16 VSM

-0.89 TEC TEN 13 HOT 600UL 81 141 0.30 152 P2 TWO 18 VH3

+0.78 TEC TEN 40 NOT 600UL 0.32 158 P2 TWD 19 VH3

-0.78 TEC TEN 40 HOT 600UL 52 142 0.32 129 P2 TWD 17 VH3

-1.19 TEC TEN 13 HOT 600UL 60 142 0.26 59 P2 TWD 14 VH3

-0.83 TEC TEN 13 HOT 600UL 80 142 0.24 122 P2 TWD 13 VSM

+0.94 TEC TEN 12 HOT 600UL 0.44 146 P2 TWD 21 VSM

-0.79 TEC TEN 12 HOT 60OUL 0.64 125 P2 TWD 26 VC3

-0.71 TEC TEN 12 HOT 600UL 0.48 139 P2 TWD 22 VC3

-0.91 TEC TEN 12 HOT 600UL 0.46 134 P2 TWD 21 VN3

+0.77 TEC TEN 12 HOT 600UL 0.62 132 P2 TWD 26 VH3

-0.89 TEC TEN 12 HOT 600UL 98 142 0.34 155 P2 TWD 18 VH2

-0.95 TEC TEN 41 HOT 600UL 110 142 0.31 77 P2 TWD 17 VC2

-0.95 TEC TEN 41 HOT 60OUL 67 143 0.26 39 P2 TWD 14 VC3

+0.84 TEC TEN 13 HOT 600UL 0.49 116 P2 TWD 23 VH3

+0.76 TEC TEN 13 HOT 600UL 107 143 0.47 134 P2 TWD 25 VH2

-0.81 TEC TEN 46 HOT 600UL 102 144 0.39 91 P2 TWD 22 VH2

+0.88 TEC TEN 46 HOT 600UL 21 145 0.26 155 P2 TWD 15 VSM

-1.03 TEC TEN 13 HOT 600UL 23 145 0.28 98 P2 TWD 14 VSM

-1.13 TEC TEN 12 HOT 600UL 53 145 0.26 98 P2 TWD 14 VH3

+0.65 TEC TEN 13 HOT 600UL 54 146 0.30 81 P2 TWD 16 VH3

-0.91 TEC TEH 17 HOT 600UL 56 146 0.52 128 P2 TWD 25 VH3

-0.91 TEC TEN 16 HOT 600UL 94 146 0.28 121 P2 TWD 14 VH2

+0.93 TEC TEN 47 HOT 600UL 0.28 156 P2 TWD 14 VH2

-1.21 TEC TEN 47 HOT 600UL 0.63 106 P2 TWD 26 VH3

-0.91 TEC TEN 47 HOT 600UL 102 146 0.41 145 P2 TWD 19 VH2

-0.84 TEC TEN 47 HOT 600UL 37 147 0.27 133 P2 TWD 14 VSM

+0.74 TEC TEN 17 HOT 6GOUL 52, 148 0.40 114 P2 TWD 20 VH3

-1.17 TEC TEN 17 HOT 600UL 72 148 0.29 121 P2 TWD 15 VC3

+0.92 TEC TEN 17 HOT 600UL 94 148 0.27 55 P2 TWD 14 VC3

+0.97 TEC TEN 47 HOT 600UL 43 149 0.40 60 P2 TWD 21 VSM

+0.90 TEC TEN 16 HOT 600UL 53 149 0.52 135 P2 TWD 23 VH3

+0.87 TEC TEN 17 HOT 600UL 93 149 0.17 35 P3 TWD 11 DBC

-1.76 TEC TEN 46 HOT 600UL 53 151 0.70 117 P2 TWD 28 VH3

+0.81 TEC TEN 17 HOT 600UL 89 151 0.35 104 P2 TWD 20 VC3

-0.87 TEC TEN 46 HOT 600UL

AREVA NP Inc 11/18/06 09:45:09 Customer Name: SONGS Unit 3 Component: S/G 88 Page 27 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 48 152 0.67 92 P2 TWD 28 VSM

-0.65 TEC TEH 17 HOT 600UL 82 152 0.30 146 P2 TWD 18 08C

-0.18 TEC TEH 46 HOT 60OUL 96 152 0.30 122 P2 TWD 15 02C

+0.85 TEC TEH 47 HOT 600UL 23 153 0.32 74 P2 TWD 18 VSM

-0.89 TEC.TEH 16 HOT 60OUL 81 153 0.21 150 P3 TWD 13 DBC

+1.89 TEC TEH 46 HOT 600UL 83 153 0.39 102 P2 TWD 18 VH2

+0.78 TEC TEH 47 HOT 600UL 44 154 0.39 95 P2 TWD 19 VSM

+0.72 TEC TEH 22 HOT 600UL 48 154 0.30 147 P2 TWD 15 VSM

+0.86 TEC TEH 22 HOT 600UL 0.15 54 P2 TWD 8 VSM

-0.08 TEC TEH 22 HOT 600UL 62 156 0.20 41 P2 TWD 10 VSM

+0.10 TEC TEH 22 HOT 600UL 83 157 0.31 87 P2 TWD 16 VH2

+0.88 TEC TEH 47 HOT 60OUL 85 157 0.21 15 P3 TWD 13 DBH

+1.35 TEC TEH 46 HOT 600UL 74 160 0.47 73 P2 TWD 21 08C

-0.25 TEC TEH 22 HOT 600UL 31 161 0.14 167 P3 TWD 9 DBH

+1.24 TEC TEH 22 HOT 600UL 77 161 0.27 37 P2 TWD 13 07C

-0.96 TEC TEH 23 HOT 600OUL 0.26 105 P2 TWD 13 08C

-0.98 TEC TEH 23 HOT 60OUL 0.20 141 P3 TWD 13 DBH

+1.78 TEC TEH 23 HOT 600UL 79 161 0.29 78 P3 TWD 16 DBH

+1.77 TEC TEH 22 HOT 600UL" 0.36 102 P2 TWD 17 08H

+0.75 TEC TEH 22 HOT 600UL 36 162 0.28 48 P2 TWD 14 VSM

+0.85 TEC TEH 23 HOT 600UL 70 162 0.31 155 P2 'TWD 15 08H

+0.81 TEC TEH 22 HOT 600UL 70 164 0.43 43 P2 TWD 19 08H

+1.06 TEC TEH 22 HOT 60OUL 65 165 0.51 116 P2 TWD 22 01C

-0.91 TEC TEH 23 HOT 600UL 56 166 0.55 99 P2 TWD 24 01C

-0.89 TEC TEH 27 HOT 600UL

'62 166 0.24 62 P2 TWD 14 01H

+0.14 TEC TEH 26 HOT 600UL 31 167 0.27 138 P3 TWD 18 DBH

+0.65 TEC TEH 27 HOT 600UL 57 167 0.27 138 P2 TWD 15 01H

+0.08 TEC TEH 26 HOT 600UL 32 168 0.11 137 P3 TWD 9 DBH

+0.18 TEC TEH 27 HOT 600UL 52 168 0.33 104 P2 TWD 17 01H

+0.04 TEC TEH 26 HOT 600OUL 0.45 120 P2 TWD 21 01C

-0.16 TEC TEH 26 HOT 600UL 45 169 0.24 76 P2 TWD 13 02C

-0.92 TEC TEH 26 HOT 600UL 49 169 0.38 79 P2 TWD 20 01C

-0.86 TEC TEH 26 HOT 600UL 38 170 0.20 40 P2 TWD 11 01H

-0.12 TEC TEH 26 HOT 600UL 28 172 0.42 42 P2 TWD 20 01C

+0.00 TEC TEH 27 HOT 600OUL 30 172 0.31 47 P2 TWD 16 06H

+0.91 TEC TEH 26 HOT 600UL 34 172 0.45 82 P2 TWD 22 VSM

+0.90 TEC TEH 26 HOT 600UL 17 173 0.47 123 P2 TWD 22 01C

-0.93 TEC TEH 27 HOT 600UL 7

175 0.30 149 P2 TWD 16 01C

-0.89 TEC TEH 38 HOT 600UL Total Tubes

820 Total Records: 1152

AREVA NP Inc Customer Name: SONGS Unit 3 11/18/06 09:45:10 Component: S/G 88 Page 28 of 28

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE

Inspection of Steam Generator Tubes Special Report Appendix 4 Page 1 of 18 Appendix 4 Tube Inspection Summary Steam Generator E-089

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 2 of 18

MAI, MCI,
MIMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 44 6

0.51 128 P2 TWD 21 VSM

+0.86 TEC TEH 20 HOT 600UL 41 7

0.51 71 P2 TWD 21 VSM

+0.88 TEC TEH 20 HOT 600UL 0.41 103 P2 TWD 18 VSM

-0.77 TEC TEH 20 HOT 600UL 18 8

0.30 59 P2 TWD 14 02H

-0.84 TEC TEH 20 HOT 600UL 54 8

0.47 109 P2 TWD 20 02C

-0.88 TEC TEH 20 HOT 600UL 55 9

0.28 129 P2 TWD 13 02C

+0.10 TEC TEH 20 HOT 600UL 41 11 0.35 73 P3 TWD 16 DBC

-0.65 TEC TEH 20 HOT 60OUL 68 12 0.45 107 P2 TWD 20 02C

+0.10 TEC TEH 21 HOT 600UL 73 13 0.47 128 P2 TWD 20 VH3

+0.00 TEC TEH 20 HOT 600UL 74 14 0.35 47 P2 TWD 17 VH3

+0.82 TEC TEH 17 HOT 600UL 72 16 0.40 94 P2 TWD 19 VH3

-1.05 TEC TEH 17 HOT 600UL 0.32 52 P2 TWD 16 VH3

+0.74 TEC TEH 17 HOT 60OUL 76 16 0.36 42 P2 TWD 17 08C

+0.00 TEC TEH 17 HOT 600UL 78 16 0.37 53 P2 TWD.17 05C

+0.80 TEC TEH 16 HOT 600UL 83 17 0.37 54 P2 TWD 17 02C

+0.88 TEC TEH 39 HOT 600UL 0.22 111 P2 TWD 11 08H

+0.23 TEC TEH 39 HOT 600UL 0.47 129 P2 TWD 20 08H

+0.72 TEC TEH 39 HOT 600UL 0.12 78 P2 TWD 6 08H

-1.12 TEC TEH 39 HOT 600UL 50 18 0.26 157 P2 TWD 13 VSM

+0.68 TEC TEH 17 HOT 600UL 0.57 75 P2 TWD 24 VSM

-0.93 TEC TEH 17 HOT 600UL 82 18 0.46 144 P2 TWD 19 08C

+0.86 TEC TEH 38 HOT 600UL 71 19 0.18 68 P3 TWD 9 DBH

+1.46 TEC TEH 17 HOT 600UL 75 19 0.64 142 P2 TWD 26 VC3

+0.74 TEC TEH 17 HOT 600UL 0.23 81 P2 TWD 12 VSM

-0.64 TEC TEH 17 HOT 600UL 50 20 0.62 91 P2 TWD 26 VSM

+0.19 TEC TEH 17 HOT 600UL 0.43 116 P2 TWD 20 VSM

+0.60 TEC TEH 17 HOT 600UL 24 22 0.26 131 P2 TWD 13 VSM

-0.89 TEC TEH 16 HOT 600UL 63 23 0.33 75 P2 TWD 16 01H

+0.77 TEC TEH 17 HOT 60OUL 65 23 0.39 144 P2 TWD 18 VH3

+0.83 TEC TEH 16 HOT 600UL 64 24 0.34 97 P3 TWD 15 DBC

+1.16 TEC TEH 12 HOT 600UL 78 24 0.50 100 P2 TWD 22 VC3

-0.91 TEC TEH 13 HOT 600UL 84 24 0.20 22 P3 TWD 10 DBC

+1.84 TEC TEH 38 HOT 600UL 96 24 0.63 97 P2 TWD 24 09C

+0.80 TEC TEH 38 HOT 600UL 98 24 0.41 153 P2 TWD 18 04H

-0.99 TEC TEH 39 HOT 600UL 79 25 0.42 71 P2 TWD 19 08C

-1.07 TEC TEH 12 HOT 600UL 81 27 0.26 127 P3 TWD 12 DBH

-2.22 TEC TEH 38 HOT 600UL 97 27 0.22 166 P3 TWD 10 DBC

-1.91 TEC TEH 38 HOT 600UL 38 28 0.31 121 P2 TWD 15 VSM

-0.83 TEC TEH 13 HOT 600UL 0.43

.58 P2 TWD 19 VSM

+0.83 TEC TEH 13 HOT 600UL 106 28 0.30 115 P3 TWD 14 DBH

+1.58 TEC TEH 39 HOT 600UL 77 29 0.65 137 P2 TWO 25 VC3

+0.81 TEC TEN 12 NOT 600UL 79 29 0.45 68 P2 TWD 20 VC3

+0.81 TEC TEH 12 HOT 600UL 0.37 103 P2 TWD 18 VSM

-0.85 TEC TEH 12 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 3 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 81 29 0.49 101 P2 TWD 20 VH3

+0.77 TEC TEH 38 HOT 600UL 103 29 0.47 109 P2 TWD 20 VH2

+0.74 TEC TEH 39 HOT 600UL 0.43 145 P2 TWD 19 VH2

-0.90 TEC TEH 39 HOT 600UL 36 30 0.42 121 P2 TWD 19 VSM

+0.88 TEC TEH 12 HOT 600UL 46 30 0.22 28 P2 TWD 12 VSM

+0.13 TEC TEH 13 HOT 600UL 72 30 0.43 121 P2 TWD 19 VH3

-0.94 TEC TEH 12 HOT 600UL 106 30 0.43 109 P2 TWD 18 09H

+0.78 TEC TEH 38 HOT 600UL 85 31 0.16 34 P3 TWD 8 DBH

-2.00 TEC TEH 38 HOT 600UL 107 31 0.32 123 P3 TWD 15 DBH

-1.44 TEC TEH 39 HOT 600UL 84 32 0.17 11 P3 TWD 8 DBH

-1.78 TEC TEH 38 HOT 600UL 110 32 0.16 66 P3 TWD 8 DBH

+1.41 TEC TEH 39 HOT 600UL 59 33 0.39 149 P2 TWD 18 VH3

-1.02 TEC TEH 12 HOT 600UL 83 33 0.46 45 P2 TWD 20 07H

+0.84 TEC TEH 39 HOT 60OUL 36 34 0.26 133 P2 TWD 13 VSM

+0.69 TEC TEH 12 HOT 600UL 110 34 0.25 40 P2 TWD 13 07H

+0.24 TEC TEH 43 HOT 600UL 36 36 0.36 68 P2 TWD 17 01H

+0.70 TEC TEH 9

HOT 600UL 1i1 37 0.37 54 P3 TWD 17 DBC

+2.04 TEC TEH 43 HOT 600UL 38 38 0.43 41 P2 TWD 19 VSM

+0.11 TEC TEH 9

HOT 60OUL 41 39 0.19 158 P3 TWD 9 DBC

+1.54 TEC TEH 8

HOT 60OUL 69 39 0.36 65 P2 TWD 16 VH3

-0.90 TEC TEH 8

HOT 600UL 77 39 0.37 110 P2 TWD 16 VC3

+0.87 TEC TEH 8

HOT 60OUL 79 39 0.53 108 P3 TWD 22 DBC

+1.77 TEC TEH 8

HOT 60OUL 109 39 0.18 130 P3 TWD 10 DBC

-1.59 TEC TEH 47 HOT 600UL 78 40 0.16 121 P3 TWD 8 DBC

-1.93 TEC TEH 9

HOT 600UL 112 40 0.35 29 P3 TWD 17 DBH

+1.71 TEC TEH 47 HOT 600UL 39 41 0.27 147 P3 TWD 13 DBH

-2.12 TEC TEH 20 HOT 600UL 55 41 0.38 141 P2 TWD 17 VH3

+1.01 TEC TEH 8

HOT 600UL 115 41 0.40 150 P2 TWD 16 VHI

+0.96 TEC TEH 48 HOT 600UL 0.22 110 P2 TWD 10 VHI

-0.88 TEC TEH 48 HOT 600UL 74 42 0.47 72 P2 TWD 20 VH3

+0.76 TEC TEH 9

HOT 600UL 100 42 0.24 29 P2 TWD 9 VH2

-0.84 TEC TEH 48 HOT 600UL 110 42 0.63 151 P2 TWD 23 VH2

-0.91 TEC TEH 47 HOT 600UL 39 43 0.41 81 P2 TWD 18 VSM

+0.84 TEC TEH 21 HOT 600UL 75 43 0.85 86 P2 TWD 29 VC3

+0.73 TEC TEH 8

HOT 60OUL 64 44 0.33 104 P2 TWD 15 VC3

+0.78 TEC TEH 8

HOT 60OUL 92 44 0.46 138 P2 TWD 18 VH2

-0.90 TEC TEH 47 HOT 600UL 102 44 0.18

.20 P3 TWD 8 DBH

+1.75 TEC TEH 48 HOT 600UL 110 44 0.31 84 P2 TWD 12 VH2

-0.72 TEC TEH 48 HOT 60OUL 124 44 0.48 113 P2 TWD 19 VH2

-0.90 TEC TEH 47 HOT 60OUL 0.34 148 P2 TWD 15 VHI

-0.90 TEC TEH 47 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 4 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 43 45 0.32 54 P3 TWD 16 DBH

+1.83 TEC TEN 20 HOT 600UL 75 45 0.48 137 P2 TWD 20 VH3

-0.87 TEC TEN 8

HOT 600UL 107 45 0.65 75 P2 TWD 23 VH2

-0.74 TEC TEN 48 HOT 60OUL 0.84 40 P2 TWD 27 VH2

+0.90 TEC TEN 48 HOT 60OUL 115 45 0.75 140 P2 TWD 25 VHI

-1.22 TEC TEN 48 HOT 600UL 123 45 0.50 123 P2 TWD 19 10C

+0.66 TEC TEN 48 HOT 600UL 125 45 0.24 139 P3 TWD 12 DBH

+0.67 TEC TEN 47 HOT 600UL 88 46 0.36 148 P3 TWD 17 DBC

-1.89 TEC TEN 47 HOT 600UL 106 46 0.28 134 P2 TWD 11 VH3

-0.90 TEC TEN 48 HOT 600UL 118 46 0.56 127 P2 TWD 20 VH1

-0.92 TEC TEH 48 HOT 60OUL 0.18 123 P2 TWD 7 VH1

+0.82 TEC TEN 48 HOT 60OUL 124 46 0.27 94 P2 TWD 12 VH2

-0.86 TEC TEN 47 HOT 600UL 41 47 0.38 105 P2 TWD 17 VSM

+0.81 TEN TEC 8

COLD 600UL 0.44 141 P2 TWD 19 VSM

+0.00 TEN TEC 8

COLD 600UL 45 47 0.22 91 P3 TWD 11 DBH

+1.37 TEN TEC 8

COLD 600UL 49 47 0.23 128 P3 TWD 11 DBH

+0.69 TEN TEC 8

COLD 600UL 53 47 0.17 149 P2 TWD 8 03C

+0.89 TEN TEC 8

COLD 600UL 57 47 0.31 129 P2 TWD 15 08H

+0.53 TEN TEC 8

COLD 600UL 111 47 0.24 162 P2 TWD 10 08C

+0.90 TEC TEN 52 HOT 600UL 26 48 0.79 35 P2 TWD 28 VSM

-0.84 TEN TEC 8

COLD 600UL 60 48 0.66 72 P2 TWD 24 08H

-0.90 TEN TEC 7

COLD 600UL 49 49 0.57 140 P2 TWD 22 08H

+1.74 TEN TEC LOCOK 1 7 COLD 600UL 65 49 0.21 156 P2 TWD 10 VH3

+0.90 TEN TEC 7

COLD 600UL 0.48 142 P2 TWD 20 VH3

-0.76 TEN TEC 7

COLD 600UL 131 49 0.26 29 P3 TWD 12 DBH

+1.60 TEC TEN 61 HOT 600UL 30 50 0.56 25 P1 MCI TSH

-0.05 TSH TSH 0.37 LAR 121 HOT 580PP 36 50 0.27 163 P3 TWD 12 DBH

+1.92 TEN TEC 7

COLD 600UL 60 50 0.34 75 P2 TWD 15 08H

-0.37 TER TEC 7

COLD 600UL 62 50 0.67 89 P2 TWD 26 08H

-0.14 TEN TEC 8

COLD 60OUL 108 50 0.44 145 P2 TWD 19 VH2

+0.97 TEC TEN 51 HOT 60OUL 31 51 0.30 135 P2 TWD 14 06N

+0.78 TEN TEC 8

COLD 600UL 43 51 0.26 120 P2 TWD 13 02H

+0.78 TEN TEC 8

COLD 600UL 437 51 0.31 143 P2 TWD 14 08H

+0.34 TEN TEC 7

COLD 600UL 0.30 113 P2 TWD 14 08H

+0.92 TEN TEC 7

COLD 600UL 81 51 0.16 175 P3 TWD 8 DBH

+1.13 TEC TEN

.51 HOT 600UL 127 51 0.36 26 P3 TWD 17 DBH

-1.59 TEC TEN 52 HOT 600UL 46 52 0.31 139 P3 TWD 13 DBH

+1.30 TEN TEC 7

COLD 600UL 37 53 0.46 93 P2 TWD 16 VSM

+0.00 TER TEC 9

COLD 600UL 63 53 0.42 95 P2 TWD 20 08H

+0.38 TEN TEC 10 COLD 600UL 65 53 0.30 77 P2 TWD 11 08H

-0.65 TEN TEC 9

COLD 600UL 0.31 79 P2 TWD 11 08H

-0.16 TEN TEC 9

COLD 600UL

'AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 5 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 71 53 0.36 96 P2 TWD 18 08H

+0.42 TEH TEC 10 COLD 600UL 73 53 0.28 75 P2 TWD 10 08H

+0.57 TEH TEC 9

COLD 600UL 97 53 0.54 54 P2 TWD 22 VH2

+0.79 TEC TEH 51 HOT 600UL 129 53 0.31 132 P2 TWD 13 VH2

+0.79 TEC TEH 52 HOT 600UL 133 53 0.50 125 P3 TWD 21 DBH

+1.50 TEC TEH 61 HOT 600UL 0.56 94 P2 TWD 23 07H

+0.00 TEC TEH 61 HOT 600UL 42 54 0.19 91 P2 TWD 11 VSM

+0.89 TEH TEC 10 COLD 60OUL 46 54 0.14 38 P3 TWD 8 DBH

+1.84 TEH TEC 10 COLD 600UL 68 54 0.41 128 P2 TWD 14 08H

+0.42 TEH TEC 9

COLD 600UL 76 54 0.22 159 P3 TWD 12 DBH

+0.98 TEH TEC 9

COLD 600UL 116 54 0.52 97 P2 TWD 21 VH2

-0.90 TEC TEH 51 HOT 600UL 130 54 0.23 168 P3 TWD 12 DBH

+1.69 TEC TEH 52 HOT 600UL 132 54 0.21 27 P3 TWD 10 DBH

+1.62 TEC TEH 60 HOT 600UL 41 55 0.28 93 P2 TWD 14 VSM

-0.55 TEH TEC 9

COLD 600UL 67 55 0.25 128 P2 TWD 13 08H

+0.63 TEH TEC 10 COLD 600UL 69 55 0.38 144 P2 TWD 14 08H

+0.83 TEH TEC 9

COLD 600UL 107 55 0.51 23 P2 TWD 20 08C

"+0.94 TEC TEH 52 HOT 600UL 38 56 0.16 129 P2 TWD 9 06H

+0.48 TEH TEC 10 COLD 600UL 70 56 0.27 116 P2 TWD 14 08H

+0.66 TEH TEC 10 COLD 600UL 126 56 0.26 142 P2 TWD 11 VHI

+0.78 TEC TEH 52 HOT 600UL 125 57 0.63 110 P2 TWD 24 VHI

-0.90 TEC TEH 51 HOT 600UL 0.38 126 P2 TWD 17 VHI

+0.86 TEC TEH 51 HOT 600UL 22 58 0.28 103 P2 TWD 15 03H

+0.86 TEH TEC 10 COLD 60OUL 64 58 0.32 35 P2 TWD 12 VH3

+0.81 TEH TEC 9

COLD 60OUL 96 58 0.39 109 P2 TWD 17 VH2

-0.75 TEC TEH 51 HOT 600UL 108 58 0.42 76 P2 TWD 18 VC3

+0.89 TEC TEH 51 HOT 600UL 124 58 0.40 96 P2 TWD 17 VHI

+0.80 TEC TEH 51 HOT 600UL 134 58 0.67 99 P2 TWD 26 VC3

+0.60 TEC TEH 60 HOT 600UL 136 58 0.18 15 P3 TWD 9 DBH

-1.38 TEC TEH 61 HOT 600UL 41 59 0.53 87 P2 TWD 18 VSM

-0.74 TEH TEC 9

COLD 600UL 0.49 114 P2 TWD 17 VSM

+0.00 TEH TEC 9

COLD 600UL 65 59 0.78 126 P2 TWD 24 VSM

-0.83 TEH TEC 9

COLD 600UL 0.41 141 P2 TWD 14 VSM

+0.77 TEH TEC 9

COLD 600UL 83 59 0.44 18 P3 TWD 20 DBH

+1.36 TEC TEH 52 HOT 600UL 137 59 0.19 16 P3 TWD 9 DEC

+1.70 TEC TEH 61 HOT 600UL 84 60 0.21 6

P3 TWD 11 DBH

+1.34 TEC TEH 52 HOT 600UL 132 60 0.69 36 P2 TWD 26 VH2

-0.84 TEC TEH 60 HOT 600UL 33 61 0.39 126 P2 TWD 19 VSM

+0.76 TEH TEC 10 COLD 600UL 77 61 0.43 98 P2 TWD 20 VH3

-0.82 TEH TEC 10 COLD 600UL 0.52 152 P2 TWD 23 VSM

+0.74 TEH TEC 10 COLD 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 6 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY:

QueryM2[l1 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 79 61 0.38 62 P2 TWD 14 VH3

-0.91 TEH TEC 9

COLD 600UL 81 61 0.22 43 P2 TWD 10 VH3

-0.76 TEC TEH 51 HOT 600UL 127 61 0.43 134 P2 TWD 17 10H

+0.38 TEC TEH 52 HOT 600UL 129 61 0.19 51 P2 TWD 9 VH1

-0.80 TEC TEH 51 HOT 60OUL 14 62 0.40 36 P2 TWD 19 07H

+1.00 TEH TEC 10 COLD 600UL 42 62 0.32 89 P2 TWD 16 VSM

+0.22 TEH TEC 10 COLD 600UL 78 62 0.43 125 P2 TWD 20 VC3

-0.64 TEH TEC 10 COLD 60OUL 88 62 0.60 122 P2 TWD 24 VH2

-0.84 TEC TEH 55 HOT 60OUL 126 62 0.53 73 P2 TWD 20 VHI

-0.64 TEC TEH 52 HOT 600UL 130 62 0.67 136 P2 TWD 24 VHl

+0.80 TEC TEH 52 HOT 60OUL 41 63 0.44 73 P2 TWD 21 VSM

-0.85 TEN TEC 10 COLD 600UL 0.60 78 P2 TWD 25 VSM

+0.04 TEH TEC 10 COLD 600UL 127 63 0.38 118 P2 TWD 18 VHI

+1.04 TEC TEH 56 HOT 600UL 0.20 137 P2 TWD 11 VHI

-0.90 TEC TEH 56 HOT 60OUL 129 63 0.51 75 P2 TWD 22 VH1

+0.88 TEC TEH 55 HOT 600UL 0.37 123 P2 TWD 17 10H

+0.40 TEC TEH 55 HOT 600UL 70 64 0.35 34 P2 TWD 16 02H

-1.25 TEH TEC 12 COLD 600UL 80 64 0.22 173 P3 TWD 9 DBH

+1.29 TEH TEC 11 COLD 600UL.

82 64 0.55 74 P2 TWD 23 VH3

+0.91 TEC TEH 55 HOT 600UL 88 64 0.44 70 P2 TWD 20 VH2

-0.97 TEC TEH 56 HOT 600UL 96 64 0.62 40 P2 TWD 25 VH2

-0.79 TEC TEH 56 HOT 60OUL 104 64 0.51 73 P2 TWD 22 VH2

-1.04 TEC TEH 56 HOT 60OUL 116 64 0.45 52 P2 TWD 21 VH2

-0.98 TEC TEH 56 HOT 600UL 140 64 0.60 73 P3 TWD 24 DBH

-1.76 TEC TEH 61 HOT 600UL 25 65 0.36 134 P2 TWD 12 VSM

+1.07 TEH TEC 11 COLD 600UL 43 65 0.35 62 P2 TWD 12 VSM

+0.24 TEH TEC 11 COLD 600UL 69 65 0.34 33 P2 TWD 16 VC3

-0.06 TEH TEC 12 COLD 600UL 0.42 149 P2 TWD 19 VC3

-0.78 TEH TEC 12 COLD 600UL 71 65 0.32 112 P2 TWD 11 VH3

+1.03 TEH TEC 11 COLD 600UL 105 65 0.35 119 P2 TWD 16 VH2

-0.65 TEC TEH 55 HOT 600UL 125 65 0.38 151 P2 TWD 18 VHI

+0.48 TEC TEH 55 HOT 600UL 127 65 0.23 145 P2 TWD 12 VH1

+0.68 TEC TEH 56 HOT 600UL 131 65 0.27 145 P2 TWD 13 VH2

+0.82 TEC TEH 60 HOT 600UL 133 65 0.16 46 P3.

TWD 8 DBH

+1.88 TEC TEH 61 HOT 600UL 22 66 0.23 48 P2 TWD 12 VSM

-0.85 TEH TEC 12 COLD 600UL 40 66 0.27 177 P3 TWD 11 DBC

+1.15 TEH TEC 11 COLD 600UL 44 66 0.29 152 P2 TWD 10 VSM

+0.59 TEH TEC 11 COLD 600UL 0.20 163 P3 TWD 11 DBC

+1.38 TEH TEC 11 COLD 600UL 86 66 0.42 89 P2 TWD 19 VSM

-0.78 TEC TEH 56 HOT 600UL 0.42 129 P2 TWD 19 09H

+0.14 TEC TEH 56 HOT 600UL 88 66 0.30 78 P2 TWD 14 09H

+1.03 TEC TEH 55 HOT 60OUL

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component:

S/G 89 Page 7 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 130 66 0.26 73 P2 TWD 13 08C

+0.86 TEC TEH 55 HOT 600UL 0.43 102 P2 TWD 19 VH1

+0.68 TEC TEH 55 HOT 600UL 21 67 0.59 87 P2 TWD 24 VSM

-0.96 TEH TEC 12 COLD 600UL 25 67 0.35 105 P2 TWD 16 VSM

-0.91 TEH TEC 12 COLD 60OUL 91 67 0.29 83 P2 TWD 15 VH3

-0.86 TEC TEH 56 HOT 600UL 113 67 0.56 108 P2 TWD 23 04C

+0.30 TEC TEH 55 HOT 600UL 127 67 0.29 93 P2 TWD 14 VHI

+0.16 TEC TEH 56 HOT 600UL 141 67 0.35 140 P2 TWD 17 VHI

-0.87 TEC TEH 61 HOT 60OUL 0.24 80 P3 TWD 11 DBC

-1.40 TEC TEH 61 HOT 600UL 24 68 0.50 137 P3 TWD 18 DBH

+1.90 TEH TEC 11 COLD 600UL 0.25 65 P2 TWD 12 VSM

-0.83 TEH TEC 11 COLD 600UL 40 68 0.42 19 P2 TWD 14 VSM

-0.62 TEH TEC 11 COLD 60OUL 90 68 0.18 50 P2 TWD 10 09H

+0.48 TEC TEH 56 HOT 600UL 130 68 0.47 130 P2 TWD 21 VHI

+1.04 TEC TEH 56 HOT 600UL 134 68 0.62 105 P2 TWD 25 10H

-0.74 TEC TEH 60 HOT 600UL 0.24 126 P2 TWD 12 10H

+0.80 TEC TEH 60 HOT 600UL 39 69 0.48 137 P2 TWO 16 VSM

+0.65 TEN TEC 11 COLD 600UL 41 69 0.57 88 P2 TWD 18 VSM

+0.69 TEH TEC 11 COLD 60OUL 112 70 0.15 14 P3 TWD 7 DBH

+0.96 TEC *TEH 55 HOT 600UL 144 70 0.57 91 P2 TWD 24 VC1

+0.16 TEC TEH 61 HOT 600UL 89 71 0.33 126 P2 TWD 16 09H

+0.40 TEC TEH 55 HOT 600UL 97 71 0.09 67 P3 TWD 3 DBH

+1.69 TEC TEH 55 HOT 60OUL 36 72 0.45 49 P3 TWD 20 DBH

-1.03 TEH TEC 11 COLD 600UL 44 72 0.63 150 P3 TWD 22 DBC

+0.87 TEH TEC 11 COLD 600UL 0.33 24 P2 TWD 12 VSM

+0.83 TEH TEC 1i COLD 600UL 46 72 0.38 117 P2 TWD 18 VSM

+0.80 TEH TEC 12 COLD 600UL 130 72 0.44 129 P2 TWD 20 VHI

+0.84 TEC TEH 56 HOT 600UL 132 72 0.51 39 P2 TWD 22 10H

+0.90 TEC TEH 60 HOT 600UL 0.43 88 P2 TWD 19 VHI

+0.88 TEC TEH 60 HOT 600UL 83 73 0.33 4

P3 TWD 16 DBH

+2.17 TEC TEH 56 HOT 600UL 89 73 0.18 152 P3 TWD 8 DBH

-1.22 TEC TEH 55 HOT 600UL 145 73 0.38 118 P3 TWD 17 DBH

+1.23 TEC TEH 61 HOT 600UL 44 74 0.28 55 P3 TWD 14 DBH

-1.56 TEH TEC 11 COLD 600UL 50 74 0.19 141 P3 TWD 9 DBH

-1.76 TEH TEC 12 COLD 600UL 92 74 0,41 40 P2 TWD 18 VH2

-0.96 TEC TEH 55 HOT 60OUL 132 74 0.35 128 P2 TWD 17 VH2

-0.82 TEC TEH 60 HOT 600UL 134 74 0.57 130 P2 TWD 24 VH2

-0.90 TEC TEH 61 HOT 600UL 136 74 0.37 92 P2 TWD 17 VHI

+0.88 TEC TEH 60 HOT 600UL 71 75 0.30 155 P2 TWD 14 VH3

+0.92 TEH TEC 12 COLD 600UL 77 75 0.47 51 P2 TWD 16 VH3

-0.98 TEH TEC II COLD 600UL 0.15 46 P3 TWD 8 DBC

+1.14 TEH TEC 1i COLD 60OUL 52 76 0.27 48 P3 TWD 14 DBC

-2.00 TEC TEH 18 HOT 60OUL

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 8 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 56 76 0.59 111 P2 TWD 24 VSM

+0.72 TEC TEH 18 HOT 600UL 86 76 0.22 111 P2 TWD 12 07H

+0.21 TEC TEH 53 HOT 60OUL 128 76 0.47 138 P2 TWD 21 VHI

+0.80 TEH TEC 35 COLD 600UL 138 76 0.44 135 P2 TWD 17 10H

+0.73 TEC TEH 59 HOT 600UL 144 76 0.16 41 P3 TWD 8 DBH

-2.23 TEC TEH 58 HOT 600UL 135 77 0.53 131 P2 TWD 23 VHl

+0.86 TEC TEH 58 HOT 600UL 50 78 0.35 115 P3 TWD 17 DBH

-1.75 TEC TEH 18 HOT 600UL 52 78 0.29 9

P3 TWD 13 DBH

+1.91 TEC TEH 19 HOT 600UL 54 78 0.41 27 P3 TWD 19 DBH

-1.22 TEC TEH 18 HOT 600UL 62 78 0.29 23 P3 TWD 15 DBH

+1.79 TEC TEH 18 HOT 600UL 122 78 0.45 139 P2 TWD 21 VHI

-1.09 TEC TEH 53 HOT 60OUL 124 78 0.36 151 P2 TWD 18 VHI

-1.21 TEC TEH 53 HOT 600UL 130 78 0.73 124 P2 TWD 27 VHI

+0.86 TEH TEC 35 COLD 600UL 144 78 0.53 112 P3 TWD 19 DBH

-2.02 TEC TEH 59 HOT 600UL 57 79 0.30 21 P3 TWD 15 DBH

+1.87 TEC TEH 18 HOT 600UL 61 79 0.25 13 P3 TWD 13 DBH

+1.89 TEC TEH 18 HOT 600UL 75 79 0.26 140 P2 TWD 12 VSM

-0.87 TEC TEH 23 HOT 60OUL 0.67 149 P2 TWD 24 VSM

+0.85 TEC TEH 23 HOT 600UL 127 79 0.66 117 P2 TWD 27 VHI

+0.90 TEC TEH 49 HOT 600UL 129 79 0.33 145 P2 TWD 13 VHI

+0.80 TEC TEH 50 HOT 600UL 137 79 0.37 69 P2 TWD 15 09H

-0.84 TEC TEH 59 HOT 60OUL 145 79 0.25 106 P3 TWD 10 DBH

-1.85 TEC TEH 59 HOT 600UL 52 80 0.21 138 P3 TWD 10 DBC

-1.59 TEC TEH 23 HOT 60OUL 0.50 115 P3 TWD 20 DBH

-1.57 TEC TEH 23 HOT 600UL 70 80 0.37 98 P2 TWD 15 VH3

-0.94 TEC TEH 23 HOT 60OUL 86 80 0.30 70 P2 TWD 15 09H

+0.27 TEC TEH 49 HOT 600UL 120 80 0.24 67 P3 TWD 10 DBH

+1.88 TEC TEH 50 HOT 60OUL 134 80 0.29 122 P2 TWD 12 VHI

+0.63 TEC TEH 59 HOT 600UL 0.67 136 P2 TWD 23 VHl

-0.92 TEC TEH 59 HOT 60OUL 144 80 0.26 171 P3 TWD 13 DBH

+1.48 TEC TEH 58 HOT 600UL 55 81 0.46 14 P3 TWD 20 DBH

+1.75 TEC TEH 23 HOT 600UL 137 81 0.38 33 P2 TWD 15 08H

+0.84 TEC TEH 59 HOT 600UL 66 82 0.28 150 P2 TWD 12 VH3

+0.84 TEC TEH 23 HOT 600UL 0.29 87 P3 TWD 13 DBH

-1.59 TEC TEH 23 HOT 600UL 108 82 0.27 146 P2 TWD 11 03C

-1.04 TEC TEH 50 HOT 600UL 132 82 0.41 94 P2 TWD 19 VHI

-0.04 TEC TEH 58 HOT 600UL 142 82 0.42 12 P3 TWD 20 DBC

+1.92 TEC TEH 58 HOT 600UL 57 83 0.28 16 P3 TWD 13 DBH

+1.35 TEC TEH 23 HOT 600UL 0.68 43 P3 TWD 25 DBH

-1.57 TEC TEH 23 HOT 600UL 137 83 0.62 44 P2 TWD 21 09H

+0.86 TEC TEH 59 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 9 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 54 84 0.72 140 P3 TWD 29 DBC

+1.85 TEC TEH 23 HOT 600UL 72 84 0.40 136 P2 TWD 19 VC3

+0.64 TEC TEH 22 HOT 600UL 0.36 131 P2 TWD 18 VC3

-0.04 TEC TEH 22 HOT 600UL 0.45 118 P2 TWD 21 VSM

-0.97 TEC TEH 22 HOT 600UL 0.23 154 P2 TWD 12 VSM

+0.91 TEC TEH 22 HOT 600UL 106 84 0.47 68 P2 TWD 21 VH2

-0.72 TEC TEH 49 HOT 600UL 110 84 0.41 124 P2 TWD 19 VH2

-0.80 TEC TEH 49 HOT 60OUL 126 84 0.39 144 P2 TWD 19 VHl

+0.82 TEC TEH 49 HOT 60OUL 134 84 0.44 147 P2 TWD 17 VHI

-0.94 TEC TEH 59 HOT 60OUL 144 84 0.57 62 P2 TWD 20 VH3

+0.82 TEC TEH 59 HOT 600UL 63 85 0.23 19 P3 TWD 11 DBH

+1.24 TEC TEH 23 HOT 600UL 123 85 0.20 117 P3 TWD 11 DBH

-1.85 TEC TEH 49 HOT 600UL 127 85 0.67 130 P2 TWD 27 VHI

-0.74 TEC TEH 49 HOT 600UL 139 85 0.31 83 P2 TWD 15 VH3

+0.94 TEC TEH 58 HOT 60OUL 70 86 0.24 76 P3 TWD 11 DBC

+1.77 TEC TEH 23 HOT 600UL 122 86 0.14 128 P3 TWD 8 DBH

+0.68 TEC TEH 49 HOT 600UL 126 86 0.36

.133 P2 TWD 18 VHE

-1.01 TEC TEH 49 HOT 600UL 0.34 81 P2 TWD 17 VH1

+0.97 TEC TEH 49 HOT 600UL 132 86 0.85 36 P2 TWD 30 VH2

-0.86 TEC TEH 58 HOT 600UL 0.47 84 P2 TWD 21 VHI

-0.92 TEC TEH 58 HOT 600UL 134 86 0.33 107 P2 TWD 16 10H

+0.25 TEC TEH 58 HOT 600UL 55 87 0.40 8

P3 TWD 17 DBH

+1.13 TEC TEH 23 HOT 600UL 57 87 0.65 96 P3 TWD 25 DBC

-1.50 TEC TEH 22 HOT 600UL 65 87 0.51 46 P3 TWD 21 DBH

+1.70 TEC TEH 22 HOT 600UL 67 87 0.28 34 P3 TWD 13 DBC

-1.77 TEC TEH 23 HOT 600UL 0.44 125 P3 TWD 19 DBH

+1.32 TEC TEH 23 HOT 600UL 93 87 0.33 93 P2 TWD 16 07H

+0.77 TEC TEH 49 HOT 600UL 0.48 143 P2 TWD 22 08H

+0.73 TEC TEH 49 HOT 600UL 145 87 0.32 147 P2 TWD 13 VH2

+0.87 TEC TEH 59 HOT 600UL 60 88 1.04 77 P3 TWD 33 DBH

-1.28 TEC TEH 22 HOT 60OUL 68 88 0.40 95 P3 TWD 18 DBH

-1.49 TEC TEH 22 HOT 600UL 78 88 0.20 164 P3 TWD 9

DBH

+1.93 TEC TEH 23 HOT 60OUL 118 88 0.47 93 P2 TWD 21 VHI

-0.92 TEC TEH 49 HOT 600UL 132 88 0.50 42 P2 TWD 22 VHI

+0.86 TEC TEH 58 HOT 600UL 0.50 100 P2 TWD 21 VHI

-0.84 TEC TEH 58 HOT 600UL 57 89 0.23 150 P3 TWD 11 DBH

-1.73 TEC TEH 23 HOT 600UL 97 89 0.21 163 P3 TWD 9

DBH

-0.08 TEC TEH 50 HOT 600UL 135 89 0.42 59 P2 TWD 19 VH3

-0.98 TEC TEH 58 HOT 600UL 139 89 0.32 140 P2 TWD 15 09H

+0.94 TEC TEH 58 HOT 600UL 0.12 139 P2 TWD 6

09H

-0.96 TEC TEH 58 HOT 60OUL 100 90 0.22 77 P3 TWD 8 DBH

-1.60 TEC TEH 50 HOT 600UL 114 90 0.25 112 P3 TWD 13 DBH

+1.68 TEC TEH 49 HOT 600UL 136 90 0.54 88 P2 TWD 23 VHE

+0.82 TEC TEH 58 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 10 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 146 90 0.45 76 P3 TWD 17 DBC

+1.86 TEC TEH 59 HOT 600UL 0.32 117 P2 TWD 13 VH3

-0.86 TEC TEH 59 HOT 600UL 53 91 0.34 167 P3 TWD 15 DBH

+2.01 TEC TEH 22 HOT 600UL 0.34 154 P3 TWD 15 DBH

-2.00 TEC TEH 22 HOT 60OUL 61 91 0.35 100 P2 TWD 15 03H

+0.08 TEC TEH 23 HOT 60OUL 103 91 0.29 45 P2 TWD 15 VH2

-0.70 TEC TEH 49 HOT 60OUL 137 91 0.46 154 P2 TWD 17 VH1

+0.82 TEC TEH 59 HOT 600UL 0.64 111 P2 TWD 22 09H

+0.80 TEC TEH 59 HOT 60OUL 58 92 0.30 28 P3 TWD 14 DBH

-1.21 TEC TEH 23 HOT 600UL 60 92 0.86 132 P3 TWD 30 DBH

-1.59 TEC TEH 22 HOT 600UL 68 92 0.27 151 P3 TWD 12 DBH

-1.61 TEC TEH 22 HOT 600UL 70 92 0.49 8

P3 TWD 19 DBH

+2.09 TEC TEH 23 HOT 600UL 0.24 52 P3 TWD 11 DBH

-1.23 TEC TEH 23 HOT 600UL 78 92 0.47 115 P3 TWD 20 DBH

+1.75 TEC TEH 23 HOT 600UL 112 92 0.42 123 P2 TWD 16 05C

+0.72 TEC TEH 50 HOT 60OUL 118 92

.0.22 55 P2 TWD 12 VH1

+1.13 TEC TEH 49 HOT 600UL 120 92.

0.41 36 P2 TWD 16 VHI

+0.74 TEC TEH 50 HOT 600UL 130 92 0.80 104 P2 TWD 30 VH1

-0.80 TEC TEH 49 HOT 600UL 0.66 105 P2 TWD 26 VH2

-0.66 TEC TEH 49 HOT 600UL 146 92 0.72 49 P3 TWD 24 DBH

+1.98 TEC TEH 59 HOT 600UL 53 93 0.40 136 P3 TWD 17 DBH

-1;63 TEC TEH 23 HOT 600UL 55 93 0.16 119 P3 TWD 8 DBH

+1.59 TEC TEH 22 HOT 600UL 133 93 0.16 42 P2 TWD 6 VH1

-0.96 TEC TEH 59 HOT 600UL 52 94 0.55 108 P3 TWD 22 DBC.

-1.28 TEC TEH 22 HOT 600UL 0.41 24 P3 TWD 18 DBH

+1.81 TEC TEH 22 HOT 600UL 60 94 0.37 11 P3 TWD 17 DBH

+1.79 TEC TEH 22 HOT 60OUL 0.11 119 P3 TWD 5 DBH

-1.98 TEC TEH 22 HOT 600UL 78 94 0.36 18 P3 TWD 16 DBH

+1.75 TEC TEH

.23 HOT 600UL 82 94 0.34 149 P2 TWD 1 7 VH3

-0.04 TEC TEH 46 HOT 60OUL 130 94 0.60 95 P2. TWD 25 VH1

+0.78 TEC TEH 49 HOT 600UL 136 94 0.59 120 P2 TWD 21 VH1

-0.94 TEC TEH 59 HOT 600UL 144 94 0.28 75 P3 TWD 12 DBH

+1.82 TEC TEH 59 HOT 60OUL 53 95 0.52 69 P3 TWD 21 DBC

-1.76 TEC TEH 23 HOT 60OUL 0.30 83 P3 TWD 13 DBH

+1.67 TEC TEH 23 HOT 60OUL 55 95 0.32 117 P3 TWD 15 DBH

-1.61 TEC TEH 22 HOT 600UL 73 95 0.33 17 P3 TWD 15 DBC

+2.25 TEC TEH 22 HOT 600UL 75 95 0.26 16 P3 TWD 12 DBC

+1.89 TEC TEH 23 HOT 600UL 0.82 69 P2 TWD 27 VC3

-0.84 TEC TEH 23 HOT 600UL 0.19 20 P2 TWD 9 VC3

+0.58 TEC TEH 23 HOT 600UL 79 95 0.22 9

P3 TWD 11 DBC

+1.75 TEC TEH 22 HOT 600UL 133 95 0.24 50 P2 TWD 12 VH1

+0.78 TEC TEH 58 HOT 600UL 135 95 0.35 115 P2 TWD 14 VH1

-0.94 TEC TEH 59 HOT 600UL 139 95 0.25 80 P2 TWD 10 VH1

-1.09 TEC TEH 59 HOT 600UL

'AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 11 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 143 95 0.24 27 P3 TWD 10 DBH

-1.43 TEC TEH 59 HOT 600UL 56 96 0.92 79 P3 TWD 31 DBC

+1.60 TEC TEH 22 HOT 600UL 0.24 104 P3 TWD 11 DBH

-1.60 TEC TEH 22 HOT 600UL 64 96 0.20 63 P3 TWD 10 DBC

+1.30 TEC TEH 22 HOT 600UL 49 97 0.45 43 P3 TWD 19 DBH

+1.07 TEC TEH 23 HOT 600UL 53 97 0.42 51 P3 TWD 18 DBH

-1.07 TEC TEH 23 HOT 600UL 59 97 0.12 164 P3 TWD 6 DBC

-1.10 TEC TEN 22 NOT 600UL 65 97 0.17 107 P3 TWD 9 DBC

-1.90 TEC TEH 22 HOT 600UL 125 97 0.46 84 P2 TWD 18 VH2

+0.94 TEC TEH 45 HOT 60OUL 141 97 0.34 64 P3 TWD 13 DBC

-1.68 TEC TEN 59 HOT 600UL 145 97 0.24 105 P3 TWD 10 DBC

-1.74 TEC TEH 59 HOT 60OUL 50 98 0.58 25 P3 TWD 22 DBC

-1.35 TEC TEH 23 HOT 600UL 0.53 83 P3 TWD 21 DBO

-1.65 TEC TEH 23 HOT 600UL 124 98 0.21 71 P2 TWD 10 VH1

+1.06 TEC TEH 45 HOT 600UL 51 99 0.46 119 P3 TWD 19 DBH

-1.37 TEC TEH 23 HOT 600UL 55 99 0.39 78 P3 TWD 17 DBH

-1.17 TEC TEH 23 HOT 600UL 61 99 0.28 147 P2 TWD 15 VSM

+0.88 TEC TEH 22 HOT 600UL 97 99 0.14 145 P3 TWD 7 DBH

+0.00 TEC TEH 45 HOT 600UL 139 99 0.25 103 P2 TWD 12 VH2

-0.95 TEC TEH 58 HOT 600UL 141 99 0.32 117 P2--TWD 13 VH1

+0.96 TEC TEH 59 HOT 600UL 0.34 75 P3 TWD 13 DBH

+1.80 TEC TEH 59 HOT 60OUL 44 100 0.47 52 P3 TWD 20 DBH

-1.59 TEC TEH 22 HOT 600UL 50 100 0.40 74 P2 TWD 16 VSM

-0.75 TEC TEH 23 HOT 600UL 52 100 0.39 37 P3 TWD 17 DBC

-1.16 TEC TEH 22 HOT 600UL 100 100 0.17 37 P3 TWD 6 DBH

+0.84 TEC TEH 45 HOT 600UL 102 100 0.17 54 P3 TWD 9 DBH

-2.16 TEC TEH 46 HOT 600UL 132 100 0.49 138 P2 TWD 21 VH1

-0.93 TEC TEH 58 HOT 600UL 144 100 0.39 66 P2 TWD 15 VH2

+0.91 TEC TEH 59 HOT 600UL 39 101 0.31 25 P3 TWD 14 DBH

-1.50 TEC TEH 22 HOT 600UL 47 101 0.57 21 P3 TWD 19 DBC

+1.98 TEC TEH 23 HOT 600UL 49 101 0.35 103 P3 TWD 16 DBH

-1.75 TEC TEH 22 HOT 600UL 53 101 0.40 149 P3 TWD 17 DBH

-1.23 TEC TEH 23 HOT 600UL 83 101 0.29 84 P2 TWD 12 VSM

+1.25 TEC TEH 45 HOT 600UL 127 101 0.25 141 P2 TWD 13 VH1

-0.74 TEC TEH 46 HOT 600UL 133 101 0.43 144 P2 TWD 16 VH1

+0.78 TEC TEH 59 HOT 600UL 54 102 0.44 34 P3 TWD 19 DBC

+1.90 TEH TEC 4

COLD 60OUL 0.36 106 P3 TWD 16 DBC

-2.00 TEH TEC 4

COLD 600UL 88 102 0.39 54 P2 TWD 19 VH2

-0.90 TEC TEH 32 HOT 600UL 144 102 0.35 136 P2 TWD 14 09H

-1.01 TEC TEH 59 HOT 600UL 0.35 84 P3 TWD 14 DBC

-1.90 TEC TEH 59 HOT 600UL 0.19 173 P3 TWD 8 DBC

+2.04 TEC TEH 59 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 12 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[I]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 41 103 0.57 109 P3 TWD 20 DBC

+1.75 TEH TEC 3

COLD 600UL 47 103 0.33 29 P3 TWD 13 DBH

-1.51 TEH TEC 3

COLD 60OUL 0.13 168 P3 TWD 5 DBH

+1.99 TEH TEC 3

COLD 600UL 0.28 20 P3 TWD 11 DBC

+1.35 TEH TEC 3

COLD 600UL 55 103 0.41 62 P2 TWD 15 VC3

+1.22 TEH TEC 4

COLD 600UL 83 103 0.69 103 P2 TWD 24 09H

+1.43 TEC TEH LOCOK 33 HOT 60OUL 87 103 0.45 130 P2 TWD 18 09H

+0.73 TEC TEH 33 HOT 600UL 0.47 93 P2 TWD 19 08H

+0.73 TEC TEH 33 HOT 600UL 133 103 0.17 153 P2 TWD 7 VHI

-0.80 TEC TEH 59 HOT 600UL 0.44 72 P2 TWD 17 08H

+0.86 TEC TEH 59 HOT 600UL 36 104 0.33 122 P3 TWD 13 DBH

+1.56 TEH TEC 3

COLD 60OUL 0.22 152 P3 TWD 9 DBC

+1.32 TEH TEC 3

COLD 60OUL 46 104 0.75 95 P2 TWD 24 VSM

-0.87 TEH TEC 4

COLD 600UL 88 104 0.12 116 P2 TWD 6 08H

-0.94 TEC TEH 32 HOT 60OUL 0.29 50 P2 TWD 15 08H

-0.23 TEC TEH 32 HOT 600UL 110 104 0.49 121 P2 TWD 19 VH2

-0.84 TEC TEH 33 HOT 600UL 114 104 0.63 107 P2 TWD 23 VH2

-0.86 TEC TEH 33 HOT 600UL 138 104 0.20 116 P2 TWD 8 VH1

-0.25 TEC TEH 59 HOT 600UL 0.52 136 P2 TWD 19 VHI

-0.84 TEC TEH 59 HOT 600UL 77 105 0.27 98 P3 TWD 11 DBH

-1.52 TEH TEC 3

COLD 600UL 115 105 0.47 68 P2 TWD 19 VH2

+0.82 TEC TEH 33 HOT 600UL 129 105 0.56 96 P2 TWD 24 VHI

+0.76 TEC TEH 32 HOT 600UL 114 106 0.32 24 P3 TWD 13 DBH

+2.00 TEC TEH 33 HOT 600UL 29 107 0.35 76 P3 TWD 14 DBC

-1.80 TEH TEC 3

COLD 600UL 41 107 0.33 101 P2 TWD 15 VSM

+1.08 TEH TEC 3

COLD 600UL 0.29 21 P2 TWD 14 VSM

-0.54 TEH TEC 3

COLD 60OUL 43 107 0.42 129 P2 TWD 16 VSM

+0.81 TEH TEC 4

COLD 600UL 0.36 87 P3 TWD 16 DBC

+1.58 TEH TEC 4

COLD 600UL 0.29 58 P2 TWD 12 VSM

+0.26 TEH TEC 4

COLD 600UL 83 107 0.29 115 P2 TWD 13 09H

-1.14 TEC TEH LOCOK 33 HOT 600UL 121 107 0.23 131 P3 TWD 12 DBH

+1.96 TEC TEE 32 HOT 600UL 133 107 0.30 131 P2 TWD 12 09H

+0.82 TEC TEH 59 HOT 600UL 0.14 160 P2 TWD 6 09H

-0.88 TEC TEH 59 HOT 600UL 0.39 71 P2 TWD 15 VH2

+0.92 TEC TEH 59 HOT 600UL 126 108 0.49 69 P2 TWD 19 10H

+0.08 TEC TEH 33 HOT 600UL 134 108 0.25 38 P2 TWD 10 10H

+0.94 TEC TEH 59 HOT 600UL 14 110 0.30 118 P3 TWD 12 DBH

-1.33 TEH TEC 6

COLD 600UL 74 110 0.42 39 P2 TWD 16 03H

-0.16 TEH TEC 4

COLD 600UL 128 110 0.26 139 P2 TWD 11 08H

+0.82 TEC TEH 37 HOT 60OUL 0.17 160 P2 TWD 8 08H

-0.86 TEC TEH 37 HOT 600UL 0.37 138 P2 TWD 15 10H

+0.90 TEC TEH 37 HOT 600UL 0.22 134 P2 TWD 10 10H

-0.92 TEC TEH 37 HOT 600UL 132 110 0.31 55 P2 TWO 15 08H

+0.94 TEC TEH 58 HOT 600UL 0.23 120 P2 TWO 12 07H

+0.59 TEC TEH 58 HOT 600UL 127 111 0.43 55 P2 TWD 17 09H

-0.25 TEC TEH 37 HOT 600UL 0.42 77 P2 TWD 17 10H

+0.29 TEC TEH 37 HOT 600UL.

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 13 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY:

QueryM2[1]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 129 I11 0.19 153 P2 TWD 11 09H

+0.53 TEC TEH 36 HOT 60OUL 0.35 124 P2 TWD 18 09H

-0.86 TEC TEH 36 HOT 600UL 44 112 0.26 129 P2 TWO 13 VSM4

+0.18 TEE TEC 3

COLD 600UL 0.26 143 P2 TWD 12 VSM

+0.89 TEH TEC 3

COLD 600UL 0.50 82 P2 TWD 20 VSM

-0.85 TEH TEC 3

COLD 600UL 80 112 0.24 10 P3 TWD 10 DBH

+1.92 TEH TEC 3

COLD 600UL 106 112 0.20 141 P2 TWD 12 VH2

-0.98 TEC TEH 36 HOT 600UL 0.24 61 P2 TWD 14 VH2

+0.92 TEC TEH 36 HOT 60OUL 120 112 0.24 58 P3 TWD 10 DBH

-0.04 TEC TEH 37 HOT 60OUL 0.46 131 P2 TWD 18 10H

+1.31 TEC TEH LOCOK 37 HOT 60OUL 122 112 0.50 65 P2 TWD 23 10H

+0.61 TEC TEH 36 HOT 600UL 140 112 0.56 35 P3 TWD 20 DBC

-1.64 TEC TEH 59 HOT 60OUL 0.50 26 P3 TWD 19 DBC

+1.64 TEC TEH 59 HOT 600UL 0.57 119 P2 TWD 20 VHl

-0.84 TEC TEH 59 HOT 600UL 0.31 134 P2 TWD 13 04H

+0.72 TEC TEH 59 HOT 600UL 35 113 0.54 87 P2 TWD 21 VSM

-0.88 TEH TEC 3

COLD 60OUL 0.26 24 P2 TWD 12 VSM

-0.12 TEH TEC 3

COLD 60OUL 41 113 0.50 129 P2 TWD 18 VSM

-0.85 TEH TEC 4

COLD 60OUL 0.22 137 P2 TWD 9 VSM

-0.12 TEH TEC 4

COLD 600UL 111 113 0.50 114 P2 TWD 19 VH2

+0.78 TEC TEH 37 HOT 600UL 0.36 113 P2 TWD 15 VH2

-0.88 TEC TEH 37 HOT 600UL 121 113 0.35 90 P2 TWD 18 VHl

-0.94 TEC TEH 36 HOT 600UL 127 113 0.30 59 P2 TWD 13 09H

-0.80 TEC TEH 37 HOT 600UL 0.32 70 P2 TWD 14 08H

+0.88 TEC TEH 37 HOT 60OUL 0.28 103 P2 TWD 12 09H

+0.37 TEC TEH 37 HOT 600UL 44 114 0.56 109 P2 TWO 21 VSM

-0.91 TEE TEC 5

COLD ECOUL 0.58 101 P2 TWD 22 VSM

+0.93 TEH TEC 5

COLD 60OUL 114 114 0.38 133 P2 TWD 16 VH2

+0.94 TEC TEH 37 HOT 600UL 0.65 53 P2 TWD 23 VH2

-0.88 TEC TEH 37 HOT 600UL 124 114 0.16 147 P2 TWD 10 05H

+0.83 TEC TEH 36 HOT 600UL 126 114 0.37 114 P2 TWD 15 08H

+0.92 TEC TEH 37 HOT 600UL 136 114 0.41 36 P3 TWD 16 DBC

+1.33 TEC TEH 59 HOT 600UL 25 115 0.81 96 P2 TWD 27 VSM

+0.82 TEH TEC 5

COLD 60OUL 83 115 0.52 117 P2 TWD 20 VSM

+1.24 TEC TEH 37 HOT 600UL 0.74 122 P2 TWD 25 09H

+1.39 TEC TEH LOCOK 37 HOT 600UL 123 115 0.30 66 P2 TWO 13 09H

+0.43 TEC TEE 37 HOT 600UL 127 115 0.32 114 P2 TWD 14 08H

+0.76 TEC TEH 37 HOT 60OUL 0.29 47 P2 TWD 12 08H

-0.47 TEC TEH 37 HOT 600UL 137 115 0.35 80 P2 TWD 14 VH2

-0.86 TEC TEH 59 HOT 600UL 14 "116 0.20 33 P2 TWO 9 OlH

-0.12 TEE TEC 6

COLD 600UL 92 116 0.35 92 P2 TWD 18 OSH

-0.75 TEC TEH 36 HOT 60OUL 124 116 0.12 36 P2 TWD 7 10H

-0.96 TEC TEE 36 HOT 600UL 0.32 99 P2 TWD 17 09H

+0.22 TEC TEH 36 HOT 600UL 0.41 122 P2 TWO 20 08H

+0.78 TEC TEE 36 HOT 600UL 128 116 0.24 71 P2 TWO 13*

09C

+0.90 TEC TEH 36 HOT 600UL 0.30 90 P2 TWD 16 V0H

+0.78 TEC TEH 36 HOT 600UL 39 117 0.32 49 P2 TWD 13 VSM

-0.82 TEE TEC 5

COLD 600UL 0.32 154 P2 TWD 13 VSM

+0.78 TEH TEC 5

COLD 60OUL 105 117 0.20 78 P3 TWD 12 DBH

+1.29 TEC TEH 36 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name:

SONGS Unit 3 Component: S/G 89 Page 14 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 123 117 0.58 139 P2 TWD 21 09H

-0.62 TEC TEH 37 HOT 600UL 0.24 17 P2 TWD 11 09H

+0.35 TEC TEH 37 HOT 600UL 125 117 0.33 147 P2 TWD 17 08H

+0.92 TEC TEH 36 HOT 600UL 32 118 0.47 125 P2 TWD 18 VSM

-0.74 TEN TEC 5

COLD 60OUL 46 118 0.19 150 P2 TWD 9 VSM

-0.83 TEH TEC 6

COLD 600UL 74 118 0.26 72 P2 TWD 12 VSM

-0.77 TEH TEC 6

COLD 600UL 43 119 0.30 81 P2 TWD 13 VSM

-0.83 TEH TEC 6

COLD 600UL 0.12 84 P2 TWD 6

VSM

+0.26 TEH TEC 6

COLD 600UL 45 119 0.43 134 P2 TWD 17 VSM

-0.82 TEH TEC 5

COLD 600UL 0.51 116 P2 TWD 19 VSM

+0.76 TEH TEC 5

COLD 600UL 47 119 0.43 62 P2 TWD 18 VSM

-0.77 TEH TEC 6

COLD 600UL 123 119 0.49 120 P2 TWD 23 09H

+0.53 TEC TEH 36 HOT 600UL 0.20 80

  • P2 TWD 12 09H

-0.16 TEC TEH 36 HOT 600UL 48 120 0.36 119 P2 TWD 15 VSM

-0.84 TEH TEC 5

COLD 600UL 0.40 52 P2 TWD 16 VSM

+0.86 TEH TEC 5

COLD 600UL 122 120 0.23 66 P2 TWD 13 08H

+0.45 TEC TEH 36 HOT 600UL 0.32 146 P2 TWD 17 08H

-0.84 TEC TEH 36 HOT 600UL 27 121 0.32 84 P3 TWD 14 DBH

-1.82 TEH TEC 6

COLD 600UL 99 121 0.43 109 P2 TWD 17 VH2

-0.99 TEC TEH 37 HOT 600UL 107 121 0.97 157 P2 TWD 29 VH2

+0.90 TEC TEH 37 HOT 600UL 0.56 17 P2 TWD 21 VH2

-1.00 TEC TEH 37 HOT 600UL 121 121 0.43 110 P2 TWD 21 09H

+0.49 TEC TEH 36 HOT 600UL 0.43 125 P2 TWD 21 10H

-0.24 TEC TEH 36 HOT 60OUL 30 122 0.29 96 P2 TWD 12 05H

+0.51 TEH TEC 5

COLD 600UL 122 122 0.64 129 P2 TWD 27 10C

+0.85 TEC TEH 36 HOT 600UL 41 123 0.58 102 P2 TWD 21 VSM

+0.88 TEH TEC 5

COLD 600UL 49 123 0.70 156 P2 TWD 24 08H

+1.67 TEH TEC LOCOK 5

COLD 60OUL 101 123 0.30 103 P2 TWD 16 VH2

+0.93 TEC TEH 36 HOT 600UL 107 123 0.17 97 P3 TWD 7 DBH

-0.96 TEC TEH 37 HOT 600UL 117 123 0.44 144 P2 TWD 21 08H

+0.86 TEC TEH 36 HOT 600UL 0.33 84 P2 TWD 17 06H

+0.82 TEC TEH 36 HOT 600UL 119 123 0.57 62 P2 TWD 21 09H

+0.76 TEC TEH 37 HOT 600UL 48 124 0.32 59 P2 TWD 14 02H

-1.09

. TEH TEC 6

COLD 600UL 112 124 0.66 127 P2 TWD 28 VH2

-0.88 TEC TEH 40 HOT 600UL 116 124 0.31 72 P2 TWD 17 09H

+0.78 TEC TEH 40 HOT 600UL 0.39 97 P2 TWD 20 08H

+0.88 TEC TEH 40 HOT 60OUL 0.20 149 P2 TWD 12 08H

+0.39 TEC TEH 40 HOT 600UL 118 124 0.33 102 P2 TWD 14 VH2

+0.84 TEC TEH 41 HOT 600UL 107 125 0.43 74 P2 TWD 17 VH2

+0.88 TEC TEH 41 HOT 600UL 117 125 0.26 106 P2 TWD 14 09H

+0.41 TEC TEH 40 HOT 600UL 0.19 57 P2 TWD 11 09H

-0.90 TEC TEH 40 HOT 600UL 119 125 0.42 141 P2 TWD 16 09H

-0.82 TEC TEH 41 HOT 600UL 0.20 59 P2 TWD 9 09H

+0.14 TEC TEH 41 HOT 600UL 116 126 0.32 108 P2 TWD 13 08H

+0.94 TEC TEH 41 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component:

S/G 89 Page 15 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 69 127 0.49 134 P2 TWD 20 VC3

-0.78 TEH TEC 7

COLD 600UL 0.40 128 P2 TWD 17 VSM

+0.86 TEH TEC 7

COLD 600UL 109 127 0.10 96 P3 TWD 6 DBC

-1.90 TEC TEN 40 HOT 600UL 115 127 0.32 126 P2 TWD 13 09H

+0.68 TEC TEH 41 HOT 600UL 38 128 0.20 119 P2 TWD 10 VSM

+0.90 TEH TEC 8

COLD 600UL 44 128 0.56 140 P2 TWD 22 VSM

-0.82 TEH TEC 7

COLD 600UL 0.63 81 P2 TWD 24 VSM

+0.82 TEH TEC 7

COLD 600UL 116 128 0.44 150 P2 TWD 17 08H

+0.70 TEC TEH 41 HOT 600UL 0.27

.129 P2 TWD 12 09H

-0.96 TEC TEH 41 HOT 600UL 0.50 96 P2 TWD 19 09H

+0.68 TEC TEH 41 HOT 600UL 49 129 0.35 49 P2 TWD 16 08H

-1.53 TEH TEC LOCOK 7

COLD 600UL 57 129 0.25 137 P3 TWD 12 DBH

-0.46 TEH TEC 8

COLD 600UL 113 129 0.38 60 P2 TWD 20 09H

+0.81 TEC TEH 40 HOT 600UL 0.47 127 P2 TWD 22 VH2

+0.83 TEC TEH 40 HOT 600UL 0.37 63 P3 TWD 19 DBH

+2.00 TEC TEH 40 HOT 600UL 115 129 0.35 108 P2 TWO 14 09N

-0.80 TEC TEN 41 NOT 600UL 117 129 0.22 109 P2 TWD 13 08H

+0.84 TEC TEH 40 HOT 600UL 86 130 0.82 103 P2 TWO 27 VE2

-0.72 TEC TEE 29 NOT 600UL 114 130 0.32 129 P2 TWD 13 09H

-0.94 TEC TEH 29 HOT 600UL 0.17 116 P2 TWO 7 09E

+0.36 TEC. TEE 29 HOT 600UL 41 131 0.60 54 P2 TWO 23 VSM

+0.68 TEC TEE 6

HOT 600UL 0.61 97 P2 TWO 23 VSM

-0.88 TEC TEE 6

HOT 600UL 43 131 0.48 110 P2 TWD 21 VSM

+0.82 TEC TEH 5

HOT 60OUL 111 131 0.22 59 P2 TWD 9 08H

-0.76 TEC TEH 29 HOT 600UL 0.33 137 P2 TWO 14 VN2

-0.82 TEC TEN 29 NOT 600UL 0.25 113 P2 TWD 11 08H

+0.80 TEC TEH 29 HOT 600UL 127 131 0.21 79 P3 TWO 9 DEN

+1.74 TEC TEN 29 NOT 600UL 68 132 0.69 99 P2 TWD 27 VC3

+0.81 TEC TEH 5

HOT 600UL 76 132 0.34 143 P2 TWD 17 VN3

-0.87 TEC TEH 5

HOT 600UL 106 132 0.53 75 P2 TWD 20 VN2

-0.92 TEC TEH 29 HOT 600UL 112 132 0.59 87 P2 TWD 25 07H

+0.87 TEC TEH 28 HOT 600UL 0.31 85 P2 TWD 16 08H

+0.14 TEC TEH 28 HOT 60OUL 0.38 139 P2 TWD 18 08H

+0.89 TEC TEH 28 HOT 600UL 114 132 0.78 131 P2 TWO 26 07N

+0.75 TEC TEN 29 NOT

.600UL 126 132 0.56 90 P2 TWO 21 VH2

-0.91 TEC TEE 29 NOT 600UL 45 133 0.19 51 P3 TWD 11 DBC

-1.35 TEC TEH 5

HOT 600UL 71 133 0.55 143 P2 TWD 23 VC3

-0.71 TEC TEH 5

HOT 600UL 0.55 142 P2 TWD 23 VH3

+0.83 TEC TEH 5

HOT 600UL 0.55 64 P2 TWD 23 VH3

-0.85 TEC TEH 5

HOT 600UL 112 133 0.31 123 P2 TWD 16 08H

+0.82 TEC TEH 68 HOT 600UL 0.20 74 P2 TWD 11 08H

-0.02 TEC TEH 68 HOT 600UL 24 134 0.24 132 P1 SCI TSH

+0.12 TSN TSH 0.45 LAR 88 NOT 580PP 44 134 0.26 91 P2 TWD 13 VSM

-0.73 TEC TEH 5

HOT 600UL 46 134 0.37 123 P2 TWD 16 VSM

+0.75 TEC TEH 6

HOT 600UL 76 134 0.22 156 P3 TWD 12 DBC

-1.75 TEC TEH 5

HOT 600UL 111 135 0.37 116 P2 TWD 16 V02

+0.70 TEC TEH 29 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 16 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 56 136 0.49 115 P2 TWD 21 VSM

-0.79 TEC TEH 5

HOT 600UL 0.38 125 P2 TWD 18 VSM

+0.83 TEC TEH 5

HOT 600UL 110 136 0.35 140 P2 TWD 15 08H

+0.98 TEC TEH 29 HOT 600UL 0.40 62 P2 TWD 16 08H

-0.84 TEC TEH 29 HOT 600UL 89 137 0.39 108 P2 TWD 18 VH2

-0.99 TEC TEH 28 HOT 600UL 0.44 119 P3 TWD 21 DBH

+1.51 TEC TEH 28 HOT 600UL 0.37 144 P2 TWD 18 VH2

+1.03 TEC TEH 28 HOT 600UL 91 137 0.31 34 P3 TWD 12 DBH

+1.62 TEC TEH 29 HOT 600UL 109 137 0.57 85 P2 TWD 24 08H

-0.99 TEC TEH 28 HOT 600UL 0.19 144 P2 TWD 10 08H

+0.80 TEC TEH 28 HOT 600UL 111 137 0.69 117 P2 TWD 24 VH2

+0.94 TEC TEH 29 HOT 60OUL 46 138 0.40 106 P2 TWD 17 04C

-0.14 TEC TEH 6

HOT 600UL 78 138 0.24 107 P2 TWD 11 VH3

-0.88 TEC TEH 6

HOT 600UL 108 138 0.22 120 P2 TWD 12 08H

-1.13 TEC TEH 28 HOT 600UL 110 138 0.31 99 P2 TWD 13 08H

+0.08 TEC TEH 29 HOT 600UL 107 139 0.42 89 P2 TWD 17 09H

+0.53 TEC TEH 29 HOT 600UL 109 139 0.12 5

P3 TWD 7 DBH

+1.50 TEC TEH 28 HOT 600UL 119 139 0.62 128 P2 TWD 23 10C

-1.20 TEC TEH LOCOK 29 HOT 600UL 74 140 0.33 79 P2 TWD 15 VC3

+0.78 TEC TEH 6

HOT 600UL 111 141 0.29 107 P3 TWD 15 DBH

-1.59 TEC TEH 68 HOT 600UL 112 142 0.53 17 P3 TWD 24 DBC

+1.88 TEC TEH 68 HOT 600UL 0.39 156 P2 TWD 19 VC2

-0.94 TEC TEH 68 HOT 600UL 57 143 0.57 97 P2 TWD 25 VH3

+0.79 TEC TEH 10 HOT 600UL 111 143 0.21 79 P2 TWD 9 VC3

+0.86 TEC TEH 29 HOT 600UL 0.26 162 P3 TWD 10 DBH

+1.41 TEC TEH 29 HOT 600UL 0.17 76 P2 TWD 7 VC3

-0.82 TEC TEH 29 HOT 600UL 36 144 0.32 132 P2 TWD 16 VSM

-0.81 TEC TEH 10 HOT 600UL 42 144 0.53 90 P2 TWD 20 VSM

+0.86 TEC TEH 11 HOT 600UL 0.16 152 P2 TWD 7 VSM

-0.73 TEC TEH 11 HOT 600UL 86 144 0.46 50 P2 TWD 21 VH2

+0.80 TEC TEH 28 HOT 600UL 98 144 0.27 61 P2 TWD 14 09H

-0.88 TEC TEH 28 HOT 600UL 37 145 0.37 105 P2 TWD 18 VSM

+0.94 TEC TEH 10 HOT 600UL 49 145 0.34 15 P3 TWD 14 DBC

+2.07 TEC TEH 11 HOT 600UL 107 145 0.60 111 P2 TWD 22 08H

+0.06 TEC TEH 29 HOT 600UL 36 146 0.25 69 P2 TWD 13 VSM

+0.96 TEC TEH 10 HOT 600UL 40 146 0.34 53 P2 TWD 17 VSM

+0.96 TEC TEH 10 HOT 600UL 46 146 0.58 109 P2 TWD 21 VSM

+0.95 TEC TEH 11 HOT 600UL 0.65 88 P2 TWD 23 VSM

-0.65 TEC TEH 11 HOT 600UL 76 146 0.45 46 P2 TWO 21 VH3

+0.83 TEC TEE 10 HOT 600UL 0.45 12S P2 TWD 21 VH3

-0.87 TEC TEH 10 HOT 600UL 106 146 0.26 148 P2 TWD 13 VH2

-0.94 TEC TEH 28 HOT 600UL 39 147 0.33 135 P2 TWD 17 VSM

+0.88 TEC TEH 10 HOT 600UL 75 147 0.55 97 P2 TWD 24 VC3

+0.77 TEC TEH 10 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 17 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY:

QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 105 147 0.60 129 P2 TWD 25 VH2

-0.84 TEC TEH 28 HOT 600UL 34 148 0.51 82 P2 TWD 19 VSM

-0.81 TEC TEH 11 HOT 600UL 42 148 0.25 126 P2 TWD 11 VSM

+0.73 TEC TEH 11 HOT 600UL 0.42 103 P2 TWD 17 VSM

+0.27 TEC TEH 11 HOT 60OUL 58 148 0.66 118 P2 TWD 23 VC3

-0.85 TEC TEH 11 HOT 600UL 0.28 143 P2 TWD 12 VH3

-0.79 TEC TEH 11 HOT 60OUL 0.53 69 P2 TWD 20 VSM

+0.85 TEC TEH 11 HOT 600UL 99 149 0.49 87 P2 TWD 22 VH2

+0.84 TEC TEH 68 HOT 600UL 103 149 0.42 110 P2 TWD 20 08H

-0.24 TEC TEH 68 HOT 600UL 0.48 134 P2 TWD 22 VH2

+0.70 TEC TEH 68 HOT 600UL 102 150 0.21 142 P3 TWD 8 DBC

+1.59 TEC TEH 33 HOT 600UL 65 151 0.36 38 P2 TWD 17 VSM

-0.77 TEC TEH 14 HOT 600UL 0.41 122 P2 TWD 19 VSM

+0.93 TEC TEH 14 HOT 600UL 0.14 58 P2 TWD 7 VSM

+0.18 TEC TEH 14 HOT 600UL 99 151 0.41 139 P2 TWD 17 08H

-0.80 TEC TEH 33 HOT 600UL 76 152 0.29 68 P2 TWD 14 VC3

-0.65 TEC TEH 14 HOT 600UL 80 152 0.28 44 P3 TWD 13 DBC

+1.96 TEC TEH 14 HOT 600UL 81 153 0.48 116 P2 TWD 21 VH3

+0.93 TEC TEH 32 HOT 600UL 0.32 129 P2 TWD 16 VH3

-0.91 TEC TEH 32 HOT 600UL 0.15 14 P3 TWD 8 DBC

+1.91 TEC TEH 32 HOT 600UL 77 155 0.72 126 P2 TWD 27 VH3

+0.79 TEC TEH 14 HOT 600UL 0.34 100 P2 TWD 16 VH3

-0.89 TEC TEH 14 HOT 600UL 86 156 0.39 49 P2 TWD 18 VH2

-0.75 TEC TEH 32 HOT 600UL 37 157 0.23 40 P2 TWO 12 VSM

+0.74 TEC TEH 14 HOT 600UL 41 157 0.52 127 P2 TWD 22 VSM

+0.74 TEC TEH 14 HOT 600UL 73 157 0.22 103 P2 TWD 11 VC3

+0.02 TEC TEH 14 HOT 600UL 75 157 0.18 154 P3 TWO 9 OBC

+1.85 TEC TEN 15 HOT 600UL 87 157 0.36 137 P2 TWO 15 03H

-1.19 TEC TEH 33 HOT 600UL 44 158 0.32 130 P2 TWO 16 VSM

+0.96 TEC TEH 14 HOT 600UL 0.35 122 P2 TWO 17 VSM

-0.72 TEC TEH 14 HOT 600UL 0.22 106 P2 TWD 11 VSM

-0.08 TEC TEH 14 HOT 600UL 43 161 0.46 124 P2 TWD 18 VSM

-0.75 TEC TEH 15 HOT 600UL 38 162 0.37 107 P2 TWD 16 VSM

-0.81 TEC TEH 19 HOT 600UL 0.34 99 P2 TWD 15 VSM

-0.06 TEC TEH 19 HOT 600UL 40 162 0.23 43 P2 TWD 12 VSM

-0.12 TEC TEH 18 HOT 600UL 0.34 125 P2 TWD 16 VSM

-0.74 TEC TEH 18 HOT 600UL 58 162 0.32 55 P2 TWO 14 VH3

-0.87 TEC TEH 19 HOT 600UL 62 162 0.27 129 P2 TWD 12 VN3

-1.13 TEC TEH 19 HOT 600UL 76 162 0.25 42 P2 TWO 12 OSH

+0.64 TEC TEH 19 HOT 600UL 71 163 0.22 63 P2 TWO 12 02C

+0.10 TEC TEH 18 HOT 600UL 46 164 0.32 53 P2 TWD 14 VSM

+0.86 TEC TEH 19 HOT 600UL 0.47 140 P2 TWD 19 VSM

-0.75 TEC TEH 19 HOT 600UL 60 164 0.23 153 P2 TWD 12 08C

+0.88 TEC TEH 18 HOT 600UL 68 164 0.28 103 P2 TWD 13 0CC

-0.16 TEC TEH 19 HOT 600UL 0.43 117 P2 TWD 18 O1C

+0.91 TEC TEH 19 HOT 600UL 70 164 0.38 136 P2 TWD 17 VH3

+0.87 TEC TEH 19 HOT 600UL

AREVA NP Inc 11/18/06 09:47:11 Customer Name: SONGS Unit 3 Component: S/G 89 Page 18 of 18

MAI, MCI,
MMI, MVI,
SAI, SCI,
SVI, 0-100%

QUERY: QueryM2[l]

ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT UTIL 1

UTIL 2

CAL # LEG PROBE 67 165 0.65 107 P2 TWD 26 01C

-0.12 TEC TEH 18 HOT 600UL 0.15 145 P2 TWD 8 01C

+0.92 TEC TEH 18 HOT 600UL 20 166 0.27 113 P2 TWD 14 02H

+0.90 TEC TEH 18 HOT 600UL 46 166 0.41 119 P2 TWD 17 VSM

+0.84 TEC TEH 19 HOT 600UL 62 166 0.31 99 P2 TWD 14 02H

-0.20 TEC TEH 19 HOT 60OUL 0.37 89 P2 TWD 16 02H

-0.82 TEC TEH 19 HOT 60OUL 64 166 0.24 20 P2 TWD 12 07H

+0.76 TEC TEH 18 HOT 60OUL 31 167 0.38 24 P2 TWD 17 VSM

+0.89 TEC TEH 19 HOT 600UL 45 167 0.15 161 P2 TWD 8 VSM

+0.92 TEC TEH 18 HOT 600UL 40 168 0.62 51 P2 TWD 25 VSM

+0.90 TEC TEH 18 HOT 600UL 0.35 47 P2 TWD 17 VSM

-0.08 TEC TEH 18 HOT 60OUL 0.18 160 P2 TWD 10 VSM

-0.70 TEC TEH 18 HOT 600UL 45 169 0.37 80 P2 TWD 17 01C

+0.88 TEC TEH 18 HOT 60OUL 22 170 0.28 59 P2 TWD 14 01C

+0.82 TEC TEH 18 HOT 60OUL 40 170 0.47 131 P2 TWD 19 01C

+0.88 TEC TEH 19 HOT 60OUL 42 170 0.21 84 P2 TWD 11 01H

-0.12 TEC TEH 18 HOT 600UL 46 170 0.30 47 P2 TWD 15 05C

+0.84 TEC TEH 18 HOT 600UL 33 171 0.27 123 P2 TWD 12 01C

-0.14 TEC TEH 19 HOT 600UL 37 171 0.59 117 P2 TWD 23 VSM

-0.83 TEC TEH 19 HOT 600UL Total Tubes

544 Total Records: 707