Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.15 Safety Function Determination Program (SFDP) (continued)
- b.
A required system redundant to the system(s) in turn supported by the inoperable supported system is also inoperable; or
- c.
A required system redundant to the support system(s) for the supported systems (a) and (b) above is also inoperable.
The SFDP identifies where a loss of safety function exists. If a loss of safety function is determined to exist by this program, the appropriate Conditions and Required Actions of the LCO in which the loss of safety function exists are required to be entered.
5.5.16 Containment Leakage Rate Testing Program
- a.
A program shall be established to implement the leakage rate testing of the containment as required by 10 CFR 50.54(o) and 10 CFR 50, Appendix J, Option B, as modified by approved exemptions. This program shall be in accordance with the guidelines contained in Regulatory Guide 1.163, "Performance-Based Containment Leak-Test Program," dated September 1995, as modified by the following exceptions:
- 1.
The visual examination of containment concrete surfaces intended to fulfill the requirements of 10 CFR 50, Appendix J, Option B testing, will be performed in accordance with the requirements of and frequency specified by ASME Section XI Code, Subsection IWL, except where relief has been authorized by the NRC.
- 2.
The visual examination of the steel liner plate inside containment intended to fulfill the requirements of 10 CFR 50, Appendix J, Option B, will be performed in accordance with the requirements of and frequency specified by ASME Section Xl Code, Subsection IWE, except where relief has been authorized by the NRC.
- 3.
The ten-year interval between performance of the integrated leakage rate (Type A) test, beginning May 4, 1994, for Unit 1 and April 30, 1993, for Unit 2, has been extended to 15 years.
- b.
The peak calculated containment internal pressure for the design basis loss of coolant accident, Pa, is 47 psig.
- c.
The maximum allowable containment leakage rate, La, at Pa, shall be 0.10% of containment air weight per day.
(continued)
DIABLO CANYON - UNITS 1 & 2 5.0-24 Unit 1 - Amendment No..1-35, 1-50, 4-72, 197 Unit 2 - Amendment No. 4,35, 450, 4-74, 198
Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.16 Containment Leakage Rate Testing Program (continued)
- d.
Leakage rate acceptance criteria are:
- 1.
Containment overall leakage rate acceptance criterion is < 1.0 La. During the first unit startup following testing in accordance with this program, the leakage rate acceptance criteria are < 0.60 L, for the Type B and Type C tests and _< 0.75 La for Type A tests;
- 2.
Air lock testing acceptance criteria are:
a)
Overall air lock leakage rate is < 0.05 La when tested at > Pa.
b)
For each door, leakage rate is < 0.01 La when pressurized to > 10 psig.
- e.
The provisions of SR 3.0.2 do not apply to the test frequencies specified in the Containment Leakage Rate Testing Program.
- f.
The provisions of SR 3.0.3 are applicable to the Containment Leakage Rate Testing Program.
5.5.17 Battery Monitoring and Maintenance Program This Program provides for restoration and maintenance, based on the recommendations of IEEE Standard 450, "IEEE Recommended Practice for Maintenance, Testing, and Replacement of Vented Lead-Acid Batteries for Stationary Applications," or of the battery manufacturer, of the following:
- a.
Actions to restore battery cells with float voltage < 2.13 V, and
- b.
Actions to equalize and test battery cells that have been discovered with electrolyte level below the top of the plates.
(continued)
DIABLO CANYON - UNITS 1 & 2 5.0-24a Unit 1 - Amendment No. 4-72, 197 Unit 2 - Amendment No. 4-74, 198