FAQ Number 06-0020 FAQ Revision 1

FAQ Title Identification of applicable NFPA standards Page 1 of 2 Plant: Harris Nuclear Plant (HNP)

Date:

02-16-07

Contact:

Alan Holder Phone:

919-546-3372 Email:

alan.holder@pgnmail.com Distribution: (NEI Internal Use) 805 TF FPWG FPRATF Purpose of FAQ:

Provide specific clarification for term, applicable NFPA standards as applied under section 4.3.1 of NEI 04-02.

Is this Interpretation of guidance?

Yes / No Proposed new guidance not in NEI 04-02? Yes / No Details:

NEI 04-02 guidance needing interpretation (include section, paragraph, and line numbers as applicable):

NEI 04-02, Section 4.3.1, Fundamental Fire Protection Program and Design Elements Transition Review, Table B-1 uses NFPA 805 chapter 3 as part of the transition review. Specific clarification is requested for certain terms and phrases found in NFPA 805.

Circumstances requiring guidance interpretation or new guidance:

Clarification of NFPA-805, Standard for Fire Protection for Light Water Reactor Electric Generating Plants (2001 Edition), Chapter 3, Section 3.3.1.2 Control of Combustibles. (6) Controls on use and storage of flammable gases shall be in accordance with applicable NFPA standards.

Specifically, identify applicable NFPA standards to be used during reviews associated with Chapter 3 transition.

Detail contentious points if licensee and NRC have not reached consensus on the facts and circumstances:

NA

FAQ Number 06-0020 FAQ Revision 1

FAQ Title Identification of applicable NFPA standards Page 2 of 2 Potentially relevant existing FAQ numbers:

FAQ 06-0007 Response Section:

Proposed resolution of FAQ and the basis for the proposal:

This FAQ asks to identify, where used in NFPA 805, Chapter 3, applicable NFPA standards for review of programs structures, systems, and components as may be required for Chapter 3 transition using NFPA 805. Because existing fire protection programs for facilities generally provide a listing of NFPA standards used in the development, implementation and maintenance of the fire protection program, the term, applicable NFPA Standards, where used in NFPA 805, Chapter 3, shall be considered to be equivalent to those NFPA standards identified in the Current License Bases (CLB) for the facility (generally found in the FSAR or approved Fire Protection Program). Because these NFPA standards have been previously approved by the staff for a given facility, this further establishes their applicability.

If appropriate, provide proposed rewording of guidance for inclusion in the next Revision:

As follows; Clarification of NFPA 805 specific sections as applied under NEI 04-02, to be included in (New) Appendix K, to NEI 04-02 upon approval of specific clarification (final formatting to be provided by NEI).

Specific clarification to NFPA 805, Chapter 3, from FAQ 06-0020, Where used in NFPA 805, Chapter 3, the term, applicable NFPA Standards is considered to be equivalent to those NFPA standards identified in the current license basis (CLB) for procedures and systems in the Fire Protection Program that are transitioning to NFPA 805. New Fire Protection Systems would be subject to the most current code or standard.