ML071280098
| ML071280098 | |
| Person / Time | |
|---|---|
| Site: | Dresden, Peach Bottom, Oyster Creek, Byron, Braidwood, Limerick, Clinton, Quad Cities, LaSalle, Crane (DPR-016, DPR-019, DPR-025, DPR-029, DPR-030, DPR-044, DPR-050, DPR-056, NPF-011, NPF-018, NPF-037, NPF-039, NPF-062, NPF-066, NPF-072, NPF-077, NPF-085) |
| Issue date: | 05/07/2007 |
| From: | Benyak D AmerGen Energy Co, Exelon Generation Co, Exelon Nuclear |
| To: | Document Control Desk, NRC/NRR/ADRO |
| References | |
| 2130-07-20490, 5928-07-20094, GL-07-001, RS-07-067 | |
| Download: ML071280098 (15) | |
Text
Exelon Generation wwwexelorncorp.com 4300 Winfield Road Warrenville. I(_ 60553 RS-07-067 5928-07-20094 2130-07-20490 10 CFR 50.54(f)
May 7, 2007 U. S. Nuclear Regulatory Commission ATTN : Document Control Desk 11555 Rockville Pike Rockville, MD 20852 Braidwood Station, Units 1 and 2 Facility Operating License Nos. NPF-72 and NPF-77 NRC Docket Nos. STN 50-456 and STN 50-457 Byron Station, Units 1 and 2 Facility Operating License Nos. NPF-37 and NPF-66 NRC Docket Nos. STN 50-454 and STN 50-455 Clinton Power Station, Unit 1 Facility Operating License No. NPF-62 NRC Docket No. 50-461 Dresden Nuclear Power Station, Units 2 and 3 Renewed Facility Operating License Nos. DPR-19 and DPR-25 NRC Docket Nos. 50-237 and 50-249 LaSalle County Station, Units 1 and 2 Facility Operating License Nos. NPF-11 and NPF-18 NRC Docket Nos. 50-373 and 50-374 Limerick Generating Station, Units 1 and 2 Facility Operating License Nos. NPF-39 and NPF-85 NRC Docket Nos. 50-352 and 50-353 Oyster Creek Nuclear Generating Station Facility Operating License No. DPR-16 NRC Docket No. 50-219 Peach Bottom Atomic Power Station, Units 2 and 3 Renewed Facility Operating License Nos. DPR-44 and DPR-56 NRC Docket Nos. 50-277 and 50-278 r
Exe Ic~ n5M Nuclear
U. S. Nuclear Regulatory Commission May 7, 2007 Page 2 Quad Cities Nuclear Power Station, Units 1 and 2 Renewed Facility Operating License Nos. DPR-29 and DPR-30 NRC Docket Nos. 50-254 and 50-265 Three Mile Island Nuclear Station, Unit 1 Facility Operating License No. DPR-50 NRC Docket No. 50-289 Subject :
Response to NRC Generic Letter 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients"
Reference:
Letter from Michael J. Case (NRC) to Addressees, "NRC Generic Letter 2007-01 :
Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients," dated February 7, 2007 On February 7, 2007, the NRC issued Generic Letter (GL) 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients" (i.e., Reference). The GL requested that all holders of operating licenses submit a written response within 90 days in accordance with 10 CFR 50.54, "Conditions of licenses,"
paragraph (f). The GL requested the following information.
Provide a history of inaccessible or underground power cable failures for all cables that are within the scope of 10 CFR 50.65 (the Maintenance Rule) and for all voltage levels.
Indicate the type, manufacturer, date of failure, type of service, voltage class, years of service, and the root causes for the failure.
(2)
Describe inspection, testing and monitoring programs to detect the degradation of inaccessible or underground power cables that support EDGs, offsite power, ESW, service water, component cooling water and other systems that are within the scope of 10 CFR 50.65 (the Maintenance Rule). provides the Exelon Generation Company, LLC (EGC) and AmerGen Energy Company, LLC (AmerGen) 90-day response to the requested information for Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Quad Cities Nuclear Power Station and Three Mile Island Nuclear Station Unit 1.
Attachments 2 through 4 provide the responses for Limerick Generating Station, Oyster Creek Nuclear Generating Station, and Peach Bottom Atomic Power Station, respectively.
There are no regulatory commitments made in this letter. Should you have any questions concerning this letter, please contact Kenneth M. Nicely at (630) 657-2803.
U. S. Nuclear Regulatory Commission May 7, 2007 Page 3 I declare under penalty of perjury that the foregoing is true and correct. Executed on the 7th day of May 2007.
Respectfully, cc :
Darin M. Benyak I
Director, Licensing and Regulatory Affairs Exelon Generation Company, LLC AmerGen Energy Company, LLC Attachments:
1. 90-Day Response to NRC Generic Letter 2007-01 for Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Three Mile Island Nuclear Station Unit 1, and Quad Cities Nuclear Power Station
- 2. 90-Day Response to NRC Generic Letter 2007-01 for Limerick Generating Station
- 3. 90-Day Response to NRC Generic Letter 2007-01 for Oyster Creek Nuclear Generating Station
- 4. 90-Day Response to NRC Generic Letter 2007-01 for Peach Bottom Atomic Power Station Regional Administrator - NRC Region I Regional Administrator - NRC Region III NRC Senior Resident Inspector - Braidwood Station NRC Senior Resident Inspector - Byron Station NRC Senior Resident Inspector - Clinton Power Station NRC Senior Resident Inspector - Dresden Nuclear Power Station NRC Senior Resident Inspector - LaSalle County Station NRC Senior Resident Inspector - Limerick Generating Station NRC Senior Resident Inspector - Oyster Creek Nuclear Generating Station NRC Senior Resident Inspector - Peach Bottom Atomic Power Station NRC Senior Resident Inspector -Three Mile Island Nuclear Station, Unit 1 NRC Senior Resident Inspector - Quad Cities Nuclear Power Station
ATTACHMENT 1 90-Day Response to NRC Generic Letter 2007-01 for Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Quad Cities Nuclear Power Station and Three Mile Island Nuclear Station Unit 1 On February 7, 2007, the NRC issued Generic Letter (GL) 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients." The GL requested that all holders of operating licenses for nuclear power reactors submit a written response within 90 days in accordance with 10 CFR 50.54, "Conditions of licenses," paragraph (f). The 90-day response to the information requested by the NRC in GL 2007-01 is provided below for Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Quad Cities Nuclear Power Station and Three Mile Island Nuclear Station Unit 1.
NRC Request.1 Provide a history of inaccessible or underground power cable failures for all cables that are within the scope of 10 CFR 50.65 (the Maintenance Rule) and for all voltage levels. Indicate the type, manufacturer, date of failure, type of service, voltage class, years of service, and the root causes for the failure.
Response
A review has been completed and no history of failures of inaccessible or underground power cables that are within the scope of 10 CFR 50.65, "Requirements for monitoring the effectiveness of maintenance at nuclear power plants," has been identified. This review examined the plant corrective action program, Maintenance Rule or other databases, maintenance records, interviews with cognizant personnel, and a review of the circuit and raceway schedules to identify power cable failures. The scope of the review included alternating current power distribution cables with voltages from 480 VAC to 15,000 VAC. This represents our best effort in that data of this nature was not necessarily recorded in a means that was conducive to identifying cable failures.
NRC Request 2 Describe inspection, testing and monitoring programs to detect the degradation of inaccessible or underground power cables that support EDGs, offsite power, ESW, service water, component cooling water and other systems that are within the scope of 10 CFR 50.65 (the Maintenance Rule).
Response
The Exelon Nuclear Cable Condition Monitoring Program is controlled under procedure ER-AA-3003, "Cable Condition Monitoring Program," which was issued in January 2007. This program is consistent with industry practices and recommendations as provided in Nuclear Energy Institute (NEI) 06-05, "Medium Voltage Underground Cable White Paper," dated April 2006. The program consists of a two-phase approach to medium voltage cable testing.
The first phase of the program is referred to as screening, and takes advantage of motor testing that is typically performed from the switchgear. Since the motor testing is performed from the switchgear, the motor feeder cables are tested along with the motors. This testing is performed with an appropriate motor analyzer and includes insulation resistance, Polarization Index, and Step Voltage HiPot Testing. This testing is done on a representative population of station Page 1
ATTACHMENT 1 90-Day Response to NRC Generic Letter 2007-01 for Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Quad Cities Nuclear Power Station and Three Mile Island Nuclear Station Unit 1 cables.
It should be noted that for Quad Cities Station and Three Mile Island, station procedures or management direction currently limit this testing to insulation resistance measurement (i.e., megger).
If the results of screening indicate problems with the cables, then an appropriate diagnostic cable test program is implemented. The diagnostic test methodology will be selected based upon the nature of the identified cable degradation. The diagnostic cable testing will be applied to all cables in the suspect population. Note that a sizeable population of the Exelon Nuclear cables is unshielded and, as such, the testing methodologies identified in the GL (i.e., partial discharge, time domain reflectometry, dissipation factor, and very low frequency alternating current) would not be applicable.
In addition to the screening/diagnostic aspects of the Cable Condition Monitoring Program, Dresden has also made a commitment as part of license renewal to cable testing programs for a population of inaccessible medium voltage cables.
The Exelon Nuclear Cable Condition Monitoring Program does not monitor low voltage inaccessible cables for degradation. As evidenced by the stations' failure history, there is no indication that there are issues associated with low voltage inaccessible power cables.
Dresden and Quad Cities have a commitment under License Renewal regarding low voltage cables with respect to exposure to external stressors. This commitment requires the identification of any adverse localized environment caused by heat or radiation in critical plant areas. Cables would then be inspected in these areas for visible degradation by the identified adverse environment. The inspections will be completed in accordance with the timing set forth in the License Renewal commitment.
In addition, Dresden and Quad Cities have a commitment under their Environmental Qualification (EQ) Programs regarding butyl rubber cables. This commitment requires a periodic inspection surveillance program on a selected sample of these cables in various harsh environmental zones in the reactor buildings to maintain their environmental qualification status.
This includes both physical inspections and insulation resistance measurements. The sample size includes both power and control cables.
Braidwood Station, Byron Station, Clinton Power Station, Dresden Nuclear Power Station, LaSalle County Station, Quad Cities Nuclear Power Station and Three Mile Island Nuclear Station Unit 1 have had no history of failures of inaccessible or underground power cables within the scope of 10 CFR 50.65. As such, these stations are using the screening methodology described above to assess the condition of a representative population of medium voltage cables.
ATTACHMENT 2 90-Day Response to NRC Generic Letter 2007-01 for Limerick Generating Station On February 7, 2007, the NRC issued Generic Letter (GL) 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients." The GL requested that all holders of operating licenses for nuclear power reactors submit a written response within 90 days in accordance with 10 CFR 50.54, "Conditions of licenses," paragraph (f). The 90-day response to the information requested by the NRC in GL 2007-01 is provided below for Limerick Generating Station.
NRC Request 1 Provide a history of inaccessible or underground power cable failures for all cables that are within the scope of 10 CFR 50.65 (the Maintenance Rule) and for all voltage levels. Indicate the type, manufacturer, date of failure, type of service, voltage class, years of service, and the root causes for the failure.
Response
A review has been completed to identify failures of inaccessible or underground power cables that are within the scope of 10 CFR 50.65, "Requirements for monitoring the effectiveness of maintenance at nuclear power plants." This review examined the plant corrective action program, Maintenance Rule or other databases, maintenance records, interviews with cognizant personnel, and a review of the circuit and raceway schedules to identify power cable failures.
The scope of the review included alternating current power distribution cables with voltages from 480 VAC to 15,000 VAC. This represents our best effort in that data of this nature was not necessarily recorded in a means that was conducive to identifying cable failures. The results of this review are provided below:
Cable Voltage Cable Date of Failure/
Type of Root Type Class Manufacturer Years of Service Service Cause 500 kcmil, 15kW13.8kV Anaconda-1995/15 years Feed to Failed Single, EPR, Ericcson Cable Circulating inservice, UniShield Water Pump manufacturing 1A-P501, defect duct, normally energized 500 kcmil, 15kW13.8kV Anaconda-1995/15 years Feed to Failed Single, EPR, Ericcson Cable Circulating inservice, UniShield Water Pump manufacturing 1 B-P501, defect duct, normally energized IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII~lllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllllll I IIII Illll lllllllllillilllllllllllllllllllllllllliillllllllllllllllllllllllllllllllllllll 500 kcmil, 15kW13.8kV Anaconda-1995/15 years Feed to Failed during Single, EPR, Ericcson Cable Circulating
- test, UniShield Water Pump manufacturing 1C-P501, defect duct, normally energized
ATTACHMENT 2 90-Day Response to NRC Generic Letter 2007-01 for Limerick Generating Station NRC Request 2 Describe inspection, testing and monitoring programs to detect the degradation of inaccessible or underground power cables that support EDGs, offsite power, ESW, service water, component cooling water and other systems that are within the scope of 10 CFR 50.65 (the Maintenance Rule).
Response
The Exelon Nuclear Cable Condition Monitoring Program is controlled under procedure ER-AA-3003, "Cable Condition Monitoring Program," which was issued in January 2007. This program is consistent with industry practices and recommendations as provided in Nuclear Energy Institute (NEI) 06-05, "Medium Voltage Underground Cable White Paper," dated April 2006. The program consists of a two-phase approach to medium voltage cable testing.
The first phase of the program is referred to as screening, and takes advantage of motor testing that is typically performed from the switchgear. Since the motor testing is performed from the switchgear, the motor feeder cables are tested along with the motors. This testing is performed with an appropriate motor analyzer and includes insulation resistance, Polarization Index, and Step Voltage HiPot Testing. This testing is done on a representative population of station cables.
If the results of screening indicate problems with the cables, then an appropriate diagnostic cable test program is implemented. The diagnostic test methodology will be selected based upon the nature of the identified cable degradation. The diagnostic cable testing will be applied to all cables in the suspect population.
The Exelon Nuclear Cable Condition Monitoring Program does not monitor low voltage inaccessible cables for degradation. As evidenced by the station's failure history, there is no indication that there are issues associated with low voltage inaccessible power cables.
Limerick has a history of medium voltage cable failures in a specific population of the originally installed cables. These failures have been attributed to voids and impurities in the Ethylene Propylene Rubber (EPR) insulation coupled with operation in a wet environment. The inservice Page 2 Cable Type Voltage Class Cable Manufacturer Date of Failure/
Years of Service Type of Service Root Cause 500 kcmil, 15kW13.8kV Anaconda-2000/20 years Feed to Failed during Single, EPR, Ericcson Cable Circulating
- test, UniShield Water Pump manufacturing 1A-P501, defect duct, normally energized 350 kcmil, 15kW13.8kV Anaconda-2005/25 years Feed to 222 Failed during Single, EPR, Ericcson Cable Transformer,
- test, UniShield duct, normally manufacturing energized defect
ATTACHMENT 2 90-Day Response to NRC Generic Letter 2007-01 for Limerick Generating Station failures have all been in 13.8kV applications associated with the non-safety related circulating water pump motor feeds. As a result, potentially wetted cables energized at 13.8kV are now being tested utilizing very low frequency (VLF) diagnostic testing.
ATTACHMENT 3 90-Day Response to NRC Generic Letter 2007-01 for Oyster Creek Nuclear Generating Station On February 7, 2007, the NRC issued Generic Letter (GL) 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients." The GL requested that all holders of operating licenses for nuclear power reactors submit a written response within 90 days in accordance with 10 CFR 50.54, "Conditions of licenses," paragraph (f). The 90-day response to the information requested by the NRC in GL 2007-01 is provided below for Oyster Creek Nuclear Generating Station.
NRC Request 1 Provide a history of inaccessible or underground power cable failures for all cables that are within the scope of 10 CFR 50.65 (the Maintenance Rule) and for all voltage levels. Indicate the type, manufacturer, date of failure, type of service, voltage class, years of service, and the root causes for the failure.
Response
A review has been completed to identify failures of inaccessible or underground power cables that are within the scope of 10 CFR 50.65, "Requirements for monitoring the effectiveness of maintenance at nuclear power plants." This review examined the plant corrective action program, maintenance records, interviews with cognizant personnel, and a review of the circuit and raceway schedules to identify power cable failures. The scope of the review included alternating current power distribution cables with voltages from 480 VAC to 15,000 VAC. This represents our best effort in that data of this nature was not necessarily recorded in a means that was conducive to identifying cable failures. The results of this review are provided below.
As a result of the early cable failures, Oyster Creek embarked upon a cable-testing program (Step Voltage HiPot Testing). Testing over a period of time showed increasing amounts of leakage current in several cables. Twenty-six additional cables were replaced due to indications from the test program ; these cables were replaced prior to failure. Additionally, due to recent failures in a population of Anaconda UniShield cables, eight cables were replaced as a possible extent of condition.
Cable Type Voltage Class Cable Manufacturer Date of Failure!
Years of Service Type of Service Root Cause 500 kcmil, 5kV/4160V Cablec 1998/7 years Feedwater A, Water intrusion Single, EPR, underground UniShield
- conduit, energized continuously 4/0 AWG 5kV/4160V Anaconda 1997/13 years Reactor Water intrusion Single, EPR, Recirc Motor-UniShield Generator Set Motor E, underground
- conduit, energized continuously
ATTACHMENT 3 90-Day Response to NRC Generic Letter 2007-01 for Oyster Creek Nuclear Generating Station Page 2 Cable Voltage Cable Date of Failure/
Type of Root Type Class Manufacturer Years of Service Service Cause 2/0 AWG 5kV/4160V GE 1988/19 years Unit Manufacturing
- Single, Substation defect
- XLPE, 1 A3,
- Shielded, underground Metallic
- conduit, energized continuously 500 kcmil, 5kV/4160V Anaconda 1990/6 years Unit Manufacturing Single, EPR, Substation defect (voids)
UniShield 1 B2, underground
- conduit, energized continuously 500 kcmil, 5kV/4160V Anaconda 2001/5 years Unit Manufacturing Single, EPR, Substation defect (voids)
UniShield 1 B2, underground
- conduit, energized continuously 500 kcmil, 5kV/4160V GE 1975/6 years EDG-1, Lightning surge
- Single, underground
- XLPE, conduit,
- Shielded, energized Metallic continuously 500 kcmil, 5kV/4160V Anaconda 1983/6 years EDG-1, Manufacturing Single, EPR, underground defect (voids)
UniShield
- conduit, energized continuously 500 kcmil, 5kV/4160V Anaconda 2003/19 years EDG-1, Manufacturing Single, EPR, underground defects and UniShield
- conduit, water intrusion energized continuously 500 kcmil, 5kV/4160V GE 1977/8 years EDG-2, Lightning surge
- Single, underground
- XLPE, conduit,
- Shielded, energized Metallic continuously 500 kcmil, 5kV/4160V Anaconda 1988/11 years EDG-2, Manufacturing Single, EPR, underground defect (voids)
UniShield
- conduit, energized continuously
ATTACHMENT 3 90-Day Response to NRC Generic Letter 2007-01 for Oyster Creek Nuclear Generating Station NRC Request 2 Describe inspection, testing and monitoring programs to detect the degradation of inaccessible or underground power cables that support EDGs, offsite power, ESW, service water, component cooling water and other systems that are within the scope of 10 CFR 50.65 (the Maintenance Rule).
Response
The Exelon Nuclear Cable Condition Monitoring Program is controlled under procedure ER-AA-3003, "Cable Condition Monitoring Program," which was issued in January 2007. This program is consistent with industry practices and recommendations as provided in Nuclear Energy Institute (NEI) 06-05, "Medium Voltage Underground Cable White Paper," dated April 2006. The program consists of a two-phase approach to medium voltage cable testing.
The first phase of the program is referred to as screening, and takes advantage of motor testing that is typically performed from the switchgear. Since the motor testing is performed from the switchgear, the motor feeder cables are tested along with the motors. This testing is performed with an appropriate motor analyzer and includes insulation resistance, Polarization Index, and Step Voltage HiPot Testing. This testing is done on a representative population of station cables.
If the results of screening indicate problems with the cables, then an appropriate diagnostic cable test program is implemented. The diagnostic test methodology will be selected based upon the nature of the identified cable degradation. The diagnostic cable testing will be applied to all cables in the suspect population. Note that some of the Oyster Creek cables are unshielded and, as such, the testing methodologies identified in the GL (i.e., partial discharge, time domain reflectometry, dissipation factor, and very low frequency alternating current) would not be applicable.
In addition to the screening/diagnostic aspects of the Cable Condition Monitoring Program, Oyster Creek has made a commitment as part of license renewal to examine inaccessible Page 3 Cable Type Voltage Class Cable Manufacturer Date of Failure/
Years of Service Type of Service Root Cause 500 kcmil, 5kV/4160V Anaconda 1996/8 years EDG-2, Water intrusion Single, EPR, (second feed) underground UniShield
- conduit, energized continuously 250 kcmil, 5kV/4160V Anaconda 2007/14 years Dilution Not determined Single, EPR,
- Pumps, UniShield underground
- ducts, energized continuously
ATTACHMENT 3 90-Day Response to NRC Generic Letter 2007-01 for Oyster Creek Nuclear Generating Station medium voltage cables. The existing cable testing program will continue to be used to meet that commitment.
The Exelon Nuclear Cable Condition Monitoring Program does not monitor low voltage inaccessible cables for degradation. As evidenced by the station's failure history, there is no indication that there are issues associated with low voltage inaccessible power cables.
Oyster Creek has had 4160V cable failures due to various mechanisms. During early operations (i.e., 1970-1980), EDG cable failures occurred due to a specific lightning surge and some cable design defects. A large number of subsequent cable failures or problems were associated with water entering conduit and cable manufactured with voids or defects in the primary insulation. As a result of the EDG cable failures in the 1970s, a program to periodically test 5KV cables was instituted in 1977. The program used DC Step Voltage HiPot tests to determine the integrity and quality of the 5KV feeder cables and equipment. Later in the 1980s, DC testing was supplemented by AC power factor tests (i.e., Doble test) for specific cases where DC tests could damage connected equipment (e.g., liquid filled transformers). In recent years, Oyster Creek has tested, on a case-by-case basis, circuits using on-line partial discharge testing. Oyster Creek is in the process of implementing the use of on-line partial discharge testing as a primary means of periodically testing inaccessible medium voltage cables.
ATTACHMENT 4 90-Day Response to NRC Generic Letter 2007-01 for Peach Bottom Atomic Power Station On February 7, 2007, the NRC issued Generic Letter (GL) 2007-01, "Inaccessible or Underground Power Cable Failures that Disable Accident Mitigation Systems or Cause Plant Transients." The GL requested that all holders of operating licenses for nuclear power reactors submit a written response within 90 days in accordance with 10 CFR 50.54, "Conditions of licenses," paragraph (f). The 90-day response to the information requested by the NRC in GL 2007-01 is provided below for Peach Bottom Atomic Power Station.
NRC Request 1 Provide a history of inaccessible or underground power cable failures for all cables that are within the scope of 10 CFR 50.65 (the Maintenance Rule) and for all voltage levels. Indicate the type, manufacturer, date of failure, type of service, voltage class, years of service, and the root causes for the failure.
Response
A review has been completed to identify failures of inaccessible or underground power cables that are within the scope of 10 CFR 50.65, "Requirements for monitoring the effectiveness of maintenance at nuclear power plants." This review examined the plant corrective action program, Maintenance Rule or other databases, maintenance records, interviews with cognizant personnel, and a review of the circuit and raceway schedules to identify power cable failures.
The scope of the review included alternating current power distribution cables with voltages from 480 VAC to 33,000 VAC. This represents our best effort in that data of this nature was not necessarily recorded in a means that was conducive to identifying cable failures. The results of this review are provided below:
Cable Type Voltage Class Cable Manufacturer Date of Failure/
Years of Service Type of Service Root Cause Unknown 35kV/33kV Unknown 2001/7 years SBO 191-00 Fault current specs Line (remote from aerial line end),
hit bollard energized, adjacent to direct buried cable trench eroding insulation.
Failure occurred about 1 month later.
1000 kcmil, 5kV/4160kV 1997/24 years 38 Recirc Not determined AL, Single, Motor, wet,
- XLPE, normally Shielded energized, underground duct
ATTACHMENT 4 90-Day Response to NRC Generic Letter 2007-01 for Peach Bottom Atomic Power Station
'` The circuit and raceway schedules do not provide manufacturer information ; it would be necessary to pull original plant procurement information from the archives in an attempt to identify the manufacturer of these cables. Based upon discussions with cognizant personnel, the original plant medium voltage cable is most likely manufactured by Reynolds Metal.
NRC Request 2 Describe inspection, testing and monitoring programs to detect the degradation of inaccessible or underground power cables that support EDGs, offsite power, ESW, service water, component cooling water and other systems that are within the scope of 10 CFR 50.65 (the Maintenance Rule).
Response
Peach Bottom has had failures of medium voltage Cross Linked PolyEthylene (XLPE) cables in wet environments. The majority of these failures were in continuously energized cables. To mitigate future cable failures in wet environments, several susceptible medium voltage XLPE cables were replaced with either tree resistant XLPE or Ethylene Propylene Rubber (EPR)
Cable Voltage Cable Date of Failure)
Type of Root Type Class Manufacturer Years of Service Service Cause 1000 kcmil, 5kV/4.2kV Reynolds Metal 1991/18 years 2EA Treeing
- Single, Transformer,
- XLPE, wet, energized, Shielded underground duct
- Single, 15kW13.8 kV 1990/17 years 3A Condensate No formal
- XLPE, Pump, wet, analysis Shielded energized, performed underground duct XLPE, Other
- Unknown, 1989/16 years 3C Circulating No formal specs 15kW13.8 kV Water Pump, analysis
- unknown, or wet, energized, performed Shielded 15kV/4160kV underground duct 250 kcmil, 5kV/4160kV 1985/12 years A ESW Pump, No formal AL, Single, wet, normally analysis
- XLPE, de-energized, performed Shielded underground duct IIN~i~l~llllgllIIII IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIillllllllllllllllllllllllllllllllllllllll I
llllllllllillllllllllllllllllllllllllllllllll IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 750 kcmil, 5kV/4160kV 1992/19 years 3D HPSW Failed during
- Single, Pump, wet,
- test, XLPE, normally de-manufacturing Shielded energized, defect underground duct
ATTACHMENT 4 90-Day Response to NRC Generic Letter 2007-01 for Peach Bottom Atomic Power Station cables. Normally de-energized circuits, and certain low-risk continuously energized circuits, have retained the original XLPE cables.
The Exelon Nuclear Cable Condition Monitoring Program is controlled under procedure ER-AA-3003, "Cable Condition Monitoring Program," which was issued in January 2007. This program is consistent with industry practices and recommendations as provided in Nuclear Energy Institute (NEI) 06-05, "Medium Voltage Underground Cable White Paper," dated April 2006. The program consists of a two-phase approach to medium voltage cable testing.
The first phase of the program is referred to as screening, and takes advantage of motor testing that is typically performed from the switchgear. It should be noted that for Peach Bottom, station procedures currently limit this testing to insulation resistance measurement (i.e., megger, polarization index).
Peach Bottom's capability to perform motor testing from the switchgear is restricted due to a number of factors. The non-safety related motors supplied from the Unit Auxiliary buses are not subject to motor testing from the switchgear since the bus voltage is 13KV and the motors are supplied with 2.4/4 KV through intervening transformers. The inaccessible cables, in potentially wet environments, supplying medium voltage safety related motors are also excluded from Step Voltage Hi Pot testing from the switchgear since the majority of these cables are original XLPE.
The second phase of the program uses diagnostic test methodology, which is in the early stages of development at Peach Bottom to support License Renewal cable testing commitments.
Peach Bottom has a commitment under License Renewal to perform cable testing for a representative sample population of inaccessible medium voltage cables. The cables identified as representative include XLPE, tree resistant XLPE, and EPR cables. The testing will be completed in accordance with the timing set forth in the License Renewal commitment.
The Exelon Nuclear Cable Condition Monitoring Program does not monitor low voltage inaccessible cables for degradation. As evidenced by the station's failure history, there is no indication that there are issues associated with low voltage inaccessible power cables.
In addition, Peach Bottom has a commitment under License Renewal regarding low voltage cables with respect to exposure to external stressors. This commitment requires the identification of any adverse localized environment caused by heat or radiation in critical plant areas. Cables would then be inspected in these areas for visible degradation by the identified adverse environment. The inspections will be completed in accordance with the timing set forth in the License Renewal commitment.