Request for Additional Information (RAI) for the Nine Mile Point Nuclear Station, Unit 1 (NMP1) License Amendment Request (LAR) to Revise Technical Specification (TS) 4.1.1, Control Rod System
ML063400269
Person / Time
Site: Nine Mile Point 
Issue date: 12/07/2006
From: Colburn T
NRC/NRR/ADRO/DORL/LPLI-1
To: O'Connor T
Nine Mile Point
Colburn T, NRR/DORL/LPLI-1, 415-1402
References
TAC MD3360
Download: ML063400269 (4)


Text

December 7, 2006 Mr. Timothy J. OConnor Vice President Nine Mile Point Nine Mile Point Nuclear Station, LLC P.O. Box 63 Lycoming, NY 13093

SUBJECT:

REQUEST FOR ADDITIONAL INFORMATION (RAI) FOR THE NINE MILE POINT NUCLEAR STATION, UNIT NO. 1 (NMP1) LICENSE AMENDMENT REQUEST (LAR) TO REVISE TECHNICAL SPECIFICATION (TS) 4.1.1, CONTROL ROD SYSTEM (TAC NO. MD3360).

Dear Mr. OConnor:

The Nuclear Regulatory Commission (NRC) staff has reviewed your October 19, 2006, LAR for NMP1 to revise TS 4.1.1, Control Rod System, surveillance requirement. Based on our review, we have determined that we will need the additional information identified in the enclosure to this letter in order for the NRC staff to complete its review. As discussed with your staff, we request that you provide the requested information within 30 days of the date of this letter in order for the NRC staff to complete its review in accordance with your requested schedule.

If you have any questions, please contact me at 301-415-1402.

Sincerely,

/RA/

Timothy G. Colburn, Senior Project Manager Plant Licensing Branch I-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket No. 50-220

Enclosure:

RAI cc w/encl: See next page

ML063400269 *Input provided. No substantive changes made.

OFFICE LPLI-1\\PM LPLI-1\\LA SBWR\\BC LPLI-1\\BC NAME TColburn SLittle GCranston*

RLaufer DATE 12/07/06 12/07/06 12/01/2006 12/07/06

Enclosure REQUEST FOR ADDITIONAL INFORMATION NINE MILE POINT NUCLEAR STATION, UNIT NO. 1 (NMP1)

LICENSE AMENDMENT REQUEST (LAR)

REVISION TO TS 4.1.1, CONTROL ROD SYSTEM SURVEILLANCE REQUIREMENTS 1.0 Control Rod System (CRS) performance reliability In order to evaluate the request to scram time test at least 20 control rods every 180 days, past CRS scram function performance should be demonstrated to determine that the scram function reliability has not deteriorated. Therefore, please provide historical scram time data in terms of relevant test results for multiple operating cycles and a description of significant changes in hardware or testing practices that relate to the validity of the data for current plant operation.

2.0 Standard Technical Specification (STS) Surveillance Requirement (SR) 3.1.4.3 In the STSs, SR 3.1.4.3 states: Verify each affected control rod scram time is within the limits of Table 3.1.4-1 with any reactor steam dome pressure prior to declaring control rod operable after work on control rod or CRS that could affect scram time. The licensees October 19, 2006, LAR states that as a precedent, the proposed change to the STT [scram time testing]

SR is consistent with a similar change for Oyster Creek Generating Station (Amendment 249),

however, the Oyster Creek LAR included an SR change similar to STS SR 3.1.4.3. Please provide the basis for not proposing an SR similar to STS SR 3.1.4.3 in the proposed NMP1 LAR.

Nine Mile Point Nuclear Station, Unit No. 1 cc:

Mr. Michael J. Wallace President Nine Mile Point Nuclear Station, LLC c/o Constellation Energy Group 750 East Pratt Street Baltimore, MD 21202 Mr. Mike Heffley Senior Vice President and Chief Nuclear Officer Constellation Generation Group 1997 Annapolis Exchange Parkway Suite 500 Annapolis, MD 21401 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 126 Lycoming, NY 13093 Charles Donaldson, Esquire Assistant Attorney General New York Department of Law 120 Broadway New York, NY 10271 Mr. Paul D. Eddy Electric Division NYS Department of Public Service Agency Building 3 Empire State Plaza Albany, NY 12223 Mr. Peter R. Smith, President New York State Energy, Research, and Development Authority 17 Columbia Circle Albany, NY 12203-6399 Mark J. Wetterhahn, Esquire Winston & Strawn 1700 K Street, NW Washington, DC 20006 Supervisor Town of Scriba Route 8, Box 382 Oswego, NY 13126 Carey W. Fleming, Esquire Senior Counsel Constellation Generation Group, LLC 750 East Pratt Street, 17th Floor Baltimore, MD 21202