FILING INSTRUCTIONS FOR SONGS UNIT 3 SINGLE-SIDED Operating License & Technical Specification/Licensee Controlled Specification L06-008/01 0 Revise Unit 2 Operating License by removing pages and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and/or dates and contain marginal/lines indicating the areas of change.
Please direct any questions regarding filing of information to: (949)368-6772 or e-mail CDM Controlled Manuals Desk.
REMOVE:
INSERT:
LOS LCS BEHIND "List of Effective Pages" White Tab BEHIND "List of Effective Pages" White Tab Pages 1 through 5 9/07/06 Pages 1 through 5 11/07/06 BEHIND "3.8 Electrical Systems" Blue Tab BEHIND "3.8 Electrical Systems" Blue Tab Page 3.8-100-1 4/25/05 REV 9 Page 3.8-100-1 11/07/06 REV 10 Page 3.8-100-4 5/28/97 REV 1 Page 3.8-100-4 11/07/06 REV 2 Page 3.8-100-5 11/22/99 REV 1 Page 3.8-100-5 11/07/06 REV 2 Page 3.8-100-7 11/22/99 REV 1 Page 3.8-100-7 11/07/06 REV 2 BEHIND "5.0 Administrative Controls" Blue Tab BEHIND "5.0 Administrative Controls" Blue Tab Page 5.0-103-6 04/24/96 REV 0 Page 5.0-103-6 11/06/06 REV 1 Filing Instructions Reviewed & Approved:
Signature/NRA Date ci~10~ J\\iiY~i1 I
Signature/CDM Processor Date Page 1 of 1 AD?,-) (
SAN ONOFRE UNIT 3 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date LOEP-I LOEP-2 LOEP-3 LOEP-4 LOEP-5 i
ii iii iv v
2.0-100-1 2.0-100-2 2.0-100-3 2.0-100-4 2.0-100-5 2.0-100-6 2.0-100-7 2.0-100-8 2.0-100-9 2.0-100-10 2.0-100-11 2.0-100-12 2.0-100-13 2.0-100-14 2.0-100-15 2.0-100-16 2.0-100-17 2.0-100-18 3.0-1 3.0-la 3.0-2 3.0-3 3.0-4 3.0-5 3.0-6 3.1-100-1 3.1-100-2 3.1-100-3 3.1-101-1 3.1-101-2
- 3. 1-101-3
- 3. 1-101-4
- 3. 1-101-5
- 3. 1-102-1 3.1-102-2 3.1-102-3 3.1-103-1 3.1-103-2 11/07/06 04/25/05 09/07/06 11/07/06 11/06/06 09/07/06 09/07/06 09/07/06 06/27/00 09/07/06 05/25/00 04/24/96 05/25/00 04/24/96 03/29/99 03/29/99 03/29/99 03/29/99 03/29/99 03/29/99 05/12/00 05/12/00 05/12/00 03/29/99 03/29/99 03/29/99 03/29/99 o5/25/00 o5/25/00 05/25/00 03/14/02 03/14/02 03/14/02 03/14/02 03/14/02 11/12/98 05/13/97 05/13/97 05/25/00 04/24/96 04/16/99 04/16/99 05/25/00 02/12/99 02/12/99 02/12/99 11/12/98 04/24/96 Page No.
- 3. 1-103-3 3.1-104-1 3.1-104-2 3.1-104-3 3.1-104-4
- 3. 1-105-1 3.1-105-2 3.1-105-3 3.1-105-4 3.1-105-5 3.1-105-6 3.1-105-7 3.1-105-8 3.1-105-9 3.1-106-1 3.1-106-2 3.1-106-3 3.1-106-4 3.1-106-5 3.1-106-6 3.1-107-1 3.1-107-2 3.1-107-3 3.1-107-4 3.1-107-5 3.1-108-1 3.1-108-2 3.1-108-3 3.1-108-4 3.1-108-5 3.2-100-1 3.2-100-2 3.2-100-3 3.2-101-1 3.2-101-2 3.2-101-3 3.2-101-4 3.2-101-5 3.2-101-6 3.2-102-1 3.2-102-2 3.3-100-1 3.3-100-2 3.3-100-3 3.3-100-4 3.3-100-5 3.3-100-6 3.3-100-7 Page 1 of 5 Rev.
Date 04 /24/96 12/02/02 05 /04/99 05/04/99 11/18/99 04/16/99 07/29/96 04/16/99 04/16/99 06/12/97 06/12/97 07/29/96 07 /29/96 12/02/96 05/25/00 05/25/00 05/31/97 05/17/99 05/17/99 05/2 5/00 11/18/05 11/18/05 11/18/05 11/18/05 11/ 18/05 07/20/06 11/ 18/05 11/18/05 11/18/05 11/ 18/05 05/11/00 04/24/96 04/24/96 04/16/99 06/01/00 06 /22/98 04/16/99 06/12/97 06/12/97 04/16/99 04/16/99 01/28/05 08/01/96 08/01/96 01/28/05 12 /08/99 01/28/05 01/28/05 11/07/06
SAN ONOFRE UNIT 3 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date 3.3-101-1 3.3-101-2 3.3-101-3 3.3-102-1 3.3-102-2 3.3-102-2a 3.3-102-2b 3.3-102-3 3.3-102-4 3.3-102-5 3.3-102-6 3.3-102-7 3.3-102-8 3.3-102-8a 3.3-102-8b 3.3-102-9 3.3-102-10 3.3-102-11 3.3-103-1 3.3-103-2 3.3-103-3 3.3-104-1 3.3-104-2 3.3-104-3 3.3-104-4 3.3-104-5 3.3-105-1 3.3-105-2 3.3-105-3 3.3-106-1 3.3-106-2 3.3-106-3 3.3-106-4 3.3-106-5 3.3-106-6 3.3-106-7 3.3-106-8 3.3-106-9 3.3-106-10 3.3-107-1 3.3-107-2 3.3-107-3 3.3-108-1 3.3-108-2 3.3-108-3 3.3-108-4 3.3-108-5 3.3-108-6 08/02/02 10/22/96 05/25/00 04/19/04 04/19/04 04/19/04 04/19/04 04/24/96 01/05/01 01/05/01 01/05/01 11/13/03 04/19/04 04/19/04 04/19/04 01/05/01 01/05/01 01/05/01 05/25/00 04/24/96 05/25/00 05/25/00 05/25/00 12/14/00 01/29/99 05/25/00 05/25/00 04/24/96 05/25/00 06/07/01 04/23/01 03/29/99 03/29/99 o5/04/99 01/02/99 05/30/97 06/07/01 06/07/01 04/23/01 08/22/00 04/24/96 05/25/00 10/05/00 04/24/96 10/05/00 10/05/00 10/05/00 10/05/00 3.3-109-1 3.3-109-2 3.3-109-3 3.3-110-1 3.3-110-2 3.3-110-3 3.3-110-4 3.3-110-5 3.3-111-1 3.3-111-2 3.3-111-3 3.3-111-4 3.3-111-5 3.3-112-1 3.3-112-2 3.3-112-3 3.3-112-4 3.3-113-1 3.3-113-2
- 3. 3-113-3 3.3-113-4 3.3-113-5
- 3. 3-113-6 3.3-113-7 3.3-114-1 3.3-114-2 3.3-114-3 3.3-114-4 3.3-114-5 3.3-114-6 3.3-114-7 3.3-115-1 3.3-115-2 3.3-115-3 3.3-115-4 3.4-101-1 3.4-101-2 3.4-101-2a 3.4-101-3 3.4-101-4 3.4-101-5 3.4-101-6 3.4-101-7 3.4-101-8 3.4-101-9 3.4-102-1 3.4-102-2 3.4-102-3 Page 2 of 5 02/06/01 02/06/01 05/25/00 07/23/01 07/02/01 07/02/01 07/02/01 07 /23/01 02 /05/01 03/06/98 03/06/98 02/0501 02/05/01 07/17/01 07/17/01 07/17/01 07/17/01 10/27/03 03/19/03 03/19/03 10/27/03 10/27/03 03/19/003 10/27/03 10/27 /03 03/19/03 03/19/03 03/19/03 10/27/03 03/19/03 10/27/03 04/25/05 04/25/05 04/25/05 04/25/05 05/25/00 05/25/00 o5/25/00 04/24/96 04/28/97 07/12/99 07/12/99 07/12/99 05/25/00 07/12/99 02/11/03 05/25/00 01/21/98 04/25/05
SAN ONOFRE UNIT 3 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Paqe No.
Rev.
Date 3.4-102-4 3.4-103-1 3.4-103-2 3.4-103-3 3.4-103-4 3.4-103-5 3.4-103-6 3.4-103-7 3.4-103-8 3.4-106-1 3.4-106-2 3.4-106-3 3.4-107-1 3.4-107-2 3.4-107-3 3.4-112.1-i 3.4-112.1-2 3.4-112.1-3 3.4-112.2-1 3.4-112.2-2 3.4-112. 2-3 3.5-100-1 3.5-100-2 3.5-101-1 3.5-101-2 3.5-101-3 3.5-101-4 3.6-100-1 3.6-100-2 3.6-100-3 3.6-100-4 3.6-100-5 3.6-100-6 3.6-100-7 3.6-100-8 3.6-100-9 3.6-100-10 3.6-101-1 3.6-101-2 3.6-101-3 3.6-101-4 3.6-101-5 3.6-101-6 3.6-101-7 3.6-101-8 3.7-101-1 3.7-101-2 3.7-101-3 02/11/03 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 04/24/96 04/24/96 12/23/99 04/24/96 04/24/96 12/23/99 02/11/02 02/02/01 02/11/02 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 05/28/04 05/28/04 04/24/96 04/24/96 05/28/04 04/24/96 04/24/96 05/28/04 12/18/02 09/21/02 09/21/02 3.7-101-4 3.7-101-5 3.7-101-6 3.7-101-7 3.7-101-8 3.7-101-9 3.7-101-10 3.7-101-11 3.7-101-12 3.7-102-1
- 3. 7-102-2 3.7-102-3 3.7-102-4 3.7-102-5 3.7-102-6 3.7-102-7 3.7-103-1 3.7-103-2 3.7-103-3 3.7-103-4 3.7-103-5 3.7-103-6 3.7-103-7 3.7-103-8 3.7-104-1 3.7-104-2 3.7-104-3 3.7-104-4 3.7-104-5 3.7-105-1 3.7-105-2 3.7-105-3 3.7-105-4 3.7-105-5 3.7-105-6 3.7-105-7 3.7-105-8 3.7-105-9 3.7-105-10 3.7-105-11 3.7-105-12 3.7-105-13 3.7-105-14 3.7-105-15 3.7-105-16 3.7-105-17 3.7-105-18 3.7-105-19 Page 3 of 5 I
0 1
0 1
0 0
0 0
8 4
1 2
2 2
6 5
1 2
0 0
1 2
4 5
3 2
4 2
11 5
3 5
3 3
3 4
5 21 1
2 3
2 11 1
2 12/18/02 09/21/02 12/18/02 09/21/02 12/18/02 09/21/02 09/21/02 09 /21/02 091/2102 04/23 /01 04/23/01 11/21/97 05/24/00 11/21/97 11/21/97 04/2 3/01 02/28/01 05/2 5/00 07/29 /99 04/24/96 04/2 4/96 05/09 /97 08/20/98 02/28/01 07/16/04 05/25/00 07/16/04 07/16/04 07/16/04 07 /21/05 05/09/01 05/09/01 06/30/03 05/09/01 05/09/01 05/09/01 10/29/04 07/21/05 06/30/03 05/09/01 05 /09/01 06/30/03 06/30/03 05/09 /01 05/09/01 05/09/01 05/09/01 06/30/03 09/07/06
SAN ONOFRE UNIT 3 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date 3.7-105-20 3.7-105-21 3.7-105-22 3.7-105-23 3.7-106-1 3.7-106-2 3.7-106-3 3.7-106-4 3.7-106-5 3.7-106-6 3.7-106-7 3.7-106-8 3.7-106-9 3.7-106-10 3.7-107-1 3.7-107-2 3.7-107-3 3.7-107-4 3.7-108-1 3.7-108-2 3.7-108-3 3.7-108-4 3.7-108-5 3.7-108-6 3.7-108-7 3.7-108-8 3.7-108-9 3.7-108-10 3.7-109-1 3.7-109-2 3.7-109-3 3.7-110-1 3.7-110-2 3.7-110-3 3.7-111-1 3.7-111-2 3.7-111-3 3.7-112-1
- 3. 7-112-2
- 3. 7-112-3 3.7-113-1
- 3. 7-113-2
- 3. 7-113-3
- 3. 7-113-4
- 3. 7-113-5 3.7-113-6 3.7-113-7
- 3. 7-113-8 31 1
5 3
0 2
0 2
1 1
22 0
2 0
0 1
5 1
1 1
1 0
1 1
4 1
2 1
1 3
0 2I 0
1 1
0 1
19 4
5 10 3
3 3
2 06/30/03 05/09/01 05/09/01 07/21/05 02/19/04 12/18/98 02/19/04 12/18/98 10/28/02 10/28/02 10/28/02 10/28/02 10/28/02 10/28/02 05/25/00 04/24/96 04/24/96 05/25/00 06/28/02 10/04/00 10/19/98 10/19/98 11/27/96 04/24/96 06/28/02 05/09/97 06/28/02 10/04/00 05/2 5/00 07/29/99 05/25/00 05/23/01 04/24/96 02/28/01 05/25/00 04/24/96 05/25/00 05/25/00 04/24/96 05/25/00 09/20/05 06/27/00 05/16/01 09/20/05 05/16/01 07/30/03 11/13/03 03/28/05 3.7-113-9 3.7-113-10 3.7-113-11 3.7-113-12 3.7-113-13 3.7-113-14 3.7-113-15 3.7-113-16 3.7-113-17 3.7-113-18 3.7-113-19 3.7-113-20 3.7-113-21 3.7-113-22 3.7-113-23 3.7-113-24 3.7-113-25 3.7-113-26 3.7-114-1 3.7-114-2 3.7-114-3 3.7-115-1 3.7-115-2 3.7-115-3 3.7-116-1 3.7-116-2 3.7-117-1 3.7-117-2 3.7-118-1 3.7-118-2 3.8-100-1 3.8-100-2 3.8-100-3 3.8-100-4 3.8-100-5 3.8-100-6 3.8-100-7 3.8-100-8 3.8-100-9 3.8-100-10 3.8-100-11 3.8-100-12 3.8-100-13 3.8-100-14 3.8-100-15 3.8-100-16 3.8-100-17 3.8-100-18 Page 4 of 5 3
5 3
4 2
2 2
1 2
2 1
3 3
2 1
8 1
2 1
0 1
10 1
3 2
3 2
1 1
10 3
22 1
2 4
2 2
1 0
1 3
3 1
1 0
06//27/00 05/16/01 03/28/05 07/13/os 06/27/00.
06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 07/13/05 07/13/05 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 05/25/00 08/14/96 05/25/00 05/2 5/00 08/27/96 05/2 5/00 03/26/01 03/2 6/01 02/19/04 06/12/02 06/12/02 06/12/02 11/07/0 6 03 /28/05 03/06/01 11/07/06 11/07/06 05/2 8/
97 11/07/06 11/22/99 11/22//99 11/22/99 05/28/97 04/24/96 04/25/05 03/06/01 03/12/02 03/12/02 03/12/02 03/12/02 11/07/06
SAN ONOFRE UNIT 3 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
3.8-101-1 3.8-101-2 3.8-101-3 3.8-101-4 3.8-101-5 3.8-101-6 3.8-101-7 3.8-101-8 3.8-102-1 3.8-102-2 3.8-102-3 3.8-102-4 3.8-102-5 3.8-102-6 3.8-102-7 3.8-102-8 3.8-102-9 3.9-100-1 3.9-100-2 3.9-100-3 3.9-101-1 3.9-101-2 3.9-102-1 3.9-102-2 3.9-103-1 3.9-103-2 3.9-103-3 3.9-104-1 3.9-104-2 3.9-104-3 3.9-106-1 3.9-106-2 3.9-106-3 3.9-107-1 3.9-107-2 3.9-107-3 3.9-107-4 4.0-100-1 4.0-100-2 4.0-100-3 5.0-100-1 5.0-100-2 5.0-100-3 5.0-100-4
- 5. 0-101-1 5.0-103-1 5.0-103-2 5.0-103-3 Rev.
Date 05/27/05 05/27/05 04/24/96 04/24/96 04/24/96 05/28/97 04/24/96 05/25/00 01/03/00 01/03/00 01/03/00 01/03/00 01/03/00 01/03/00 01/'03 /00 01/03/00 01/03/00 11/18/05 11/18/05 11/18/05 05/25/00 05/25/00 05/25/00 05/25/00 o5/25/00 05/09/97 05/25/00 o5/25/00 05/25/00 05/25/00 o5/25/00 05/09/97 05/25/00 12/21/00 o5/25/00 12121/00 12/21/00 12/01/97 12/01/97 12/01/97 08/29/06 08/29/06 08/29/06 09/24/03 04/24/96 05/20/03 05/20/03 04/24/96 Paqe No.
5.0-103-4 5.0-103-5 5.0-103-6 5.0-104-1 5.0-104-2 5.0-105-1 5.0-105-2 5
01 1
1 2
2 Rev.
Date 02/28/01 04/24/96 11/06/06 02/14/97 02/14/97 03/21/06 03/21/06 Page 5 of 5 11/06/06
Containment Penetration Conductor Overcurrent Protective Devices LCS 3.8.100 3.8 ELECTRICAL POWER SYSTEMS LCS 3.8.100 Containment Penetration Conductor Overcurrent Protective Devices The Containment Penetration Conductor Overcurrent Protective Devices listed in Table 3.8.100-1 shall be OPERABLE.
VALIDITY STATEMENT:
Rev.
2 and 10 effective 11/07/06, to be implemented within 60 days APPLICABILITY:
MODES 1, 2, 3, and 4.
ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.
One or more of the A.1 Restore Protective 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> required containment Device to OPERABLE penetration conductor status.
overcurrent protective device(s) inoperable.
OR A.2.1 De-energize the 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> circuit(s) using the OPERABLE protective device(s) and declare the affected system or component inoperable.
AND A.2.2 Verify the OPERABLE Once per 7 days protective device is tripped or the inoperable protective device is removed or racked out.
(continued)
SAN ONOFRE--UNIT 3 3.8-100-1 Rev. 10 11/07/06 1
Containment Penetration Conductor Overcurrent Protective Devices LCS 3.8.100 Table 3.8.100-1 (ýaqe 2 of 11)
Containment Penetration Conductor Overcurrent Protective Devices Primary Device Number Backup Device Number Service Description 3BA11 3BA25 3BA26 3BA27 3BA28 3BA31 3BA32 3BA33 3BA36 3BA37 3BA38 3BA39 3BA40 3 BA41 3BA42 3BA43 3BA44 3BA45 3BA46 3BA47 3BA49 3BA50 3BA51 3BA55 3BLP0905 3BLP0910 3BLP0911 3BLP0912 3BLP0823 3BLP0913 3BLP0914 3BLP0915 3BLP0808 3BLP0809 3BLP0810 3BLP0901 3BLP0811 3BLP0817 3BLP0818 3BLP0819 3BLP0820 3BLP0902 3BLP0903 3BLP0807 3BLP0821 3BLP0822 3BLP0804 3BLP0805 Cont. Structure Electric Heater E-467 Cont. Cooling Unit E-393 Circ. Water Outlet HV-9940FB Cont. Cooling Unit E-394 Circ. Water Outlet HV-9940EB Cont.
Cooling Unit E-397 Circ. Water Outlet HV-9940DB Containment Sump Pump P-008 Cont. Cooling Unit E-393 Circ.
HV-9940FC Cont. Cooling Unit E-394 Circ.
HV-9940EC Cont.
Cooling Unit E-397 Circ.
HV-9940DC RCP 1A Oil Lift Pump 1A1 P-260 RCP 1B Oil Lift Pump 1BI P-264 Water Outlet Water Inlet Water Inlet RCP 2B Oil Lift Reactor Coolant RCP 2A Oil Lift Pump 2B1 P-262 Drain Pump (W) P-023 Pump 2AI P-266 RCP 1A Anti Rev.
Rotation Device Lube Pump
- I,P-399 RCP 2B Anti Rev.
Rotation Device Lube Pump
- 1,P-401 RCP 1B Anti Rev. Rotation Device Lube Pump
- 1,P-403 RCP 2A Anti Rev.
Rotation Device Lube Pump
- 1,P-405 Reactor Cavity Cooling Fan A-319 Standby Reactor Cavity Cooling Fan A-321 Charging Line to Reactor Cooling Loop 1A HV-9203 Reactor Cavity Cooling Unit C HV-9905C Reactor Cavity Cooling Unit A HV-9905A Quench Tank to Reactor Drain Tank HV-9101 RCP Bleed Off to Quench Tank HV-9216 (continued)
SAN ONOFRE--UNIT 3 3.8-100-4 Rev.
2 11/07/06
Containment Penetration Conductor Overcurrent Protective Devices LCS 3.8.100 Table 3.8.100-1 (page 3 of 11)
Containment Penetration Conductor Overcurrent Protective Devices Primary Device Backup Device Number Number Service Description 3BA57 3BLP0916 CEDM Cooling Unit E-403 CCW Outlet HV-9907AA 3BA58 3BLP0917 CEDM Cooling Unit E-403 CCW Inlet HV-9907AC 3BA59 3BLP0806 SI Tank to Reactor Drain Tank HV-9335 3BA60 3BLP0904 Welding Receptacles Containment (50 KVA) 3BA62 3BLP0824 Recept. for Portable Cont.
Sump Pump (H.P.)
P-005 3BA63 3BLP0906 Containment Elevator P-003 3BA65 3BLP0815 Lower Level Air Circulator A-031 3BA66 3BLP0816 Lower Level Air Circulator A-033 3BE09 3BLP1001 SI Tk Drain to Refueling Wtr. Tank HV-9334 3BEIO 3BLP1002 Sl Tk T-007 to Reactor Coolant Loop 1B HV-9350 3BE11 3BLP1003 Sl Tk T-009 to Reactor Coolant Loop 2A HV-9360 3BE17 3BLP1010 Auxiliary Spray to Pressurizer HV-g201 3BE21 3BLP1012 CCW Noncritical Cont. Inlet Isol.
Valve HV-6223 3BE25 3BLP1005 SDC Flow from Reac. Coolant Loop 2 HV-9337 3BE26 3BLP1015 Reac. Coolant Drain Tk Sample Cont. Isol.
HV-0516 3BE27 3BLP1016 Containment Isol. Reactor Coolant Drain to Radwaste System HV-7512 3BE30 3BLP1017 Quench Tank Vapor Sample Cont. Isol.
HV-0514 3BE31 3BLP1004 Containment Sump to Radwaste Sump HV-5803 3BE33 3BLP1021 Containment Purge Inlet HV-9949 3BE35 3BLP1018 Containment Emergency Sump Outlet HV-9305 3BE46 3BLP1011 CCW Noncritical Containment Isol. Valve HV-6236 3BJ05 3BLP1101 SDC Flow from Reac. Coolant Loop 2 HV-9339 3BJ06 3BLP1104 SI Tk T-008 to Reactor Coolant Loop 1A HV-9340 3BJ07 3BLP1105 SI Tk T-010 to Reactor Coolant Loop 2B HV-9370 3BJ17 3BLP1123 RCP Bleed off to Volume Control Tank HV-9217 (continued)
SAN ONOFRE--UNIT 3 3.8-100-5 Rev.
2 11/07/06
Containment Penetration Conductor Overcurrent Protective Devices LCS 3.8.100 Table 3.8.100-1 (page 5 of 11)
Contai~nment Penetration Conductor Overcurrent Protective Devices Primary Device Number Backup Device Number Service Description 3BN39 3BN40 3BN42 3BN43 3BN44 3BN45 3BN46 3BN47 3BN49 3BN52 3BN53 3BN54 3BN56 3BN57 3BN58 3BN59 3BN60 3BLP1215 3BLP1216 3BLP1305 3BLP1217 3BLP1306 3BLP1218 3BLP1308 3BLP1219 3BLP1319 3BLP1221 3BLP1222 3BLP1220 3BLP1310 3BLP1311 3BLP1312 3BLP1313 3BLP1314 3BLP1315 3BLP1223 3BLP1224 3BLP1225 3BLP1228 3BLP1202 RCP 1A Anti Rev.
Rotation Device Lube Pump
- 2,P-404 RCP 2A Anti Rev.
Rotation Device Lube Pump
- 2,P-406 Welding Recpt.
Cont.
(50KVA)
- 2RO05A, 2RO05B, 2R005C CEA Change Mechanism Transfer Machine Console (8 KVA)
L-023 Welding Recpt.
Cont.
(50KVA)
- 2RO07A, 2RO07B, 2R007C Refueling Pool End Junction Box (8KVA)
L-371 Welding Recpt. Cont.
(50KVA)
- 2RO13A, 2RO13B, 2R013C Recpt. for Portable Cont.
Sump Pump (lhp)
P-005 Equip. Hatch 200R, Elect. Hoist Z-028, Z-029 Lower Level Air Circulator A-032 Lower Level Air Circulator A-034 Containment Sump Pump P-007 Cont. Cooling Unit E-396 Circ. Water Outlet HV-9940BB Cont. Cooling Unit E-396 Circ. Water Inlet HV-9940BC Cont. Cooling Unit E-398 Circ. Water Outlet HV-9940CB Cont. Cooling Unit E-398 Circ. Water Inlet HV-9940CC CEDM Cooling Unit E-404 CCW Outlet HV-9907BA 3BN61 3BN62 (3BN62-A) 3BN62 (3BN62-B) 3BN62 (3BN62-C) 3BN62 (3BN62-H) 3BN62 (3BN62-G)
CEDM Cooling Unit E-404 CCW Inlet Cont. Recirculation Unit A-353 (Motor Enclosure Heater)
CEDM Cooling Supply Fan E-404A (Motor Enclosure Heater)
CEDM Cooling Supply Fan E-404B (Motor Enclosure Heater)
Cont. Normal Cooling Fan E-398 (Motor Enclosure Heater)
Cont. Normal Cooling Fan E-396 (Motor Enclosure Heater)
HV-9907BC (conti nued)
SAN ONOFRE--UNIT 3 3.8-100-7 Rev. 2 11/07/06
Procedures,
- Programs, and Manuals LCS 5.0.103 5.0.103.2.9 Not Used.
5.0.103.2.10 Pre-stressed Concrete Containment Tendon Surveillance Program This program provides controls for monitoring any tendon degradation in the pre-stressed concrete containment, including effectiveness of its corrosion protection medium, to ensure containment structural integrity.
The program shall include baseline measurements taken prior to initial operations.
The Tendon Surveillance Program, inspection frequencies, and acceptance criteria shall be in accordance with Regulatory Guide 1.35, Revision 3, 1979; and Proposed Regulatory Guide 1.35.1, April 1979.
The content and frequency of written reports shall be in accordance with LCS 5.0.104.2, "Special Reports."
The provisions of Technical Specification Surveillance Requirement 3.0.2 and Technical Specification Surveillance Requirement 3.0.3 are applicable to the Tendon Surveillance Program inspection frequencies.
SAN ONOFRE--UNIT 3 5.0-103-6 Rev.
1 11/06/06 I
FILING INSTRUCTIONS FOR SONGS UNIT 2 SINGLE-SIDED Operating License & Technical Specification/Licensee Controlled Specification L06-008 Revise Unit 2 Operating License by removing pages and inserting the enclosed pages. The revised pages are identified by the captioned amendment number and/or dates and contain marginal/lines indicating the areas of change.
Please direct any questions regarding filing of information to: (949)368-6772 or e-mail CDM Controlled Manuals Desk.
REMOVE:
INSERT:
LCS LCS BEHIND "List of Effective Pages" White Tab BEHIND "List of Effective Pages" White Tab Pages 1 through 5 9/07/06 Pages 1 through 5 11/6/06 BEHIND: "Administrative Controls"-Blue Tab BEHIND: "Administrative Controls" -Blue Tab Page 5.0-103-6 4/24/96 REV 0 Page 5.0-103-6 11/06/06 REV 1 Filing Instructions Reviewed & Approved:
Signature/NRA Date Signature/CDM Processor Page 1of 1
SAN ONOFRE UNIT 2 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date LOEP-1 LOEP-2 LOEP-3 LOEP-4 LOEP-5 ii iii iv v
2.0-100-1 2.0-100-2 2.0-100-3 2.0-100-4 2.0-100-5 2.0-100-6 2.0-100-7 2.0-100-8 2.0-100-9 2.0-100-10 2.0-100-11 2.0-100-12 2.0-100-13 2.0-100-14 2.0-100-15 2.0-100-16 2.0-100-17 2.0-100-18 3.0-1
- 3. 0'-1 a 3.0-2 3.0-3 3.0-4 3.0-5 3.0-6 3.1-100-1 3.1-100-2 3.1-100-3 3.1-101-1 3.1-101-2 3.1-101-3 3.1-101-4 3.1-101-5 3.1-102-1 3.1-102-2 3.1-102-3 3.1-103-1 3.1-103-2 11/06/06 04/20/06 09/07/06 09/20/05 11/06/06 09/07/06 09/07/06 09/07/06 06/27/00 09/07/06 05/25/00 04/24/96 05/2 5/00 04/24/96 03/29/99 03/29/99 03/29/99 03/29/99 03/29/99 03/29/99 05/12/00 05/12/00 05/12/00 03/29/99 03/29/99 03/29/99 03/29/99 05/2 5/00 05/25/00 05/2 5/00 03/14/02 03/14/02 03/14/02 03/14/02 03/14/02 11/12/98 05/13/97 01/15/97 05/2 5/00 04/24/96 04/16/99 04/16/99 05/2 5/00 02/12/99 02/12/99 02/12/99 11/12/98 04/24/96 3.1-103-3 3.1-104-1 3.1-104-2 3.1-104-3 3.1-104-4 3.1-105-1 3.1-105-2 3.1-105-3 3.1-105-4 3.1-105-5 3.1-105-6 3.1-105-7 3.1-105-8 3.1-105-9 3.1-106-1 3.1-106-2 3.1-106-3 3.1-106-4 3.1-106-5 3.1-106-6 3.1-107-1 3.1-107-2 3.1-107-3 3.1-107-4 3.1-107-5 3.1-108-1 3.1-108-2 3.. 1.-108-3 3.1-108-4 3.1-108-5 3.2-100-1 3.2-100-2 3.2-100-3 3.2-101-1
.3.2-101-2 3.2-101-3 3.2-101-4 3.2-101-5 3.2-101-6 3.2-102-1 3.2-102-2 3.3-100-1 3.3-100-2 3.3-100-3 3.3-100-4 3.3-100-5 3.3-100-6 3.3-100-7 Page 1 of 5 04/24/96 12/02/02 02/12/99 02/12/99 11/18/99 11/12/98 07/29/96 02/19/97 02/19/97 02/19/97 02/19/97 07 /29/96 07 /29/96 12/02/96 05/25/00 05/25/00 05/31/97 05/17/99 05/17/99 05/25/00 11/18/05 11/18/05 11/18/05 11/18/05 11/18/05 07/20/06 11/18/05 11/18/05 11/18/05 11/18/05 02/15/06 04/24/96 04/24/96 02/19/99 02/19/99 06/22/98 02/19/99 02/19/97 02/19/97 04/16/99 04/16/99 01/28/05 08/01/96 04/24/96 01/28/05 12/08/99 01/28/05 01/28/05 11/06/06
SAN ONOFRE UNIT 2 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date 3.3-101-1 3.3-101-2 3.3-101-3 3.3-102-1 3.3-102-2
- 3. 3-102-2a
- 3. 3-102-2b 3.3-102-3 3.3-102-4 3.3-102-5 3.3-102-6 3.3-102-7 3.3-102-8 3.3-102-8a 3.3-102-8b 3.3-102-9 3.3-102-10 3.3-102-11 3.3-103-1 3.3-103-2 3.3-103-3 3.3-104-1 3.3-104-2 3.3-104-3 3.3-104-4 3.3-104-5 3.3-105-1 3.3-105-2 3.3-105-3 3.3-106-1 3.3-106-2 3.3-106-3 3.3-106-4 3.3-106-5 3.3-106-6 3.3-106-7 3.3-106-8 3.3-106-9 3.3-106-10 3.3-107-1 3.3-107-2 3.3-107-3 3.3-108-1 3.3-108-2 3.3-108-3 3.3-108-4 3.3-108-5 3.3-108-6 08/02/02 10/22/96 05/25/00 04/19/04 04/19/04 04/19/04 04/19/04 04/24/96 01/0 5/01 01/05/01 01/05 /01 01/05/01 04/19/04 04/19/04 04/19/04 01/05 /01 01/05/01 01/0 5/01 05/25/00 04/24/96 05/25/00 05/25/00 05/25/00 12/14/00 01/29/99 05/25/00 05/25/00 04/24/96 05/25/00 06/07/01 04/23/01 03/29/99 03/29/99 05/30/97 05/30/97 05/30/97 06/07/01 06/07/01 04/23/01 08/22/00 04/24/96 05/25/00 10/05/00 04/24/96 10/05/00 10/05/00 10/05/00 10/05/00 3.3-109-1 3.3-109-2 3.3-109-3 3.3-110-1 3.3-110-2 3.3-110-3 3.3-110-4 3.3-110-5 3.3-111-1
- 3. 3-111-2 3.3-111-3 3.3-111-4 3.3-111-5 3.3-112-1 3.3-112-2 3.3-112-3 3.3-112-4 3.3-113-1 3.3-113-2 3.3-113-3 3.3-113-4 3.3-113-5 3.3-113-6 3.3-113-7 3.3-114-1 3.3-114-2 3.3-114-3 3.3-114-4 3.3-114-5 3.3-114-6 3.3-114-7
- 3. 3-115-1
- 3. 3-115-2
- 3. 3-115-3 3.3-115-4 3.4-101-1 3.4-101-2 3.4-101-2a 3.4-101-3 3.4-101-4 3.4-101-5 3.4-101-6 3.4-101-7 3.4-101-8 3.4-101-9 3.4-102-1 3.4-102-2 3.4-102-3 Page 2 of 5 04/20/06 04/20/06 04/20/06 07/23/01 07/02/01 07/02/01 07/02/01 07/23/01 02/05/01 03/06/98 03/06/98 02/05/01 02/05/01 07/17/01 07/17/01 07/17/01 07/17/01 10/27/03 03/19/03 03/19/03 10/27/03 10/27/03 03/19/03 10/27/03 10/27/03 03/19/03 03/19/03 03/19/03 10/27/03 03/19/03 10/27/03 04/25/05 04/25/05 04/25/05 04/25/05 05/25/00 05/25/00 05/25/00 04/24/96 04/28/97 07/12/99 07/12/99 07/12 /99 05/2 5/00 07/12/99 02/11/03 05/2 5/00 01/21/98 04/20/06
SAN ONOFRE UNIT 2 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date 3.4-102-4 3.4-103-1 3.4-103-2 3.4-103-3 3.4-103-4 3.4-103-5 3.4-103-6 3.4-103-7 3.4-103-8 3.4-106-1 3.4-106-2 3.4-106-3 3.4-107-1 3.4-107-2 3.4-107-3 3.4-112.1-1 3.4-112.1-2 3.4-112.1-3 3.4-112.2-1 3.4-112.2-2 3.4-112.2-3 3.5-100-1 3.5-100-2 3.5-101-1 3.5-101-2 3.5-101-3 3.5-101-4 3.6-100-1 3.6-100-2 3.6-100-3 3.6-100-4 3.6-100-5 3.6-100-6
.3.6-100-7 3.6-100-8 3.6-100-9 3.6-100-10 3.6-101-1 3.6-101-2 3.6-101-3 3.6-101-4 3.6-101-5 3.6-101-6 3.6-101-7 3.6-101-8 3.7-101-1 3.7-101-2 3.7-101-3 02/11/03 09/07/06 09/07/06 09/07/06 09/07/06
.09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 09/07/06 04/24/ 96 04/24/96 12/23/99 04/24/96 04/24/96 12/23/99 02/11/02 02/02/01 02/11/02 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 02/02/01 02/23/04 02/23/04 04/24/96 12/27/96 02/23/04 04/24/96 04/24/96 02/23/04 12/18/02 09/21/02 09/21/02 3.7-101-4 3.7-101-5 3.7-101-6 3.7-101-7 3.7-101-8 3.7-101-9 3.7-101-10 3.7-101-11 3.7-101-12 3.7-102-1 3.7-102-2 3.7-102-3 3.7-102-4 3.7-102-5 3.7-102-6 3.7-102-7 3.7-103-1 3.7-103-2 3.7-103-3 3.7-103-4 3.7-103-5 3.7-103-6 3.7-103-7 3.7-103-8 3.7-104-1 3.7-104-2 3.7-104-3 3.7-104-4 3.7-104-5 3.7-105-1 3.7-105-2 3.7-105-3 3.7-105-4 3.7-105-5 3.7-105-6 3.7-105-7 3.7-105-8 3.7-105-9 3.7-105-10 3.7-105-11 3.77105-12 3.7-105-13 3.7-105-14 3.7-105-15 3.7-105-16 3.7-105-17 3.7-105-18 3.7-105-19 Page 3 of 5 1
0 1
0 1
0 0
0 0
8 41 1
3 2
6 6
2 2
0 0
1 2
4 5
3 2
4 2
11 5
3 5
3 3
3 4
5 21 1
2 3
2 11 1
2 12/18/02 09/21/02 12/18/02 09/21/02 12/18/02 09/21/02 09 /21/02 09 /21/02 09/21/02 04/23/01 04/23/01 11/21/97 11/21/97 05/24/00 11/21/97 04/23 /01 02/19/04 02/19/04 07/29/99 04/2 4/96 04/24/96 05/09/97 08/20/98 02 /28/01 07/16/04 05/25/00 07/16/04 07/16/04 07/16/ 04 07/2 1/05 05/09/01 05/09/01 06/30/03 05/09 /01 05/09/01 05/09 /01 10/29/04 07 /21/05 06 /30/03 05/09/01 05/09/01 06/30/03 06/30/03 05/09/01 05/09/01 05 /09/01 05/09/01 06/30/03 09/07/06
SAN ONOFRE UNIT 2 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
Rev.
Date Page No.
Rev.
Date 3.7-105-20 3.7-105-21 3.7-105-22 3.7-105-23 3.7-106-1 3.7-106-2 3.7-106-3 3.7-106-4 3.7-106-5 3.7-106-6 3.7-106-7 3.7-106-8 3.7-106-9 3.7-106-10 3.7-107-1 3.7-107-2 3.7-107-3 3.7-107-4 3.7-108-1 3.7-108-2 3.7-108-3 3.7-108-4 3.7-108-5 3.7-108-6
- 3. 7-108-7
- 3. 7-108-8 3.7-108-9 3.7-108-10 3.7-109-1 3.7-109-2 3.7-109-3 3.7-110-1 3.7-110-2
- 3. 7-110-3
- 3. 7-111-1 3.7-111-2 3.7-111-3 3.7-112-1
- 3. 7-112-2 3.7-112-3 3.7-113-1 3.7-113-2 3.7-113-3 3.7-113-4 3.7-113-5 3.7-113.-6 3.7-113-7 3.7-113-8 31 1
5 2
0 1
0 11 1
22 0
2 0
0 1
5 1
I 1
1 3
0 1
1 4
12 1
4 10 30 2
1 01 1
0 1
19 4
5 10 3
2 3
2 06/30/03 05/09/01 05/09/01 07/21/05 10/28/02 12/18/98 05/25/00 12/18/98 10/28/02 10/28/02 10/28/02 10/28/02 10/28/02 10/28/02 05/25/00 04/24/96 04/24/96 05/25/00 06/28/02 10/04/00 10/19/98 10/19/98 11/27/96 04/24/96 06/28/02 05/09/97 06/28/02 10/04/00 o5/25/00 07/29/99 o5/25/00 05/23/01 04/24/96 02/28/01 o5/25/00 04/24/96
.o5/25/00 o5/25/00 04/24/96 05/25/00 09/20/05 06/27/00 05/16/01 09/20/05 05/16/01 06/27/00 11/13/03 03/28/05 3.7-113-9
- 3. 7-113-10 3.7-113-11 3.7-113-12 3.7-113-13 3.7-113-14 3.7-113-15 3.7-113-16 3.7-113-17 3.7-113-18 3.7-113-19 3.7-113-20 3.7-113-21 3.7-113-22 3.7-113-23 3.7-113-24 3.7-113-25 3.7-113-26 3.7-114-1 3.7-114-2 3.7-114-3 3.7-115-1 3.7-115-2 3.7-115-3 3.7-116-1 3.7-116-2 3.7-117-1 3.7-117-2 3.7-118-1 3.7-118-2 3.8-100-1 3.8-100-2 3.8-100-3 3.8-100-4 3.8-100-5 3.8-100-6 3.8-100-7 3.8-100-8.
3.8-100-9 3.8-100-10 3.8-100-11 3.8-100-12 3.8-100-13 3.8-100-14 3.8-100-15 3.8-100-16 3.8-100-17 3.8-100-18 Page 4 of 5 06/27/00 05/16/01 03/2 8/05 07/13/05 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 07/13/05 07/13/05 06/27/00 06/27/00 06/27/00 06/27/00 06/27/00 05/25/00 08/14/96 05/25/00 05/2 5/00 08/27/96 05/25/00 03/26/01 03/26/01 06/12/02 06/12/02 06/12/02 06/12/02 04/25/05 03/28/05 03/06/01 05/28/97 11/22/99 05/28/97 11/22/99 11/22/99 11/22 /99 11/22/99 05/28/97 05/28/97 04/25 /05 03/06/01 03/12/02 03/12/02 03/112/02 03/12/02 09/20/05
SAN ONOFRE UNIT 2 LICENSEE CONTROLLED SPECIFICATIONS LIST OF EFFECTIVE PAGES Page No.
3.8-101-1 3.8-101-2 3.8-101-3 3.8-101-4 3.8-101-5 3.8-101-6 3.8-101-7 3.8-101-8 3.8-102-1 3.8-102-2 3.8-102-3 3.8-102-4 3.8-102-5 3.8-102-6 3.8-102-7 3.8-102-8 3.8-102-9 3.9-100-1 3.9-100-2 3.9-100-3
- 3. 9-101-1 3.9-101-2 3.9-102-1 3.,9-102-2 3.9-103-1 3.9-103-2 3.9-103-3 3.9-104-1 3.9-104-2 3.9-104-3 3.9-106-1 3.9-106-2 3.9-106-3 3.9-107-1 3.9-107-2 3.9-107-3 3.9-107-4 4.0-100-1 4.0-100-2 4.0-100-3 5.0-100-1 5.0-100-2 5.0-100-3 5.0-100-4 5.0-101-1 5.0-103-1 5.0-103-2 5.0-103-3 Rev.
Date 05/27/05 05/27/05 04/24/96 04/24/96 04/24/96 05 /28/97 05/28/97 05/25/00 0 1/03/00 01/03/00 01/03/,00 0 1/03/00 01/03/00 01/03/00 0 1/03/00 0 1/03/00 0 1/03/00 11/18/05 11/18/05 11/18/05 05/25/00 05/25/00 05 /25/00 05/25/00 05 /25/00 05 /09/97 05/25/00 05/25/00 05/25/00 05/25/00 05/25/00 04/24/96 05/25/00 12 21/00 05/25/00 12/21/00 12/21/00 12/01/97 12 /01/97 12/01/97 08/29/06 08/29/06 08/29/06 09/24/03 04/24/96 05/20/03 05/20/03 04/24/96 Page No.
5.0-103-4 5.0-103-5 5.0-103-6 5.0-104-1 5.0-104-2 5.0-105-1 5.0-105-2 Rev.
Date 5
0 1
1 2
2 02/28/01 04/24/96 11/06/06 02/14/97 02/14/97 03/21/06 03/21/06 Page5 of 5 11/06/06
Procedures,
- Programs, and Manuals LCS 5.0.103 5.0.103.2.9 Not Used.
5.0.103.2.10 Pre-stressed Concrete Containment Tendon Surveillance Program This program provides controls for monitoring any tendon degradation in the pre-stressed concrete containment, including effectiveness of its corrosion protection medium, to ensure containment structural integrity.
The program shall include baseline measurements taken prior to initial operations.
The Tendon Surveillance Program, inspection frequencies, and acceptance criteria shall be in accordance with Regulatory Guide 1.35, Revision 3, 1979; and Proposed Regulatory Guide 1.35.1, April 1979.
The content and frequency of written reports shall be in accordance with LCS 5.0.104.2, "Special Reports."
The provisions of Technical Specification Surveillance Requirement 3.0.2 and Technical Specification Surveillance Requirement 3.0.3 are applicable to the Tendon Surveillance Program inspection frequencies.
SAN ONOFRE--UNIT 2 5.0-103-6 Rev. 1 11/06/06 1