Technical Specification, 2.0 Safety Limits
ML063170083
Person / Time
Site: Dresden Constellation icon.png
Issue date: 11/07/2006
From: John Honcharik
NRC/NRR/ADRO/DORL/LPLIII-2
To: Crane C
Exelon Generation Co
Williams J, NRR/DLPM/LPD1, 415-1470
Shared Package
ml062990294 List:
References
TAC MD2706
Download: ML063170083 (1)


Text

SLs 2.0 2.0 SAFETY LIMITS (SLs) 2.1 SLs 2.1.1 Reactor Core SLs 2.1.1.1 With the reactor steam dome pressure < 785 psig or core flow < 10% rated core flow:

THERMAL POWER shall be s 25% RTP.

2.1.1.2 With the reactor steam dome pressure Ž 785 psig and core flow Ž 10% rated core flow:

For Unit 2 two recirculation loop operation, MCPR shall be Ž 1.11, or for single recirculation loop operation, MCPR shall be Ž 1.12.

For Unit 3 two recirculation loop operation, MCPR shall be Ž 1.12, or for single recirculation loop operation, MCPR shall be R te1.14. I 2.1.1.3 Reactor vessel water level shall be greater than the top of. active irradiated fuel.

2.1.2 Reactor Coolant System Pressure SL Reactor steam dome pressure shall be : 1345 psig.

2.2 SL Violations With any SL violation, the following actions shall be completed within

.2 hour2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />s:

2.2.1 Restore compliance with all SLs; and 2.2.2 Insert all insertable control rods.

Dresden 2 and 3 2.0-1 Amendment No. 199/213