Jý,amsNoggleý-Tigge values atIPEC Page1 From:

"Adl (, Joseph J." <jO/1er@entergy.com>

To:

<j71 @nrc.gov>, <jdn @ nrc.gov>

Date:

05/18/2006 1:20:46 PM

Subject:

Trigger values at IPEC John /Jim:

Trigger values for our monitoring well / REMP water sampling program are as follows:

MW-38 o

5000 pCi/L H-3 o

3 pCi/L Sr-90 MW-40, MW-48 and MW-51 o

2000 pCi/L H-3 o

2 pCi/L Sr-90 The H-3 trigger values are based on 25% and 10% of the drinking water criteria. The basis for the Sr-90 trigger value are also 25% and 10% of the drinking water criteria, plus an allowance for background in drinking water based on EPA RADNET data for NYS at the 95th PC (-0.4 pCi/L), and then raised to the next highest whole number.

If you have any questions or would like to discuss them please call me at 914 734 6606 Jay Adler CC:

"Hinrichs, Gary H" <ghinric@entergy.com>