ML062340366
| ML062340366 | |
| Person / Time | |
|---|---|
| Site: | Byron (NPF-037) |
| Issue date: | 08/17/2006 |
| From: | Condra D Oak Ridge Institute for Science & Education |
| To: | Jamnes Cameron NRC/RGN-III/DNMS/DB |
| References | |
| FOIA/PA-2010-0209, IR-06-004, RFTA 06-001 | |
| Download: ML062340366 (4) | |
Text
OAK RIDGE INSTITUTE FOR SCIENCE AND EDUCATION August 17,2006 Mr. James Cameron US. Nuclear Regulatory Commission Region 111 2443 Warrenvdle Road Lisle, IL 60532-4351 SUBJECI:
ANALYTICAL RESULTS FOR THREE WATER SAMPLES IN BATCH SIX FROM THE VICINITY OF THE BYRON GENERATING STATION, BYRON, ILLINOIS
[INSPECTION REPORT NO. 050-00454/2006-0041 (RFTANO.06-001)
Dear Mr. Cameron:
The Oak Ridge Institute for Science and Education (ORISE) received Batch Six, consistiig of three water samples on August 2,2006 that were collected in the vicinityof the Byron Generating Station in Byon, Illinois. The samples were analyzed for tritium to a minimum detectable concentration of 180 p W L using a liquid scintillation analpr. The chain-of-custodyidentified one watersample to be analyzed by gamma spectroscopy (GS). The sample identifications and collection data are presented in Table 1. The GS data are presented in Table 2. The tritium data are presented in Table 3. The pertinent procedure references are provided in the specific tables.
ORISEs Quality Control (QCJ requirements were met for these analrses. The Qc files are available for p u r review upon request.
My contact information is listed below. You m y also contact Wade Ivcy at 865.576.9 184 with any questions or comments.
Sincerely, Dale Condra, Manager Laboratory RDC:WI:ess Enclosures c:
B. Watson, NMSS/DWMEP/DD/SP 7E18 E. Ahelquist, ORISE E. Knox-Davin, NRC/NMSS/TWFN 8A23 File 1689 S. Kirk, ORISE Distribution approval and concurrence :
Technical Management Team Member
@ality Manager 1 Initials Voice: 865.241.3242 Fax: 865.241.3248 E-mail: CondraD@orau.gov RECEIVED AUE 2 2 2006
TABLE 1 ORISE Sample ID 1689W0080 SAMPLE IDENTIFICATIONS AND COLLECTION DATA BYRON GENERATING STATION BYRON, ILLINOIS NRC Region 111 Collection Collection Sample ID Date Time BY-06-6-01 7/20/06 09:20 1689W0081 I BY-06-6-02 I
7/20/06 1
09:40 1689W0082 I BY-06-6-03 I 7/20/06 I 10:21 Byron Generating Scarion projecdl689 Data Tahler/2006-08-17 Data Tables Barch S k
TABLE 2 NRC Region I11 ORISE Sample ID Sample ID I
CONCENTRATIONS OF SELECTED GAMMA EMITTING RADIONUCLIDES IN A SELECTED WATER SAMPLE BY GAMMA SPECTROSCOPY CPl, REVISION 15 BYRON GENERATING STATION BYRON, ILLINOIS Radionuclide Concentrationsa (pCi/L)
CO-58 Co-60 I Cs-134 [
(3-137 1689W0082 BY-06-6-03 I 1.5 6.2h I 3.2 f 5.2 I 4.0 5.71 -3.3 f 8.6 Byon Genenrlng Starion projrcd1689 Data Tahler/200~08-17 Dara Tahlrr Batch Six
TABLE 3 ORISE NRC Region 111 Sample ID Sample ID 1689W0080 BY-06-6-01 1689W0081 BY-06-6-02 1689W0082 BY-06-6-03 CONCENTRATIONS OF TRITIUM IN WATER SAMPLES BY LIQUID SCINTILLATION ANALYSIS AP2, REVISION 15; -4, REVISION 3 BYRON GENERATING STATION BYRON, ILLINOIS Tritium Concentdons, TPUs, and MDCs" (pCi/L) 590 f
12Oh (180) 380 120 (180) 3,120 f
200 (180)
Bymn Gcneraifflg Scarion projccr/1689 Dara Tablrr/ZGGb08-17 Dara Tahlrr Batch SLY