August 18, 2006 Mr. Timothy S. Rausch Site Vice President

AmerGen Energy Company, LLC

P.O. Box 388

Forked River, NJ 08731-0388

SUBJECT:

SAFETY EVALUATION REPORT WITH OPEN ITEMS RELATED TO THE LICENSE RENEWAL OF OYSTER CREEK GENERATING STATION

Dear Mr. Rausch:

By letter dated July 22, 2005, AmerGen Energy Com pany, LLC (AmerGen or the applicant) submitted an application to the U.S. Nuclear Regulatory Commission (NRC or the staff) for the

renewal of the Oyster Creek Generating Station (OCGS) operating license for up to an

additional 20 years. The license renewal application (LRA) was submitted pursuant to

Title 10 of the Code of Federal Regulations Part 54, "Requirements for Renewal of Operating Licenses for Nuclear Power Plants." The NRC staff determined that the LRA was complete and

acceptable for docketing on September 9, 2005.

The NRC staff has reviewed the AmerGen LRA and has developed the enclosed "Safety Evaluation Report with Open Items related to the License Renewal of the Oyster Creek

Generating Station" hereinafter referred to as the Safety Evaluation Report (SER). This SER

reflects the status of the staff's review of the LRA, requests for additional information (RAIs), the

applicant's responses to the NRC staff's RAIs and other questions related to the LRA through

July 10, 2006, unless otherwise noted. Issuance of the enclosed SER is an important milestone

for both the applicant and the staff.

The NRC staff has identified open items in its review that must be resolved before it can make a final determination on the application. The open items are summarized in Section 1.5 of the

SER. In order to resolve these items, the staff has requested additional information, as

identified in the SER.

In accordance with the schedule for completing the review of the OCGS LRA, the applicant is requested to review the enclosed SER, verify its accuracy, provide comments to the NRC staff

and your responses to the requests for additional information on open items, by

October 20, 2006. The NRC staff plans to review the current content and format of the SER for

further improvement while incorporating the applicant's comments. A complete and revised

SER will then be issued by December 1, 2006.

T. Rausch 2 The staff is committed to completing the review of the OCGS SER in a timely manner. If you have any questions regarding this matter, please contact the license renewal project manager, Donnie J. Ashley, at 301-415-3191 or e-mail DJA1@nrc.gov

.Sincerely,/RA/Frank P. Gillespie, Director Division of License Renewal

Office of Nuclear Reactor Regulation Docket No. 50-219

Enclosure:

Safety Evaluation Report cc w/encl: See next page

Pkg - ML062300332; Ltr. - ML062280337; SER - ML062300330OFFICEPM:DLR:RLRALA:DLR:RLRABC:DLR:RLRAOGCTech EditorNAMEDAshleyYEdmondsLLundMYoungHChang DATE7 /19/06 7/19/ 067/21/ 067/27/067/27/06 OFFICEBC:DLR:RLRCD:DCID:DED:DRAD:DSS NAMEKChangJGrobe (WBateman for)MMayfield (EImbro for)JLyonsTMartinDATE8/01/068/15/ 068/14/068 /15/ 068 /14/ 06OFFICED:DLR NAMEFGillespie DATE8/18/06

Oyster Creek Nuclear Generating Station cc: Site Vice President - Oyster Creek Nuclear Generating Station

AmerGen Energy Company, LLC

P.O. Box 388

Forked River, NJ 08731 Senior Vice President of Operations

AmerGen Energy Company, LLC

200 Exelon Way, KSA 3-N

Kennett Square, PA 19348 Kathryn M. Sutton, Esquire Morgan, Lewis, & Bockius LLP

1111 Pennsylvania Avenue, NW

Washington, DC 20004 Kent Tosch, Chief New Jersey Department of

Environmental Protection

Bureau of Nuclear Engineering

CN 415 Trenton, NJ 08625 Vice President - Licensing and Regulatory Affairs

AmerGen Energy Company, LLC

4300 Winfield Road

Warrenville, IL 60555 Regional Administrator, Region I U.S. Nuclear Regulatory Commission

475 Allendale Road

King of Prussia, PA 19406-1415 Mayor of Lacey Township 818 West Lacey Road

Forked River, NJ 08731 Senior Resident Inspector U.S. Nuclear Regulatory Commission

P.O. Box 445

Forked River, NJ 08731 Director - Licensing and Regulatory Affairs AmerGen Energy Company, LLC

Correspondence Control

P.O. Box 160

Kennett Square, PA 19348 Manager Licensing - Oyster Creek Exelon Generation Company, LLC

Correspondence Control

P.O. Box 160

Kennett Square, PA 19348 Regulatory Assurance Manager Oyster Creek

AmerGen Energy Company, LLC

P.O. Box 388

Forked River, NJ 08731 Assistant General Counsel AmerGen Energy Company, LLC

200 Exelon Way

Kennett Square, PA 19348 Ron Bellamy, Region I U.S. Nuclear Regulatory Commission

475 Allendale Road

King of Prussia, PA 19406-1415 Correspondence Control Desk AmerGen Energy Company, LLC

200 Exelon Way, KSA 1--1

Kennett Square, PA 19348 Oyster Creek Nuclear Generating Station Plant Manager

AmerGen Energy Company, LLC

P.O. Box 388

Forked River, NJ 08731 License Renewal Manager Exelon Generation Company, LLC

200 Exelon Way, Suite 230

Kennett Square, PA 19348 Oyster Creek Nuclear Generating Station cc:

Mr. James Ross Nuclear Energy Institute

1776 I Street, NW, Suite 400

Washington, DC 20006-3708 Mr. Michael P. Gallagher Vice President License Renewal

Exelon Generation Company, LLC

200 Exelon Way, Suite 230

Kennett Square, PA 19348 Mr. Christopher M. Crane President and Chief Nuclear Officer

AmerGen Energy Company, LLC

4300 Winfield Road

Warrenville, IL 60555 Mr. Richard Webster Rutgers Environmental Law Clinic

123 Washington Street

Newark, NJ 07102-5695 Ltr. to T. A. Rausch from F. Gillespie dated: August 18, 2006

SUBJECT:

SAFETY EVALUATION REPORT WITH OPEN ITEMS RELATED TO THE LICENSE RENEWAL OF OYSTER CREEK NUCLEAR GENERATING STATIONAdams Accession No.:

ML062280337 HARD COPY DLR R/F DISTRIBUTION

JFair RWeisman AMurphy RPettis GGalletti DShum GBagchi SSmith (srs3)

SDuraiswamy

YL (Renee) Li

RidsNrrDlr

RidsNrrDlrRlra

RidsNrrDlrRlrb

RidsNrrDe RidsNrrDci

RidsNrreEemb

RidsNrrDeEeeb

RidsNrrDeEqva

RidsNrrDss

RidsNrrDnrl

RidsOgcMailCenter

RidsNrrAdes

DLR Staff


VRodriguez

DAshley RLaufer GMiller RBellamy, RI

RCureton, RI

JLilliendahl, RI

MModes, RI MSykes, RI

AHodgdon RidsOpaMail

RidsNrrDorl