ML062200297
| ML062200297 | |
| Person / Time | |
|---|---|
| Site: | Byron |
| Issue date: | 08/03/2006 |
| From: | Condra D Oak Ridge Institute for Science & Education |
| To: | Snell W NRC/RGN-III/DNMS/DB |
| References | |
| FOIA/PA-2010-0209, RFTA 06-001 IR-06-004 | |
| Download: ML062200297 (4) | |
Text
OAK RlDDE INSTITUTE FOR SCIENCE AND EDUCATION August 3,2006 Mr. William hell U S Nuclear Regulatory Commission Region 111 2443 Warrenville Road Lisle, IL 60532-4351
SUBJECT:
ANALYTICAL RESULTS FOR SIX WATER SAMPLES IN BATCH FIVE FROM THE VICINITY OF THE BYRON GENERATING STATION, BYRON, ILLINOIS
[INSPECTION REPORT NO. 050-00454/2006-0041 (RFTA NO.06-001)
Dear Mr. Snek The Oak Ridge Institute for Science and Education (ORISE) received Batch Five, consisting of SIX water samples on July 17,2006 that were collected in the vicinity of the Byron Generating Station in Byron, Illinois. The samples were analyzed for tritium to a minimum detectable concentration of 180 pCi/L using a liquid scintillation analyzer. The chain-of-custody identified one water sample to be analyzed by gamma spectroscopy (GS). 'l'he sample identifications and collection data are presented in Table 1. The GS data are presented in Table
- 2. The tritium data are presented in Table 3. The pertinent procedure references are provided in the specific tables.
ORISE's Quality Control (QC) requirements were met for these analyses. 'l'he QC files are available for your review upon request.
My contact information is listed below. You may also contact Wade Ivey at 865.576.9184 with any questions or comments.
Sincerely, Dale Condra, Manager Laboratory RDC:WPI:db Enclosures C:
B. Watson, NMSS/DWMEP/DD/SP 7E18 E. Abelquist, ORISE E. Knox-Davin, NRC/NMSS/TWFN 8A23 G. Bonano, NRC Region 111 S. IGrk, ORISE File 1689
~~
Distribution approval and concurrence :
Techmcal hlanagement Team Member 1x52 A
Quality Manager A T P I Initials,
Voice: 865.241.3242 Fax: 865.241.3248
&mall: CondraD@orau.gov RECEfVED AUG 0 8 2006
TABLE 1 ORISE Sample NRC Region 111 Collection ID Sample ID Date 1689W0074 BY-06-5-01 7/13/06 1689W0075 BY-06-5-02 7/13/06 Collection Time 855 AM 9:14 AM 1689W0076 BY-06-5-03 7/13/06 9:25 AM 1689W0077 BY-06-5-04 7/13/06 9:40 AM 1689W0078 BY-06-5-05 7/13/06 9:53 AM 1689WOO79 BY-06-5-06 7/13/06 10:09 AM Byron Generating Station projecVl689 Data Tablesl2006-08-03 Data Tables Bash Five
TABLE 2 ORISE Sample ID 1689W0078 NRC Region I11 Radionuclide Concentrations (pCi/L)
Sample ID CO-58 CO-60 cs-134 Cs-137 BY-06-5-05 0.2 t 2.$
1.6 k 3.1 0.0 2 3.3 -0.2 i 2.9 Byron Generating Station project11689 Data Tabled2006-08-03 Data Tables Balch Five
TABLE 3 ORISE Sample NRC Region 111 Tritium Concentrations, TPUs, ID Sample ID and MDCs' @Ci/L) 1689W0074 BY-06-5-01 60 loob (180) 1689W0075 BY-06-5-02 20 t
100 (180) 1689W0076 BY-06-5-03 60
?
100 (1 80) 1689W0077 BY-06-5-04 60 i-100 (180) 1689W0078 BY-06-5-05 50 t
100 (1 80) 1689W0079 BY-06-5-06 20 100 (1 80)
Byron Generating Station projectil689 Data Tablesl2006-08-03 Data Tables Batch Five