Constellation Energy" P.O. Box 63 Lycoming, NY 13093 0 Nine Mile Point Nuclear Station June 19, 2006 U. S. Nuclear Regulatory Commission Washington, DC 20555-0001 ATTENTION:
Document Control Desk
SUBJECT:
Nine Mile Point Nuclear Station Unit No. 1; Docket No. 50-220 Special Report: Channel #11 of the Containment Hydrogen Monitoring System Inoperable for Unplanned Maintenance In accordance with Action 4.a of Nine Mile Point Unit I Technical Specification Table 3.6.11-2, "Accident Monitoring Instrumentation Action Statements," Nine Mile Point Nuclear Station, LLC, is submitting the following Special Report concerning inoperability of Channel #11 of the Containment Hydrogen Monitoring (CHM) System.
Description of Event On June 4, 2006, at 0021 hours2.430556e-4 days <br />0.00583 hours <br />3.472222e-5 weeks <br />7.9905e-6 months <br />, operators declared Channel #11 of the CHM System inoperable due to low sample flow.
Cause of Jnoperabilitv Channel #11 of the CHM System was declared inoperable due to low sample flow.
Troubleshooting determined that the cause of low sample flow was a malfunctioning return sample flow switch. Normal sample flows were not impacted and oxygen and hydrogen indications were available in the Control Room, therefore Channel #11 of the CHM System was able to perform its finction as designed.
Channel #12 of the CHM System was verified to be operable prior to removing Channel #11 from service.
Actions Taken The malfunctioning sample flow switch was replaced, post maintenance testing was performed satisfactorily and Channel # I1 of the CHM System was restored to operable status on June 8, 2006, at 1316 hours0.0152 days <br />0.366 hours <br />0.00218 weeks <br />5.00738e-4 months <br />.
Should you have any questions regarding this submittal, please contact M. H. Miller, Licensing Director, at (315) 349-1510.
Document Control Desk June 19, 2006 Page 2 Jpames A. Hutton Plant General Manager JAH/RF/sac cc: