OAK RlDQE INSTITUTE FOR SCIENCE AND EDUCATION May 3,2006 Mi-. William Snell U.S. Nuclear Regulatory Commission Rcgmn I11 2443 Warrenvllle Road Lisle, IL 60532-4351

SUBJECT:

ANALYTICAL RESULTS FOR FIVE WATER SAMPLES, BATCH ONE, FROM THE VICINITY OF PERRY STATION, PERRY, ILLINOIS

[INSPECTION REPORT NO. 050-00440/441/2006-0031 (RETA NO.06-001)

Dear MI. Snell:

The Oak Ridge Institute for Science and Education (ORISE) received five water samples, Batch One, on April 26,2006 whch were collected in the vicinity of Perry Station in Perry, Illinois. The five water samples were analyzed for ttitium using a liquid scintillation analyzer. The chain of custody identified one water sample to be analyzed by gamma spectroscopy (GS). The sample identifications and collection data are presented in Table 1. The GS data are presented in Table 2. The tritium data are presented in Table 3. The pertinent procedure references are provided in the specific tables.

ORISE's Quality Control (QC) requirements were met for these analyses. The QC files are available for your review upon request.

My contact information is listed below. You may also contact Wade Ivey at 865.576.9184 with any questions or comments.

Sincerely, Dale Condra, Manager Laboratory RDC:WPI:ar Enclosure C:

T. McLaughlin, NRC/NMSS/TWFN 7F27 E, Abelquist, ORISE S. Kirk, ORISE File 1702 E. Knox-Davin, NRCINMSSITWFN 8A23 G. Bonano, NRC Region I11 Distribution approval and concurrence :

Technical Management Team Member I

S ! C -

Quality Manager 1 9 1 Initials,

Voice: 865.241.3242 Fax: 865.241.3248 E-mail: CondraD@orau.gov RECEIVED MAY 1 5 2086

TABLE 1 ORISE Sample ID I'my station NRC Region 111 Collection Collection Sample ID Time Date SAMPLE IDENTIFICATIONS AND COLLECTION DATA PERRY STATION PERRY, ILLINOIS 1702W0001 1702W0002 P-06-1-01 03/30/2006 3:50 PM P-06-1-02 04/03/2006 9:10 AM 1702W0003 1702W0004 1702W0005 P-06-1-03 04/20/2006 N D P ~

P-06-1-04 04/20/2006 10:40 AM P-06-1-05 04/20/2006 5:22 PM projccts/l702/l>ata 'lsblcs/ZOllh~ilS-U9 I>aa'l'ablus Hatch Onc

TABLE 2 Radionuclide Concentrations" @Ci/L)

ORISE NRC Region 111 Sample ID Sample ID CO-58 CO-60 cs-134 cs-137 1702W0005 P-06-1-05

-2.5 ? 4.2' 0.8 ? 4.3 -1.5 k 4.8 0.2 :k 4.1 I'rrry station

TABLE 3 ORISE Sample ID 1702W0001 1702W0002 1702W0003 1702W0004 1702W0005 NRC Region 111 Tritium Concentrations, TPUs, Sample ID and MDCS" (pCi/L)

P-06-1-01 140 2

llOb (1 80)

P-06-1-02 51,800 1,400 (180)

P-06-1-03 380

?

120 (1 80)

P-06-1-05 150

?

110 (180)

P-06-1-04 37,400

  • 1,000 (200)

'hlDCs arc in parmthcsis.

"Unccrtaiuntier rcprcscnt thc 95% confidenrr level, based on total propagated unccrtsinhrs.

Perry Station projects/l702/lhta 'l'ablcr/2006-05-09 I)afa 'Tables Batch On<