PLA-6046, Revision to Technical Specification Surveillance Requirements 3.8.4.7 and SR 3.8.4.8
| ML061080583 | |
| Person / Time | |
|---|---|
| Site: | Susquehanna |
| Issue date: | 04/07/2006 |
| From: | Mckinney B Susquehanna |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| PLA-6046 | |
| Download: ML061080583 (10) | |
Text
Britt T. McKlnney Sr. Vice President & Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Boulevard Berwick, PA 18603 Tel. 570.542.3149 Fax 570.542.1504 btmckinney@pplweb.com PP TM APR 0 7 2006 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop OP1-17 Washington, DC 20555-0001 SUSQUEHANNA STEAM ELECTRIC STATION PROPOSED AMENDMENT NO. 286 TO LICENSE NPF-14 &
PROPOSED AMENDMENT NO. 254 TO LICENSE NPF-22:
REVISION TO TECHNICAL SPECIFICATION SURVEILLANCE REQUIREMENTS 3.8.4.7 & SR 3.8.4.8 PLA-6 046 Docket Nos. 50-387 and 388 Referen ce:
PLA-6014, G. T. Jones (PPL) to Document Control Desk (USNRC),
"Proposed Amendment No. 286 to License NPF-14 and Proposed Amendment No. 254 To License NPF-22:
Revision to Techinical Specification Surveillance Requirements 3.8.4.7 & SR 3.8.4.8," dated Febnrary 28, 2006.
The purpose of this letter is to revise the amendment request proposed in Reference 1.
The amendment request proposed clarifications to the Technical Specification Surveillance Requirements 3.8.4.7 and 3.8.4.8. This revision is based on the teleconference held on April 5, 2006 between NRC and PPL Susquehanna, LLC.
The revision makes a change to the proposed Surveillance Requirement (SR) wording, as such; new TS markups are provided in Attachment 1. The revised wording has no impact on implementation of the Technical Specification requirements as originally proposed.
Corresponding Technical Specification Bases wording is provided in Attachment 2 for your information.
PPL has reviewed the "No Significant Hazards Consideration" and the "Environmental Consideration" submitted with Reference 1 relative to this supplemental information.
We have determined that there are no changes required to either of these documents.
74 OD (
Document Control De~k PLA-6046 Any questions regarding this request should be directed to Mr. Michael H. Crowthers at (610) 774-7766.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on:
Britt T. McKinney : Revised Proposed Technical Specification Markups : Revised Technical Specification Bases Changes (Markups provided for information) cc:
NRC Region I Mr. A. J. Blarney, NRC Sr. Resident Inspector Mr. R. V. Guzman, NRC Project Manager Mr. R. Janati, DEP/BRP
E to PLA-6046 Revised Proposed Technical Specification Changes (Markups)
E
PPL. Rev.}F DC Sources-Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.4.6 Verify each required battery charger supplies its 24 months associated batteries at the following rates for 2 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />s:
- a. 2 100 amps for the 125V Battery at 2 127.8V
- b. Ž 300 amps for the 250V Battery at 2 255.6V
- c. Ž 200 amps for the 125V Diesel Generator E Battery at 2 127.8V SR 3.8.4.7
NOTES---------------------------------
- 1. The modified performance discharge test in SR 3.8.4.8 may be performed in lieu of the service test in SR 3.8.4.7 once per 60 months.
- 2. This Surveillance shall not be Performed in Mode 1, 2, or 7-------------------------------------------__
Verify battery capacity is adequate to supply, and maintain 24 months in OPERABLE status, the required emergency loads for the design duty cycle when subjected to a battery service test.
5 e.-
(continued)
SU'SQUEHANNA - UNIT 1
-1'/3.8-26 Amendme~nt J5
PPL. Rev./,
DC Sources-Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
T SURVEILLANCE FREQUENCY SR 3.8.4.8 I---------__________________
This Surveillance shall not be Performed in Mode 1, 2, or,.
Verify battery capacity is 2 80% of the manufacturer's rating when subjected to a performance discharge test or a modified performance discharge test.
60 months AND 12 months when battery shows degradation or has reached 85%vo of expected service life with capacity
< 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected service life with capacity 2 100% of manufacturer's rating SUSQUEHANNA - UNIT 1 75/3.8-27 AmendME~nt J,;
PPL. Rev.,
81 DC Sources-Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.4.7 KIAtCrr-r lvi)---------------------
J I t------------------______-
- 1. The modified performance discharge test in SR 3.8.4.8 may be performed in lieu of the service test in SR 3.8.4.7 once per 60 months.
- 2. This Surveillance shall not be Performed in MODE 1, 2or
(/
Verify battery capacity is adequate to supply, and maintain in OPERABLE status, the required emergency loads for the design duty cycle when subjected to a battery service test.
24 months (continued)
SU'SQUEHANNA - UNIT 2 5 / 3.8-30 AmendmentX)8
WW PPI Rev.,W DC Sources-Operating 3.8.4 SURVEILLANCE REQUIREMENTS (continued)
SURVEILLANCE FREQUENCY SR 3.8.4.8
NOTE----------------------------
This Surveillance shall not be Performed in MODE 1, 2, or 3.
Verify battery capacity is 2 80% of the manufacturer's rating when subjected to a performance discharge test or a modified performance discharge test.
SC I 60 months AND 12 months when battery shows degradation or has reached 85% of expected service life with capacity
< 100% of manufacturer's rating AND 24 months when battery has reached 85% of the expected service life with capacity 2 100% of manufacturer's rating (continued)
SU',QUEHANNA - UNIT 2 rS / 3.8-31 Amendment.iW
Insert except for the Diesel Generator E DC electrical power subsystem. This Surveillance can be performed on the Diesel Generator E DC electrical power subsystem when the Diesel Generator E is not aligned to the Class IE distribution system.
ft
E to PLA-6046 Revised Technical Specification Bases Changes (Markups provided for information)
E
TS Bases insert Since the Diesel Generator E DC electrical power subsystem does not support loads other than the Diesel Generator E required loads, the mode restriction note need not be applied to the Diesel Generator E subsystem unless it is aligned to the class lE distribution subsystem. The note does have applicability to the Diesel Generator E subsystem when the Diesel Generator E is substituted for one of the other Diesel Generators. When the Diesel Generator E is aligned to the class lE distribution subsystem, the Diesel Generator E subsystem is required to support operability of the Diesel Generator E. Thus when in this configuration, the note does need to be applicable since performing the Surveillance would remove a required DC electrical power subsystem from service.