April 21, 2006 MEMORANDUM TO: David Terao, Chief Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation FROM:
Mel B. Fields, Senior Project Manager
/RA/
Plant Licensing Branch IV Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation
SUBJECT:
WATERFORD STEAM ELECTRIC STATION, UNIT 3 -
SUMMARY
OF MEETING HELD ON APRIL 6, 2006, RE: EMERGENCY DIESEL GENERATOR FUEL OIL STORAGE PROJECT On April 6, 2006, Entergy Operations, Inc. (Entergy), the licensee for Waterford Steam Electric Station, Unit 3, met with the Nuclear Regulatory Commission (NRC) staff at NRC Headquarters in Rockville, Maryland. The purpose of the meeting was to discuss Entergy<s plans for fulfilling a regulatory commitment made during the extended power uprate review process, which was to improve the onsite fuel oil storage capability for the emergency diesel generators.
Entergy presented a design concept that would involve installation of two new 20,000 gallon non-safety storage tanks, which would increase the existing fuel oil storage capability to assure 7 days of diesel generator operation at full rated capacity, with a margin for testing. The new tanks and additional piping would be located underground and designed to withstand design basis hurricane and flood conditions. However, the new tanks and additional piping would not be designed to Seismic Category 1 requirements. The NRC staff indicated that its expectations were that the new tanks would be designed to the same seismic requirements as the existing fuel oil storage tanks. Entergy indicated that it would evaluate the options available and inform the staff of its intended course of action as soon as practical.
A list of attendees is provided as an enclosure to this memorandum. There were no members of the public represented at the meeting. The slides used during the meeting by Entergy are available in the Agencywide Documents Access and Management System under Accession Number ML061010333.
Docket No. 50-382
Enclosure:
As stated cc w/encl: See next page
ML061080082 NRC-001 OFFICE NRR/LPL4/PM NRR/LPL4/LA NRR/LPL4/BC NAME MFields;mxr4 DJohnson DTerao DATE 4/21/06 04/20/2006 04/21/2006
ENCLOSURE APRIL 6, 2006 MEETING WITH ENTERGY OPERATIONS, INC.
WATERFORD STEAM ELECTRIC STATION, UNIT 3 EMERGENCY DIESEL GENERATOR FUEL OIL STORAGE PROJECT LIST OF ATTENDEES Entergy Operations, Inc.
Bill Eaton Gary Payne Tom Tankersley Jerry Burford Dana Millar U. S. Nuclear Regulatory Commission David Solorio David Terao Rebecca Karas James Tatum Mark Hartzman Angelo Stubbs Thomas Cheng Mel Fields
Waterford Steam Electric Station, Unit 3 cc:
Mr. Michael E. Henry, State Liaison Officer Department of Environmental Quality Permits Division P.O. Box 4313 Baton Rouge, Louisiana 70821-4313 Vice President Operations Support Entergy Operations, Inc.
P. O. Box 31995 Jackson, MS 39286-1995 Director Nuclear Safety Assurance Entergy Operations, Inc.
17265 River Road Killona, LA 70066-0751 Wise, Carter, Child & Caraway P. O. Box 651 Jackson, MS 39205 General Manager Plant Operations Waterford 3 SES Entergy Operations, Inc.
17265 River Road Killona, LA 70066-0751 Licensing Manager Entergy Operations, Inc.
17265 River Road Killona, LA 70066-0751 Winston & Strawn 1700 K Street, N.W.
Washington, DC 20006-3817 Resident Inspector/Waterford NPS P. O. Box 822 Killona, LA 70066-0751 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011 Parish President Council St. Charles Parish P. O. Box 302 Hahnville, LA 70057 Executive Vice President
& Chief Operating Officer Entergy Operations, Inc.
P. O. Box 31995 Jackson, MS 39286-1995 Chairman Louisiana Public Services Commission P. O. Box 91154 Baton Rouge, LA 70825-1697 Mr. Joseph E. Venable Vice President Operations Entergy Operations, Inc.