Tennessee Valley Authority, Post Office Box 2000, Soddy-Daisy. Tennessee 37384-2000 March 27, 2006 Ms. Pamala Myers Permit Section Tennessee Department of Environment & Conservation Division of Water Pollution Control 6th Floor, L & C Annex 401 Church Street Nashville, Tennessee 37243-1534
Dear Ms. Myers:
SEQUOYAH NUCLEAR PLANT (SQN) - NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) PERMIT NO. TN0026450 - ADDITION OF MSW-101 TO THE BIOCIDE/CORROSION TREATMENT PLAN Sequoyah Nuclear Plant (SQN) plans to add MSW-101 to our Biocide/Corrosion Treatment Plan. This addition is considered a minor change by SQN due to the fact that MSW-101 is similar to the already approved PCL-222. All relevant information (frequency of discharge, active ingredients, discharge concentration, maximum daily usage, MSDS, product bulletin, etc.) on MSW-101 is attached. SQN considers this a courtesy notification which does not require pre-approval and will submit this information again in the 2007 annual report.
If you need additional information or have comments or questions, please contact Ann Hurt (423-843-6714) or myself (423-843-6700).
I certify under penalty of law that this document and all of its attachments were prepared under my direction or my supervisor in accordance with a system designed to assure qualified personnel properly gathered and evaluated the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violations.
Sincerely, 0ftLL W
- c. _
Stephanie A. Howard Principal Environmental Engineer Signatory Authority for J. Randy Douet Site Vice President Sequoyah Nuclear Plant e0c) 1 Premd Mn reCCW Pm
Enclosures cc (Enclosures):
Mr. Edward M. Polk, Jr., P.E.
Manager, Permit Section Tennessee Department of Environment & Conservation Division of Water Pollution Control 6th Floor, L & C Annex 401 Church Street Nashville, Tennessee 37243-1534 Nuclear Regulatory Commission ATTN: Document Control Desk
. Washington, D.C. 20555 Chattanooga Environmental Assistance Center Division of Water Pollution Control State Office Building, Suite 550 540 McCallie Avenue Chattanooga, Tennessee 37402-2013
Raw Water Chemical Additives at Sequoyah Nuclear Plant PRODUCT PURPOSE FREQUENCY ACTIVE INGREDIENTS REPRESENTATIVE AQUATIC TOXICITY DISCHARGE OF
/DESCRWPTO R CONCENTRATION' DISCHARGE (ppm active ingredients)
(ppm active ingredients)
MSW-1012 Dispersant to Continuous Orthophosphate, Pimeplhales promelas
< 0.2 facilitate iron Hexametaphosphate 7-day NOEC Growth = 625 mg/L corrosion 7-day LOEC Growtl = 1,250 mg/L inhibition Ceriodaplinia dubia 7-day NOEC Reproduction = 313 ing/L 7-day LOEC Reproduction = 625 mg/L 1.
2.
The maximum discharge concentration is indicated EXCEPT where noted. Discharge concentrations are achieved through dilution.
Toxicity of MS W-101 assumed to be similar to PCL-222. No actual toxicity data available for this product. Tests will be conducted at a toxicity lab under contract to the manufacturer.
Raw Water Chemical Application Guide' Product Injection Points Max Feed In Plant Frequency of Average Duration EstimatedMax Maximum Daily (ppm)
Target Application of Application.
Days per Year Usage (lbs/day)2 MSW-101 ERCW Train A & B and RCW 2.4 2.4 Dailv 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> per day 365 2280
- 1.
Concentrations and usage are expressed for the active ingredient(s) shown in the previous table of this plan.
- 2.
Maximum Daily Usage provides an indication of loading in the receiving stream. It is the maximum amount of active ingredients for the worst case scenario of flow and feed concentration being proposed plus a 10% margin of error. SQN will request a change to this plan should an increase in maximum daily usage becomes necessary for the continued safe operation of the plant.
- 3.
MSW-101 is a blend of orthophosphate and hexametaphospliate. MSW-101 is injected into the RCW system continuously, except during periods of other chemical injection due to common injection lines. MSW-101 is injected into the ERCW Train A & B system only during warmi weather months. During cool weather months PCL-401 is injected.
Calculations Showing Worst Case Scenario (final values rounded to the nearest 5 Ibs)
MSW-l01 2.4 mgI lb 71,800 gal 3.785 L 60 min 24 hr 1.10
= 2280 lbs/day MSWV-101 2.4 ppm active 454,000 mg min gal I hr day 3/27/2006 SQN Biocide/Corrosion Treatment Plan l
TN0026450 RATIONALE for Raw Water Chemical Additives SQN IVMSW-1 01 A dispersant commonly used in water treatment programs. MSW-101 is a phosphate dispersant used to minimize fouling and under-deposit corrosion in the ERCW and RCW systems. This product makes carbon piping corrosion inhibitors more effective. MSW-101 is not considered hazardous per OSHA regulations.
Document Summary Material Safety Data Sheet.
MSW-101 MSDS m
Product Bulletin MSW-101 PB 3/27/2006 SQN Biocide/Corrosion Treatment Plan Rationale 2
- NALCO' MATERIAL SAFETY DATA SHEET PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC
- 1.
I CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NAME:
MSW-101 APPLICATION:
WATER TREATMENT COMPANY IDENTIFICATION:
Nalco Company 1601 W. Diehl Road Naperville, Illinois 60563-1198 EMERGENCY TELEPHONE NUMBER(S):
(800) 424-9300 (24 Hours)
CHEMTREC NFPA704M/HMIS RATING HEALTH:
0/1 FLAMMABILITY:
0/0 INSTABILITY:
0/0 OTHER:
0 = Insignificant I = Slight 2 = Moderate 3 = High 4 = Extreme
- 2.
I COMPOSITION/INFORMATION ON INGREDIENTS Based on our hazard evaluation, none of the substances in this product are hazardous.
- 3.
HAZARDS IDENTIFICATION
"*EMERGENCY OVERVIEW**
CAUTION May cause irritation with prolonged contact.
Do not get in eyes, on skin, on clothing. Do not take internally. Use with adequate ventilation. In case of contact with eyes, rinse immediately with plenty of water and seek medical advice. After contact with skin, wash immediately with plenty of water.
Wear suitable protective clothing.
May evolve oxides of phosphorus (POx) under fire conditions.
PRIMARY ROUTES OF EXPOSURE:
Eye, Skin HUMAN HEALTH HAZARDS -ACUTE:
EYE CONTACT:
No adverse effects expected.
SKIN CONTACT:
No adverse effects expected.
INGESTION:
Not a likely route of exposure. No adverse effects expected.
Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 1/8
MATERIAL SAFETY DATA SHEET PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC INHALATION:
Not a likely route of exposure. No adverse effects expected.
SYMPTOMS OF EXPOSURE:
Acute:
A review of available data does not identify any symptoms from exposure not previously mentioned.
Chronic:
A review of available data does not identify any symptoms from exposure not previously mentioned.
AGGRAVATION OF EXISTING CONDITIONS:
A review of available data does not identify any worsening of existing conditions.-
- 4.
J FIRST AID MEASURES EYE CONTACT:
Flush affected area with water. If symptoms develop, seek medical advice.
SKIN CONTACT:
Flush affected area with water. If symptoms develop, seek medical advice.
INGESTION:
Do not induce vomiting without medical advice. If conscious, washout mouth and give water to drink. If symptoms develop, seek medical advice.
INHALATION:
Remove to fresh air, treat symptomatically. If symptoms develop, seek medical advice.
NOTE TO PHYSICIAN:
Based on the individual reactions of the patient, the physician's judgement should be used to control symptoms and clinical condition.
- 5.
FIRE FIGHTING MEASURES FLASH POINT:
None EXTINGUISHING MEDIA:
This product would not be expected to burn unless all the water is boiled away. The remaining organics may be ignitable. Keep containers cool by spraying with water. Use extinguishing media appropriate for surrounding fire.
FIRE AND EXPLOSION HAZARD:
May evolve oxides of phosphorus (POx) under fire conditions.
SPECIAL PROTECTIVE EQUIPMENT FOR FIRE FIGHTING:
In case of fire, wear a full face positive-pressure self contained breathing apparatus and protective suit.
Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 2/8
MATERIAL SAFETY DATA SHEET PRODUCT
- : : :-MSW-101
- N LC
-EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC
- 6.
ACCIDENTAL RELEASE MEASURES PERSONAL PRECAUTIONS:
Restrict access to area as appropriate until clean-up operations are complete. Ensure clean-up is conducted by trained personnel only. Ventilate spill area if possible. Do not touch spilled material. Stop or reduce any leaks if it is safe to do so. Use personal protective equipment recommended in Section 8 (Exposure Controls/Personal Protection). Notify appropriate government, occupational health and safety and environmental authorities.
METHODS FOR CLEANING UP:
SMALL SPILLS: Soak up spill with absorbent material. Place residues in a suitable, covered, properly labeled container. Wash affected area. LARGE SPILLS: Contain liquid using absorbent material, by digging trenches or by diking. Reclaim into recovery or salvage drums or tank truck for proper disposal. Wash site of spillage thoroughly with water. Contact an approved waste hauler for disposal of contaminated recovered material. Dispose of material in compliance with regulations indicated in Section 13 (Disposal Considerations).
ENVIRONMENTAL PRECAUTIONS:
Do not contaminate surface water.
- 7.
HANDLING AND STORAGE HANDLING:
Do not take internally. Do not get in eyes, on skin, on clothing. Have emergency equipment (for fires, spills, leaks, etc.) readily available. Ensure all containers are labelled. Keep the containers closed when not in use. Use with adequate ventilation.
STORAGE CONDITIONS:
Store the containers tightly closed. Store in suitable labelled containers.
SUITABLE CONSTRUCTION MATERIAL:
HDPE (high density polyethylene), Stainless Steel 304, Compatibility with Plastic Materials can vary; we therefore recommend that compatibility is tested prior to use.
- 8.
l EXPOSURE CONTROLS/PERSONAL PROTECTION OCCUPATIONAL EXPOSURE LIMITS:
This product does not contain any substance that has an established exposure limit.
ENGINEERING MEASURES:
General ventilation is recommended.
RESPIRATORY PROTECTION:
Respiratory protection is not normally needed. Respiratory protection is not normally needed. FULL-FACE MASK WITH WHITE CARTRIDGE HAND PROTECTION:
Neoprene gloves, Nitrile gloves, Butyl gloves, PVC gloves NEOPRENE, NITRILE, NATURAL RUBBER OR PVC GLOVES NEOPRENE, NITRILE, NATURAL RUBBER OR PVC GLOVES, SLICKER SUIT, RUBBER BOOTS Nalco Company 1601 W. Diehl Road e Naperville, Illinois 60563-1198 (630)305-1000 3/8
SNAIL) t MATERIAL SAFETY DATA SHEET PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424.9300 (24 Hours)
CHEMTREC SKIN PROTECTION:
Wear standard protective clothing.
EYE PROTECTION:
Wear chemical splash goggles. CHEMICAL GOGGLES HYGIENE RECOMMENDATIONS:
If clothing is contaminated, remove clothing and thoroughly wash the affected area. Launder contaminated clothing before reuse. Keep an eye wash fountain available. Keep a safety shower available.
- 9.
PHYSICAL AND CHEMICAL PROPERTIES PHYSICAL-STATE Liquid APPEARANCE Colorless Clear ODOR None SPECIFIC GRAVITY 1.35 @ 77 0F I 25 0C DENSITY 11.2 Ib/gal SOLUBILITY IN WATER Complete pH (100 %)
4.7 - 5.3 BOILING POINT 212 'F / 100 'C Minimum VAPOR PRESSURE Same as water VOC CONTENT 0 % Calculated Note: These physical properties are typical values for this product and are subject to change.
- 10.
lSTABILITY AND REACTIVITY STABILITY:
Stable under normal conditions.
HAZARDOUS POLYMERIZATION:
Hazardous polymerization will not occur.
CONDITIONS TO AVOID:
Freezing temperatures.
MATERIALS TO AVOID:
Contact with strong alkalies (e.g. ammonia and its solutions, carbonates, sodium hydroxide (caustic), potassium hydroxide, calcium hydroxide (lime), cyanide, sulfide, hypochlorites, chlorites) may generate heat, splattering or boiling and toxic vapors.
HAZARDOUS DECOMPOSITION PRODUCTS:
Under fire conditions:
Oxides of phosphorus, Oxides of sodium Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 4/8
sNALCO..
MATERIAL SAFETY DATA SHEET PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC
- 11.
lTOXICOLOGICAL INFORMATION I
No toxicity studies have been conducted on this product.
SENSITIZATION:
This product is not expected to be a sensitizer.
CARCINOGENICITY:
None of the substances in this product are listed as carcinogens by the International Agency for Research on Cancer (IARC), the National Toxicology Program (NTP) or the American Conference of Governmental Industrial Hygienists (ACGIH).
- 12.
l ECOLOGICAL INFORMATION l
ECOTOXICOLOGICAL EFFECTS:
No toxicity studies have been conducted on this product.
MOBILITY:
High phosphate levels in surface water can cause eutrophication with subsequent algal blooms and oxygen depletion.
BIOACCUMULATION POTENTIAL This preparation or material is not expected to bioaccumulate.
If released into the environment, see CERCLAJSUPERFUND in Section 15.
113.
l DISPOSAL CONSIDERATIONS If this product becomes a waste, it is not a hazardous waste as defined by the Resource Conservation and Recovery Act (RCRA) 40 CFR 261, since it does not have the characteristics of Subpart C, nor is it listed under Subpart D.
As a non-hazardous waste, it is not subject to federal regulation. Consult state or local regulation for any additional handling, treatment or disposal requirements. For disposal, contact a properly licensed waste treatment, storage, disposal or recycling facility.
1 14.
I TRANSPORT INFORMATION I
The information in this section is for reference only and should not take the place of a shipping paper (bill of lading) specific to an order. Please note that the proper Shipping Name / Hazard Class may vary by packaging, properties, and mode of transportation. Typical Proper Shipping Names for this product are as follows.
LAND TRANSPORT:
Proper Shipping Name:
PRODUCT IS NOT REGULATED DURING TRANSPORTATION Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 5/8
'NALCO:
MATERIAL SAFETY DATA SHEET PRODUCT II MSW-1 01 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC AIR TRANSPORT (ICAO/IATA):
Proper Shipping Name:
PRODUCT IS NOT REGULATED DURING TRANSPORTATION MARINE TRANSPORT (IMDG/IMO):
Proper Shipping Name:
PRODUCT IS NOT REGULATED DURING TRANSPORTATION
- 15.
l REGULATORYINFORMATION NATIONAL REGULATIONS, USA:
OSHA HAZARD COMMUNICATION RULE, 29 CFR 1910.1200:
Based on our hazard evaluation, none of the substances in this product are hazardous.
CERCLAJSUPERFUND, 40 CFR 117, 302:
Notification of spills of this product is not required.
SARA/SUPERFUND AMENDMENTS AND REAUTHORIZATION ACT OF 1986 (TITLE l1l) - SECTIONS 302, 311, 312, AND 313:
SECTION 302 - EXTREMELY HAZARDOUS SUBSTANCES (40 CFR 355):
This product does not contain substances listed in Appendix A and B as an Extremely Hazardous Substance.
SECTIONS 311 AND 312 - MATERIAL SAFETY DATA SHEET REQUIREMENTS (40 CFR 370):
Our hazard evaluation has found that this product is not hazardous under 29 CFR 1910.1200.
Immediate (Acute) Health Hazard Delayed (Chronic) Health Hazard Fire Hazard Sudden Release of Pressure Hazard Reactive Hazard Under SARA 311 and 312, the EPA has established threshold quantities for the reporting of hazardous chemicals.
The current thresholds are: 500 pounds or the threshold planning quantity (TPQ), whichever is lower, for extremely hazardous substances and 10,000 pounds for all other hazardous chemicals.
SECTION 313 - LIST OF TOXIC CHEMICALS (40 CFR 372):
This product does not contain substances on the List of Toxic Chemicals.
TOXIC SUBSTANCES CONTROL ACT (TSCA):
The substances in this preparation are included on or exempted from the TSCA 8(b) Inventory (40 CFR 710)
NSF INTERNATIONAL:
This product has received NSFllnternational certification under ANSIINSF Standard 60 in the corrosion and scale control and sequestering categories. The official name is "Blended Corrosion Inhibitor." Maximum product application dosage is: 34 mgil.
Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 618
- i MATERIAL SAFETY DATA SHEET
-q N ALCO:
PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC FEDERAL WATER POLLUTION CONTROL ACT, CLEAN WATER ACT, 40 CFR 401.15/ formerly Sec. 307,40 CFR 116.4 /formerly Sec. 311:
This product contains the following substances listed in the regulation:
Substance(s)
Citations Sodium Phosphate, Tribasic Sec. 311 CLEAN AIR ACT, Sec. 111 (40 CFR 60, Volatile Organic Compounds), Sec. 112 (40 CFR 61, Hazardous Air Pollutants), Sec. 602 (40 CFR 82, Class I and 11 Ozone Depleting Substances):
None of the substances are specifically listed in the regulation.
CALIFORNIA PROPOSITION 65:
This product does not contain substances which require warning under California Proposition 65.
MICHIGAN CRITICAL MATERIALS:
None of the substances are specifically listed in the regulation.
STATE RIGHT TO KNOW LAWS:
The following substances are disclosed for compliance with State Right to Know Laws:
Sodium Phosphate, Tribasic 7601-54-9 NATIONAL REGULATIONS, CANADA:
WORKPLACE HAZARDOUS MATERIALS INFORMATION SYSTEM (WHMIS):
This product has been classified in accordance with the hazard criteria of the Controlled Products Regulations (CPR) and the MSDS contains all the information required by the CPR.
WHMIS CLASSIFICATION:
Not considered a WHMIS controlled product.
CANADIAN ENVIRONMENTAL PROTECTION ACT (CEPA):
The substances in this preparation are listed on the Domestic Substances List (DSL), are exempt, or have been reported in accordance with the New Substances Notification Regulations.
- 16.
l OTHER INFORMATION This product material safety data sheet provides health and safety information. The product is to be used in applications consistent with our product literature. Individuals handling this product should be informed 6f the recommended safety precautions and should have access to this information. For any other uses, exposures should be evaluated so that appropriate handling practices and training programs can be established to insure safe workplace operations. Please consult your local sales representative for any further information.
REFERENCES Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 7/8
.: ^S
'-: NALCO MATERIAL SAFETY DATA SHEET PRODUCT MSW-101 EMERGENCY TELEPHONE NUMBER(S)
(800) 424-9300 (24 Hours)
CHEMTREC Threshold Limit Values for Chemical Substances and Physical Agents and Biological Exposure Indices, American Conference of Governmental Industrial Hygienists, OH., (Ariel Insight# CD-ROM Version), Ariel Research Corp.,
Bethesda, MD.
Hazardous Substances Data Bank, National Library of Medicine, Bethesda, Maryland (TOMES CPS# CD-ROM Version), Micromedex, Inc., Englewood, CO.
IARC Monographs on the Evaluation of the Carcinogenic Risk of Chemicals to Man, Geneva: World Health Organization, International Agency for Research on Cancer.
Integrated Risk Information System, U.S. Environmental Protection Agency, Washington, D.C. (TOMES CPS# CD-ROM Version), Micromedex, Inc., Englewood, CO.
Annual Report on Carcinogens, National Toxicology Program, U.S. Department of Health and Human Services, Public Health Service.
Title 29 Code of Federal Regulations, Part 1910, Subpart Z, Toxic and Hazardous Substances, Occupational Safety and Health Administration (OSHA), (Ariel Insight# CD-ROM Version), Ariel Research Corp., Bethesda, MD.
Registry of Toxic Effects of Chemical Substances, National Institute for Occupational Safety and Health, Cincinnati, OH, (TOMES CPS# CD-ROM Version), Micromedex, Inc., Englewood, CO.
Ariel Insight# (An integrated guide to industrial chemicals covered under major regulatory and advisory programs),
North American Module, Western European Module, Chemical Inventories Module and the Generics Module (Ariel Insight# CD-ROM Version), Ariel Research Corp., Bethesda, MD.
The Teratogen Information System, University of Washington, Seattle, WA (TOMES CPS# CD-ROM Version),
Micromedex, Inc., Englewood, CO.
Prepared By: Product Safety Department Date issued: 02/26/2004 Version Number: 1.6 Nalco Company 1601 W. Diehl Road
- Naperville, Illinois 60563-1198 (630)305-1000 8/8
Product Bulletin MSW-1 01 Corrosion and Deposit Inhibitor PRODUCT DESCRIPTION AND APPLICATION MSW-101 corrosion and deposit Inhibitor is a liquid inhibitor formulated to control corrosion and scale build-up in municipal water systems, industrial service water, or cooling water systems.
PHYSICAL & CHEMICAL PROPERTIES These properties are typical. Refer to the Material Safety Data Sheet (MSDS), SECTION 9, for the most current data.
Appearance Physical State Density @ 77°F (250C)
Specific Gravity@ 770F (250C) pH (Neat)
Freeze Point Viscosity Flash Point Solubility in Water Vapor Pressure Odor Boiling Point VOC content Clear, Colorless Liquid 11.2 lb/gal (1.35 KgIL) 1.35 4.7-5.3 Not Available Not Available None complete same as water None 2120F (1000C) 0% as calculated ACTIVE CONSTITUENTS Active Orthophosphate Sodium Hexametaphosphate Function Corrosion Inhibitor Scale/corrosion Inhibitor
REGULATORY APPROVALS NSF INTERNATIONAL: This product has received NSF/Intemational certification under ANSI/NSF Standard 60 in the corrosion and scale control and sequestering categories. The official name is 'Blended Corrosion Inhibitor." Maximum product application dosage is: 33 mg/I. Only product manufactured at Plant 11 USA and whose container label bears the ANSI/NSF Mark may be used in potable water treatment applications.
MATERIALS OF COMPATIBILITY Compatible High Density Polyethylene Crosslinked Polyethylene Low Density Polyethylene EPDM FRP (Bisphenol)
Neoprene Viton Stainless Steel 316 Stainless Steel 304 Polypropylene PVC CPVC Kynar Hypalon Not Compatible Carbon steel Buna-N FRP (isophthalic)
Plasite 7122 (epoxy)
Plasite 4100 (vinyl ester)
Silicone 65 DOSAGE AND FEEDING For complete dosage and feeding recommendations, consult your Nalco representative.
MSW-101 should be fed via a closed feed system. A closed feed system is defined as a system in which fluid is moved from a closed storage vessel into a treated media without exposure to the atmosphere except through normal venting or pressure relief devices.
ENVIRONMENTAL AND TOXICITY DATA Biological Oxygen Demand (5-day BODO5)
Chemical Oxygen Demand (COD)
Not Available Not Available Not Available Refer to SECTIONS 11 and 12 of the MSDS for all available mammalian and aquatic toxicity information.
SAFETY AND HANDLING Chemical resistant gloves and safety goggles should be worn when handling MSW-101. Before handling MSW-101, read SECTION 8 of the MSDS for specific personal protective equipment (PPE) recommendations and SECTION 3 for health effects information.
STORAGE MSW-101should be stored in a location where the product can be maintained between 320F (OOC) and 110OF (430C). Recommended in-plant storage limit Is 1 year.
REMARKS If you need assistance or more information on this product, please call your nearest Nalco Representative. For more news about Nalco Company, visit our website at www.nalco.com.
For Medical and Transportation Emergencies involving Nalco products, please see the Material Safety Data Sheet for the phone number.
ADDITIONAL INFORMATION NALCO is a registered trademark of Nalco Company (10-27-04)