January 24, 2006 Mr. Mano K. Nazar Senior Vice President and Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106

SUBJECT:

DONALD C. COOK NUCLEAR PLANT, UNITS 1 AND 2 - CORRECTION TO AMENDMENTS RE: MONTHLY OPERATING REPORTS AND ANNUAL OCCUPATIONAL RADIATION EXPOSURE REPORTS (TAC NOS. MC8166 AND MC8167)

Dear Mr. Nazar:

On January 12, 2006, the Nuclear Regulatory Commission (NRC) issued Amendment No. 292 to Renewed Facility Operating License No. DPR-58 and Amendment No. 274 to Renewed Facility Operating License No. DPR-74 for Donald C. Cook Nuclear Plant, Units 1 and 2. The amendments changed the technical specifications in response to your application dated July 29, 2005, deleting the requirements to submit monthly operating reports and annual occupational radiation exposure reports.

Subsequent to issuance, the NRC staff noted that due to an administrative error, the amendment package did not correctly reflect that the amendments were issued to the renewed facility operating licenses. Specifically, the word renewed was missing on a number of pages.

Enclosed are the corrected pages with marginal lines indicating the areas changed. Please use these pages to replace corresponding pages in the January 12, 2006, amendment package.

The NRC staff regrets any inconvenience this may have caused you.

Sincerely,

/RA/

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-315 and 50-316

Enclosures:

As stated cc w/encls: See next page

January 24, 2006 Mr. Mano K. Nazar Senior Vice President and Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106

SUBJECT:

DONALD C. COOK NUCLEAR PLANT, UNITS 1 AND 2 - CORRECTION TO AMENDMENTS RE: MONTHLY OPERATING REPORTS AND ANNUAL OCCUPATIONAL RADIATION EXPOSURE REPORTS (TAC NOS. MC8166 AND MC8167)

Dear Mr. Nazar:

On January 12, 2006, the Nuclear Regulatory Commission (NRC) issued Amendment No. 292 to Renewed Facility Operating License No. DPR-58 and Amendment No. 274 to Renewed Facility Operating License No. DPR-74 for Donald C. Cook Nuclear Plant, Units 1 and 2. The amendments changed the technical specifications in response to your application dated July 29, 2005, deleting the requirements to submit monthly operating reports and annual occupational radiation exposure reports.

Subsequent to issuance, the NRC staff noted that due to an administrative error, the amendment package did not correctly reflect that the amendments were issued to the renewed facility operating licenses. Specifically, the word renewed was missing on a number of pages.

Enclosed are the corrected pages with marginal lines indicating the areas changed. Please use these pages to replace corresponding pages in the January 12, 2006, amendment package.

The NRC staff regrets any inconvenience this may have caused you.

Sincerely,

/RA/

Peter S. Tam, Senior Project Manager Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation Docket Nos. 50-315 and 50-316

Enclosures:

As stated cc w/encls: See next page DISTRIBUTION PUBLIC LPLIII-1 R/F RidsNrrPMPTam RidsNrrLATHarris RidsOgcRp GHill(2)

RidsAcrsAcnwMailCenter RidsNrrDorlLple RidsRgn3MailCenter RidsNrrDirsItsb RidsNrrDorl Accession Number: ML060200500 OFFICE NRR/LPL3-1/PM NRR/LPL3-1/LA NRR/LPL3-1/BC(A)

NAME PTam THarris TKobetz DATE 1/24/06 1/24/06 1/24/06 OFFICIAL RECORD COPY

INDIANA MICHIGAN POWER COMPANY DOCKET NO. 50-315 DONALD C. COOK NUCLEAR PLANT, UNIT 1 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE l

Amendment No. 292 License No. DPR-58 1.

The U.S. Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Indiana Michigan Power Company (the licensee) dated July 29, 2005, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

Corrected by letter dated 1/24/06 l

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of l

Renewed Facility Operating License No. DPR-58 is hereby amended to read as follows:

l (2)

Technical Specifications The Technical Specifications contained in Appendix A and Appendix B, as revised through Amendment No. 292 are hereby incorporated in the renewed l

operating license. The licensee shall operate the facility in accordance with the l

Technical Specifications.

3.

This license amendment is effective as of its date of issuance and shall be implemented within 45 days.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Timothy J. Kobetz, Acting Chief Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: January 12, 2006 Corrected by letter dated 1/24/06 l

ATTACHMENT TO LICENSE AMENDMENT NO. 292 TO RENEWED FACILITY OPERATING LICENSE NO. DPR-58 l

DOCKET NO. 50-315 Replace the following pages of Appendix A, Technical Specifications, with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

REMOVE INSERT 5.6-1 5.6-1 5.6-2 5.6-2 Corrected by letter dated 1/24/06 l

INDIANA MICHIGAN POWER COMPANY DOCKET NO. 50-316 DONALD C. COOK NUCLEAR PLANT, UNIT 2 AMENDMENT TO RENEWED FACILITY OPERATING LICENSE l

Amendment No. 274 License No. DPR-74 1.

The U.S. Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Indiana Michigan Power Company (the licensee) dated July 29, 2005, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

Corrected by letter dated 1/24/06 l

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Renewed Facility Operating License No. DPR-74 is hereby amended to read as follows:

l (2)

Technical Specifications The Technical Specifications contained in Appendix A and Appendix B, as revised through Amendment No. 274, are hereby incorporated in the renewed l

operating license. The licensee shall operate the facility in accordance with the l

Technical Specifications.

3.

This license amendment is effective as of its date of issuance and shall be implemented within 45 days.

FOR THE NUCLEAR REGULATORY COMMISSION

/RA/

Timothy J. Kobetz, Acting Chief Plant Licensing Branch III-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical Specifications Date of Issuance: January 12, 2006 Corrected by letter dated 1/24/06 l

ATTACHMENT TO LICENSE AMENDMENT NO. 274 RENEWED FACILITY OPERATING LICENSE NO. DPR-74 l

DOCKET NO. 50-316 Replace the following pages of Appendix A, Technical Specifications, with the attached revised pages. The revised pages are identified by amendment number and contain marginal lines indicating the areas of change.

REMOVE INSERT 5.6-1 5.6-1 5.6-2 5.6-2 Corrected by letter dated 1/24/06 l

SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 292 TO RENEWED l

FACILITY OPERATING LICENSE NO. DPR-58 AND AMENDMENT NO. 274 TO RENEWED FACILITY OPERATING LICENSE NO. DPR-74 l

INDIANA MICHIGAN POWER COMPANY DONALD C. COOK NUCLEAR PLANT, UNITS 1 AND 2 DOCKET NOS. 50-315 AND 50-316

1.0 INTRODUCTION

By application dated July 29, 2005 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML052220266), the Indiana Michigan Power Company (the licensee) requested amendments to the Technical Specifications (TSs) for the Donald C. Cook Nuclear Plant, Units 1 and 2. The requested changes would delete Section 5.6.1, Occupational Radiation Exposure Report, and Section 5.6.4, Monthly Operating Report, as described in the Notice of Availability published in the Federal Register on June 23, 2004 (69 FR 35067).

The proposed amendments are consistent with Revision 1 of the NRC-approved Industry/Technical Specifications Task Force (TSTF) Standard Technical Specification Change Traveler, TSTF-369, "Elimination of Requirements for Monthly Operating Reports [MORs] and Occupational Radiation Exposure Reports [ORERs]." This TS improvement was published in the Federal Register (69 FR 35067) on June 23, 2004, as part of the Consolidated Line Item Improvement Process (CLIIP).

2.0 REGULATORY EVALUATION

Section 182a. of the Atomic Energy Act of 1954, as amended, (the Act) requires applicants for nuclear power plant operating licenses to propose such TSs as the Commission may deem necessary. Such TSs shall be a part of the license issued. The Commission's regulatory requirements related to the content of TSs are set forth in 10 CFR 50.36, Technical specifications. The regulation requires that TSs include items in five specific categories, including (1) safety limits, limiting safety system settings, and limiting control settings; (2) limiting conditions for operation (LCOs); (3) surveillance requirements; (4) design features; and (5) administrative controls. However, the regulation does not specify the particular requirements to be included in a plant's TSs.

The Commission has provided guidance for the content of TSs in its "Final Policy Statement on Technical Specification Improvements for Nuclear Power Reactors (58 FR 39132, published July 22, 1993), in which the Commission indicated that compliance with the Final Policy Statement satisfies Section 182a. of the Act. The Final Policy Statement identified four criteria Corrected by letter dated 1/24/06 l

Donald C. Cook Nuclear Plant, Units 1 and 2 cc:

Regional Administrator, Region III U.S. Nuclear Regulatory Commission Suite 210 2443 Warrenville Road Lisle, IL 60532-4351 Attorney General Department of Attorney General 525 West Ottawa Street Lansing, MI 48913 Township Supervisor Lake Township Hall P.O. Box 818 Bridgman, MI 49106 U.S. Nuclear Regulatory Commission Resident Inspector's Office 7700 Red Arrow Highway Stevensville, MI 49127 James M. Petro, Jr., Esquire Indiana Michigan Power Company One Cook Place Bridgman, MI 49106 Mayor, City of Bridgman P.O. Box 366 Bridgman, MI 49106 Special Assistant to the Governor Room 1 - State Capitol Lansing, MI 48909 Mr. John A. Zwolinski Safety Assurance Director Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106 Michigan Department of Environmental Quality Waste and Hazardous Materials Div.

Hazardous Waste & Radiological Protection Section Nuclear Facilities Unit Constitution Hall, Lower-Level North 525 West Allegan Street P. O. Box 30241 Lansing, MI 48909-7741 Lawrence J. Weber, Plant Manager Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106 Mr. Joseph N. Jensen, Site Vice President Indiana Michigan Power Company Nuclear Generation Group One Cook Place Bridgman, MI 49106