NL-05-2346, Inservice Inspection Summary Report
| ML060180170 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 01/11/2006 |
| From: | Grissette D Southern Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| NL-05-2346 | |
| Download: ML060180170 (97) | |
Text
{{#Wiki_filter:I Don E. Grissette Southern Nuclear Vice President Operating Company, Inc. 40 Inverness Center Parkway Post Office Box 1295 Birmingham, Alabama 35201 Tel 205.992.6474 Fax 205.992.0341 SOUTHERNAM COMPANY January 11, 2006 Energy to Serve Your World Docket No.: 50-425 NL-05-2346 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Vogtle Electric Generating Plant Inservice Inspection Summary Report Ladies and Gentlemen: Southern Nuclear Operating Company (SNC) submits herewith the Vogtle Electric Generating Plant Unit 2, Interval 2, Period 3, Outage I Inservice Inspection Summary Report (Enclosure). This report describes and summarizes the inservice inspection activities performed during the fall 2005 maintenance/refueling outage. Paragraph IWA-6230 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section XI, 1989 Edition requires submittal of the enclosed report. Also included in the report are inspection results required by Vogtle Electric Generating Plant Technical Specification 5.6.10.b for submittal to the NRC within 12 months following completion of the steam generator tube examinations. The supporting inservice inspection documentation, e.g., examination plans and schedules, examination results and reports, examination methods and procedures, evaluation results, and corrective action and repairs, is available for review upon request at Vogtle Electric Generating Plant. The signed original and one copy of the subject report are provided for your review. This letter contains no NRC commitments. If you have any questions, please advise. Sincerely, Don E. Grissette DEG/DRG/daj
Enclosure:
Inservice Inspection Summary Report Vogtle Electric Generating Plant Unit 2 - Refueling Outage (2R11 1) pOH
U. S. Nuclear Regulatory Commission NL-05-2346 Page 2 cc: Southern Nuclear Operating Company Mr. J. T. Gasser, Executive Vice President Mr. T. E. Tynan, General Manager - Plant Vogtle RType: CVC7000 U. S. Nuclear Regulatory Commission Dr. W. D. Travers, Regional Administrator Mr. C. Gratton, NRR Project Manager - Vogtle Mr. G. J. McCoy, Senior Resident Inspector-Vogtle
Vogtle Electric Generating Plant Unit 2 Eleventh Maintenance/Refueling Outage (2R11) Owner's Report for Inservice Inspection Southern Nuclear Operating Company the southern electric system
OWNER'S REPORT FOR INSERVICE INSPECTIONS for the ELEVENTH MAINTENANCE/REFUELING OUTAGE of VOGTLE ELECTRIC GENERATING PLANT, UNIT 2 (7821 River Road, P. 0. Box 1600, Waynesboro, Georgia 30830) COMMERCIAL OPERATION DATE: May 20, 1989 DOCUMENT COMPLETION DATE: January 2006 Prepared by SOUTHERN NUCLEAR OPERATING COMPANY (40 Inverness Center Parkway, P. 0. Box 1295, Birmingham, Alabama 35201) as LICENSEE AND OPERATING AGENT for GEORGIA POWER COMPANY (241 Ralph McGill Boulevard, N.E., P. 0. Box 4545, Atlanta, Georgia 30308-3374) as OWNER
TABLE OF CONTENTS Page Introduction 1-1 ASME Form NIS-I with Abstract - ASME Class I and 2 2-1 Class MC and CC Examinations and Tests (IWE/IWL) 3-1 Augmented Examinations (Steam Generators) 4-1 Class 1 and 2 Weld and Support Examination Summary 5-1 System Pressure Tests Summary 6-1 Indication Notification Forms 7-1 NIS-2 Forms with Listing 8-1 i
LIST OF ABBREVIATIONS ACC Acceptable AD Anchor/Darling AFW Auxiliary Feedwater System Al GPC Action Item (followed by unique no. denoting Action Item number) ANII Authorized Nuclear Inservice Inspector ASME American Society of Mechanical Engineers ASNT American Society for Nondestructive Testing ASTM American Society for Testing and Materials BC Branch Connection CCSS Centrifugally Cast Stainless Steel CCW Component Cooling Water CE Combustion Engineering CH Closure Head CR Condition Report CS Containment Spray CVCS Chemical and Volume Control System DS Downstream ET Eddy Current Examination EVAL Evaluation FAC Flow-Accelerated Corrosion (may also be referred to as "erosion/corrosion") FB Flange Bolting FNF FAC Notification Report FW Feedwater System FSAR VEGP Final Safety Analysis Report (includes updates thereto) GEO Geometric Indications GPC Georgia Power Company HHSI High Head Safety Injection HL Hanger Lug HX Heat Exchanger HYD Hydraulic Snubber IEN NRC Information Notice (may also be shown as "IN" followed by unique no. denoting notice number) IND Indication INF Indication Notification Form ISI Inservice Inspection IST Inservice Testing ITS VEGP Improved Technical Specification ID Inside Diameter IR Inside Radius LB Large Bore i LD Longitudinal Seam Weld Extending Downstream LD-I Longitudinal Seam Weld Downstream Inside Radius of Elbow LD-O Longitudinal Seam Weld Downstream Outside Radius of Elbow LMT Lambert, MacGill and Thomas LU Longitudinal Seam Weld Extending Upstream LU-I Longitudinal Seam Weld Upstreamn Inside Radius of Elbow LU-O Longitudinal Seam Weld Upstream Outside Radius of Elbow MECH Mechanical Snubber MS Main Steam System MT Magnetic Particle Examination NCI Nonconformance Item NDE Nondestructive Examination ii
LIST OF ABBREVIATIONS - (continued) NI No Indication NRC United States Nuclear Regulatory Commission NRC-B NRC Bulletin (followed by unique no. denoting Bulletin number) NRI No Recordable Indication NSCW Nuclear Service Cooling Water System OR Outside Radius PL Pipe Lug PM Paul-Munroe ENERTECH PR Pipe Restraint PROF Profile PS Pipe Support PSA Pacific Scientific PSI Preservice Inspection PT Liquid Penetrant Examination RCS Reactor Coolant System RCP Reactor Coolant Pump RHR Residual Heat Removal System RI Recordable Indication RLW Refracted Longitudinal Wave RL Restraint Lug RPV Reactor Pressure Vessel RR Relief Request (followed by unique no. denoting relief request number) RWST Refueling Water Storage Tank SAT Satisfactory Examination Results SB Small Bore SCS Southern Company Services SI Safety Injection System SNC Southern Nuclear Operating Company SUP Supplemental Data T&C Thickness and Contour TDAFW Turbine Driven Auxiliary Feedwater (Pump) UNSAT Unsatisfactory Examination Results US Upstream UT Ultrasonic Examination VEGP Vogtle Electric Generating Plant (common unless followed by "-1" or "-2" to designate a specific plant unit) VT Visual Examination W Westinghouse iii
INTRODUCTION This report documents the examinations and tests performed at Vogtle Electric Generating Plant, Unit 2 (VEGP-2) between May 16, 2004 (date of last examination performed during the tenth maintenance/refueling outage, 2R1 0) and October 13, 2005 (date of last examination performed during the eleventh maintenance/refueling outage, 2RI 1) to meet the requirements of Article IWA-6000 of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section XI, 1989 Edition (Code). In addition, a summary of the following augmented examinations are included in this report: VEGP Technical Specification 5.5.9 - Steam Generator Tube Inspections This report also addresses Code-applicable repairs and/or replacements, which were documented since the last maintenance/refueling outage at VEGP-2 through the completion of the eleventh maintenance/refueling outage in October 2005. The Owner's Reports for Repairs or Replacements (Form NIS-2) are included herein. 1-1
FORM NIS-I OWNER'S REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner:
Georgia Power Company, 241 Ralph McGill Blvd., N. E. P. 0. Box 4545, Atlanta, Georgia 30308-3374
- 2.
Plant: Vogtle Electric Generating Plant, 7821 River Road P. 0. Box 1600, Waynesboro, Georgia 30830
- 3.
Plant Unit: Two
- 4.
Owner Certification of Authorization: N/A
- 5.
Commercial Service Date: 05/20/89
- 6.
National Board Number for Unit: N/A
- 7.
Components Inspected: Component or Manufacturer or Manufacturer or Installer State or Province National Board Appurtenance Installer and Serial Number Number Number Address Reactor Combustion Eng. 7372 N/A 22004 Pressure Vessel Inc., Chattanooga, TN Steam Westinghouse Elec., GBGT 1984 (77743), N/A 36, Generators I Pensacola, FL GBGT 1983 (77745), 35, through 4. GBGT 1982 (77742), 34, GBGT 1981 (77744) 33 Pressurizer Westinghouse Elec., 77749 NA 24 Pensacola, FL Reactor Westinghouse Elec., 6-9744D35G01 N/A 37 Coolant Pump 2 Cheswick, PA Safety Injection Pacific Pumps, 52229 NA 446 Pump, Train Huntington Park, "A" CA Centrifugal Pacific Pumps, 52235 NA 412 Charging Huntington Park, Pump, Train CA "A"' Selected Piping, Pullman Power System Numbers 1201, 1202, N/A N/A Components,
- Products, 1204,1205, 1206,1208,1301, and Supports Williamsport, PA 1302, 1305, 1501 & 1515.
2-1
FORM NIS-I (Back)
- 8.
Examination Dates: May 16. 2004 to October 13. 2005
- 9.
Inspection Period Identification: Third Period
- 10.
Inspection Interval Identification: Second Insnection Interval
- 11.
Applicable Edition of Scction XI 1989 Addenda None
- 12.
Date/Revision of Inspection Plan: November 17. 2005 /Revision 8
- 13.
Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. (See Abstract and Examination Summary Listings)
- 14.
Abstract of Results of Examinations and Tests. (See Abstract)
- 15.
Abstract of Corrective Measures. (See Abstract) We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code, Section XI, and c) corrective measures taken conform to the rules of the ASME Code, Section XI. Certificate of Authorization No. (if applicable) N/A Expiration Date N/A Date: -0SA 20c Signed: Southern Nuclear Oeratine By: '2 Company. Inc. for Georgia Power Comnanv (Owner) CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Georgia and employed by The Hartford Steam Boiler Inspection and Insurance Company of Connecticut of Hartford. CT have inspected the components described in this Owner's Report during the period May 16. 2004 to October 13. 2005. and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commission: 60.- 7 S' Insposp for's Signature National Board, State, Province, and Endorsements Date: MA" ny i 20Q.A 2-2
ABSTRACT - ASME CLASS 1 AND 2 Introduction/Status The ASME Boiler and Pressure Vessel Code, Section XI, 1989 Edition (Code), is the applicable code for conducting inservice inspection activities during the second ten-year inspection interval at VEGP-2. Examinations and tests required by the Code are scheduled in accordance with "Inspection Program B" as defined in Code paragraphs IWB-2412 and IWC-2412. This "Owner's Report for Inservice Inspection" is for those third period examinations and tests which were performed between May 16, 2004 (date of last examination performed during the tenth maintenance/refueling outage, 2R1 0) and October 13, 2005 (date of last examination performed during the eleventh maintenance/refueling outage, 2R1 1) The Risk Informed Program was approved by the NRC by letter dated September 30, 2003 and implemented during the VEGP 2R10 refueling outage (ASME Class 1 and Class 2 piping only). By Federal Register Notice 64 FR 51370 dated September 22, 1999,1 OCFR 50.55a(g)(6)(ii)(C), Implementation of Appendix VIII to Section XI, was incorporated into the rule to expedite implementation of Appendix VIII. The specific Supplements of Appendix VIII to Section XI, ASME Boiler and Pressure Vessel Code, 1995 Edition with the 1996 Addenda were implemented prior to the 2R1 I maintenance/refueling outage as required. In addition to the summary of inservice inspection activities, this report addresses Code-applicable repairs and replacements documented at VEGP-2 since 2R10 through the end of 2R1 1. The Owner's Reports for Repairs or Replacements (Form NIS-2) are provided herein. It should be noted that Authorized Nuclear Inservice Inspector (ANII) inspection services were provided for those examinations and tests required by the Code. ASME Section XI examinations and tests are itemized in the applicable sections by reference to Examination Category. Examinations which do not meet the Code-required coverage either reference request(s) for relief or indicate that additional relief is required. Class 1 Examinations Selected Class 1 components were examined utilizing ultrasonic testing (UT), liquid penetrant testing (PT), visual testing (VT) and magnetic particle testing (MT) methods, as applicable. Specific components and examination areas are itemized in the applicable portions of this document. A summary of those components examined are listed below: Reactor Pressure Vessel (RPV) Interior Surfaces, CRD Housing Welds, and RPV Closure Studs, Pressurizer Circumferential Weld and Support Skirt, Steam Generator Manway Bolting, Reactor Coolant Pump Sealwater Housing Cap Screws, Piping Welds, and Valve and Flange Bolting. The Class I Examinations resulted in no components having unacceptable conditions. In addition to components already identified in current requests for relief, one (1) equipment component had limited visual coverage during VT examinations because of physical limitations due to the geometric configuration of the component area. It is impractical to achieve the ASME Section XI Code-required coverage due to the geometric configuration of the component area. Relief from the ASME Section XI Code requirements will be requested from the NRC for this component through the relief request process as allowed by 10 CFR 50.55a. The applicable component is indicated by "Relief Required" in the combined Class 1 and 2 Weld Examination Table. 2-3
The eddy current (ET) examinations of steam generator tubing, as required by VEGP Technical Specification 5.5.9, were performed by Westinghouse and are discussed in the "Augmented Inspections" portion of this document. Class I Pressure Test Table IWB-2500-1, Examination Category B-P, of ASME Section XI requires the performance of a system leakage test (IWB-5221) each maintenance/refueling outage. This system leakage test (LT-1) was performed prior to plant startup following the refueling outage. These visual examinations revealed minor leakage and boron residue at mechanical connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation per approved plant procedures. ASME Section XI, Subparagraph IWA-5242(a) requires removal of insulation from pressure-retaining bolted connections for VT-2 examination during system pressure testing for systems borated for the purposes of controlling reactivity. ASME Section XI Code Cases N-533-1 and N-616 were utilized during the refueling outage. These Code Cases were approved for use in Revision 13 of Regulatory Guide 1.147 dated June 2003. Case N-533-1 allows insulation to be removed while the connections are at atmospheric or static pressures. With the insulation removed a direct visual examination is performed to detect previously occurring leakage through the presence of boric acid crystals. Case N-616 allows the VT-2 examination to occur without insulation removal provided the bolting material is resistant to boric acid degradation. The test boundary of the system leakage test includes both Class I and Class 2 components. The frequency for removal of insulation and direct visual examination for Class I pressure-retaining bolted connections is once each refueling outage (refer to Table IWB-2500-1, Examination Category B-P) and as such those activities occurred during the refueling outage. The Class 2 components comprise part of the reactor coolant pressure boundary but are not required to be classified as Class I per I OCFR50.55a(c)(2). The frequency for removal of insulation and direct visual examination for Class 2 pressure-retaining bolted connections is once each inspection period (refer to Table IWC-2500-1, Examination Category C-H). Those activities will be completed prior to the end of the inspection period. Class 2 Examinations Selected Class 2 components were examined utilizing ultrasonic testing (UT), liquid penetrant testing (PT), visual testing (VT) and magnetic particle testing (MT) methods, as applicable. Specific components and examination areas are itemized in the applicable portions of this report document. A summary of those components examined are listed below: Steam Generator Welds, Safety Injection Pump Welds, Centrifugal Charging Pump Welds, and Piping Welds. The Class 2 Examinations resulted in no components having unacceptable conditions. In addition to components already identified in current requests for relief, one (1) equipment weld and one (I) piping weld had limited volumetric coverage during UTexaminations because of physical limitations due to the geometric configuration of the welded areas. More than ninety percent (90%) of the required volume must be examined as addressed in ASME Section XI Code Case N-460 for adequate ASME Section' XI Code-required examination coverage to be attained. As noted herein, the subject code case has been approved by' the NRC for use as documented in NRC Regulatory Guide 1.147.; It is impractical to achieve the ASME Section XI Code-required coverage due to the 'geometric configuration of the welded areas! Relief from the ASME Section XI Code requirements will be requested from the NRC for the affected welds through the relief request process as allowed by 10 CFR 50.55a. The applicable welds are indicated by "Relief Required" in the combined Class I and 2 Weld Examination table. 24
Class 2 Pressure Tests Table IWC-2500-1, Examination Category C-H, of ASME Section XI requires system pressure testing each inspection period. The specific system pressure tests performed are itemized in the 'Pressure Tests" portion of this report document. The visual examinations performed during these system pressure tests generally found only minor leakage or residue at mechanical joints such as valve stem packing and at flanged connections. These leakage conditions were either corrected or evaluated and determined acceptable for continued system operation per approved plant procedures. A through wall leak, which was less than one drop per minute, was discovered on a sample line associated with Accumulator Tank 1204-V6-005. This leak was isolatable from the tank and was corrected during the refueling outage. ASME Section XI, Subparagraph IWA-5242(a) requires removal of insulation from pressure-retaining bolted connections for VT-2 examination during system pressure testing for systems borated for the purposes of controlling reactivity. ASME Section XI Code Cases N-533-1 and N-616 were utilized. These Code Cases were approved for use in Revision 13 of Regulatory Guide 1.147 dated June 2003. Case N-533-1 allows insulation to be removed while the connections are at atmospheric or static pressures. With the insulation removed a direct visual examination is performed to detect previously occurring leakage through the presence of boric acid crystals. Case N-616 allows the VT-2 examination to occur without insulation removal provided the bolting material is resistant to boric acid degradation. Class 1 and 2 Component Supports Visual examinations were performed on supports for the following Class I and 2 components: Reactor Coolant System Equipment and Piping (1201), Nuclear Service Cooling Water Piping (1202), Safety Injection System Equipment and Piping (1204), Residual Heat Removal (1205), Containment Spray (1206), Chemical and Volume Control System Equipment and Piping (1208), Main Steam (1301), Auxiliary Feedwater (1302), Condensate and Feedwater (1305), Containment Heat Removal System Piping (1501) and Containment Building Auxiliary Air Cooling System Piping (1515) The visual examinations resulted in no supports having unacceptable conditions. 2-5
CLASS CC Examinations and Tests (IWL) Cateeorv L-A. Concrete The Containment concrete surface examination (including grease cans) was performed during the summer of 2005 to satisfy the requirements of 10 CFR 50.55a and the 1992 Edition of ASME Section XI Subsection IWL with the 1992 Addenda. The concrete examinations were performed by a qualified vendor per criteria specified by the 1992 Edition and the 1992 Addenda of ASME Section XI and under the guidance of a Registered Professional Engineer. Request for Engineering Review 1052234101 was initiated to provide and document technical assistance. Optical aids and flashlights were used when performing the examination that included both direct and indirect visual examination methods. This VT-3C concrete surface examination required no VT-IC examinations of areas that had not been previously identified during the last concrete visual examination and zero grease leakage was detected on the Containment concrete surface. While performing a liftoff on the Unit 2, buttress 3 side of horizontal tendon H-66, the jack chair came into contact with the protruding nonstructural concrete causing the corner of the buttress to spall off. During the subsequent VT-IC examination this condition was determined to be acceptable based on its nonstructural location on the outer edge of the buttress. The condition was remedied however, to ensure adequate rebar cover, by replacing the spalled area with grout per Maintenance Work Order 2052210901. Based on the results of the Containment concrete surface visual examination the Containment concrete has no evidence of degradation that warrants further evaluation and repair and remains in an acceptable structural condition. Catenory L-B, Unbonded Post-Tensionina System The Containment unbonded post-tensioning system examination was performed during the summer of 2005 to satisfy the requirements of 10 CFR 50.55a and the 1992 Edition of ASME Section XI Subsection IWL with the 1992 Addenda. The examinations were performed by a qualified vendor per criteria specified by the 1992 Edition and the 1992 Addenda of ASME Section XI. Request for Engineering Review 1052234101 was initiated to provide and document technical assistance. All requirements, including tendon force and elongation, a tendon strand sample, tendon anchorage areas, and corrosion protection medium, to satisfy acceptance by examination criteria, per IWL-3221, were met. After detensioning tendon V21-91 for strand removal, it was noted that four strands on end 91 were longer than the remaining 51 strands by between 3.44 and 5.88 inches. It was determined that these four strands were longer since the original installation. Prior to retensioning tendon V21-91 each of these strands were verified not to be broken. These strands were then seated with new wedges, stressed to a lock off value of 3% above the as found value, which was less than 70% of minimum ultimate tensile strength of tendon, and cut even with the remaining strands. Based on the results of the Containment unbonded post-tensioning examination, the Containment post-tensioning system has experienced no abnormal degradation and remains in an acceptable condition. 3-1
Technical Specification 5.5.9 - Steam Generator Tube Inspections NOTE The following discussion on the steam generator tubing inspections, in addition to fulfilling the reporting requirements of ASME Section XI for Inservice Inspection activities, constitutes the report required by VEGP Technical Specification 5.6.10.b to be submitted to the NRC within twelve (12) months following completion of the steam generator tube inspections. Accordingly, a separate submittal is not being made to the NRC regarding the inspection of the steam generator tubes performed during the eleventh maintenance/refueling outage (2RI 1) at VEGP-2. Introduction During 2RI I the Steam Generator Maintenance Services Group of the Westinghouse Nuclear Services Division performed eddy current testing of two (2) Westinghouse Model F steam generators (SGs), numbers I and 4, in parallel from September 25th to October 5th, 2005. At the start of 2RI 1 each SG had 5626 tubes with five (5) plugged tubes in SG I and twenty-one (21) plugged tubes in SG 4. The base inspection scope for SGs I and 4 follows: Bobbin examination of the full length of 100% of the tubes except for the U-bends of Rows I and 2. +PointTM RPC examination of the inlet top of tubesheet of 50% of the tubes. +PointTm RPC examination of the U-bends of 50% of the tubes in Row I and 2. +PointTm RPC examination of areas of special interest identified during the bobbin examination. +PointTN! RPC examination of 100% of hot leg (HL) straight length Dents and Dings > 5 volts, not previously inspected during the current inspection sequential period (as defined by EPRI Guidelines). +PointT1l RPC examination of 100% of Over-Expansions (OXP) and Bulges (BLG) located within the upper 17" of the hot leg tubesheet area. +PointTm RPC examination of 60-80 tubes at TSPs 6 and 7 on HL side to gage quatrefoil blockage by deposits +PointTm RPC examination of areas of special interest related to possible loose parts. Visual inspection of previously installed mechanical plugs. All of the Hot Leg BLGs with amplitudes > 18V and OXPs with excess diameters > 1.5 mils in the top 17 inches of the tubesheet were examined with the +Point probe for the first time during this inspection. No circumferential PWSCC indications were found in these areas and therefore no stabilization or plugging due to PWSCC were required. The inspection was limited to the top 17 inches of the tubesheet based on the approval of the site's change to Technical Specification 5.5.9, "Steam Generator (SG) Tube Surveillance Program", which modified the inspection requirements for portions of the SG tubes within the hot leg tubesheet region (Amendments 138 and 117 for VEGP Units I and 2, respectively). This report satisfies the 12-month NRC report required by VEGP Technical Specification 5.6.10.b, in addition to fulfilling the ASME Section XI report for Inservice Inspection activities. Note that personnel qualifications, test equipment certifications, and calibration data are not in this report, but are contained in the Westinghouse Electric Company, Nuclear Service Division, Steam Generator Maintenance Services Field Service Report, MSR-FSR-1419-GBE. That report will be available at the plant site for review upon request. 4-1
Tube Inspection Plan Steam generator tube inspections conducted during 2RI 1 met or exceeded the recommendations made in the EPRI report 1003138-VIR6, "PWR Steam Generator Examination Guidelines", which were adopted by SNC for steam generator tube inspections. The VEGP inspection plan requires that 100% of the tube population be inspected from two steam generators each outage, except for rows I and 2 U-bends which are inspected in accordance with the RPC program. This inspection plan meets the requirements of 1003138-V1R6 and is required by site procedure 84002-C, "Steam Generator Inspections and Reports". No scope expansions were required as a result of this inspection. The eddy current inspection program was conducted in accordance with Westinghouse Field Procedure MRS 2.4.2 GPC-3 Rev. 11, "Eddy Current Inspection of Preservice and Inservice Heat Exchanger Tubing." Inspection probes used were in accordance with the Probe Authorization. The test configurations and acquisition rates were in accordance with the Eddy Current Acquisition Technique Sheets (ACTS). In addition to the above 2R1 1 data collected, a review was performed of all 2R9 bobbin data for SG I and 4 to look for artifacts that would indicate susceptibility to SCC similar to that found at Seabrook and Braidwood. There were no similar indications found in the Vogtle Unit 2 bobbin data for SGs 1 and 4. The review was performed using information provided by the Electric Power Research Institute (EPRI) Steam Generator Management Program (SGMP). With this review of the lower rows (rows 1 through 10) in SG I and SG 4, the lower row review is now completed for all 4 VEGP Unit 2 SGs. For those SG 1 and SG 4 higher row tubes (rows 11 through 59) which were identified in the review for special monitoring as being potentially more susceptible to crack initiation at TSPs, no potential ODSCC precursor signals at the TSPs were reported. Data Evaluation Resolution analysis and data management were performed on site. In addition, an SNC Level III was located at the Vogtle site to facilitate the evaluation of eddy current data and to perform the duties of the independent qualified data analyst. Primary analysis was performed manually at Westinghouse's Waltz Mill Facility. Secondary analysis was performed by Zetec, using Computerized Data Screening (CDS), at their facility in Snoqualmie, Washington, under direct contract with Southern Nuclear. Two T-I lines were used to connect Waltz Mill to the Vogtle site. Data was collected using TechradTm TC6700 eddy current testers. ANSERTm software was used for acquisition, data quality monitoring (DQM) and for primary and resolution analyses. STMaxTm software was used for Data Management. Tube Wear Because of a 25% volumetric indication at Row 42 Column 93 (R42C93) on cold leg side, within 1" above the tubesheet, a visual inspection was performed on the secondary side to ensure that a loose part was not responsible for the indication. A wire similar to scaffold bailing wire was found at this location and removed. No objects were known to be left in SG 4 after 2RI 1. The remaining wear indications were at AVB's. Tables 1 and 2 list the locations and percent of wall thickness penetration for indications, including those due to wear, in all tubes having indications identified during the 2RI 1 inspection, including expansions. 4-2
Tube Plugming No tube plugging or stabilization was required during the 2R1 I inspection. Final Results Based on prior inspection results and the numbers of indications observed, as well as the change rates, there exist no "Active" damage mechanisms in the Vogtle 2 SGs. AVB wear is the only systematic degradation mechanism that has been observed at Vogtle 2. Based on the applications of conservative AVB growth rates, the condition of the Vogtle 2 SGs tubes have been analyzed with respect to continued Operability of the SGs, to not exceed the structural integrity recommendations of draft Reg. Guide 1.121 until the end of Cycle (EOC) 12. Conservative projection of the AVB wear in SG 2 and SG 3 to EOC12 indicates that all structural criteria will continue to be satisfied for these SGs as well until the next planned inspection (2R12) for these SGs. 2R11 Indications Tables I and 2 list the percent of wall thickness penetration for indications identified during the 2R1 I inspection of SG I and SG 4. 4-3
TABLE I - SGI PERCENT WALL THICKNESS PENETRATION FOR EACH INDICATION Page l of 2 SO - I LISTING OF U2R11 PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTSI Vogtle 2 U2R11 GBE 20050901 1010312005 13:37:17 t- + ++ +--,---,----+----- + ---------- +-----------+-----+----- +------------+- I ROW COL VOLTS DEG IND PER CHN LOCN INCHI INCHZ BEGT ENDT PDIA PTYPE CAL Li _+_+ _+_---_----_----+-----+- _+_ __----+__-+------+-- +--__+_- _-+_- _+- + I 30 10 .38 0 PCT 13 P2 AV6 .27 TEH TEC .560 ZBALL 46 Cl t 35 14 .41 0 PCT 15 P2 AV4 .25 TEH TEC .560 ZBALL 46 Ct 36 17 .27 0 PCT 10 PZ AV6 -.54 TEH TEC .560 ZBALL 44 Cf 1 36 17 .43 0 PCT 15 P2 AVO .16 TEH TEC .560 ZBALL 44 Cf 1 41 20 .19 0 PCT 8 P2 AVI .00 TEH TEC .560 ZBALL 50 Cf 1 41 20 .55 0 PCT 17 P2 AVZ .08 TEH TEC .550 ZBALL 50 Cl 1 41 20 .37 0 PCT 13 P2 AV3 .11 TEH TEC .550 ZBALL 50 C1 1 41 20 .42 0 PCT 14 PZ AV4 -.05 TEH TEC .560 ZMALL 50 Cl 1 41 20 .40 0 PCT 14 P2 AV5 .02 TEH TEC .560 ZMALL 50 Cl t4 20 .57 0 PCT IS P2 AV2 .I0 TEH TEC .560 MALL 50 C1 44 22 .44 0 PCT 15 P2 AV4 .07 TEH TEC .560 ZMALL 50 C1 1 44 22 .35 0 PCT 13 P2 AVO .00 TEH TEC .560 ZBALL 50 Cl 41 23 .43 0 PCT 14 P2 AV5 .00 TEH TEC .560 ZMALL 48 Ct 1 41 23 .28 0 PCT 9 P2 AV6 .00 TEH TEC .560 ZBALL 48 Cl 1 44 23 .38 0 PCT 13 P2 AVZ .00 TEH TEC .560 ZBALL 48 Cl 1 44 23 .53 0 PCT 16 P2 AV3 .00 TEH TEC .560 ZBALL 48 Cf 1 44 23 .53 0 PCT 17 P2 AV4 .00 TEH TEC .560 ZBALL 48 Cl 1 44 23 .93 0 PCT 25 P2 AV5 .03 TEH TEC .560 ZMALL 48 Cl 1 46 24 .41 0 PCT 14 P2 AV4 .10 TEH TEC .560 ZBALL 50 Cl 34 25 .30 0 PCT 9 P2 AVI .11 TEH TEC .560 ZBALL 26 Cl 46 26 .59 0 PCT 18 P2 AV4 .00 TEH TEC .560 ZBALL 50 Cf 1 41 27 .39 0 PCT 11 P2 AV5 .20 TEH TEC .560 ZBALL 26 Cf I I 1 44 27 .29 0 PCT 10 P2 AV2 .00 TEH TEC .560 ZBALL 48 Cl 1 44 27 .33 0 PCT 11 P2 AV3 .00 TEH TEC .560 ZBALL 48 Cl 47 27 .82 0 PCT 23 P2 AVZ .00 TEH TEC .560 ZBALL 48 Cf 1 48 27 .27 0 PCT 1 PZ AV3 .00 TEH TEC .560 ZBALL 48 Cl 1 48 27 .41 0 PCT 14 P2 AV3 .00 TEH TEC .560 ZBALL 48 Cf 48 28 .46 0 PCT 15 P2 AVY .00 TEH TEC .560 ZBALL 50 Cl 50 28 1.04 0 PCT 26 P2 AV3 .00 TEH TEC .560 ZMALL 48 Cl l 50 28 1.29 0 PCT 29 P2 AV4 .0o TEH TEC .560 ZBALL 48 Cf 1 50 Z .33 0 PCT 11 P2 AV6 .00 TEH TEC .560 ZBALL 48 Cf I49 29 .31 0 PCT 10 P2 AV6 .00 TEN TEC .560 ZBALL 48 Cf I 4 32 .33 0 PCT 12 P2 A3 .11 TEH TEC .560 ZBALL 50 Cl 46 32 .48 0 PCT 16 P2 AV4 .02 TEH TEC .560 ZBALL 50 Cf 137 33 .26 0 PCT 10 P2 AV3 -.03 TEH TEC .560 ZBALL 26 Cl 1 53 33 .53 0 PCT 17 P2 AV4 .02 TEH TEC .560 ZBALL 48 Cf 1 53 34 .37 0 PCT 13 P2 AV3 .00 TEH TEC .560 ZBALL 50 Cf 1 53 34 .43 0 PCT 15 P2 AV4 .00 TEH TEC .560 ZBALL 50 Cf 1 37 35 .25 0 PCT 9 P2 AV3 .08 TEH TEC .560 ZBALL 26 Cl 1 47 36 .33 0 PCT 12 P2 AVI .00 TEH TEC .560 ZBALL 50 Cf 1 37 39 .29 0 PCT 11 P2 AV4 .00 TEH TEC .560 ZBALL 50 Cf +_ _+ + ---- _--------------------------------+._------ -+--.---- +- +-_ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 BEGT ENDT POIA PTYPE CAL Li + + + _-_+----_ _ + -_-+ -+ _+-----___-+-+ -4_ +--- +_ _- +- + 1 44
TABLE I - SGI PERCENT WALL THICKNESS PENETRATION FOR EACH MNDICATION Page 2 of 2 SG - 1 LISTING OF U2RI1 PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTS) Vogtle 2 U2R11 GBE 20050901 10/03/2005 13:37:17 + + + --- + + + +--- I ROW CoL VOLTS DEG IND PER CNN LOCK INCHI INCH2 sEGT ENDT PDIA PTYPE CAL Li +----+-------------- + _ _ + _ _ _ _ _ _ _ _ _ + _ _ + _ _ _ _ + _ _ _ _ _ _ _ + _ _ _ _ +I__ _ + _ _ _ + _ _ _ _ _ _ + _ 1 55 39 .22 0 PCT 9 P2 AVZ .0O TEN TEC .560 ZBALL 50 Cl 1 55 39 .33 0 PCT 12 P2 AV3 .0O TEN TEC .560 ZBALL So C1 1 54 50 .33 0 PCT 10 P2 AVZ .00 TEN TEC .560 ZBALL 52 CI 1 54 50 .40 0 PCT 13 P2 AV3 .00 TEN TEC .560 ZBALL 52 C1 58 53 .32 0 PCT 10 P2 AV1 .00 TEN TEC .560 ZBALL 52 Cl 59 68 .36 0 PCT 12 P2 AVI .16 TEN TEC .560 ZBALL 64 Cl 1 44 72 .33 0 PCT 11 P2 AV6 .00 TEN TEC .560 ZBALL 64 CI 1 58 72 .36 0 PCT 12 PZ AVI .00 TEN TEC .560 ZBALL 64 Cl 1 58 73 .37 0 PCT 12 PZ AVI .00 TEH TEC .560 ZBALL 64 C1 1 35 74 .30 0 PCT 11 P2 AV4 .20 TEN TEC .560 ZBALL 10 Cj I .I 1 58 75 .52 0 PCT 17 P2 AV6 .00 TEN TEC .560 ZBALL 40 Cl 1 55 81 .29 0 PCT 10 PZ AVZ .00 TEN TEC .560 ZBALL 64 Cl 1 53 89 .35 0 PCT 12 PZ AV5 .00 TEN TEC .560 ZBALL 64 Cl 1 50 92 .31 0 PCT 11 P2 AV2 .17 TEN TEC .560 ZBALL 70 CI 50 93 .27 0 PCT 10 PZ AV3 .22 TEN TEC .560 ZBALL 70 C1 44 94 .36 0 PCT 12 P2 AVs .08 TEN TEC .560 ZBAR3 74 C1 48 96 .24 0 PCT 10 P2 AVZ .22 TEN TEC .560 ZBAR3 74 C1 47 99 .46 0 PCT 16 P2 AVZ .00 TEN TEC .560 ZBAR3 72 C1 1 47 99 .41 0 PCT 15 P2 AVs .00 TEN TEC .560 ZBAR3 72 C1 1 43 100 .30 0 PCT 12 PZ AV2 .03 TEN TEC .560 ZBAR3 74 CI 1 43 100 .67 0 PCT 21 P2 AV3 .06 TEN TEC .560 ZBAR3 74 C1 43 100 .75 0 PCT 22 P2 AV4 -. 09 TEN TEC .560 ZBAR3 74 Cl 1 43 lee .34 0 PCT 13 P2 AV5 .36 TEN TEC .560 ZBAR3 74 C1 I 29 105 .21 0 PCT 8 P2 AV2 .10 TEN TEC .560 ZBAR3 72 C1 1 29 112 .28 0 PCT 9 P2 AV2 .03 TEN TEC .560 ZBAR3 82 CI ROW COL VOLTS DEG IND PER CHN LOCN INCHI INCH2 BEGT ENDT PDIA PTYPE CAL LI 4------------+----- + +-_-- 4---+- Tubes: 44 Records: 66 2 4-5
TABLE 2 - SG4 PERCENT WALL THICKNESS PENETRATION FOR EACH INDICATION Page 1 of 4 SG - 4 LISTING OF U2Rll PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTS) Vogtle 2 U2RI1 GBE 20050901 10/03/2005 13i37,l8 +.- + ++----+----+----+----+---- I ROW COL VOLTS DEG IND PER CNN LOCN INCH1 INCH2 BEGT ENDT PDJA PTYPE CAL LI +-++----+--------+--------+ +-+-- 1 30 9 .52 0 PCT 19 P2 AV5 .eo TEN TEC .560 ZBAR3 10 Cl I 27 12 .18 0 PCT 16 P2 AV6 .29 TEH TEC .560 ZBAR3 12 C: I I 1 36 13 .30 0 PCT 13 P2 AV3 .18 TEN TEC .560 ZBAR3 10 Cl I I 1 29 14 .28 0 PCT 10 P2 AV6 .13 TEN TEC .560 ZBAR3 12 C I I 36 14 .39 0 PCT 15 P2 AV2 .00 TEN TEC .560 ZBAR3 le CI I 43 21 .34 0 PCT 10 P2 AV5 .00 TEN TEC .56e ZBAR3 12 CI 42I 1 45 22 .25 0 PCT 11 P2 AV2 .00 TEN TEC .560 ZBAR3 10 Cj I 45 22 .26 0 PCT 12 P2 AV3 .00 TEH TEC .560 ZBAR3 10 ce 1 45 23 .25 0 PCT 10 P2 AV2 .00 TEN TEC .560 ZBAR3 12 CI 45 23 .28 0 PCT 10 P2 AV3 .13 TEN TEC .560 ZBAR3 12 Cf I 45 23 .36 0 PCT 11 P2 AV -.16 TEN TEC .560 ZBAR3 12 Oj I I 1 46 26 .41 0 PCT 15 P2 AV4 .00 TSH TEC .560 ZBAR3 24 Cf 1 46 26 .44 0 PCT 16 P2 AV6 -.03 TSH TEC .560 ZBAR3 24 Cl 46 26 .21 0 PCT 8 P2 AV4 -. 11 TEN TEC .560 ZBAR3 86 Ce I46 26 .39 0 POT 14 P2 AV6 -.11 TEN TEC .560 ZBAR3 86 Cf I 4 44 29 .50 0 PCT 14 Pz AV3 -.03 TEN TEC .560 ZBAR3 28 Of I 44 29 .50 0 PCT 14 P2 AV4 .03 TEN TEC .560 ZsAR3 28 Cl I 46 31 .38 0 POT 14 P2 AV4 .00 TEN TEC .560 ZBAR3 24 CI 46 31 .39 0 PCT 12 P2 AV5 .00 TEN TEC .560 ZBAR3 24 Cl 46 31 .43 0 PCT 12 P2 AV4 .03 TEN TEC .560 ZBAR3 24 Cf I46 32 .59 0 POT 22 P2 AV3 .03 TEN TEC .560 ZBAR3 30 Cl 48 31 .25 0 PCT 9 P2 AV3 -. 07 TEN TEC .560 ZBAR3 28 cl 48 31 .43 0 PCT 12 P2 AV4 .03 TEN TEC .56e ZBAR3 28 Cl lI I 45 32 .96 0 PCT 22 P2 AV3 .13 TEN TEC .560 ZBAR3 32 0l I 52 33 .53 0 PCT 15 P2 AV2 -.05 TEN TEC .560 ZBAR3 28 CI 52 33 .62 0 PCT 19 P2 AV3 .13 TEN TEC .560 ZBAR3 28 CI 1 52 33 .55 0 PCT 18 P2 AV4 .00 TEN TEC .560 ZBAR3 30 CI 1 52 33 1.70 0 PCT 34 P2 AV5 .13 TEN TEC .560 ZBAR3 28 CI I 52 33 .42 0 PCT 15 P2 AV6 3.0 TEN TEC .560 ZBAR3 28 Ol 5 43 34 .39 0 PCT 11 P2 AV2 -.73 TEN TEC .560 ZBAR3 30 Cf 1 53 34 .27 0 PCT 9 P2 AV6 -. 18 TEN TEC .560 ZBAR3 30 Cl I 51 35 .71 0 PCT 18 P2 AV4 .00 TEN TEC .560 ZBAR3 30 Cf I I I 54 35 .29 0 PCT 11 P2 AV5 -. 08 TEN TEC .560 ZBAR3 28 Cf I 54 35 .32 0 PCT 12 P2 AV6 -. 15 TEN TEC .562 ZBAR3 28 CI 5 43 39 .21 0 PCT 12 P2 AV4 -.03 TEN TEC .560 ZBAR3 28 Cf I I 35 36 .47 0 PCT 14 P2 AV2 -. 03 TEN TEC .560 ZBAR3 30 Cl 1 51 39 .33 0 PCT 11 P2 AV3 .08 TEN TEC .560 ZBAR3 30 Cf 51 39 .64 0 PCT 17 P2 AV4 .16 TEN TEC .560 ZBAR3 30 CI 4ROW CL VOLTS CEG INC PER CNN LOON INCHI INCH2 BEGT ENDT PDIA PTRPE CAL Ll II 3+ 39 + 2 + +C + + 2 +V + 1 TE + E +56 +R 28 + + 1I 4-6
TABLE 2 - SG4 PERCENT WALL THICKNESS PENETRATION FOR EACH INDICATION Page 2 of 4 SG - 4 LISTING OF U2R11 PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTS) Vo9tie 2 U2R11 GBE 20050901 10/03/2205 13:37:18 +___ +___ +___ -_+__---- + __----+----_ +___ 4 +-----+--------- +-+- + I ROW COL VOLTS DEG IND PER CHN LOCN INCHI INCH2 BEGT ENDT PDIA PTYPE CAL Li +-- ---- +---- +-+ +-------------+- I I 47 41 .39 0 PCT 12 P2 AV2 -.10 TEN TEC .560 ZBAR3 30 Cl 47 41 .33 9 PCT 11 P2 AV3 -.21 TEN TEC .560 ZBAR3 30 CI I I 1 44 42 .43 0 PCT 15 P2 AV3 -.26 TEN TEC .560 ZBAR3 28 Cl I 44 42 .62 0 PCT 20 P2 AV4 -.16 TEN TEC .560 ZBAR3 28 Cl 1 44 42 .97 0 PCT 26 P2 AV5 .11 TEH TEC .560 ZBAR3 28 Cl I 44 42 .49 o PCT 17 P2 AV6 -.03 TEN TEC .560 ZBAR3 28 Cl I I 1 56 42 .43 0 PCT 15 P2 AV6 .03 TEH TEC .560 ZBAR3 28 C; I I 1 51 43 .30 0 PCT 10 P2 AV3 .00 TEN TEC .560 ZBAR3 30 Cl I 51 43 .43 o PCT 13 P2 AV4 .00 TEN TEC .560 ZBAR3 30 CI 51 43 .46 o PCT 13 P2 AV5 -.16 TEN TEC .560 ZBAR3 30 C; 1 I 53 43 .41 0 PCT 12 P2 AV1 .49 TEH TEC .560 ZBAR3 30 Cf 1 53 43 1.70 0 PCT 31 P2 AV3 .00 TEH TEC .560 ZBAR3 30 Ci 5 S3 43 .64 0 PCT 17 P2 AV4 .00 TEN TEC .560 ZBAR3 30 CI 1 53 43 .58 o PCT 16 P2 AV5 -.03 TEH TEC .560 Z8AR3 30 C; I I 1 44 44 .63 0 PCT 20 P2 AV3 .03 TEH TEC .560 ZBAR3 28 CI 53 44 .61 0 PCT 17 P2 AV3 .13 TEH TEC .560 ZBAR3 30 Cl 52 45 .31 o PCT 6 P2 AV2 .11 TEH TEC .560 ZBAR3 28 CI 52 45 .34 0 PCT 9 P2 AV4 .03 TEH TEC .560 ZBAR3 28 C; 52 45 .37 0 PCT 10 P2 AV4 .02 TEN TEC .560 ZBAR3 28 C; 5T i 56 45 .39 o PCT 11 P2 AVs .03 TEH TEC .560 ZBAR3 28 Cl I I 1 43 47 .43 9 PCT 13 P2 AV2 .00 TEH TEC .560 ZBAR3 30 C; I I 56 47 .70 0 PCT 19 P2 AV3 -.11 TEH TEC .560 ZBAR3 28 C; S 4I I 57 48 .34 0 PCT 11 P2 AV2 -.13 TEN TEC .560 ZBAR3 30 Cl 1 57 48 .76 0 PCT 19 P2 AV3 -.15 TEN TEC .560 ZBAR3 30 Cl I57 48 .51 9 PCT 15 P2 AV4 .18 TEN TEC .560 ZBAR3 30 Cl i 57 48 1.01 O PCT 23 P2 AV5 -.16 TEH TEC .560 ZBAR3 30 Cl 46 51 .38 0 PCT 11 P2 AV6 .05 TEH TEC .560 ZBAR3 40 C; 43 53 .34 o PCT 12 P2 AV3 -. 11 TEH TEC .560 ZBAR3 40 Cl I 44 54 .35 e PCT 11 P2 AVI .00 TEN TEC .560 ZBAR3 42 C; 44 54 .40 o PCT 12 P2 AV5 .90 TEN TEC .560 ZBAR3 42 C; 51 54 .90 o PCT 24 P2 AV4 .15 TEN TEC .560 ZBAR3 42 C; 51 54 .36 o PCT 11 P2 AVS .28 TEN TEC .560 ZBAR3 42 C; 1s 55 .26 o PCT 12 P2 AV3 .oe TEN TEC .560 ZBAR3 so C 51 55 .44 0 PCT 17 P2 AVZ .00 TEN TEC .560 ZBAR3 80 C; 51 55 .83 0 PCT 15 P2 AV3 .00 TEN TEC .560 ZBAR3 80 C; 12 57 .73 88 PCT 14 3 TSH .34 TSH TSH .560 ZPS3C 81 H; 48 57 .45 0 PCT 15 P2 AV3 -.e5 TEH TEC .560 ZBAR3 82 Cl 48 57 .34 0 PCT 12 P2 AV4 -.08 TEN TEC .560 Z8AR3 82 C; 48 57 .58 o PCT 19 P2 AVs .16 TEN TEC .560 ZBAR3 82 C; 43 58 .22 0 PCT 11 P2 AV5 .00 TEN TEC .560 ZBAR3 80 C; 45 58 .66 0 PCT 22 P2 AV3 .21 TEN TEC .560 ZBAR3 80 C; 45 58 .26 0 PCT 12 P2 AV4 -.13 TEN TEC .560 ZBAR3 s8 C; 45 58 .50 0 PCT 19 P2 AVs -.16 TEN TEC .560 ZBAR3 80 C; +____+____+_____ _+____+ ____+_-___+_--_-- -_---_---_---- + -+ ___+ ___- __+_____-+______-+__ ROW COL VOLTS DEG IND PER CNN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL LI +--------------+--- +___+__ _+
. +------
+____+____ _+ _+__-+ 2 4-7
TABLE 2 - SG4 PERCENT WALL THICKNESS PENETRATION FOR EACH INDICATION Page 3 of 4 SG - 4 LISTING OF U2R11 PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTS) Vo 9tle 2 U2Rll GBE 20050901 10/03/2005 13s37tl8 ~ -+----+ 4-----+----+------------4--------- --------------- +--- ------- I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL LI + +-_-_+-____-+-_--_----_-____+---_--------------+---- +------+--------- I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I (8 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII 44 44 44 51 59 39 39 39 39 39 43 43 45 45 52 52 52 52 52 52 52 52 52 43 43 43 43 43 50 43 52 52 52 57 52 52 38 57 37 58 43 57 52 59 59 59 60 63 64 64 64 64 64 65 65 66 66 66 66 66 66 66 66 66 66 66 68 68 68 68 69 70 71 71 71 71 71 72 72 73 73 74 75 76 76 78 .40 .49 .42 .41 .36 .49 .23 1.23 .38 .69 .46 .22 .46 .51 .37 .61 .32 .31 .70 .36 .31 .72 .35 .18 .61 .84 .73 .56 .39 .38 .30 .77 .87 .36 .95 .44 .27 .44 .38 .39 .52 .57 .42 0 PCT 14 0 PCT 17 0 PCT 15 0 PCT 17 0 PCT 15 0 PCT 18 0 PCT 10 0 PCT 31 0 PCT 15 0 PCT 22 0 PCT 18 0 PCT 11 0 PCT 18 0 PCT 19 0 PCT 15 0 PCT 21 0 PCT 14 0 PCT 11 0 PCT 21 0 PCT 13 0 PCT 11 0 PCT 21 0 PCT 13 0 PCT 9 0 PCT 21 0 PCT 25 0 PCT 23 0 PCT 20 0 PCT 15 0 PCT 14 0 PCT 13 0 PCT 24 0 PCT 26 0 PCT 11 0 PCT 27 O PCT 17 0 PCT ,10 0 PCT
- 13 0
PCT '15 0 PCT 16 0 PCT 15 0 PCT 16 0 PCT 12 P2 AV1 P2 AV3 P2 AV4 P2 AV3 P2 AV6 P2 AVI P2 AV2 P2 AV3 P2 AV4 P2 AV6 P2 AV4 P2 'AV6 P2 AV2 P2 AV5 P2 AV1 P2 AV2 P2 AV3 P2 AVI P2 AV2 P2 AV3 P2 AV1 P2 AV2 P2 AV3 P2 AVI P2 AV3 P2 AV4 P2 AV5 P2 AV5 P2 AV3 P2 AV4 P2 AVI P2 AV2 P2 AV3 P2 AV6 ,.; 1 P2 AV2 P2 AV3 P2 AV5 P2 tAV2 P2 AV3 P2 AV2 P2 AV5 P2 AV5 P2 AV4 .00 -.10 -.05 -. 15 .00 -.06 -.09 .10 .03 -. 22 .00 .00 .13 .11 .03 .00 -. 03 .00 -.05 -.20 .09 .27 -. 10 .44 .00 .00 .00 .24 .00 .19 .00 .00 .11 .00 .00 .00 .08 -. 16 -. 07 .00 .00 -. 10 .00 TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEN TEC TEN TEC TEN TEC TEH TEC TEH TEC TEN TEC TEN TEC TEH TEC TEH TEC TSH TEC TSH TEC TSH TEC TEN TEC TEN TEC TEN TEC TEN TEC TEH TEC TEH TEC TEH TEC TEH TEC TEH TEC TEN TEC TEH TEC TEN TEC TEN TEC TEN TEC TEN TEC TEN TEC TEN TEC TEH TEC TEN TEC TEH TEC TEN TEC TEH TEC TEH TEC TEH TEC TEN TEC TEN TEC .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 Z8AR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 ZBAR3 .560 Z8AR3 .560 ZBAR3 .560 ZBAR3 .560 Z8AR3 .560 Z3AR3 82 Ct 82 Ct 82 CI 80 CI 48 Cl 60 Cj 60 Cl 60 Cl 60 Cl 60 Cl 80 Cj 80 Cl 80 Cl 80 Cl I 48 Cl 48 Cl 48 Ct 82 Ct 82 Cl 82 Cl 86 Ct 86 Cl 86 Ct I 80 Cl B0 Ct 80 Ct 80 Ct 80 Ct 4 CI 60 Ct 62 Ct 48 Cl 48 Cl 48 Cl 50 Ct I 48 CI 48 Ct 62 CI 50 Ct I 60 CI 48 Ct 1 56 Cl 50 Ct 56 CI 4 CI +____+__ -_+_________+____+____+_-_-+-__ +_ __+_________+______ __+___-----+ +---- _____+ ___+_ ____+ I ROW COL VOLTS DEG IND PER CNN LOCN INCHI INCH2 BEGT ENDT PDIA PTYPE CAL LI +___ + _______+----__ _+_ _+ __+_ _+ +__- +----__ +_----__+ -__ __+-___ _+_ +__ 3 4-8
TABLE 2 - SG4 PERCENT WALL THICKNESS PENETRATION FOR EACH INDICATION Page 4 of 4 L SG - 4 LISTING OF U2R11 PERCENT THROUGH WALL INDICATIONS (TECH SPEC REPORTING REQUIREMENTS) Vogtle 2 U2R11 GBE 20050901 10103/2005 13:37:18 +___+___+_______+__-----+____+___+___+___-----+-_______+____-____+____+-------+-_____+-_____+____-_ I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL Li +__ _+_ __+ ___+___---------_------ -+----- +---- +-------+ +--- __+ __-__+-_ 57 78 .46 0 PCT 13 P2 AV6 .e0 TEH TEC .560 ZBAR3 56 C; 27 79 .27 0 PCT 9 P2 AVs .00 TEH TEC .560 ZBAR3 50 C) 4S 79 .36 o PCT 12 P2 AV2 .es TEH TEC .s5e ZBAR3 58 C I 48 79 .22 0 PCT 7 P2 AV3 .66 TEH TEC .560 ZBAR3 58 Cj 53 e2 .38 o PCT 11 PZ AV5 .es TEH TEC .560 ZBAR3 56 C1 l56 sz .47 o PCT 14 P2 AV2 -.e3 TEH TEC .560 ZBAR3 56 C1 49 73 .50 0 PCT 16 P2 AV3 -.08 TEH TEC .560 ZBAR3 58 Cl 54 B3 .39 o PCT 13 P2 AV5 -. 18 TEH TEC .560 ZBAR3 58 Cl I55 3 .43 o PCT 14 P2 AV5 .43 TEH TEC .560 ZBAR3 58 C i 43 85 .36 0 PCT 12 P2 AV4 .05 TEH TEC .560 ZBAR3 58 Cj 44 85 .34 o PCT 12 P2 AV3 .2e TEH TEC .560 ZBAR3 58 Cl 46 88 .25 0 PCT 5 P2 AV3 .0e TEH TEC .560 ZBAR3 56 C) 53 89 .42 o PCT 14 P2 AV6 .oe TEN TEC .560 ZBAR3 58 Cl 6 1 92 .27 o PCT 11 P2 AV .40 TEH TEC .560 ZBAR3 60 Cl I i 42 93 1.61 58 PCT 25 3 TSC .99 TSC TSC .560 ZPS3C 110 Cl 49 93 .56 0 PCT 18 P2 AV4 -.05 TEH TEC .560 ZBAR3 62 C) 49 93 .92 0 PCT 26 P2 AV5 -.18 TEH TEC .560 ZBAR3 62 C) 49 96 .43 0 PCT 15 P2 AV2 -. 4s TEH TEC .560 ZBAR3 62 C; 48 97 .26 0 PCT 12 P2 AV2 -.05 TEH TEC .560 ZBAR3 62 CI 44 97 .31 0 PCT 11 P2 AV3 -. 11 TEH TEC .560 ZBAR3 65 C) 4e 106 .31 0 PCT 11 P2 AV1 .03 TEH TEC .560 ZBAR3 64 C 40 186 .27 0 PCT le P2 AV3 .00 TEH TEC .560 ZBAR3 64 C1 32 809 .38 0 PCT 12 P2 AV6 .02 TEH TEC .560 ZBAR3 66 C) 31 113 .27 0 PCT 7 P2 AV2 -. 44 TEN TEC .560 ZBAR3 66 C; +__+_________+____+____+____+-------------------------+------+----------------------------------------- I ROW COL VOLTS DEG IND PER CHN LOCN INCH1 INCH2 BEGT ENDT PDIA PTYPE CAL Li +----+----+---------+----+----+----+----+----+---------+--------------+_---+-__-__+______+______+__+ Tubest 66 Recordse 153 4 4-9
SOUTHERNA COMPANY C7 C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1 I ASME Section )a Catlltem No. Augmented Examination Requirement(s) Component IDI Description-- Examination Procedure(s) Calibration Block(s) Exam Sheet No.(s) Results Remarks B-B NA 21201-V6-002-W05 ES-MISN-V-41 1 403A, 411A B2.11 B-B B2.12 LOWER SHELL TO LOWER HEAD WELD NA 21201-V6-002-W09 LOWER SHELL LONGITUDINAL WELD ES-MISN-V-411 403A S05V2U5021 S05V2U5022 S05V2U5023 S05V2U5024 S05V2U5053 S05V2U5054 S05V2U5055 S05V2U50-56 S05V2U5025 S05V2U5026 S05V2U5027 S05V2U5028 S05V2U5033 S05V2U5035 S05V2U5034 S05V2U5036 S05V2V0162 NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI NRI 84% Coverage Obtained due to pads & support sidrt weld. Ref. RR-7. NA B-G-1 B6.30 NA B-G-1 B6.30 B-G-2 B7.30 B-G-2 B7.50 B-G-2 B7.50 B-G-2 B7.50 B-G-2 B7.50 NA NA NA NA 21201-V6-001-BO2R CLOSURE HEAD STUDS 21201-V6-001-B26R CLOSURE HEAD STUDS 21201-B6-004-B01 - B32 PRIMARY MANWAY BOLTING 21204-078-8 FB 1.5 FLANGE BOLTING ASSEMBLY FOR FE-0925 21204-079-11 FB 1.5S FLANGE BOLT ASSEMBLY FOR FE-0926 21208-043-16 FB 1.5' FLANGE BOLT ASSEMBLY FOR RC PUMP 002 21208-045-20 FB 1.5 FLANGE BOLT ASSEMBLY FOR RC PUMP 003 ES-MISN-V-482 ES-MISN-V-482 ES-MISN-V-715 ES-MISN-V-715 ES-MISN-V-715 ES-MISN-V-715 ES-MISN-V-715 S05V2V0099 S05V2V0100 419A 419A NRI NRI NA Sat Sat Sat Sat Sat NA NA NA NA NA S05V2V0158 S05V2V0159 Sectlon 5 1 of 16
SOUTHERNA COMPANY C7 C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I ASME Section Xl CatJltem No. Augmented Examination Requirement(s) Component ID/ Description Examination Procedure(s) Calibration Block(s) Exam Sheet No.(s) Results Remarks B-G-2 NA 21201-P6-002-B25 - B32 ES-MISN-V-715 S05V2V0161 Unsat Boric acid residue. Determined acceptable, no successive exams required. Ref. 105V2002 and Condition Report No. 2005108088. 75% Coverage due to plant mounted vibration monitoring equipment. Relief Request Required. B7.60 1.5 DIA SEALWATER HOUSING CAP SCREWS B-G-2 B7.60 B-G-2 B7.70 B-G-2 B7.70 B-H B8.20 B-N-1 B13.10 NA NA NA NA NA 21201-P6-002-B33 - B48 2 DIAMETER SEAL-WATER HOUSING BOLTS 21201HV8701A VALVE BOLTING (ISI-21201-036) 21204U6150 VALVE BOLTING (ISI-21204-045) 21201-V6-002-W35 SUPPORT SKIRT WELD 21201-V6-001-102 VESSEL CLOSURE HEAD INTERIOR (FSAR 5.3.3.7) ES-MISN-V-715 ES-MISN-V-715 ES-MISN-V-715 ES-MISN-V-505 ES-MiSN-V-735 S05V2V0160 S05V2V0208 Sat Sat Sat NRI NRI Sat NA NA NA NA NA S05V2V0207 8732 S05V21M0001 S05V2U5020 S05V2V0151 B-0 B14.10 B-0 B14.10 NA NA 21201-V6-001-W184 CRD HOUSING WELD 21201-V6-001-W185 CRD HOUSING WELD ES-MISN-V-605 S05V2P0008 NRI NA NRI NA ES-MISN-V-605 S05V2P0009 Section 5 2 of 16
SOUTHERNA COMPANY C C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR11 ASME Section )a Catjltem No. Augmented Examination Requirement(s) Component IDI Description Examination Procedure(s) Calibration Block(s) Exam Sheet No.(s) Results Remarks B-O 21201-B6-001-T01 VENDOR-ET 806A,B,C,D, 807AB MRSFSR-141 9-GBE NA Examination performed by Westinghouse. See Augmented Examination Section for Examnation Results. B16.20 TUBING - ENTIRE LENGTH OF SELECTED TUBES B-0 21201-B6-004-T01 VENDOR-ET 806A,B,C,D, 807AB MRS-FSR1419-GBE NA Examination performed by Westinghouse. See Augmented Examination Section for Examnation Results. B16.20 TUBING - ENTIRE LENGTH OF SELECTED TUBES C-A NA 21201-B6-002-W03 ES-MISN-V-41 1 409A S05V2U5045 S05V2U5046 S05V2U5047 S05V2U5048 RI RI NRI NRI No change from previously recorded indications. C1.10 UPPER SHELL BARREL C TO TRANSITION CONE WELD (98-VO05) C-A C1.10 C-A C1.10 NA NA 21201-B6-002-W04 TRANSITION CONE TO LOWER CONE END STUB BARREL WELD 21201-B6-003-W05 LOWER CONE END STUB BARREL TO LOWER SHELL BARREL B ES-MISN-V-41 1 ES-MISN-V-41 1 409A 409A S05V2U5041 S05V2U5042 S05V2U5043 S05V2U5044 S05V2U5029 S05V2U5030 S05V2U5031 S05V2U5032 NRI NRI NRI NRI NRI NRI NRI NRI NA NA 409A C-B NA 21201-B6-002-W19 ES-MISN-V-505 S05V2M0002 S05V2U5049 S05V2U5050 S05V2U5051 S05V2U5052 NRI NRI RI NRI NRI 50% Code Coverage: Ref. RR-
- 14. No change from previously recorded indications.
C2.21 16 MAIN FEEDWATER NOZZLE TO SHELL WELD C-B C2.22 NA 21201-B6-002-1R04 MAIN FEEDWATER NOZZLE INNER RADIUS ES-MISN-V416 409A S05V2U5057 NRI NA Section 5 3 of 16
SOUTHERN A COMPANY ASME Section Xl Cat~ltem No. C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-C C3.20 C-D C4.30 C-F-1 C5.41 C-F-1 C5.41 C-F-1 C5.41 Augmented Examination Requirement(s) NA NA NA NA NA NA NA NA NA Component IDI Description 21204-006-56 SUPPORT H006 21204-020-7 SUPPORT H008 21204-063-16 SUPPORT H006 21205-027-6 SUPPORT H008 21208-003-21 SUPPORT H022 21208-003-44 SUPPORT H007 21208-411-6 SUPPORT H021 21204-P6-003-B01 - B32 PUMP CASING STUDS 21204-P6-003-W02 C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s: ES-MISN-V-605 S05V: ES-MISN-V-605 S05V: ES-MISN-V-605 S05V: ES-MISN-V-605 S05V ES-MISN-V-605 S05V ES-MISN-V-605 S05V ES-MISN-V-605 S05V ES-MISN-V422 415A S05V ES-MISN-V-605 S05V C_ n Sheet 2P001 1 2P0007 2P0004 2P0001 2P0010 2P0012 2P0005 V2U506 2P0006 '2P0002 Results NRI NRI NRI NRI NRI NRI NRI NRI NRI Remarks NA NA NA NA NA NA NA NA 82% Coverage obtained due to portion of weld is located behind base cradle. Relief Request Required. NA NA PUMP CASING TO SUCTION NOZZLEWELD-21208-P6-002-WO1 PUMP CASING TO 6' SUCTION NOZZLE WELD 21208-P6-002-W02 DISCHARGE NOZZLE TO PUMP CASING ES-MISN-V-605 5051V NRI NA NRI NA ES-MISN-V-605 S05V2P0003 Section 5 4 of 16
SOUTHERN A COMPANY C7 C ASME Section XU Catjltem No. F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 Augmented Examination Requirement(s) Component ID! Description 21201-030-H611 MECH SNUBBER 21201-030-H614 RESTRAINT 21201-030-H616 RESTRAINT 21201-030-H621 STRUT 21201-030-H626 MECH SNUBBER 21201-042-H002 RESTRAINT 21201-042-H003 MECH SNUBBER 21201-042-H004 STRUT 21201-048-H004 STRUT 21204-023-H003 MECH SNUBBER 21204-023-H004 VAR SPRING 21204-034-H002 MECH SNUBBER Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s) ES-MISN-V-735 S05V. ES-MISN-V-735 S05V; ES-MISN-V-735 S05V; ES-MISN-V-735 S05V: ES-MISN-V-735 S05V: ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V Sheet 2V01 16 2V0131 2V0132 2V0129 2V0130 2V0201 2V0122 2V0179 2V0178 2V01 18 2V0143 V2V0102 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 5 of 16
SOUTHERN A COMPANY C' C ASME Section Xl Cat./Itemn No. F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 Augmented Examination Requirement(s) Component ID! Description 21204-044-1-009 RESTRAINT/LUGS 21204-045-HOOB UNDERSUPPORT 21204-078-HOOl RESTRAINT 21204-078-1-002 ANCHOR 21204-078-1-004 RESTRAINT 21204-125-HOOl VAR SPRING 21204-125-1-002 RESTRAINT 21204-125-1003 STRUT 21204-125-H-004 STRUT 21204-125-MHSN STRUT 21204-125-H-007 MECH SNUBBER 21204-125-HOOB STRUT Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VReI Examination Calibration Exam Procedure(s) Block(s) No.(sN ES-MISN-V-735 505v: ES-MISN-V-735 SosV: ES-MISN-V-735 SowV ES-MISN-V-735 SowV ES-MISN-V-735 505V: ES-MISN-V-735 505V ES-MISN-V-735 505V ES-MISN-V-735 505V ES-MISN-V-735 505V ES-MISN-V-735 505V ES-MISN-V-735 505V ES-MISN-V-735 505V Sheet 2V0199 2V0146 2V0176 2V0175 2V0177 2V0188 2V0202 2V0203 2V0189 2V0190 2V0123 '2V0191 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 6 of 16
SOUTHERN A COMPANY ASME Section XI Catiltem No. F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 F-A F1.10 Augmented Examination Requirement(s) Component IDI Description 21204-125-HO19 STRUT 21204-125-H020 RESTRAINT 21204-127-H007 MECH SNUBBER 21204-244-HOOl RESTRAINT 21204-244-H003 RESTRAINT 21204-244-H006 RESTRAINT 21204-244-HOO0 RESTRAINT 21204-244-HOIO RESTRAINT 21204-244-HO16 RESTRAINT 21208-043-H602 VAR SPRING 21208-045-1603 RESTRAINT 21208-047-H604 MECH SNUBBER C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s: ES-MISN-V-735 S05V; ES-MISN-V-735 S05V: ES-MISN-V-735 S05V: ES-MISN-V-735 S05V: ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V ES-MISN-V-735 S05V Sheet 2V0192 2V0193 2V0117 2V0147 2V0194 2V0195 2V0196 2V0108 2V0197 V2V0198 '2V0200 '2V0 15 C Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Sectlon 5 7 of 16
SOUTHERN A COMPANY ASME Section Xi Catiltem No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 Augmented Examination Requirement(s) Component ID! Description 21202-188-1-004 STRUT 21202-218-HR31 RESTRAINT/LUGS 21202-220-HR13 RESTRAINT 21202-220-HV14 RESTRAINT 21202-220-HR31 RESTRAINT 21202-225-H012 VAR SPRING 21204-006-H013 RESTRAINT 21204-006-H018 RESTRAINT/1LIGS 21204-006-H020 RESTRAINT 21204-008-HO10 RESTRAINT 21204-011-1-006 STRUT 21204-012-1006 UNDERSUPPORT C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1II Examination Calibration Exam Procedure(s) Block(s) No.(sN ES-MISN-V-735 505VI ES-MISN-V-735 S05VI ES-MISN-V-735 505VI ES-MISN-V-735 505VI ES-MISN-V-735 505VI ES-MISN-V-735 505VI ES-MISN-V-735 SO5VI ES-MISN-V-735 505V: ES-MISN-V-735 505VI ES-MISN-V-735 S05VI ES-MISN-V-735 S05V:I ES-MISN-V-735 505VI Sheet 2V0148 2V0144 2VO109 2VO106 2VO209 2VO145 2V0056 2V0057 2V0041 2V0149 NV0012 2V0076 C7 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 8 of 16
SOUTHERNA COMPANY C C0 ASME Section XI Cat~ltem No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 Augmented Examination Requirement(s) Component ID/ Description 21204-012-H012 RESTRAINT 21204-020-H005 MECH SNUBBER 21204-020-H008 MECH SNUBBER 21204-039-H032 VAR SPRING 21204-057-H007 RESTRAINT 21204-057-HOIO RESTRAINT 21204-057-H019 LISEGA HYD SNUBBER 21204-057-H039 VAR SPRING 21204-057-H602 RESTRAINT 21204-063-H003 UNDERSUPPORT 21204-063-H006 RESTRAINT/LUGS 21204-177-H002 UNDERSUPPORT Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s) ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 SO5V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 SO5V2 ES-MISN-V-735 SO5V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 Sheet !Vo1 11 !V0 101 !V0105 !V011o !V0120 !V0014 !V0226 !V0225 !V01 12 !V0001 !V0002 !VO070 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 9 of 16
SOUTHERN A COMPANY C ASME Section Xl CatJltem No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 Augmented Examination Requirement(s) Component IDI Description 21205-007-H019 MECH SNUBBER 21205-008-H036 UNDERSUPPORT 21205-008-H043 STRUT 21205-009-HOOB RESTRAINT 21205-027-H008 RESTRAINT 21206-001-H009 RIGID STRUT 21206-005-H009 STRUT 21206-008-H078 RESTRAINT 21208-139-H003 RESTRAINT 21208-139-HOIO VAR SPRING 21208-144-H006 STRUT 21208411-HOOl RESTRAINT Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s] ES-MISN-V-735 .05V ES-MISN-V-735 S05VI ES-MISN-V-735 S05VI ES-MISN-V-735 S05Vu ES-MISN-V-735 S05Vu ES-MISN-V-735 S05VX ES-MISN-V-735 S05VI ES-MISN-V-735 S05VI ES-MISN-V-735 S05Vx ES-MISN-V-735 S05VX ES-MISN-V-735 S05V ES-MISN-V-735 S05VI Sheet 'V0003 ?V0073 ZV0058 2V0004 2V0021 ZV01119 2VO107 ZV0022 2V0025 2V0013 2V0075 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 10 of 16
C SOUTHERNA COMPANY C7 C ASME Section Xl Cat./Item No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 Augmented Examination Requirement(s) Component ID/ Description 21208-411-H006 RESTRAINT 21208-411-H020 RESTRAINT 21208-411-H021 STRUT 21301-014-H006 MECH SNUBBER 21301-014-HOIO STRUT 21301-107-H002 MECH SNUBBER 21301-107-H003 MECH SNUBBER 21301-107-H004 MECH SNUBBER 21301-107-H005 MECH SNUBBER 21301-107-H007 VAR SPRING 21302-107-H005 RESTRAINT 21302-107-H006 STRUT Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s) ES-MISN-V-735 S05Vz ES-MISN-V-735
- S05V, ES-MISN-V-735 S05VI ES-MISN-V-735
- S05V, ES-MISN-V-735 S05V.
ES-MISN-V-735 S05V; ES-MISN-V-735 S05V: ES-MISN-V-735 S05V; ES-MISN-V-735 S05V: ES-MISN-V-735 S05V: ES-MISN-V-735 S05V ES-MISN-V-735 S05V Sheet /20221 /2V0113 2V0074 2V0061 2V0062 2V0079 2V0080 2V0081 2VW082 2V0086 2V0172 2V0204 Results Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA NA NA NA NA NA NA NA NA NA NA NA Section 5 11 of 16
C SOUTHERN A COMPANY C7 C: ASME Section XI Catlitem No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 Augmented Examination Requirement(s) NA Component IDI Description 21302-107-H007 STRUT 21302-107-H008 STRUT 21302-107-HO10 MECH SNUBBER 21302-107-HO15 VAR SPRING 21302-107-H016 MECH SNUBBER 21302-108-H017 MECH SNUBBER 21302-109-H014 VAR SPRING 21305-062-HOOI UNDERSUPPORT 21305-155-H002 VAR SPRING 21305-155-H003 MECH SNUBBER 21305-157-H002T MECH SNUBBER 21501-024-HOOl UNDERSUPPORT Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1 I Examination Calibration Exam Procedure(s) Block(s) No.(s) ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 Sheet 'V0205 'VO206 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MiSN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 S05V2V0227 S05V2V0114 S05V2V0087 S05V2VO085 S05V2V0084 S05V2V0088 S05V2V0065 S05V2V0064 505V2V0063 S05V2V0060 S05V2V0173 Results Sat Unsat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks NA Ref. INF No. 105V1 005 and Condition Report No 2005108758. NA NA NA NA NA NA NA NA NA NA Section 5 12 of 16
SOUTHERNA COMPANY C C' Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Biock(s) No.(s: ES-MISN-V-735 S05V; ASME Section )a Cati/tem No. F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.20 F-A F1.40 F-A F1.40 F-A F1.40 Augmented Examination Requirement(s) Component ID/ Description 21501-024-H003 RESTRAINT 21501-030-H002 RESTRAINT 21501-032-H004 UNDERSUPPORT 21501-033-H004 RESTRAINT 21501-039-H002 RESTRAINT 21501-039-H004 RESTRAINT 21515-008-H002 RESTRAINT 21515-009-HOOl UNDERSUPPORT 2151 5-000-H002 RESTRAINT 21201-B6-001-S01 Steam gen supp 21201-B6-001-S02 Steam gen supp 21201-B6-001-S03 Steam gen supp n Sheet 2V0174 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 ES-MISN-V-735 S05V2V0 168 S05V2V0171 S05V2V0211I S05V2V0169 S05V2V021 0 S05V2V0212 S05V2V0170 S05V2V0213 S05V2V0133 S05V2V0134 S05V2V0135 Results Unsat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Sat Remarks U-bolt instead of box restraint Ref. 105V1004 and Condition Report No 2005108504. NA NA NA NA NA NA NA NA NA NA NA NA NA NA Section 5 13 of 16
SOUTHERNA COMPANY C C ASME Section XI Catiltem No. F-A F1.40 F-A F1.40 F-A F1.40 F-A F1.40 F-A F1.40 F-A F1.40 F-A F1.40 R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11 Augmented Examination Requirement(s) NA NA NA NA NA NA NA N/A N/A NA NA NA Component ID/ Description 21201-B6-001-S04 Steam gen supp 21201-B6-001-S06 HYD SNUBBER 21201-B6-001-S08 HYD SNUBBER 21201-B6-001-S10 Upper supp frame 21201-B6-001-Sll Lower iat supp 21201-B6-001-S12 Lower lat supp 21201-B6-001-S13 Lower lat supp 21201-006-1-RI 31' NOZZLE TO ELBOW 21201-007-1-RI 31-NOZZLE TO ELBOW 21201-031-2-RI 2" PIPE TO ELBOW 21201-042-2-RI 2-PIPE TO ELBOW 21201-046-2-RI 2 PIPE TO ELBOW Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1 I Examination Calibration Exam Procedure(s) Block(s) No.(s) ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05V2 ES-MISN-V-735 S05VI ES-MISN-V-735 S05V\\ ES-MISN-V-735 S05V. ES-MISN-V-406 329A S05V: S05V; ES-MISN-V-406 329A S05V: S05V: ES-MISN-V-481 346A, 8734 S05V: ES-MISN-V-481 346A, 8734 S05V: ES-MISN-V-481 346A, 8734 S05V Sheet 'V0136 'V0137 2V0138 QVW139 2V0140 2V0141 2V0142 /2U5037 /2U5039 /2U5038 /2U5040 /2U5008 2U5010 22U5012 Results Sat Sat Sat Sat Sat Sat Sat NRI NRI NRI NRI NRI NRI NRI Remarks NA NA NA NA NA NA NA 50% Code Coverage: Ref. RR-10 50% Code Coverage: Ref RR-10 NA NA NA Section 5 14 of 16
C SOUTHERN A COMPANY C C ASME Section X) CatJltem No. R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11 R-A R1.11H R-A R1.11H R-A R1.11H R-A R1.11H Augmented Examination Requirement(s) NA NA NA NA NA NA NA NA NA NA Vog Component IDI Description 21201-048-1-RI 3 BRANCH CONNECTION TO PIPE (Al 87-0131) 21201-051-2-RI 2" PIPE TO ELBOW 21204-006-2-RI 24" VALVE TO ELBOW (Al 87-0131) 21204-024-21-RI 6" PIPE TO BRANCH CONNECTION 21204-025-27-RI 6" PIPE TO BRANCH CONNECTION 21204-177-11-RI 8" TEE TO PIPE 21201-031-3-RI 2" ELBOW TO PIPE 21201-042-3-RI 2' ELBOW TO PIPE 21201-046-3-RI 2" ELBOW TO PIPE 21201-051-3-RI 2" ELBOW TO PIPE gtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I Examination Calibration Exam Procedure(s) Block(s) No.(s] ES-MISN-V481 334A, 8734 S05VI Sheet 2U5016 Results Remarks NRI NA ES-MISN-V-481 ES-MISN-V-481
- 346A, 345A, 8734 8734 ES-MISN-V-481 ES-MISN-V-481 ES-MISN-V-481 ES-MISN-V-481 ES-MISN-V-481 ES-MISN-V-481 ES-MISN-V-481 304A, 8734 304A, 8734 414A, 8734 346A, 8734 346A, 8734 346A, 8734 346A, 8734 S05V21.5014 S05V21.501 S05V21.502 S05V2U5017 S05V2U5018 S05V21.503 S05V21.504 S05V21.5009 S05V2U5011I S05V21.5013 S05V2U.501 5 NRI NRI GEO NA 78.5%Code Coverage Obtained.
Relief Request Required. No Change from Previous Exam. NRI NA NRI NA NRI NRI NRI NRI NRI NRI NA NA NA NA NA Section 5 15 of 16
SOUTHERNA COMPANY C Vogtle Unit 2 Eleventh Refueling Outatge Inservice Inspection Report Interval 2, Period 3, 2VR1I ASME Section XI Catiitem No. Augmented Examination Requirement(s) Component ID0 Description Examination Procedure(s) Calibration Block(s) Exam Sheet No.(s) Results Remarks R-A NA 21208-005-CV1 10 ES-MISN-V-466 S05V2U507 RI See Condition Report 2005108176. R1.13 3-PIPE DS (FO-0200, 201, 202) Section 5 16 of 16
SYSTEM PRESSURE TESTS The following pressure tests on Class I and Class 2 components were included in the scope of the maintenance/refueling outage. These pressure tests included system functional tests, system hydrostatic tests, system inservice tests, and system leakage tests. It should be noted that the hydrostatic tests identified were performed to satisfy the "once per ten year" requirements described in ASME Section XI, Code Case N-498-1. These hydrostatic test packages are needed to document tests where the current inservice and functional tests do not fully meet the "once per 10-year" requirements of N-498-1. Boundaries for the pressure tests are described in the VEGP-2 Inservice Inspection Plan - Second 10-Year Interval document. Examination results are discussed in the applicable sections of this report document. The examination data for these pressure tests is available at the plant site for review upon request. System Functional Test Schedule (Fis) FT Exam. Test Number Cat. Description 4 C-H Safety Injection Pump 1204-P6-003 Discharge Functional Test (Partially performed) 5 C-H Safety Injection Pump 1204-P6-004 Discharge Functional Test 8 C-H Penetration 30 (Safety Injection to Cold Legs) Functional Test (Partially performed) 10 C-H Safety Injection (SI) Pump Suction Functional Test 1 C-H Residual Heat Removal System (RHRS) to Chemical and Volume Control System (CVCS) Suction Functional Test 12 C-H Containment Spray Train "A" Functional Test 13 C-H Containment Spray Train "B" Functional Test 17 C-H Line 1208-133 (HV-8104 to Valve 185 Flow Test) Functional Test System Hydrostatic Test Schedule (HTs) HT Exam. Test Number Cat. Description 1 B-P Class I Hydrostatic Test (Partially performed) C-H 3 C-H SI, Normal Charging & Containment Spray Pump Suction Hydrostatic Test (Partially performed) 4 C-H SI Pump Discharge Hydrostatic Test (Partially performed) 17 C-H Reactor Pressure Vessel Head Vent Pipe Hydrostatic Test 95 C-H SI Miniflow Hydrostatic Test I System Inservice Test Schedule (JTs) IT Exam. Test Number Cat. Description i_!_ I C-H Charging Line Inside Containment Inservice Test I 2 C-H Letdown Line Inside Containment Inservice Test I l 3 C-H Reactor Coolant (RC) Pumps 1,2,3, and 4 Seal Leakoff Inside Containment Inservice 4 P IitTest 4 C-H RC Pump 1 Seal Injection from Penetration 54 to Valve 006 Inservice Test 5 C-H RC Pump 2 Seal Injection from Penetration 53 to Valve 359 Inservice Test 6 C-H RC Pump 3 Seal Injection from Penetration 52 to Valve 360 Inservice Test 7 C-H RC Pump 4 Seal Injection from Penetration 51 to Valve 361 Inservice Test. 8 C-H Reactor Coolant System (RCS) Hot Leg Sample Lines to Penetration 24 Inservice Test 9 C-H Sample Line from Valve 101 to Valve HV-3514 Inservice Test 6-1
IT Exam. Test Number Cat. Description 10 C-H CVCS Inservice Test with Normal Charging Pump Operating (Outside Containment) (Partially performed) 11 C-H Centrifugal Charging Pump 1208-P6-002 (Train "A") Discharge Inservice Test 12 C-H Centrifugal Charging Pump 1208-P6-003 (Train "B") Discharge Inservice Test 14 C-H Accumulator Tank Loop I (1204-V6-002) Inservice Test 15 C-H Accumulator Tank Loop 2 (1204-V6-003) Inservice Test 16 C-H Accumulator Tank Loop 3 (1204-V6-004) Inservice Test 17 C-H Accumulator Tank Loop 4 (1204-V6-005) Inservice Test 18 C-H Residual Heat Removal System Train "A" Inservice Test (Partially performed) 19 C-H Residual Heat Removal System Train "B" Inservice Test (Partially performed) 23 C-H Refueling Water Storage Tank (RWST) Inservice Test (Partially performed) 24 C-H Sample Line from Valve 097 to Valve HV-3508 Inservice Test 25 C-H Penetration 24 (RCS Hot Leg Sample) Outside Containment Inservice Test 26 C-H Nuclear Service Cooling Water (NSCW) Train "A" Inservice Test (Outside Containment) 30 C-H NSCW Train "B" Inservice Test (Outside Containment) 34 C-H Containment Coolers 1501-A7-001 and 1501-A7-002 Inservice Test 35 C-H Containment Coolers 1501-A7-003 and 150 1-A7-004 Inservice Test 36 C-H Containment Coolers 1501-A7-005 and 1501-A7-006 Inservice Test 37 C-H Containment Coolers 1501-A7-007 and 1501-A7-008 Inservice Test 38 C-H Cooling Coils 151 I-E7-002 and 1515-A7-001 Inservice Test 39 C-H Cooling Coils 1511 -E7-001 and 1515-A7-002 Inservice Test 45 C-H Steam Generator 1201-B6-001 Inservice Test 46 C-H Steam Generator 1201-B6-002 Inservice Test 47 C-H Steam Generator 1201-B6-003 Inservice Test 48 C-H Steam Generator 1201-B6-004 Inservice Test 49 C-H Penetration 7 Inservice Test (Outside Containment Steam Generator I Blowdown to Heat Exchanger) 50 C-H Penetration 8 Inservice Test (Outside Containment Steam Generator 2 Blowdown to Heat Exchanger) 51 C-H Penetration 9 Inservice Test (Outside Containment Steam Generator 3 Blowdown to Heat Exchanger) 52 C-H Penetration 10 Inservice Test (Outside Containment Steam Generator 4 Blowdown to Heat Exchanger) 53 C-H Penetration I IB Inservice Test (Outside Containment Steam Generator I Blowdown to Sample) 54 C-H Penetration I IC Inservice Test (Outside Containment Steam Generator 2 Blowdown to Sample) 55 C-H Penetration 12B Inservice Test (Outside Containment Steam Generator 3 Blowdown to Sample) 56 C-H Penetration 12C Inservice Test (Outside Containment Steam Generator 4 Blowdown to Sample) 57 C-H Main Steam Loop I Inservice Test (Outside Containment) 58 C-H Main Steam Loop 2 Inservice Test (Outside Containment) 59 C-H Main Steam Loop 3 Inservice Test (Outside Containment) 60 C-H Main Steam Loop 4 Inservice Test (Outside Containment) 64 C-H Auxiliary Feedwater (AFW) Inservice Test With Pump 1302-P4-002 (Train "B") Operating 65 C-H AFW Inservice Test With Pump 1302-P4-003 (Train "A") Operating 71 C-H Main Feedwater Loop I Inservice Test (Outside Containment) 72 C-H Main Feedwater Loop 2 Inservice Test (Outside Containment) 73 C-H Main Feedwater Loop 3 Inservice Test (Outside Containment) 6-2
IT Exam. Test Number Cat. IDescription 74 C-H Main Feedwater Loop 4 Inservice Test (Outside Containment) 79 C-H Excess Letdown Heat Exchanger Inservice Test 80 C-H Residual Heat Removal System Cleanup Inservice Test System Leakaee Test Schedule (LT) LT Exam. Test Njumber Cat. Description I B-P Class I System Leakage Test 6-3
INDICATION NOTIFICATION FORMS The following Indication Notification Form(s) (INFs) were issued by Materials and Inspection Services (M & IS) of Southern Nuclear Operating Company (SNC) due to reportable indications or conditions being observed during the examination of either Class I or 2 components during the eleventh maintenance/refueling outage at VEGP-2 (referenced attachments are available at the VEGP plant site for review upon request): INF No. Affected Component/Area INF Disposition 105V200I NA Not applicable to an ASME Class I or 2 examination I05V2002 21201-P6-002-25-32 During a VT examination of the 1.5" Diameter Seal Water Housing Cap Screws, unacceptable conditions were reported. Boron residue and corrosion products are present on the top of one Seal Water Housing Cap Screw for RCP 2. Also, boron residue is present in mating surfaces held together by these cap screws. See data Sheet No. S05V2V161. Condition Report 2005108088 was written to address this issue. Per the dispositions of the CRs "The boric acid deposits noted during a walk-down and detailed in this condition report are most likely due to the process of back seating the reactor coolant pumps. Discussions with Westinghouse l personnel that back seated the pumps revealed that no boric acid deposits were noted when personnel began the back seating process. It is normal during this process for boric acid to splash around the splash ring and deposit in the area of the seal housing. It is normally wiped up immediately. The characteristics of the boric acid identified are not consistent with at power seal leakage. An at-power leak is normally identified by boric acid deposits down the seal housing and into the motor stand. I05V2002 21201-P6-002-25-32 Also, at the request of ISI Engineer, the equivalent bolting on the remaining three pumps were examined and CR 2005108167 documents those conditions. 105V2003 21208-005-CV110 During ultrasonic examination of 2-CV-I10 (Components DS of CVCS Flow Orifices), per the RI Calc Notes, wall thickness readings were reported on the 2" and 3" components downstream of the CVCS flow orifices which were below the 12Y/2% mil spec tolerances. (See Data Sheet No. S05V2U507). Condition Report 2005108176 was written to address this issue. Per RER 2052788001 (Log: PS-05-1747) the actual pipe wall thicknesses are acceptable until 2R12. Vogtle Action Item Al 2005203261 has been created to either replace this section at the next refueling outage, or perform UT scans again at that time i_ l to ensure the minimum wall thickness is not violated. 7-1
INF No. Affected Component/Area INF Disposition 105V2004 21501-024-H003 During a VT examination of hanger 21501-024-H003, Restraint, unacceptable conditions were reported. Corrosion on U-bolt nuts with some material degradation. See Data Sheet No. S05V2V174. Condition Report 2005108504 was written to address these conditions. This hanger is still capable of performing its design function, because the general corrosion which does not reduce the load bearing capacity of the support is a non-relevant condition in accordance with IWF-3400, Acceptance Standards. 105V2005 21302-107-H008 During a VT examination of hanger 21302-107-H008, Strut, unacceptable conditions were reported. Upper locknut is loose and strut is bound. See Data Sheet No. S05V0206. Condition Report 2005108758 was written to address these conditions. This hanger / strut is still capable of performing its design function, because stated above conditions does not affect the intended purpose of this strut. Work Order No. 2052977501 was generated to correct the above conditions and the strut was re-inspected and founded to be acceptable. The INF(s) constitute only those reportable indications or conditions observed during the SNC M & IS Department scope of work. Any reportable indications or conditions observed by VEGP Site personnel or outside contractors during their scope of work should be identified by/to the VEGP site in report document(s) which are referenced herein. 7-2
OWNER'S REPORTS FOR REPAIRS OR REPLACEMENTS (FORM NIS-2) The following Owner's Reports for Repairs or Replacements (Form NIS-2) are provided for work activities documented at VEGP-2 since the last maintenance/refueling outage (2R10) through the completion of the eleventh maintenance/refueling outage (2R1 1). Reports are identified by their respective traveler number which is denoted on each of the NIS-2 reports. The originals of the NIS-2 reports are filed with their respective traveler packages at the plant site. Only those NIS-2 reports applicable to VEGP-2 are included in this report document. Any attachments, e.g., code data reports, etc., referenced in the NIS-2 reports will be made available for review upon request at the plant site. The NIS-2s for the following travelers are included herein: 99053** 02090 02091 03078 03116 03117 03119 03125** 03126 03127 04007 04010 04011 04018 04020 04029 04031 04032 04033 04034 04035 04036 04037 04044 04045 04046 04047 04049 04050 04055 04058 04060 04061 04063 04064 04068 04071 04073 04077 04078 04079 04087 04101 04103 04164 05031 05036 05041
- Traveler 99053 is certified on the same NIS-2 report as traveler 03125.
8-1
ORIGINAL FORM NIS.2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provislods Of The ASME Code Section Xi 0 02090 I
- Ii Traveler #
0511134 4
- 1.
Owner Southem Nuclear Opereting Company Name 40 Inverness Center Parkway, BSirrnghem. AL
- 2.
Plant Vogde Electdc Generating Plant Waynesboro, GA 30830 Address
- 3.
Work Performed by Nuclear Operetbns Maintenance Name Date Sheet Unit MWO tJ I Of If!O 20 2 01
- O8IOt7 202018U7 Repair Organization P.O. No., Job No., etc:
Plant VWate II Address I
- 4.
Identification Of System 1205/ResidualtHeat Renoval Sys S. (a) Applicable Construction Code ASME SEC fit 1974 Edition, Summer 1976 1 (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components tdem
- Addenda, NMA Code Case NAIE NAME MANUFACTURER NATIONAL
- REPAIRED, AME CODE; OF OF
. SERLAL BOARD OTHER YEAR REPLACED OR STAUPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NOMi ENCAPSULA. RICHMOND N-2432.20 N/A 2.1205-V4002 1981 REPLACEMENT YES TION VESSEL ENIINNG CO.. INC. L
- 7.
Description Of Work Instaled ftina tuqs by weldina on vessel cover In accordance wMh DCP 99-VANOOOI A 10 CFR 50. Anpendi9 J. leakkqe test was competed efter the instetation In accordance with tocedure 24936-2. B. Test Conducted: NIA Q Hydrostatic ] PneumaticQ] Nominal Operating Pressurej] Other fg, Pressure N/A PSI Test Temp. NA F 4 es CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code. Section Xi. repair or replacement Type Code Symbol Stamp NIA Certificate of dhorizatlon No. NIA Expiration Date ,NIA Signed (. 7_ Le,, Team Leader Date -A 4 5r Owneuvr Owners tOeslpree. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the national Board of boiler and Pressure vessel Inspectors and the Stateior Province of Georcla and employed by Harftrd Steam Soler Insoecfon end Insurence Co. of Connectcut of Hartford. Connecgtic hive inspected the components described In this Owner's Report during the period' 07i2203 to <-ef and state that to the best of my knowledge and belief. the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME 'Code, Section XI. By signing this certlficate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinatidns and corrective measures described In this Owners Report. Furthermore. neither the Inspector nor his employer sh'al be liable In any matner for any personal Injury or property damage or a loss of any kind arising from or connected with this InsMR5Zt-Z Commissions GA wa3 Insirector's Signature Date _________ National Board. State, Province and Endorsements I~ I I I . J. -
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler P 20i I
- 1.
Owner Southern Nuclear Operating Company Name 40 Inverness CenterPartway, Birmingham. AL
- 2.
Plant Vogte Electrc Generting Plant Waynesboro, GA 30830 Address
- 3.
Work Performed by Nuclear Operations Maintenancr Name Date 05/1ZV4 Sheet I Of I l .0 I Unit
- 12. t4
%$c6/oB/c-MWO # 20201848 Repair Organization P.O. No., Job No., etc. Plant Vogfe I. i. Address i 4 Identification Of System 120t6 Contalnment Spray System S. (a) Applicable Construction Code ASME SEC 11 1t974 Edition. Summer 1975
- Addenda, N/A Code Case (b)Appiicable Edition of Section Xl Utilized For Repairs Or Replacements 19_J
- 6.
Identification Of Components Repairs Or Replacement Components I NAME NAME MANUFACTURER NATIONAL REPAIRED. ASlE CODE I OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT UANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO)I ENCAPSULA-RICHMOND N-243Z30 N/A 2-1206-V4-001 1981 REPLACEMENT YES I TION VESSEL ENGINEERING I
- 7.
Description Of Works Instalfed Rrdna luas by weldIng on vessel cover In accordance with QCP i10-VAN0001. A 10 CFR 50. Ao~oendix'j J. leakage test was completed aftr the hnstaffooon In accordance wmh orocedure 24938-2.
- 8.
Test Conducted: Hydrostatic (j Pneumatki] Nominal operating Pressure!]3 NIA Q] Other (r' Pressure NIA PSI Test Temp. N/A F I. CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate oI A horization No. NIA Expiration Date N/A Signed Team Leader Date S.4 4a... roOwngdr Owner's Designee. 7itie j CERTIFICATE OF INSERVICE INSPECTION I 1 the undersigned, holding a valid commission Issued by the national Board of boiler and Pressure vessel inspectors and the State !or Province of Georala i and employed by Hartford Steam Ooierlnspegtion end Insurance Co. of Connectcut of Hartford Connecffcut have Inspected the components described In this Owner's Report I during the period 110f2A12 to _../7-0.- , and state that to the best of my knowledge and belief, the Owner has perto.med examinations and taken corrective measures described in this -Owners Report in accordance with the requirements of the ASME Code, Section Xl. .p I
- 'i By signing this certificate, neither the Inspector nor his eimployer makes any warranty, expressed or knplied conceming the examinations and corrective measures' described 'In this Owners Report.
Furthermore, neither the Inspector nor his employer shall be liable In any manwr for any personal injury or property damage or a loss of any kind arising from or connected with ffhis M M Commissfons A2n1 i I I speamor's Signature Date ,5-1 7-0 j National Board. State, Province and Endorsements I, i
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 03078 August 10 2004 1
- . Owner
- 2. Plant Southern Nuclear Operating Company Name 40 Inverness Canter Parkway, Bilmingham, AL Address Vogtle Electric Generating Plant Plant Waynesboro, GA 30830 Date Sheet Unit MWO #
I of I 2 20300909 Repair Organization P.O. No., Job No., etc. Plant Voatle Address
- 3. Work Performed by Nuclear OperationshMaintenance Name Address
- 4.
identification Of System 1208 1 Chemical and Volume Control System S. (a) Applicable Construction Code ASME Section ill 1977 Edition, Winter 1977
- Addenda, MIA Code Case (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
Identirication Of Components Repairs Or Replacemnent Conponents
- 7. Description Of Work Install studs and nuls on p/P/nc flanges at heat Exchanger 2.1208-E.002.
- 8. Tests Conducted:
Hydrostatic 0 Pneumatic U Nominal Operating Pressure E N/A ED Other 3 Pressure N/A PSI Test Temp. NIA O lI0 I CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this rules of the ASME Code, Section Xl. rep Type Code Symbol Stamp NIA Certificate of A horizatin No. q / NIA Expiration Dale Signed Team Leader Datea g ronlacrment conforns to the air or replacement MA '4rner or Owner's Designee. Title I I ii i I CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission Issued by the National Board of Biler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by I I Hartford Steam Boiler Inspection and Insurance Co of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period i 11 I September 2.2003 to 8-.1-3L... and state that to the best of my knowledge and belief. the Owner has performed examinations and tests and takei corrective measures described in this Owners Report in accordance with the requirements of tthe ASME Code. Section Xi. i I iI 1 1 1 I' By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied. conceming the examinations and corrective measures described In this Owners Report. Furthemiore, neither the Inspector nor his employer shall be liable in any man, r for any personal Injury or property damage or a loss of any kind arising from 'or connected with this (Commissions G;A 10 a !T Inspec r's Signature National Board. State, Province and Endorsements Date 13-O4 I
- lit ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Or The ASME Code Section xi I 6"3) 1
- 1. Owner Southern Nuclear Operating Company Name 40 inverness CenterParhwav, Birmingham, AL Address
- 2. Plant Voctle Electric Ganeroina Plant Date Sheet Unit MWO U Traveler #
0311S May 18 2004 of I 2 I Plant Waynesboro, GA 30830 20301489 Address
- 3. Work Performed by Nuclear Operatlons Maintenance Name Repair Organization P.O. No., Job No.. etc.
Plant Voatle Address
- 4.
Identification Of System 1209 I Chemical Volume Control System S. la) Applicable Construction Code ASME Section fit 1974 Edition. Summer 1976 Addenda, WA Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6. Identilication Of Conponents Repairs Or Replacement Components
- 7. Description Of Work Perform seal wefd on vave 2-1208.06 oer Weld Process Control Shset O30O4.
- 8. TestsConducted:
Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 IA O Other 0 Pressure WIA PSI Test Temp. NIA F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report art correct and this replacement conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symboi Stamp NIA Certificate of Authorization No. WA Expiration Date NiA Signed / -ZO rs eig e Team Leader Date _ trorOwe'DeineTh, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commrdssion Issued by the National Board of Eolier and Pressure Vessel Inspectors and the State or Province ot Goorab and employed by Hartford Steam Boler Insectlon and Insurance Co o1 Connectcut of Hartford Connecticut have Inspected the components described in this Owner's Report during the period r December 5 2003 to <-;o-Oi and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section Xi, By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthennore. neither the Inspector nor his employer shall be l aabk In any m ner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions GA4 3 L V i r Inspictor's Signature National Board, State, Province and Endorsements I Date
R OORIGINAL FORM NIS 2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler# 03117
- 1. Owner Southem Nuclear Operating Company Date May 18, 2004 Name 40 Inverness Center Parkway, BSimingham, AL Sheet I
of Address
- 2. Plant Vootle Electric Generating Plnt Unit 2
Plant Waynesboro. GA 30830 MWO # 20301490 Address
- 3. Work Performed by Nuclear Operations Maintenance Name Repair Organization P.O. No. Job No., etc.
Plant Vogtle Address
- 4. Identification Of System 120 1 Chemical Volume Control System
- 6.
(a) Applicable Construction Code ASME Section III 1974 Edition. Summner 1976 Addenda, MIA Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Cornponents Repairs Or Replacement Components NAME MANUFACTURER NATIONAL REPAIRED l ASME COOE OF OF SERIAL BOARD OTHER YEAR REPLACED OR 5TAMPED COMPONENT MANUFACTURER No. NO. IDENTIFtCATION BUILT REPLACEMENT (YES OR NO) Vate Dresser HS31ABH WA 2-1208-U4437 1970 REPLA CEMEN YES Industries
- 7.
Description Of Work Perform seal weld on vatve 2-120-J4-437 er Weld Process Control Shet 3O066J3.
- 8.
Tests Conducted: Hydrostatic 3 Pneumatic 0 Noninal Operating Pressure NIA 13 other 0 Pressure NIA PSI Test Temp. IA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacernte conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate ofAlIthorization No. N/A Expiration Date NWA Signed Team Leader Date 5// .9:... 0Ctneror rDeigree, Title71 ) 5 ,'I-601 IF CERTIFICATE OF INSERVtICE INSPECTION 1 the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the State or Provinceof Ceoerga and employed by Hartford Steam Boller n doctlon and Insurance Co otConnecdlcut I otHartftrd Connecticut have Inspected the components described in this Owner's Report during the period, D ecember 8 2003 to a and state that to the best of my knowledge and belief. the Owner has performed examinations and tests and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME ICode Section XI. By signing this certificate, neither the Inspector nor his employer nakes any warranty, expressed or implied, concerning thc examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any "nner for any personal injury or property damage or a loss of any kind arising from or connected with thil Commissions CVt7 r I In9fctor's Signature National Board. State, Province and Endorsements Date_
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Traveler # 03119
- 1. Owner Southern Nuclear operating Company Name 40Jnvemess CenterParklway,8 lngtzatn, AL Address
- 2. Plant Vogde Electric Geneoraing Plant Plant Waynesboro, GA 30830 Address
- 3. Work Performed by Nuclear Openattons Maintenance Name Date May 17. 2004 Sheet I
of I Unit 2 MWO # 20303427 Repair Organization P.O. No., Job No., etc. Plant Vogtle Address
- 4. IdentIfication Of System 12011 Reactor Coolant System
- 5. la) Applicable Construction Code ASME Section III 1971 Edition, Wmnter 1972 Addenda.
NA Code Case (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
identification Of Components Repairs Or Replacerent Components Ti I
- 7. Description Of Work Relief valve SW NS6904<00-001t was removed for Inseryce testino and was replaced by relief valve S/
N566i4-00030. Relief valve SAY N5696+00-036 was orlidnatlv Installed during construction as IPSV80108 and Is now belna utilized as a rotalne soar. S. Tests Conducted: NIA 0 Hydrostatic O PneumatIc 0 Nominal Operating Pressure 1 Other Q Pressure WA PSI Test Temp. NA CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp NIA Certificate of thorization No. NIA Expiration Date WA Signed a 7 Te mLeader Date_5___________ Wner or Owneers Designee. Tite CERTIFICATE OF INSERVICE INSPECTION I,'j I, the undersigned, holding a valid comnmission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georla and employed by Hartford Steaim Boller Inspection and Insurance Co of Connecticut of lHato Connecticut have Inspected the components described In this Owner's Report during the period December 16 2003 to k and state that to the best of my knowledge and belieft the Owner has performed exaninations and tests and taken correctIve measures described in this Owners Report in accordance with the requirements of the ASME Code. Section Xt. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any ner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions G f d Ins tosSignature National Board, State, Province and Endorsements Date _ .iI
--i. r.7 -ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl 7 Traveler#I 03125
- 1.
Owner
- 2.
Plant Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date Sheet Unit Address Vogile Electric Generating Plant 09/15/04 1 of 3 2 WOa 20301714. PO# 7038022 and PO# 7038895 Name Waynesboro, GA 30830 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by _
- 4.
Identification of System Maintenance Department Name Plant Vogute Address Type Code Symbol Stamp Authorization No. Expiration Date NAL MIA NVA 1201 /Reactor Coolant System S. (a) Applicable Construction Code ASME SEC III 19 71 Edition, Winterf1972 Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Components National
- Repaired, ASME Code Name of Name of Manufacturer Board Other Year
- Replaced, Stamped Component Manufacturer Serial No.
No. Identification Built or Replacement (Yes or No) SAFETY CROSBY VALVE N60446.00029 633 2PSV-8010A 1978 REPLACEMENT I YES VALVE A GAGE CO.
- 7.
Description of Work Valve was replaced. The replacement valvewas purchased under PO7038022 from Union Electric's, Plant Calloway. The selpoint pressure lor this valve was changed by Crosby Valve & Gage Company personnel under PO 7036895 and
- t.
-nnr .,.n -n n a ~ .,r... AL k,. ~ evil 11 1.
- 8.
Test Conducted: N/A ]
- 9.
Remarks See Item 7 Hydrostatic [] Pneumatic] Nominal Operating Pressure[ Other Pressure N/A PSI Test Temp. NA Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp Certifncate od uthorzstlon No Signed /z N/A NIA Expiration Date NIA Team Leader Date 7 2-Owner df Owner's Ddsianee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georcia and employed by Hartford Steam Boiler tnsoection and Insurance Co. of Connecticut of HarQa Conn have inspected the components described In this Owner's Report during the period 01/25/99 to...- L.... and stale that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the inspector nor his employer shalt be liable In any manner or any personal Injury or property damage or a loss of any kind arising from or connected with this v Commissions tQB1355C I qA 20 Inspect 8 Signature National Board, State, Province and Endorsements Date____________
- I
' : -1 ' R J YWR ENTH AN, MASS -rnvelef43 2 FORU NV-t FOR SArETY AND SArZTY RELIEF' VALVES C.C.*44C As Esquited by lb& provisioos of UCeASUE Code Ru!.. IDArA REI'ORT Safuiy at~d saresy Reief( Val-Ios
- t. Manufactured by Crosby Valve ICage Co.,.43 ')endri~k St., Wr-enthom. MA 02093
~~Kaine and Address 3 Mrodel F-t 13 8 6 81TOrder No K64135
- Contract Datej6117176 'natLona1 Board No.........
Westinghouse Electric Corp4.- Nuclear Energy System~s P..O.iscwd a Box 355 - Pittsburgh, PA 15230 1.54-CCS-250055-BN Nso. sA~ AGd.sess Wacou and Addiems 4; Lcaton f 1131 issouri S. Valve Identificationi 6'RV88-HTB.SFP si No. 1460446.00-0029 Dtowia; ma.- DS -C0446 Rev. B Type-Safety orince. Sii...kl.... M Pipe Sige.._.iniet..6 outlet.... j $.zfety.Sa(cly Reiil.I.Psowep.. Actuated4 Inch InCtk Inch
- 0. Set Fucssutv I PSIC) 2485 mp50tu Sunpvd Clcaiiiy' A20006 lbs. /hr. -gat. o r 0w~~tspsuwa Biovdom jPsIC) 57 belawS.P.
it)-deasblte Test (?uID) inlgz 3730 Couple:. Valle. 750 patz T. Tbe Om168a31. design. constructaon and varkMARab~lp Compff With ASUC Coad. Section Mf. Clais 1 8dition. 19.74,Addenda Date L~ET" 1975 ,Case No. - ~ ~ 1`148IaV1 Contaitning ar prigugug Rouualnig conoa~owenu actial No0. lbt,.fla3 SPtClffl04ia S.. ZXx 7orgings IdeatilIcAuIOa Z1ncluiduin Type Jor Crads Body 1491487-31-0026 ASHF. SA182 Gr. FJ316 bone 91496-31-0013 'ASKE SA1O5
- b. bar Stocki and rorgings Sugpp-qt Reds Nottl~e H914S9-31-0011 A.SH 5A1B2. Gr. F316 R"nee191494-34-0049 RE es stellite Alloy 1.a. 68s S;Atrng Wialieui K58693-31-0006
_N_________ A)MSNO A~dju'sing Sol% 191499-31-0006 ASHE SA193-75 Cr. 86 SpnPaint. 1491492-32-03042 As h__ _ ~__________ KS8692-33-0038 1~19-03ASTM SA27Z7 Gr. D4C Spindle Ball. .H19-03ASTKEA27? Gr. 4,410-c Disc Holder N491490-35-0045 ASM SA637 Cr. 718 Bellows-14586g 1-38-0032 bushing Disc Holder 1491491-34-0045 Haynies Stellte Allay No. 631 A.
- 0**
0.. IO II 3 a., Y M .9
- t.
.5
- I A
M-Now
A
- ' ' 4 :_Y t'.' I '.".'.
t "." I I. .V. .11. I'.-
- P%
. Tnueer632 Skcwer4 63 [?- Serlal No. or fLtei&Ispeculfcation ideanification I acludIzng T)"p or Cnade e... spIsig TX58693-fCQ
- y'.
. Wthet 7.115 such as pilot Co MX.3104-0013 &STM A304-76 Cr. 1SIS911 I ~ I 1 mpagents Stu ?9150O0-037 thru 0348 ASHE SA4.53 Cr. 660 Ru i91501-0337 thru 0248 ASHE SA193 Cr. 6 We corgify that the sute,3113 nm eu int thiti report are Correc. el .zaaz," / Vale 6 -/ 3 ig 79.-.... swgnd -Crosby Valve & Cage Co. ",-J-r masufactsaw ceniricate or Auihanizatlas No.* -1878 expaves -Septem~ber 30. 1980 iI .I CERTirICATC or stior ItSPICTION
- 1. the undersigned. butdi= a Taid commissions issued by thf~attonat Baud nr Boiler and
~r se ne V,,e n~ ec or a d h S at o F o Ilea of ass. sod * " tpoyed by ifnspected the equipment descnihed in this Vitl Reprwt as 1-2 1O2. sos saite that to tna beat of my knowledge and belief. the )aniifactutee his CdagisUutted this equip. meant In xecozdaars with the aPppteabte Subsections of ASUC Section III. 'byI 5Ignl'g tIAs eltttiteats. 0,etther %he InsPectta nY" his sOmplOY61 makes au! w21rrint). .s-pnessed'oz implied. concerrning thte equipment deactl..d to this DataiRjotFrhr oe neither tb. Inspector ant his employet %ball be Itabl. In say mannR for any Petsonal injury cc property damage of A loss of any kind srising (frow or connected with titlE Inspection. Akc~p Ccmmieetons AXA."IZ0
- Arkwvrisht-Boston Mantufacturers Mutual Insurance Company - Nutual BoLler Le Machinery Division, I
- I.- .1,. .1.... .. A. ; I. -. I:-" _"' ': i I. I I. .. I , I - 3 .Ili. . t .': I. :....- -it..... ' ': 4". --. I."::Y .1 I..'V j"
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler#l 03126 y
- 1.
Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birmingham, AL Date 09/11514 Sheet 1 of I
- 2.
Plant Address Vogtle Electric Generating Plant Name Waynesboro, GA 30830 Unit 2 WO# 20301714 Address
- 3.
Work Performed by Maintenance Department Name Plant Voctle Repair Organization P.O. No.. Job No., etc. Type Code Symbol Stamp Authorization No. Expiration Date
- N/A N/A N/A Address 1201 /Reactor Coolant System
- 4.
Identification of System
- 5.
(a) Applicabie Construction Code ASME SEC III 19 71 Edition, Winter 1972 Addenda, N/A (b)Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Code Care
- 6.
Identification Of Components Repaired or Replaced and Roplecement Components National
- Repaired, ASME Code Name of Nof Mnufurer Board Other Year
- Replaced, Stamped Component Manufacturer Serial No.
No. Identification Built or Replacement (Yea or No) SAFETY CROSBY VALVE N60446-00-0006 542 2PSV-80 t0O 1978 REPLACEMENT YES VALVE A GAGE CO.
- 7.
Description of Work Valve was replaced. The replacement valve is a rotating spare that was originally purchased under PO 7038022 and has been previously installed In the plant.
- 8.
Test Conducted: N/AfD
- 9.
Remarks See Item 7 Hydrostatic n Pneumatklc Nominal Operating Pressureso Other a Pressure NWA PSI Test Temp. N/A Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp NWA Certificate oNIuthorl tion No M/A Expiration Date N/A Signed Team Leader Date oZ g 9 / tad Ow i~ar or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Hartford Steam Boiler Inspection and Insurance Co. of Connecticut ot Hartord. Connecicut have inspected the components described in this Owner's Report during the period 01/05/04 to /0- 1 -... ./ and State that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the. inspector nor his employer makes any warranty, expressed or Impiled, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this In s gt7 ,.c.Commissions CA-, Ins or's Signature National Board, State, Province and Endorsements Date________ y~W
.'4: ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provlsi6ns Of The ASME Cods Section Xl y
- 1. Owner Southern Nuclexr Operating Company Name 40 Inverness Center Parkway, Blimingham, AL Date Sheet Traveler S 03127 09115104 t
of I 2 WON 20301714 Address
- 2.
Plant Vogule Electric Generating Plant Unit Name Waynesboro. GA 30830 Address Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by _
- 4.
Identification of System Maintenance Department Name Plant Vogtle Address Type Code Symbol Stamp Authorization No. Expiratthn Date tWA tWA i/A 1201 /Reactor Coolant SYstem
- 5. (a) Applicable Construction Code ASMESECIII 19 71 Edition, Winter 1972 Addenda, (b)Applicable Edition of Section Xi Utilied for Repairs or Replacement& 19PY
- 6.
Identification Of Components Repaired or Replaced and Replacement Components WlA Code Case National
- Repaired, ASME Code Name of Name of Manufacturer Board Other Year
- Replaced, Stamped Coinonent Manufacturer Serial No.
No. Identilcation Built or Replacement (Yes or No) SAFETY CROSBY VALVE N60446-00-028 632 2PSV-8010C 1978 REPLACEMENT YES VALVE S GAGE CO.
- 7.
Description olWork Valve wasreplaced. Thereplacement vaheIsa rotatingspare that wasoriginallypurchasedunderP0 7038022 and has been previoosly Installed In the plant.
- 6.
Test Conducted: NIA Q]
- 9.
Remarks See Item 7 Hydrostatic [] Pneumatic[ Nominal Operating Pressureg Other J] Pressure AWA PSI TestTemp. tAL/A Applicable Manufacturer's Data Reports to be attached 4'~1 J CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the. ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp WA Certificate ot`Authorlzatlon No. N/A Expiration Date N/A Signed 'r"-4afi~' eam Leader Date. Owng or Owner's Designee, Title li iI I CERTIFICATE OF INSER VICE INSPECTION 1, the undersigned, holding a valid commission Issued by the national Board of Boller and Pressure Vessel inspectors and the State or Province of Georoia and employed by Hartford Steam Boiler lnspection and Insurance Co. of Connecticut of Hartford. Connecticui have Inspected the components described in this Owner's Report during the period 01105/4 to LO-Q-04 f end state that to the best of my knowledge and belief, the Owner has perforrned examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, SectIon Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and.corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shal be lIable In any maryr for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions A, g43 Inspeior's Signature National Board. State, Province and Endorsements Dote /-a!/
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl I
- 1.
Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway. Birningham. AL
- 2.
Plant Vogtle Eectric Generating Plant Waynesboro. GA 30830 Traveler # 04007 Date 0M51V4 Sheet I Of I Unit 42 %i 6/84 $-/ C ( MWO # 20303103 Address
- 3.
Work Performed by Nuclear Operaons Maintenance Repair Organization P.O. No.. Job No.. etc. Plant Voge Address Name
- 4.
Identification Of System 1201 /Reador Coolant System
- 6.
(a) Applicable Construction Code ASME SEC Ni 1977 Edition, Winter 1977 A (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Conponents Repairs Or Replacement Components Addenda NI/A Code Case NAME NAME MwtANUFACTURER NATIONAL REPAIRED. ASME CODE OF OF SERIAL BOARD OTH ER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) PIPE SUPPORT PULLMAN N/A N/A V2-1201-012-H608 1989 REPLACEMENT YES POWER PRODUCTS
- 7.
DescriptionOtWork SnubberPSA-1/2 senal# 14125 was ranacedwith PSA-1t2. seria# 19715to supportsurveAance testng.
- 8.
Test Conducted: Hydrostatic 5 PneumaticE5 NominalOperatingPressure5 NIA J Other 5 Pressure NWA PSI Test Temnp. NWA CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symboi Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Team Leader Date a 10 FOrwner's Designee. Title t6 61 CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission Issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Geormia and employed by HarffordSteam Bofferlnsoecton and Insurance Co. of Connectcut of Hartford. Connecticut have Inspected the components described In this Owner's Report during the period Of30,V4 to L5-.Z7-4 2 . and state that to the best of my knowledge and belief the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions GA 2 ? Inspedtor's Signature National Board, State, Province and Endorsements Date._5______
i vJnlhJIPIVJL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Pr6visions Of The ASME Code Section XI (I& I Traveler II 04010 0511144
- 1.
Owner Southem Nuclear Operafing Company Name 40 Inverness CenterParkway. Birmingham. AL
- 2.
Plant Vogue Ele chic Generating Rent Waynesboro. GA 30830 Address
- 3.
Work Performed by Nuclear Operations Maintenance Name Date Sheet Unit. MWO II I Of I 4-1 20303106 Repair Organization P.O. No, Job No., etc. Plant Vogue r1 v I v Address
- 4.
Identification Of System 1201 1Reactr Coolant System
- 6.
(a) Applicable Construction Code ASMESECNI 1977
- Edition, Winter 1977
- Addenda, N/A Code Case (b)Appiicable Edition of Section XI Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Conponents NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODEi OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO): PIPE SUPPORT PULLMAN N/A NA V2-1201-048-H001 1989 REPLACEMENT YES POWER PRODUCTS
- 7.
Description Of Work Snubber PSA3. sendal #25369 was repaced with PSA-3 seial# 26804to suDroitsurveilnce testna. L Test Conducted: Hydrostatic [ Pneumnatic[5 NominaloperatinglPressuref] MAEI Other 5] Pressure WA PSI Test Temp. NWA OF CERTiFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp NIA Certificate of Auth ion No. /A Expiration Date NM Signed A Team Leader Date Owner or 0neres Designee, Title CERTIFICATE OF INSERVICE INSPMCTION 1, the undersigned, holding a valid conuiiission issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georcia and employed by Haifordci Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. Connecticut have Inspected the components described In this Owners Report during \\ the \\ penod 01130,V4 1 to 5-7J-d ., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor Nis employer shall be liable In any ner for any personal Injury or property damage or a loss of any kind arising from or connected with this Cornmnissions _'A O3 Dateg Si nature Date -7e/ National Board, State, Province and Endorsements
U111%.311WML FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 04011 05/1i04
- 1.
Owner Southem Nuclear Operating Company Date Name 40 Inverness CenterParkway, Binmngham, AL
- 2.
Plant Vogite Electrfc Generating Pant Waynesborm. GA 30830 Address
- 3.
Work Perforned by NuclearOperetions Maintenance Name Sheet Unit MWO # I Of I 4' 2 octet l/A* 20303107 Repair Organization P.O. No. Job No. etc. Plant Vogfet Address 4. 6. 6. Identification Of System 1201 /Reactor Coolant System (a) Applicable Construction Code ASME SEC III 1n77
- Edition, Winter 1977
- Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989 Identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE:
OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO); PIPE SUPPORT PULLMAN N/A N/A V2-1201-0534H-01 1989 REPLACEMENT YES POWER PRO D U CTS
- 7.
Description Of Work SnubberPSA-35. senfal# 12257 was relacedwfh PSA-35. senal# 12263 to suoor sub.eance testing
- 8.
Test Conducted: Hydrostatic a PneunaticrQ Nominal Operating Pressuren NWA[K Other [ Pressure NIA PSI Test Temp. MA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are corwect and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Autporization No. ON/A Expiration Date N/A Signed T41 2 .ream Leader Date Owner rawner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georgia and employed by Hartford Steam Bol7erlnspec ion and Insurance Co. of Connecticut of gartford. Connecticut have Inspected the components described In this Owner's Report during 'the period 01430)04 to ^J70 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any ma for any personal Injury or property damage or a loss of any kind arising from or connected with this Is aL__ Commissions rGAq Te ns r's Signature National Board, State, Province and Endorsements Date C_ /7 i II
UHI IINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi r . (11;') Traveler# 04018
- 1. Owner Southern Nuclear Operating Company
- 2.
Plant Name 40 Inverness Center Parkway, Birmingham. AL Address Vogtle Electric Generating Plant Plant Waynesboro, GA 30830 Date April27, 2004 Sheet I of Unit 2 MMWO # Address
- 3. Work Performed by Nuclear Operations Maintenance 20303126 Repair Organization P.O. No., Job No.. etc.
Plant VoQtle Name Address
- 4. Identification Of System 1208! Chemical and Volume Control System
- 6. (a) Applicable Construction Code ASME Section III 1977 Edition.
Winter 1977 Addenda, WA Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacerments 19p.
- 6. Identification Of Components Repairs Or Replacernent Components I
- 7. Description Of Work SnubberAD-4f. seriat #785 was replaced with AD-4f. serial#722 to surPort surveillance testinaThe removed snubber (serial # 785) failed an Inservlce functional test as documented In CRI*204001552.
B. Tests Conducted: IA 0 Hydrostatic a Pneumatic 0 Nominal Operating Pressure 0 Other a Pressure NIA PSI Test Temp. IWA 'F CERTIFICATE OF COMPULANCE We certify that the statements made In the report are correct and this rules of the ASME Code. Section Xl. re Type Code Symbol Stamp N/A Certificate of Authorization No. JWA a Expiration Dat Signed o l replacement ' conforms to the pair or replacement e A(N/A 1/2/2c.L ce1 '/-Vo owner ocA~uner's Designleaeitie IS-CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgaa and employed by Hartford Steam 0oller Insoecllon and Insurance Co of Connecticut I of Harford Connecticut have inspected the components described In this Owner's Report during the period I
I i i January 30,2004 to S and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section Xl. I i' ' I By signing this certificate, neither the Inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any mner for any personal Injury or property damage or a loss of any kind arising from or connected with this C commissions GAb3 Inspdctors Signature National Board, State, Province and Endorsements Date__ __ __ __
A i UnKI.UI1MfL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 04020 Traveler A 05/I1904 I_
- 1.
Owner Souftein udear Operaing Company Name 40 Inverness CenterParlway. 8imingham. AL Date
- 2.
Plant Vogte Electnc Generating Plant Waynesboro, GA 30830 Sheet Unit MWO# J Of II -2 o4iqA4-c&, &lk~, Address
- 3.
Work Performed by Nudear Operatons Maintenance Name 20303129 I Repair Organization P.O. No., Job No.. etc. Plant Voafte K.1-I Address
- 4.
Identification Of System 1208/Chemical and Volume Control
- 6.
(a) Applicable Construction Code ASME SEC fit 1977
- Edition, Winter 1977 lb)Applicable Edition or Section Xl Utilized For Repairs Or Replacements 19§9
- 6.
Identification Ot Components Repairs Or Replacerent Components System Addenda. N/A Code Case
- 7.
Description OrWork SnubberPSA-1/2 senal# 14119 was retaced with PSA-1/2, serialI# 14114 to suVotsurvelance tesftno.
- 8.
Test Conducted: Hydrostatic Q Pneumaticfl Norninal Operating Pressure[ NtA [EJ Other [] Pressure NIA PSI Test Temp. NtA F I a-c CERTIFICATE OF COMPiJANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code. Section XL repair or replacement Type Code Symbol Stamp NIA Certificate oNAh n No. NM Expiration Date NIA Signed Team Leader Date ___g -er or Owner's Designee. Title .f CERTIFICATE OF INSERVICE INSPECTION
- i. the undersigned, holding a valid comrmnsion Issued by the national Board of boiler and Pressure vessel inspectors and the Statefor Province of Georoia and employed by Hartford Steam BoierlnsPecion and Insurance Co. of Connectcut of Hartford. Connecticut have inspected the components described In this Owneres Report during the period 01/30A24 to S- /
7 and state that to the best of my knowledge and belief, the Owner has performred examinations and taken correcive measures described in this Owners Report In accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or inpied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer sthall be liable in any for any personal Injury or property damage or a loss of any kind arising from or connected with this insep> I ) Commissions GA 4: 5 Inspeci6r s Signature National Board, State, Province and Endorsements Date ~ - 7 e A I I I I
Hii %eU/ I 1%IlMLI FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 9I. Traveler # 04029 05."W4
- 1.
Owner Southem Nudear Operating Company Name 40 Inverness CenterParkway. Bkm'ingham, AL
- 2.
- Plant, Vogfe Electric Generating Plant Date Sheet Unit MWO UI I
OfI 4-Z $Y4 064*L~j//1/i 20303162 Waynesboro, GA 30830 Address
- 3.
Work Perforned by Nuclear Operations Maintenance Name Repair Organization P.O. No., Job No., etc. Plant Vogile Address
- 4.
Identification Of System 1206 IContalinment Spray Syste
- 5.
(a) Applicable Construction Code ASME SEC I# 1977 Edition. Winter 1977 A (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components m
- Addenda, N-249-1 Code Case NAME NAME MANUFACTURER NATIONAL REPAIRED.
ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) PIPE SUPPORT PULLMAN N/A N/A V2-1206-002.H005 1989 REPLACEMENT YES POWER l PRODUCTS
- 7.
Description OS Work Snubber A L.501. seial # 414 and snubber AD-503. serial # 376 were replaced with ibid sfuts in accordence with QCP 01-V2WW004.
- 8.
Test Conducted: NIA El
- Hydrostatic D PneumaticQ Nominal Operating PressureO Other 5 Pressure NIA PSI Test Temp.
NIA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code. Section XL repair or replacement Type Code Symbol Stamp N/A Certificate of AL porizaton No. NIA Expiration Date NIA Signed Team Leader Date Owntfr Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid conmiission issued by the national Board of boiler and Pressure vessel Inspectors and the State of Province of Geornla and employed by Hartford Steam BoDerinsoecdon and Insurance Co. of Cannectcut ofHartford. Connecticut have inspected the components described In this Owner's Report during the period 021D9J4 l to -/ , and state that to the best of mny knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any rner for any personal Injury or property damage or a loss of any kind arising from or connected with this Ins 17p CommissionsAft oibr Inspors Slgnature Nationa Board, State, Province and Endorsements Date A-D74*
FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl W:i
- 2 Traveler #
04031
- 1.
Owner Southern Nuclear Opera 1ng Company Narne 40 Inverness Center Parkway, Sikningham. AL
- 2.
Plant Vogde Electric Genera Ung Plant Waynesboro, GA 30830 Date 0511304 Sheet I Of I Unit 2 Xt4 W a6 I /'>.. MWO# 20303161 Repair Organization P.O. No., Job No., etc. Plant Vogge Address
- 3.
Work Performed by Nuclear Operations Maintenance Name Address
- 4.
Identification Of System 1206 1Containment Spray Syste S. (a) Applicable Construction Code ASME SEC Hi 1977 Edition, Wnter 1977 A (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components m
- Addenda, N/A Code Case
.NAME NAME lMANUFACTURER NAINLREPAIRED, ASME CODE-OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED I COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) a PIPE SUPPORT PULLMAN N/A N/A V2-1206-O01-HOO9 1989 REPLACEMENT YES POWER PRODUCTS T. Description Of Work Snubber PS3. serial #27598 and snubber PSA-3. serl # 26756 were remdced with diid stuts In accordance with DCP 01-V2N0004.
- 8.
Test Conducted: Hydrostatic D Pneunmtic[] Noninal Operating PressureQ N/A S Other a Pressure NIA PSI Test Temp. NIA SF CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl.. repair or replacement Type Code Symbol Stamp NIA Certificate of Au)"orizatio No. N/A Expiration Date NIA Signed -Z Lz-e Team Leader Date do, Ownerp oOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid conuiisslon Issued by the national Board of boiler and Pressure vessel Inspectors and the State or Province of Geongia and employed by Hartford Steam Boer Inspecfon and Insurance Co. of Connecticut of Hartfoid. Connectiut have inspected the components described In this Owneres Report during the period 02110,V4 to.. L..., and state that to the best of my knowledge and belief, the Owner has performed examinations and taken correcive measures described In this Owners Report In accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer sfiaU be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this rag__ zComnmissions Gs o703 Inspeofor's Signature Date 5.7_o7' National Bhoard, State, Province and Endorsements I
4. FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi (V
- 1.
Owner Southern Nudear Operaltng Company Name 40 Inverness Center Parkway. Bimingham. AL
- 2.
Plant Vogtle Electnc Generating Plant T Date 0: Sheet I Unit MWO # 20 raveler U 04032 V/134 Of I 4-2 aA2673/I/5/ Waynesboro. GA 30830 303160 Address
- 3.
Work Perforred by Nulear Operations Mainbenance Repair Organization P.O. No., Job No. etc. Plant Vogt00 Address Name
- 4.
Identification Of System 1301 IMain Steam System S. (a) Applicable Construction Code ASMESECIII 1977
- Edition, Winter 1977 (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989 S. Identification Ot Components Repairs Or Replacernent Components
- Addenda, NA-249-1 Code Case
- 7.
Description Of Work SnubberAD-153. senal# 777was replacedwith a,ifdstLtlinaccordance w~h DCPOI-V2NO004.
- 8.
Test Conducted: Hydrostatic Q Pneurnatic[] Nominal Operating Pressurefl NWA nX Other Q Pressure NIA PSI Test Temp. NA
- F C#I I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this rules of the ASME Code. Section Xl.
rep Type Code Symbol Stamp N/A Certificate of Aujiorization No. ,Z N/A Expiration Datt Signed A1S°4cE i&.. Team Leader Date REPLACEMENT conforms to the Mir or replacement e N/A -gwz', Z5 lw fnor lwn*er s fOl~ann~. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid cornmission Issued by the national Board of boiler and Pressure vessel Inspectors and the State or Province of Georgia and employed by HartfordSteam Boierinspection andinsurance Co. of Connectcut of Hartford. Connectfcut have inspected the components described In this Owner's Report I during the period 02/1qa.'4 to 6- /7-O/t and state that to the best of my knowledge and belief, the Owner has perforned examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section *Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty. expressed or implied concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any mann for any personal Injury or property damage or a loss of any kind arising from or connected with this oins ~Commissions GA 203 lnspRQtr-s Signature Date 5-17-601
- National Board, State, Province and Endorsements
.2 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi
- 1.
Owner Southern Nucdear Operating Company Traveler U 04033 051134 Date Name 40 Invemess Center Parkway. Birmingham. AL
- 2.
Plant Vogtfe Electric Generating Plant Waynesboro, GA 30830 Sheet Unit MWO # I Of i -4+ ? Wd (o-20303159 Address
- 3.
Work Performed by Nuclear Operations Maintenance Name Repair Organization P.O. No. Job No., etc. Plant Vogde Address
- 4.
Identification Of System 1301 Main Steam System S. (a) Applicable Construction Code ASME SEC Ill 1977
- Edition, Winter 1977 (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components
- Addenda, N-249-1 Code Case 7.
S. Description Of Work SnubberAD-71 senat # 1093 was repdaced with a riold strnt in accordance wth DCP O1.V2N0004. Test Conducted: Hydrostatic a Pneurnatic Nominal Operating Pressure] NIAO Other [] Pressure N/A PSI Test Temp. NWA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xl repair or replacement Type Code Symbol Stamp N/A Certificate of A rization No. N/A Expiration Date N/A Signed or Team Leader Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned. holding a valid conmnission issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georala and employed by Harnford Steam Boler lnspection and Insurance Co. of Conncficut of Hartford. Conneccut hve Inspected the components described in this Owner's Report during the period 02110,V4 to 5EJEt and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code. Section XI. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or inplied. concerning the examinatlins and corrective measures described In this Owners Report. Furthermore, neither the inspector nor his employer shall be liable In any man,~r for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions' _A_ Insp os Signature National Board. State. Province and Endorsements Date
r %JnE'JI IYML FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As-Required By The Provisions Of The ASME Code Section Xi
- 1.
Owner Southern Nuclear Operaffng Company Name 40 Inverness CenterPa,*way. Bimingham. AL
- 2.
Plant VogUe Electric Generating Plant Date Sheet Unit MWO # Traveler U 04034 i 05/3/04 I Of I - 2"kakj/$ Q& /S/-O 20303158 Repair Organization P.O. No. Job No., etc. Plant Voode Waynesboro, GA 30830 Address
- 3.
Work Perforned by NudearOperatfons Mafintenance Name Address 4. 6. 6. Identification Of System 130t /Main Steam System (a) Applicable Construction Code ASME SEC 11. 1977
- Edition, Wnter 1977 A
(b)Applicable Edition of Section Xl Utilized ForRepairs Or Replacements 1969 Identification Of Components Repairs Or Replacement Components
- Addenda, N-249-1 Code Case NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE:
OF i OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO): PIPE SUPPORT PULLMAN N/A N/A V2-1301-121-H005 1989 REPLACEMENT YES POWER PRODUCTS
- 7.
Description OfWork SnubberAI:-7. senIa# 609 was raacedwith a rddstnrtln accordance wth DCP0I-V2N0004.
- 8.
Test Conducted: Hydrostatic D PneumaticEl Nominal Operating PressureE] N1A E Other 5 Pressure N/A PSI Test Ternp. NrA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT confoims to the rules of the ASME Code, Section XL repair or replacement Type Code Symbol Stamp N/A Certificate of Autbrization No. N/A Expiration Date NIA Signed T Date Owu r 6ier's Designee. Title
- e\\\\X\\Q CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission Issued by the national Board of boiler and Pressure vessel Inspectors and the State or Province of Geortlis and employed by Han-ord Steam Boiler Inspection and Insurance Co. of Connecticut of Hartford. Connectcut have Inspected the components described In this Owner's Report during the period 02/10,V4 to 4--
e . and state that to' the best of my knowledge and belief, the Owner has performned examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or irnplied, concerning the examinations and corrective measures described I In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions GAwt Inspector's Signature iateI I Oate 5 Iz-4 National Board, State. Province and Endorsements I I I
k FORM NIS-2 OWNER'S R9 9JQAM S OR REPLACEMENTS I As Required By The Provisions Of The ASME Code Section Xi
- 1.
Owner Southern Nudear Operating Company Name 40 Inverness CenterParkway, Bimingham. AL
- 2.
Plant Vogue Electric Generating Plant Date Sheet Unit 'MWO# Traveler # 04035 1 05/1W4 1 Of I__ 20303157 Repair Organization P.O. No., Job No.. etc. Plant Vogue Waynesboro, GA 30830 Address
- 3.
Work Performed by Nudear Operatons Malntenance Name Address
- 4.
Identification Of System 1301 /Main Steam System
- 6.
(a) Applicable Construction Code ASME SEC 111 1977
- Edition, Winter 1977 (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components Addenda. N-249-1 Code Case NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) - PIPE SUPPORT PULLMAN N/A N/A V2-1301-015-H004 1989 REPLACEMENT YES POWER PRODUCTS
- 7.
Description O Work Snubber ADt1603. serial #329 was replaced with a rlodstnit in accordance with DCP 01-V2N0004
- 8.
Test Conducted: Hydrostatic D PneumaticE] Nominal Operating Pressure[] NWA [X Other j Pressure N/A PSI Test Teop. N/A OF CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section XL repair or replcement Type Code Symbol Stamp NMA Certificate of A horization No. N/A Expiration Date N/A Signed Teader Date owl or Owner's Designec. Tatle CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid comnission issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georol and employed by Harffofd Steam Bo~er/nsgec6on and Insurance Co. of Conneeacut of Hartfodr . Connedicut hlave inspected the components described In this Owner's Report during the period 02110.V4 to - , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection. ./ -Commissions (A:Z r Inqfector's Signature National Board, State, Province and Endorsements Date 5 In Ad
r UnIUIIMML FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl
- 1.
Owner Souther Nudoear Operading Company Namn 40 Inverness Center Par*way, Bimingham. AL
- 2.
Plant Vogtle Elecdtc Generating Plant Traveler # 04036 Date OS/l31V4 Sheet I of I Unit -*,2 qc4£ ICzi//o& MWOt 20303156 .Repair Organization P.O. No., Job No, etc. Pyant Vodtle Waynesboro, GA 30830 Address
- 3.
Work Pertorned by Nuclear Operabons Maintenance Name Address
- 4.
Identification Of System 1301 /Main Steaim System
- 5.
(a) Applicable Construction Code ASME SEC liX 1977
- Edition, "inter 1977 (b)Applicable Edition of Section XI Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components Addenda. N-249-1 Code Case
- 7.
Description OF Work Snubber AD.1603. senal# 148 was rerdaced witho a ,idslnjt In accordance wim OCP 01.V2AN0004.
- 8.
Test Conducted: Hydrostatic ] Pneumatic[] Nominal Operating Pressure[] MAE[ Other 0 Pressure N/A PSI Test Temp. N/A 'F 94x
- \\'\\
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp NMA Certificate of Au rization No. A Expiration Date NMA Signed ./,2 ,/ / Team Leader Date / 9 Owner owne~b.inee, Title IF CERTIFiCATE OF INSERVICE iNSPECTION I, the undersigned, holding a valid cornmission issued by the national Board of boiler and Pressure vessel Inspectors and the State or Province of Georia and employed by Hartford Steam Boer nspecfion and Insurance Co. of Connecticut of Hartfbrd. Connec-Ucut have Inspected the components described In this Owner's Report Iduring i the perod 02/10W4 to 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section XL By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or inmplied. concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any ma for any personal injury or property damage or a loss of any kind arising from or connected with ihis in s ~ Commissions GA.02 InspeCtor's Signature National Board, State. Province and Endorsements Date___ ___ I
- I FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 04037 Traveler #_
0&1 34
- 1.
Owner Southem Nucear Operating Company Name 40 Invemess Center Parkway, Binmingham AL
- 2.
Plant Vogee Electnc Generaffng Plant Waynesboro. GA 30830 Address
- 3.
Work Performed by NucearOperations Maintenance Name Date Sheet Unit MWO # II I
- of I
4-2 $fbd6/0 4C4 t 9L //6/06C 20303155 i . Repair Organization P.O. No, Job No. etc. Plant Voatoe Address I
- 4.
Identification Of System 1301 /Main Steam System
- 5.
(a) Applicable Construction Code ASMESECXI 1977
- EditIon, Wter 1977 (b)Applicable Edition of Section XI Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components
- Addenda, N-249-1 Code Casle
- 7.
Description Of Work SnubberAD-43. serial# 716 was repdacedwith a ridstnrtin accordance with OCPOI.V2N0004.
- 8.
Test Conducted: Hydrostatic [] Pneumatic[] Nominal Operating PressureD WA[ Other [I Pressure _NIA PSI Test Temp. NWA OF (41 - 1. I CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section XL. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Team Leader Date Owne or Owner's Designee, Title I CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the national Board of boiler and Pressure vessel Inspectors and the State' or Province of Geormia and employed by Hartford Steam Soier lnsce tion and Insurance Co of Connectcut of Hartford Connecticut have inspected
- he components described In this Owners Report during the period 0?/Ia?4 I
to -- /7-01! , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section XL By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or inplied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shali be liable In any manwr for any personal Injury or property damage or a loss of any kind arising from or connected with this insvev~jorib ./AJI f/=> we Comrnmisslons _I Ins ors Signature National Board, State. Province and Endorsements Date_______ I I I II I I I ^UT"O CORt
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Ot Thc ASME Code Section Xi Traveler # 040U
- 1. Owner Southern Nucleer Operating Company Date May 12,2004 Name 40 Inverness Center Pa*way. Birmingham. AL Sheet I
of Address
- 2. Plant Vogtfe Electric Generating Plant Plant Wavnesboro. GA 30830 I
i Unit MWO # 2 1 20303133 Repair Organization P.O. No., Job No, etc Address
- 3.
Work Performed by Nuclear Operaons Maintenance Name Plant Vogtle Address 1301 MAIN STEAM SYSTEM
- 4. Identification Of System
- 5. (a) Applicable Construction Code AWE Section XI 1977 Edition, Winter1977
- Addenda, N-249-1 CodeCase (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacernents 1S89
- 6. Identification Ot Components Repairs Or Replacerent Cornponents
- 7. Description Of Work Snubber AD-161L serial # 707 was replaced with snubber Llsega 3009. serial #0361640"28 In accordance with DCP-99VANOM=
S. Tests Conducted: Hydrostatic C] Pneumatic C[ Nominal Operating Pressure 0 N/A X Other p Pressure NIA PSI Test Temp. N/A F CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this rules of the ASME Code, Section Xi. replacement conforms to the II IiI repair or replacement N/A Type Code Symbol Stamp !of Team Leader Date 7 I I ,CERTIFICATE OF INSERVICE INSPECTION I 1, the undersigned, holding javld cornrnsilon Issued by the National Board ol Eoiler and Pressure Vessel Inspectors and the State or Province of Georola and employed by _; Warfford Steam Boller lnsoectlon and Insurance Co of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period February 19, 2004 to.5- /7-../ ., and state that to the best of my knowiedge and belief, the Owner has perfored examinations and tests and taken corrective measures described in this Owners Report In accordance with the requirements of the'ASME Code. Section Xl! 1 II lI By signing this certificate, neither the Inspector nor his enployer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this InI Conmmissdons cA.aoS Inspor's Signature National Board. State. Province and Endorsements Date 5-.,7-
ORIGINAL (I1 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 04046
- 1.
Owner Southern Nuclear Operating Company Date May 11, 2004 Name 40 1nivemoss Center Parkway, Blrnnr gham, AL Sheet t ot Address
- 2.
Plant Vo tie Electric Generating Plant Unit 2 Plant Waynesboro, GA 30830 MWO # 20303134 Address Repair Organization P.O. No. Job No. etc.
- 3.
Work Performed by Nuclear Operatfons Maintenance Plant Voate Name Address
- 4. Identificatlon OtSystem 13011 Main Steam System S.
(a)ApplicableConstructionCode ASME Section Ii 1977 Edition, Winter1977
- Addenda, N-249-1 CodeCase (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1999
- 6. Identification Of Components Repairs Or Replacement Comnponents NAME NAME MANUFACTURER NATIONAL REPAIRED.
ASUE CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. No. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) P/pe Support Puilman Power tVA IWA V2-1301-109-HOW 1989 REPLACEMENT YES Products 7.Dsrpio fWr S Ibe A-5L eIa 46wsrncdwihsubrLsa30.sral085402Incodne
- 7.
Description OtWorkt Snubber AiN1S1L ser/ail # 8Jwas rerlaced wltbsnubber Llseea.a 1J9serlal # 315640/29 Jnaccordance with DCP199VANOW33
- 8.
Tests Conducted: Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 N/A E Other 0 Pressure MIA PSI Test Temp. MA OF CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this rniplacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp NiA Certificate o Authorization No. N/A Expiration Date A NIA Signed Team Leader Date A Owner or owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Harntrd Steam Boller Inspectlon and Insurance Co of Connecticut of He Connecticut have Inspected the components described In this Owner's Report during the period February 19 2004 to a-n ure
- nd state that to the best of my knowledge and belief, the Owner has performed examinations and tests and takei corective reasures described In this Owners Report In accordance with the requirements of the ASME Code, Section XI By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Irnplied, concerning thy examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shal be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with thi Commissions GAi7&?
Inspeetor's Signature National Board. State. Province and Endorsements Date 1 7 _if
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler # 04046
- 1. Owner Southern Nuclear Operating Conpany Date May11, 2004 Narne 40 Invemess Center Par*waK, Birmingham, AL Sheet I
of I Address
- 2. Plant Vootle Electric Genwatino Plant Unit 2
Plant Waynesboro, GA 3030 MWO # 20303137 1 Address Repair Organization P.O. No, Job No., etc.
- 3.
WorkPerfornedby NuclearOperatfonsMaintenance Plant Vogthe Name Address
- 4.
Identification Of System 13011 Main Steam System
- 6.
(a) Applicabie Construction Code ASHE Section ill 1977 Edition, Winter 1977 Addenda. .MW 6 Case (b)Appiicable Edition ot Section XI Utiiized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL REPAIRED. ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipo Support Pullman Power __A NA V_-1301-167.H*30 1989 REPLACEMENT YES Products
- 7.
Description O Work Snubber Ai-163. seria #716 was rentacd wth snubber Ltsea 3o38o01 sertal $ 0181496010 hi accordance wth DCP 99-VAN0033.
- 8.
Tests Conducted: Hydrostatic 3 PneumatIc [ Nominal Operating Pressure 0 N/A E Other 0 Pressure N/A PSI Test Temp. N/A
- F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code. Section XI.
repair or replacement Type Code Symbol Stamp N/A Certificateoflzthorization No. N Expiration Date NIA Signed ¢/ t eo rg Team Leader Date 5 Ow or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid conmrission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geormla and employed by Hartord Steam Boiler Insnecton and insurance Co of Connecicut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period I February 19,2004 to -4an7-d and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this I1 Commissions (A .2a Ins tar's Signature National Board, State, Province and Endorsements Date i-i 7_O4
UMIUIINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS d As Required By The Provisions Of The ASME Code Section Xl Traveler # 04047 0513J04
- t.
Owner Southern Nuclear Operadng Company Name 40 Inverness Center Parkway, Bim'inghem, AL Date
- 2.
Plant Vogtfe ESectrfc Generefng Plant Waynesboro. GA 30830 Sheet Unit MWO # I Of J -4 Z .1 20303140 Address
- 3.
Work Performned by Nudear Opersbons Mantenance Repair Organization P.O. No., Job No., etc. Plant Vogie Address Name
- 4.
Identification Of System 1302/Auxlary Feedovater System S. (a) Applicable Construcion Code ASME SEC Ill 1977 Edition. Winter 1977 Addenda. N-249-1 Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL REPAIRED. ASME CODE' OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) PIPE SUPPORT PULLMAN N/A N/A V2-1302-110-H017 1989 REPLACEMENT YES POWER PRODUCTS
- 7.
Description OfWork SnubberAD-501. serat# 567was roelaced wth. Usesa Type 30snubberseial# 0261515a)61 In accortance w, DCP 99-VAN0033.
- 8.
Test Conducted: HydrostatIcEQ Pneumatic[] Nominal Operating Pressure[] N/A F[3 Other 5 Pressure N/A PSI Test Temp. NtA F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code. Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Aut rization No. N/A Expiration Date N/A Stgned ream Leader Date Owner owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- i. the undersigned, holding a valid comnnisslon Issued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georgla and employed by Hartford Steam Bofler Insoeclon and Insurance Co. of Conned/cut of Harfford. Connec6cut have Inspected the components described In this Owner's Report during
'the period 02/19i04 to 17-n and state that to the best of my knowledge and belief, the Owner has pertormed examinations and taken correctIve measures described In this Owners ' Report In accordance wlth the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inpector nor his employer makes any warranty, expressed or Implied, conceming the examinations and coffective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any m er for any personal injury or property damage or a loss of any kind arising from or connected with ihis ins //l I Commissions GA v Ins-or's SIgfaure I National Board, State, Province and Endorsements Date 1 I
FORM NIS-2 OWNER'S REPOQAgII OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler 1 04049
- 1. Owner Southern Nuclear Operating Company Date May 11, 2004 Name 40InvemessCenterParkway. Bknnlnham, AL Sheet I
of I Address
- 2.
Plant Vocile Electrfc Generating Plant Unit 2 Plant Waynesboro, GA 30830 MWO D 20303126 1 Address Repair Organization P.O. No, Job No., etc.
- 3. Work Performed by Nuclear Operations Maintenance Plant Vogtle Name Address
- 4. Identification Of System 1206 1 Residual Heat Removal System
- 5. (a) Applicable Construction Code ASME Section 1ff 1977 Edition.
Winter1977 Addenda, N-249-1 CodeCase (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6. Identification Of Components Repairs Or Replacernent Components NAME iNAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL BOARD OTHER YER REPLACEo OR jSTAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NOj Pipe Support Pullman Power WA WA V2-1206-007-H007 1989 REPLACEMENT t YES Products =D r I I I I I
- 7. Description Ol Work Snubber PSA-3. serlal #28724 was replaced wih snubber LIseqa 305202Z serbil #01015200102 in accordance with DCP-49VAN0033 S. Tests Conducted:
Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 N/A 0 Other O Pressure N/A PSI TestTemp. NIA F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Cerliflcate of Aptorizatioo No. NIA Expiration Date N/A Signed /Tean Leader Date gL OwYrrorOwneri Designee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid cornmission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Geormia and employed by.
Hanrtfbrd Steam Boiler inspection and Insurance Co of Connecticut I of Connecticut have Inspected the components described in this Owner's Report during the period Febr 19, 2004 to .. r7-07. and state that to the best of my knowledge and belief. the Owner has performed examinations and tests and taken corrective rneasures described In this Owners Report In accordance with the requirerments of the ASME Code, Section XI. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any maer for any personal injury or property damage or a loss of any kind arising from or connected with this -e Cornnmissions GS;2n! Inspor's Signature National Board. State, Province and Endorsements --V'f-7-n-q oate _at., t i n
X t F ORIGINAL FORM NIS-2 OWNER'S REPO FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl
- 1. Owner Southern Nuudear Operatdng Company Date Traveler #
11, 2004 o1 2 04050 i °4;°s°I Name 40 Invemere Center Parkway, Blnningham, AL Address
- 2. Plant Vogfe Electric Generating Plant Sheet I
Ptant Waynesboro, GA 308-30 Unit MWO # 20303U94 Repair Organization P.O. No, Job No., etc. Address
- 3. Work Perforned by Nuclear Operalions Maintenance Name Plant Vogtke Address
- 4. Identification Of System 12061 Residual Heat Removal System S.
(a) Applicable Construction Code ASMESection iII 1877 Edition, Winter?977
- Addenda, N.2491 CodeCase (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 191f B. Identification Of Components Repairs Or Replacement Components NAME NAME I
MANUACTURER NATiONAL
- REPAIRED, ASME CODE OF OF SERIAL BODARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power AVA WA V2 1205-008H006 1989 REPLACEMENr YES Products
- 7. Description Of Work Snubber PSA-1. seral # 17J3 wa relbcd wt snubber Ltsge 303801. serial #01149013 in accordance yfrth DCP-99VANOa3I I
I ii I I I I I I I
- 8.
Tests Conducted: Hydrostatic O Pneumatic 0 Nominal Operating Pressure O NIA Other E Pressure N/A PSI Test Temp. N/A Of CERTiFICATE OF COMPtlANCE We certify that the statemnents nade In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacenent Type Code Symbol Stamp N/A Certificate oIhorization No. N/A Expiration Date N/A Signed ZZ4 Team Leader Date d~ner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned. holdinr a valid cornmission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Hartford Steam Boiler insoectonand Insurance Co of Conneetkit I of hrtford Conneicicut have inspected the components described in this Owner's Report during the period E February 19.2004 to . and state that to the best of my knowledge and belief, the Owner has perforrmed examinations and tests and takeri corrective measures described in this Owners Report In accordance with the requiremnrts of the ASME Code. Section Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed 'or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, netther the Inspector nor his employer shail be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this i___ _ Comrnisslons eC .A.W T? Insporor's Signature i I National Board, State, Province and Endorsements Date 5j7_o i I
ORIGI1NAL fORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS - As Required By The Provisions Ol The ASME Code Section Xi Traveler # 04055 May 12.2004
- 1. Owner Southem Nuclear Opoemtlng Comrpny Name 40 Inverness Center ParAway, Binningham, AL Address
- 2.
Plant Vogetl Electric Generating Plant Plant Waynesboro, GA 30830 Address
- 3. Work Performed by Nuclear Operations MaIntenance Date Sheet Unit MWO t I
of I 2 20303376 Repair Organization P.O. No., Job No., etc.
- Plant Vogtle Name Address
- 4. Identification Of System 1302 /AUXILlARY FI S. (a) Applicable Construction Code ASME Section 1l 1977 Edition, (b)Appiicabie Edition of Section XI Utilized For Repairs Or Replacements 1999
- 6. Identification Of Components Repairs Or Replacement Components EEDWATER SYSTEM W
Winte~r 1977 Addenda, N-2 9t1 Code Case NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF 3ERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT I MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power tVA AVA V2-1302-110-H002 1989 REPLACEMENT YES Products
- 7. Description Of Work Snubber PSA-10. serlal V 16092 was replaced with snubber L/seeas 306201. serlal U01614940104 In accordance with DCP-99VAN0033 B. Tests Conducted:
N/A l Hydrostatic D Pneumatic 03 Nominal Operating Pressure O Other 03 Pressure N/A PSI Test Temp. N/A OF CERTIFICATE OF COMPLIANCE We certiy that the statemnents made inthe report are correct and this replacement conforms to the rules of the ASME Code. Section X. repair or replacement Type Code Symbol Stamp NIA Certificate ot Sthorization No. NA Expiration Date NWA Signed 6 4 / Team Leader Date a 9 ener or Owner's Designee, Title I i #-,p 6 CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid comnnission Issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Goomis and employed by Hartford Steam BLoller insection and Insurance Co of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period I February 16. 2004 to 5-tz.~Y7-0 .., and state that to the best of ery knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners jReport In accordance with the requirements of the ASME Code, Section Xl By signing this certificate, neither the Inspector nor his employer makes any warrantylexpressed or Impied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any masner for any personal Injury or property damage or a loss of any' kind arising from or connected with this ICommissions GA v03 InsjpCtor's 87gnature. National Board, State. Province and Endorsements Date A-{7 4
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler I
- 068
- 1. Owner Southem Nuclear Operating Company Date May 12,2004 Name 40 Inverness Center Parkway, Blrmingham, AL Sheet I
of I Address
- 2.
Plant _Vogte Electric Generating Plant Unit 2 Plant Waynesboro, GA 30830 MWO # 20303363 Address Repair Organization P.O. No., Job No. etc.
- 3. Work Performed by Nuclear Operations MaIntenance Plant Voqtke Name Address
- 4.
Identification Of System 12021 NUCLEAR SERVICE COOLING WATER SYSTEM
- 6. (a) Applicable Construction Code ASME Section III 1977 Edition, WInter 1977 Addenda, N-249.1 Code Case (b)Appllcable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6. IdentIficatIon Of Components Repairs Or Replacement Cornponents NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power WIA N/A V2-1202-231.H0" t19S REPLACEMENT YES Products
- 7.
Description Of Work Snubber AD-1U. seral #a196 was replaced whh snubber Ltsaa 0309. serlal 016149839 In accordance with DCP-99VANOO33
- 8.
Tests Conducted: Hydrostatic 0 Pneumatic El Norminal Operating Pressure 0 NIA 0 Other 0 Pressure N/A PSI Test Temp. N/A F CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code. Section XI. repair or replacement Type Code Symbol Stamp N/A Certificate of Authorization No IA Expiration Date WA Signed Team Leader Date __ __e_ o or Owneia Designee, Ttl7e CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid cornisdon issued by the National Board of BMier and Pressure Vessel Inspectors and the State or Province of Georala end employed by Hartford Steam Bolter /nsPectUon and Insurance Co of Connectcut of Hartford CornntgcLt have inspected the components described in this Owner's Report during the period February 16, 2004 to 5.IL-
/f-o0V and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any malner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions 6 0 .7O3 Inspoltor's Signature National Board, State, Province and Endorsements Date__________
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions or The ASME Code Section Xi Traveler # 04060
- 1. Owner Southern Nuclear Operating Company Date May 11, 2004 Name 40 Inverness Center ParkwaY. Birmingham, AL Sheet I
of I Address
- 2.
Plant Vogde Electrc Generating Plant Unit 2 Plant Waynesboro, GA 30830 MWOO 20303361 Address Repair Organization P.O. No, Job No.. etc.
- 3. Work Performedby NuclearOperations Maintenance Plant VotIe Name Address
- 4. Identification Of System 12061 Containment Spray System
- 6. (a) Applicable Construction Code ASME Section iti 19TT Edition, Winter197T
- Addenda, N-249-1 CodeCase (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6. Identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE Of OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power WA WA V2-1206-002-HO1S 1898 REPLACEMENT YES Products
- 7. Description OWork SnubberAD-503. serial213 was replacedwithLisea snubber3062. serfai#66348135inaccordancewih DCP S9-VAN033. The removed snubber (serial #213) fatled an Insernvce Aunctronal test es documented In CR S 200400874.
S. Tests Conducted: Hydrostatic O Pneumatic a Norminal Operating Pressure 0 N/A 0 Other 3 Pressure N/A PSI Test Temp. NIA
- F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
repair or replacement Type Code Symbol Stamp N/A Certificate of Aulhorizationl4o. A Expiration Date N/A Signed Team Leader Date er or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boller and Pressure Vessel Inspectors and the State or Province of Georola and employed by Hartford Steam Boller Insrectlon and Insurance Co of Connecticut of Hart/ord Connecticut have Inspected the components described In this Owner's Report during the period February 18 2004 to 4 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore. neither the Inspector nor his employer shall be liable in any frnner for any personal Injury or property damage or a loss of any kind arising from or connected with this Conrnissions GA o I Insp&Itor's Signature Nafional Doad. State, Province and Endorsements Date .50. /*.d
sw e
- FORM NIS-2 OWNER'S RI ~Rc1 NAL REPL As Required By The Provisions Of The ASME Code Section Xl ACEMENTS
/ I Traveler # 04061 May 12,2004 I Of I 21 2
- 1. Owner Southern Nuclear ODeratna Company Date Narne N
40 Inverness Canthr Parkway, Btrinngham, AL Address
- 2. Plant YVoge Electric Generating Plant Sheet I
Unit Plant Waynesboro, GA 30830 20303350 MWO N Address Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by Nuclear Operatlons Maintenance Plant Vogtue Name Address
- 4. Identification Of System 1205 6 RESIDUAL HEAT REMOVAL SYSTEM
- 6. la) Applicable Construction Code ASME Section II 1977 Edition.
Whtner 1977
- Addenda, 11-249-1 Code Case lb)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 19S9
- 6. Identification Of Components Repairs Or Replacement Comnponents NAME NAME MANUFACTURER NATONAL
- RPARED, ASME CODE OF OF SERIAL BOARD OTHER YEAR REPACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power N/A N/A V2412065030H012 1989 REPLACEMENT YES Products
- 7.
Description Of Work Snubber AD-43. seral# 1620 was reDlaced with snubber Llseoa 3018. ser/Ia #1477048 In accordance wtth I DCP-99VANo001
- 9.
Tests Conducted: Hydrostatic 0J Pneumatic 3 Nominal Operating Pressure 0 N/A 0 Other O Pressure NA PSI Test Temp. WA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code. Section XI. repair or replacement Type Code Symbol Stamp N/A Certificale oI A thotization No. U6 Expiration Date MIA Signed /TeamLeader Date S_ 'Oner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION t, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georla and employed by Hartford Steam Boller insoection and Insurnnco Co of Connecticut of Hartford Connecticut have Inspected the components described In this Owner's Report during the period February 19,2004 to A.W10L 1 , and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall he liable In any "nner for any personal Injury or property damage or a loss of any, kind arising from or connected with this Commissions 4GAd. 3r Insictor's Signature Date 5 -o' National Board. State. Province and Endorsements I
FORM NIS-2 OWNER'S REPORT FOR "pCEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler#U 04063
- 1.
Owner Southem Nudear Operating Company Date Name 40 Inverness Center Parkway, Binningham. AL Sheet Address
- 2.
Plant Vogde Electric Genereting Plant Name Waynesboro, GA 30830 Address November10, 2004 I of 3 2 20301663 Unit Repair Organization P.O. No., Job No. etc.
- 3.
Work Performed by _
- 4.
Identification of System Maintenance Depatment Name Plant Vogffe Type Code Symbol Stamp Authorization No. Expiration Date NIA .A. Address 120B /Chemlkal J Vdrume Control System S. (a) Applicable Construction Code ASME SEC I 19 74 Edition. Wnter 1975
- Addenda, (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
- 6.
Identication Of Components Repaired or Replaced and Replacement Components Code Camx National
- Repaired, ASME Code Name of Name of Manufacturer Board Other Year Replaced.
Stamped Component Manufacturer Serial No. No Identification Built or Replacement (Yes or No) HEAT JOSEPH OAT 2635 3436 2-1208-E6.003 2004 REPLACEMENT YES EXCHANGER CORP.
- 7.
Description ot Work Replaced the Lefdown Heat Exchanger serle t#2322-48 with srIal #2035 In accordance with MDt 03-V2M088 *ad welded assodated pping. Form N-I for new heat axchanger *ttached. (40 1 B. Test Conducted: NIA r
- 9.
Remarks See Item 7 Hydrostatic C Pneumatic C Nominal Operating Pressure IS Other C Pressure N/A PSI Test Temp. N/A F Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLiANCE We certify that the statements made In the report are correct and this Replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp Certificate of Authorization No. Signed /4 N/A NA Expiration Date NMA Team Leader Date Jo 3 , 2 c54-W oiwne~r Own~rrs'sIgnee. Title CERTIFICATE OF fNSERVICE INSPECTION 1 the undersigned. holding a valid commission Issued by the national Board of Boller and Pressure Vessel Inspectors and the State or Province of Geonrga and employed by Hanford Steam Boer InsDecton endinsurance Co. of Connectcut of Hartford. Conneebtcut have Inspected the components described in this Owners Report during the period Aafr9 26 2004 to..-. gc. e and state that to the best of my knowledge and belief. the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report Furtherrore, neither the Inspector nor his employer *hall be liable In any IIannel for any personal Injury or property damage or a loss of any kind arising from or connected with this >7/5 a~k Commissions CA ? Inspectsfs Signature National Board. State. Province and Endorsements Date /I2 4-o
FORM N-i cERTRA7E moLvERs, DATA REPORT FOR NuClARn vEmas&B As RaquIred the Provtuiosac of ths ASME Coda. Smcton 11L DIVIan I Pg. I of 2
- 1.
nufcturer end cdrlmGd by Joseph Oat C2oortgoem 2500 Breen~y Cme.W08104
- 2. Manufactured for PAW1 a ~
Ni lo Oin 0W!; Vogdo Eisef UmtikaPli.Id 2
- 3. Location of Instaflstlofl HORFZ Most Exdwflge 238-OIZ02AW 3438 2004
- 4. Type d.or Wr)-
(3k -O testj -ruLuiiw" si Ga -j o-w ym fv I .1974. WhW 1r1978._ L. ASME Cede., 6s.60n 11U. OMWOn 1: hit i.ds ~ mm W. keaee lka .315, .22 1'.1W0I i6-Lg37
- 7. Sems Y*
65 meeVYe C Con we
- rcl W-
- tft!
Ca o fCAV!r If suqiovable. baits used 0l.dinflng ~Jce iet$OW Oft on am mittM Wm ~Wsgud.~i
- 10. Design pmaw' 2S At nm. on
.Mn p~t~mu4m timp. Pwwu..hyd0.rma.. ~ mr hmiv11 sand U 20t bA 01e 1 Wf 11.030 .XDtTEti teaisy. asht. -. 1low. I. tes W. 54 maa gu. bof.itI. SA24__ __.750 .049 142 U
- 2. 7UbSS
-onge IJ 0 p;41 1ia -on - soN 60 bwaSisevoU2
- 14. S5em*.
V w -m i'i n fo. or uui 15 ee s A240404 75 K81 Cliimlh-.s4 icmma pagm(ly e F sdu f Rojo Ap-(Angle a'qiI 1.1ml .J tatS.iw (of Top, bettom&i IWIS I-~C 1bW Channel I 1trnvbd aeue A9-6. Vn I3 8A194-2H. 1. 58 064r~fistoing la. Deig pr~~ W... M~int. piswsure-loot t,,hp. 50 Paoli. hydra., or comb. tes pr'essaure C ~J M pcatw hi haWOW.& Lst UN hf fflfl. i Sqm W iisiI prwure w~t coladdent tlfi~arsurs 106, e1Ppilemlik uppn,, 1 ift hI~lOm 51~ lhonsof lflts. skuidwia a'r drvmnp ine be used lowtdWi~d ( I va1 11% X l.flW Infor iobI"sqs V--iou% Ass Uan boto Roporsl Cisoch ihoit. PI sodS ihrest Is yu, jib and SilfAWi of aheat 1 Iv ~ a it top 4 SE fUs `La I~ ThM)is ton ICO "WSS be gabeld froon he~ Oma'r D05%. ABIAL 221a LowDiv, SOm 2300. Fodirfsd. NJ 07007.2300.
F ORM N-1 (Back - Pg. 2 of.2-J 17-fjmist-Insnecdioa and safetv Vshve OPednQW 11 Purpoee NOWe Kok arurnuto liner ouidvl. draln. etc-i Gluntity Oim or as. Type Ataclud man 1Wd~n0u. maomw Location IN I OUT 2 v EWwr w EDD SA0-M IN IOUT 2 3' PJVM -WELDED SAt5I I4__lie_ VENT .75& CPLG WEDE SAIDS 3000D__ DRAIN j .7w0 CPLG WELED SA1O ___5_ IS. Supports: Skirt Logp gs O. ther Sem u llala SHELL. w Desig specdficatuon eayifd by Gerald A. WeOWa P.E. S~tal pp
- g no.
11222-E Design im port 0e tlle bY __wt
- 6. S eb.
kp i P Ag. no c~ffnUCATE OF SHOP COMPLUUCE. W ce am the athteMn nude In thib report ant correct and that this nurger vessel ordorrs to the nie ft construcilon of thn ASME C Sean ML DiSbon I. N No N-1488 PO_ Aug 4.2006 Nave. ~Jo a~ph Oat o or t n-9' 'l F CERT f WAM OF SO UPICNO W I the undersined, holding a vald vonrrAalon Issued by the National Dord of Dollar ard Piwmue Vessal Inspectore and the Stot or ProvInc of NJ 1nd rnod by One Bisni Am e nusunce Ccm* o tf Bostn bha" I pne thebrnp ed hithidMh DPOrt on and-stof My knowd1 end bH rha stettndge nnd e wih h ASI4E Code. Section Ul, nhdo L Sy sging thi eartfats neithe the Inpactor nor hNo employer makes any werrary, exprsed or mplad, Concmrng the omponant described In this Dat Itaport Fuiilwtanor. neither " Inapector nor his emlkrw uham be liable In any manner ot any personal inku or proprty demags or a ton of any knd ading ft or co!! .~ _~hd s ~ m _)g e w . ~ CE.TNFCATE OF FMD ASSWLY COIPLIANCE We cr" that the stataments on this report an correct Nad that tn field amwr* conxtrudlon of all parts of this nucler wli 10mw to ow nhn of conrbuction of the ASME Coda Secdon Mi DWvsin I. N Crific.a( Authorton No. Expir Da" Nr m Signed CfTICATE OF FIRED ASSEMBLY WISPEClO
- 1. the underigned, holding a valid convnlslon imiud by the National Bord tof Boiler and Pressure Venal Inspectors and the Steae or Protwince of and orpoyM by of ha" compared the statrnants hI this Data Report with the descrbod cormonent nnd astt tht pers rWarred to - data ka, r not Inolded In the ssrtificste of ohop inaton.
he been knpected bys an nW that lo t b of my knowledge and bei th Certficaft Hoder has contwructed snd saevnblad thia component In aecordance with the ASME Code, Section I, DMvbion 1.
- 1 By signing this crtificate neither the lnsetor nor his eployer m I any warranty, axpresed or bV9d, concrning th component described in ts Dt Report. Furhrw ore, nalther the inwsoltor nor his *nr4oyar ahall be lIable In any mnner for any pasonw Injury or property daimag or a Ie of any kind ariairng from or connrcd ih this Inspection.
Do" Signed C esio sd Wow FZi he Ed fad 0.delm mNO 0-d'. p.. a"a mej
FORM NIS-2 OWNER'S RINA4, ImR REPLACEMENTS As Required By ' Provisions Of The ASME Code Seitlon Xl Traveler# 04064 Southern Nuclear Operating Company' Date November2?. 2004
- 1.
Owner Name 40 Inverness Center Parkway, BIrmingham, AL Address
- 2.
Plant Vogtle Electrfc Generatng Plant Name Waynesboro, GA 30830 Address
- 3.
Work Performed by Maintenance Department Name Plant Vogde Sheet Unit I of 2 1 20301663 Repair Organization P.O. No., Job No. etc. Type Code Symbol Stamp N/A Authorialon No. N/A xpiratfon Date MA Address
- 4.
Identification of System 1208 Cherncal S Vohlme Control System I
- 6.
(a) Applicable Construction Code ASME SEC /II 19 77 Edition, Whter 77
- Addenda, N/A Code Case (b)Applicable Edition of Section Xi Utilized for Repairs or Replacements 1989
- 6.
Identification Of Components Repaired or Replaced and Replacement Components
- 7.
Description of Work Modifed (he CVCS inlet piping to the Letdown Heat Exchanger to support Installeaon of the new heat exchanger under MDC 03-V2M088. Code Case N.416-t was usedforthe instaltbon ofthis piping. I H [I fI A t. 9. Test Conducted: Hydrostatic EJ Pneumnaticio Norninal OperatinglPressure[M NWA[0 Other jr Pressure N/A PSI Test Tenp. N/A OF Remarks See Item 7 I Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the stadements made In the report are correct and this replacement conforms to the rules of th~e ASME Code. Section Xl. repar or vepacemWn Type Code Symbol Stamp NM CertificAe o A rizatlon No. NMA Expiration Date NM_! Signed TeemLeader Date ____a_ _ Ovfer or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION i 1, the undersigned, holding a valid commission issued by the national Board of Boiler and Pressure Vessel Inspectors end the State or Province of Georgia and employed by Herffrd Steam B3oRer Insoecffon end Insurance Co. of Connecticut of Harford Connectcut have Inspected the components described In this Owners Report during the period AphT 13 2004 I to t2ya::EA0 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or i"plled, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any rnyver for any personal Injury or property damage or a loss of any kind arising from or connected with ihis lnsiI,;5
- ?
~ Commissions (A.20 ? tInspttor s Signature National 11oard, State, Province and Endorsements Date _ I I I I...
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl iCX 04068 Traveler s_ 07107/04
- 1.
Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Bflmingham AL
- 2.
Plant Vootle Electric Generating Plant Date Sheet Unit MWOA# Waynesboro GA 30830 Address
- 3.
Work Performed by Nuclear Operations Malntenance Name I of .I 2 1 20400262 Repair Organization P.O. No., Job No., etc. I Plant VooIe I Address l II I
- 4.
Identification Of System 1305/Condensate and Feed water S S. (a) Applicable Construction Code ASME SEC Ili 197;' Edition, Winter 1977 A (b)Applicable Edition of Section Xl Utilized For Repa ira Or Replacements 19fl2
- 6.
Identification Of Components Repairs Or Replacement Components System
- kddenda, NIA Code Cane NAME NAME MANUFACTURER NATiONAL
- REPAIRED, ASME CODE i OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) I 1305 PIPING PUllMAN N/A A 2K5-1305-058-01 1989 REPLACEMENT YES SYSTEM POWER PRODUICTS.
- 7.
Description Of Work Studs and nutls were reolaced in Din/n flanoes at valve 2lV-5230.
- 8.
Test Conducted: Hydrostatic Q PneumaticQ Nominal Operating Pressure[] WNAM Other fl Pressure NIA PSI Test Temp. WA OF CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code, Section XI. repair or replacement Type Code Symbol Stamp hUA Certificate of Authorization No. NiA Expiration Date N/A Signed 11/ Team Date I O oer or Owner-s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the national Board of boiler and Pressure vessel Inspertors and the Statefor Province of GeoroJa and employed by Hartford Steam Boller Insoection and Insurance Co. of Conneu of Harford Connecticu have Inspected the components described In this Owner's Report during the period 03/15104 to /7- .., and state that to the best of my knowledge and belief, the Owner is pertormed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section ?11. By signing this certificate, neither the Inspector nor his employer makes any warranty. expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manna for any personal injury or property damage or a loss of any kind arising from or connected with tAis wi / ,,Commissions e;Afizas3 Ins rs Signature National Board, State, Province and Endorsements Date 7-jl.6 _L
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler,0 04071 OSI&04
- 1.
Owner Sou66emNudlarOpe rtngCompny Name 40 Inveness Center Parkway. 8ringheam. AL
- 2.
Plant Voga Electric Generabho Plant Date Sheet Unit MWO 8 I Of I Waynesboto. GA 30830 Address
- 3.
Werk Performed by Nudear Operaffions Alfsenance Name 20401067 Repair Organization PO. No. Job No., et. Pfnt Voot e Address 4. S. S. Idetficauin of System 1208 /Cheic'a and Vdunm CoarWr SYotem (a) Applicable Construction Code ASME SEC Wl 1977 Edition W ter1977
- Addenda, WA Code Ca"e (b)Appicable Edtion o Section XI UtUized For Repairs Or Replacemens lf Identification Or Componts Repairs Or Replacement Components A"ANJFACTURER NATIONAL REPAIREDW
- $*ECO OP Off SERIAL
- BOARD OTffER YER REPLAE OR STAMPD COMPONENT MANUFACTURER NO.
NO. IWENTIFICATKOf WULT REPLACEMENT (T OR NO) PIPE SUPPORT PULLMAN NK/A N/A V2-1208-0024-HOI 1989 REPLACEENT YES POWER
- 7.
Oescription OfWork Snubber PSA-112 seriat 8 8755 wps redaced wih PSA-I). se$l 8 175W to sWraord surnce tesina. The rmovedsnubber se 87551) tiaed n inserice funconal lestas documneied bYCR8 2004001737. I. Test Conlducted: NAE] Hydrostaic Q Pneuatk3 NIoAPinal OperatingPressureNA Other [] Pressure W/A PSI Test Temp. N/A O CERTIFICATE OF COMPUANCE We certify tha the statements made in the report are correct aNd this REPLACEMENT conrorms to the rues of tOe ASME Code. Section XL repair of rp t Type Code Symboi Starnp NWA Certificate of Authorization No. NIA Expiration Date NA Signed TeamLeader Da / a L t0ner or Owes Designee, Tmc 46 CERTIFICATE OF INSERVICE INSPECTIOIN I, the undersigned. holding a valid connission Issued by the national oard of boiler and Pressure Vessel inspectors and the State. or Province of G -a andenployedbyHattfordSteam BoierinsoedonandinsuranceCo.oIConnectic otHarltbd. Connecd have Inspected the components described In this Owners Report during the period 0/n4 to a-.7-a nd state that to the best of my knowledge and beliet the Owner has perfomed examinations and taken corrective trsres described hi this Owners Report In accordance with the requirements of the ASME Code. Section Xl By signing this certiftiate. neither the Inspector nor his employer makes any warranty, expressed or frpied., concmeing the exainawidns and corrective measures described hi this Owners Report Furthermor neither the Inspector nor his employer slW be liable In any manne for any personal InJury or property damage or a loss of any Wind *rising from or connected with this CCortssions fAi4 a.Y Slgne National Board. State. Province nd Endorsements Date__________
-4 FORM NIS-2 OWNER'S ReFORT PAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi I i I. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, BIrmIngham, AL Address
- 2.
Plant Vogtle Electric Generatina Plant Date Sheet Unit MWO t Traveler P 04073 May 24,2004 1 of t Plant Waynesboro. GA 30830 2 20303261 Address
- 3.
Work Performed by Nuclear OPeratons MaIntenance Narre Repair Organization P.O. No., Job No., etc. Plant Vogtle Address
- 4. Identification Of System 13021 Auxiliary Feedwater System
- 6. (a) Applicable Construction Code ASMESecton OlI 1974 Edition, Summer 1975 Addenda, MA Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Of Replacements 1999
- 6.
Identification Of Components Repairs Or Reptacement Conponents NAME NAME MANUFACTURER NATIONAL REPAIRED. ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Valve Anchor/Darting E9OO1-28-T N7A 2-1302-U4-114 1880 REPLACEMENT YES Valve Co.
- 7. Description O Work Replaced valve disc In valve 2.1302-114-114
- 8.
Tests Conducted: Hydrostatic O Pneumatic 3 Nominal Operating Pressure 03 N/A i1 Other 3 Pressure NIA PSI Test Temnp. A
- F CERTIFICATE OF COMPLIANCE We certity that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.
repair or replacement Type Code Symbol Stamp NtA Certificate of ortzarkon No RI/A Expiration Date NIA Slgned Ar//gse, Team Leader Date 6/*2ii ii9 never or Owler's Designee. Title II 7 i II I i i I iI I (,\\dl CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georala and employed by Hartford Steam Bolr lnspectlon and InsuranceCoofConnectIcut I ofHartford Connecticut have Inspected the components described In this Owner's Report during the period, April 23,2004 to and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code, Section Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be; iiable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this I y 5 C ~~Comn isslons A 2 Inspedor's Signature Date G-AIG - O g National Board. State. Province and Endorsements I I i I
FORM NIS-2 OWNER'S RPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 04077 Traveler #_ Maw 17. 2004
- 1. Owner Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address
- 2. Plant Vogte Electric Generating Plant Plant Waynesboro, GA 30830 Date Address
- 3.
Work Performed by Nuclear Opvftlons Maintenance Sheet I of I Unit 2 MWO # 20401278 Repair Organization P.O. No.. Job No.. etc. Plant Vogtle Address 1201 I REACTOR COOLANT SYSTEM Name
- 4.
Identification Of System
- i.
la)ApplicableConstructionCode ASME Section III 1971 Edition, (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989
- 6. Identification Of Components Repairs Or Replacement Comnponents Summer 1972 Addenda, WA Code Case NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) REACTOR COMBUSTION 7373 22004 2-1201-VS-001 1or REPLACEMENT YES ENGINEERING INC =
- 7.
Description Of Work Reblaced nuts and washers at vessel had ocations 3. 8. and 3O S. Tests Conducted: HydrostatIc 0 Pneumatic 0 Nominal Operating Pressure 0 N/A 13 Other 0 Pressure N/A PSI Test Temp. NIA OF CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of Au orization No. NIA Expiration Date NIA Signed XxTeam Leader Date____ lneror Owners Designee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Hartford Steam Boller Insoection and Insurance Co of Connectict_ of Hartford Connecticut have Inspected the components described In this Owner's Report during the period April 30,2004 to A-/Y-O4 and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Inplied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any nnner for any personal Injury or property damage or a loss of any kind arising from or connected with this 8
- 6.
Commissions C GA 7e7c3 Inspdctors Signature National Board, State, Province and Endorsements Date 5-.. .4
f. ORIGINAL FORM NIS-2 OWNER'S'REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi
- i.
Owner. Southern Nuclear Operating Company Name 40 Inverness Center Parkway, Bimrnigham. AL
- 2.
Plant Vogfe Electnc Generating Plant Waynesboro. GA 30830 Address
- 3.
WorkPerformed by NuclearOperationsMaintenance Name Date Sheet Unit Traveler # 04078 0521/4O I Of 2 2 20302285 Repair Organization P.O. No. Job No., etc. Plant Vooffe MWO # Address 1301 IMain Steam System
- 4.
Identification Ot System
- 6.
(a) Applicable Construction Code ASME SEC III 1974 Edition. Summer.1975 Addenda. N/A (b)Applicable Edition of Section XI Utilized For Repairs Or Replacements 1989
- 6.
Identification Of Components Repairs Or Replacernent Components Code Case NAME NAME MANUFACTURER NATIONAL REPAIRED. ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO. No. IDENTIFICATION BUILT REPLACEMENT IYES OR NOI VALVE ANCHOR I E9001-50-8 N/A 2-1301.U4-117 1980 REPLACEMENT YES DARUNG VALVE
- 7.
Description Of Work Insted redVacement bonnet. A COD ot Form N.? for the redacement bonnet s altached
- 1.
Test Conducted: Hydrostatic Pneumatic[] NominalOperatingPressure[ N/AO Other [ Pressure NIA PSI Test Temp. WA Of CERTIFICATE OF COMPiANCE We certify that the statements made In the report are correct and this REPLACEMENT conforms to the rules of the ASME Code. Section XL repair or replacement Type Code Symbol Stamp NIA Certificate oS4uthorization No. NA Expiration Date N/A Signed 'ream Leader Date / 4. Owiler or Owne' Deignee. Thite CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the naUonal Board of boiler and Pressure vessel Inspectors and the State or Province of Geo a and employed by Harnord Steam BolWer Inspection and Insurance Co. of Connecticut of Hartford. Connecdcut have Inspected the components described In this Owner's Report during the period 04129W4 to _'VJr-.0J1 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of the ASME Code. Section Xi. By signing this certificate, neither the Inspector nor his empioyer makes any warranty, expressed or irnlped, concerning the examinations and corrective measures described In this Owners Report. Furthermnore, neither the Inspector nor his employer shall be liable In any mayer for any personal Injury or property damage or a loss of any kind arising from or connected with this Is Commissions GA o. 3 -Vs (or's Signature National Board. State, Province and Endorsements Date__
B3es + A ve; I lo let cop - ,a/1 o 1,ff( il-:i IL 1 Af t !-W 4 l lllll I'l I I1 V Li W E1-K A ana m m m Debt-ftw d."O L _W4"44i OM E - -I Nb,;14~*-3 Z9,4 1.7 ON lwos~l m e t tI 5 -A-d 'got ll U IML.I= I I I If I AN.FMI L.ii I Z%.7 i s e f iqstF wre...
- ~V.l~
Q a-._AFt aeechw f ti_ .rJ kB! OR T7lr~v~ EYOU 96r'E Dh I XI Je TE Ffis moERR X 1 XI I ~~,l An fw .~~V n 4,',. A g~~Y Rv-X~ r.- .J._,
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler # 04079
- 1. Owner Southern Nudear Opeaing Company Date May 11.2004 Nqme 40 Inverness Center ParkwaY. Birningham. AL Sheet t
of I Address
- 2.
Plant Vote Elctric Generating Plant Unit 2 Plant Waynesboro, GA 30830 MWO # 20401389 Address Repair Organization P.O. No. Job No., etc.
- 3. Work Performed by Nuclear Operations Maintenance Plant Vogte Name Address
- 4. Identification Of System 1202 1 Nuclear Service Cooling Water S. la) Applicable Construction Code ASME Section /li 1977 Edition.
Wlnter1977
- Addenda, N249-1 CodeCae (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 1989
- 6. Identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL BORD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NOI Pipe Support Pullman Power N/A N/A V21305-06WH004 1989 REPLACEMENT YES PrFOucts ,L. O
- 7. Description Of Work SnubberAD-153 serial #420 was rwolaed with snubber AD-163. serIal #4M1 to supworf surveillance testing.
L. Tests Conducted: Hydrostatic E Pneunatic C Nominal Operating Pressure 03 N/A i Other Gi Pressure NJA PSI Test Temp. H/A OF CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this teplacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp NIA Certificate of Au orization No. N/A Expiration Date N/A Signed / G ez>O ° Team Leader Date / 5 Qffer or Owneres Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commisslon Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of GMg4 and employed by Hartford Steam Boller Inspection and Insurance Co of Connecticut of Hanford Connecticut have inspected the components described In this Owner's Report during the period April 30.2004 to s .and state that to the best of my knowledge and belief, the Owner has perfonmed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any rnner for any personal Injury or property damage or a loss of any kind arising from or connected with this Commissions GA7Jo3 Insp S Signature National Board, State. Province and Endorsements Date 4S2e~a/
ORIGINAL FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi Traveler U 04037
- 1. Owner Southern Nuclea, Operating Company Date May 12,2004 Name 40 Awmuerss Center Pat*way, Birmingham, AL Sheet I
of I Address
- 2. Plant VogUe Electric Generating Plant Unit 2
Plant Waynesboro GA 30830 MWO 20401453 Address Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by Nuclear Opeations: Maintenance Plant Voqtke Name Address
- 4. Identification Of System 13021 Auxiliary Feedwater System
- 6. (a)ApplicableConstructionCode ASME Section III 1977 Edition, Winter'1977 Addenda, N.249.1 CodeCase (blAppicable Edition of Section Xl Utiized For Repairs Or Replacements 19*9
- 6. identification Of Components Repairs Or Replacement Components NAME NAME MANUFACTURER NATIONAL
- REPAIRED, ASME CODE OF OF SERIAL WARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) Pipe Support Pullman Power NZA N/A V2-1302.108-H016 1989 REPLACEMENT YES Products
- 7. DescriptionOtWork SnubberAD4o1. sor/al 1*3was reiaced w)thsnubborAD-4OI.
e1 a #139to Suenort survellance testingr
- 8. Tests Conducted:
Hydrostatic O Pneumatic C Nominal Operating Pressure 0 NIA 1 Other O Pressure NJA PSI Test Temp. MA F CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement con/ormsto the rules of the ASME Code. Section XI. repair or replacement Type Code Symbol Stamp N/A Certiflcate of horization No. NiA Expiration Date NJA Signed Team Leader Dte a Mj\\ or Owner s~signee, Title CERTIFiCATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid comnuission issued by the National Board of Soiler and Pressure Vessel Inspectors and the State or Province of Ceorol and employed by HartfordStam Pollerinspectionandinsurance Co ofConnectIcut oft br Connecicut have Inspected the components described in this Owner's Report during the period I May 3,2004 to ZV810 , and state that to the best of my knowiedge and belief, the Owner has perfoomed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi. By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and cotrective measures described in this Owners Report Furthermore, neither the Inspector nor his e"ployer shall be liable in any nner for any personal Injury or property damage or a loss of any kind arising from or connected with this LCornrnisslons &A,2i07! Ins or's Signature National Board, State, Province and Endorsements Date_
FORM NIS-2 OWNER'S REPORT, W P 6S OR REPLACEMENTS M As Required Di The Provisions Of The ASMECode Section Xl Traveler # 04101
- 1.
Owner Southern Nudear Operating Company Date 0&V4)V4 Name 40 Inveness Center Parkwsy. Bnngham. AL
- 2.
Plant Vogtte EteCdrk Generabing Plant Waynesboro. GA 30830 Address
- 3.
Work Performed by PCIEnergySer.4ces-Westinghouse Name Sheet I Of I Unit 2 20401434 and PO #7056205 MWO it Repair Organization P.O. No, Job No., etc. Plant Volo Address
- 4.
Identification Of System 1201 /Reactor Coolant System S. (a) Applicable Construction Code ASME SEC rl 197t Edition. Summer 1972 Addendas 1484-2 Code Case (b)Applicable Edition of Section Xi Utilized For Repairs Or Replacements 1989 S. tdenUtiication Oi Comnponents Repairs Or Replacemnent Comnponents NAME NAME MANUFACTURER NATIONAL REPAIRED. ASME CODE OF OF SERIAL BOARD OTHER YEAR REPLACED OR STAMPED COMPOtNENT MANUFACTURER NO. NO. IDENTIFICATION BUILT REPLACEMENT IYES OR NO) STEAM WESTWGHOUSE 1983 35 2-1201-86-02 1982 REPLACEMENT YES GENERATOR ELECTRIC CORP. j
- 7.
Descriptlon OtWork Installed welded duMs in tubn sheet on hot le side lube locatons row 12-cohlmn 59 nd mow 11-column 60. Welded VAua Instalatdon was completed In eccordance with the 1995 Edittons o' Section fit and Xt with no Addenda. Evaluation of the suitabiliv of reuatr comleted under CR# 2004001954 end MAC0 04-V2htO21. Final root cause deterrnatnon ot the eddy current indccetions In the assocated tubas will be opmked bv Westinohouse gAction Item # 2004201162).
- 8.
Test Conducted: NiA J Hydrostatic 5 Pneunatico Nominal Operating Pressureo Other 5 Pressure NIA PSI Test Temp. NIA
- F CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this rules of the ASME Code, Section Xi.
REPAIR conforms to the repair or replacement NIA Type Code Symbol Stamp Certificate ot uthorizalioit No. Signed 4 NIA Expiration Date Team Leader Date 4:S; A NMA Owieir or Owner's Desionee. Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commisslonltssued by the national Board of boiler and Pressure vessel inspectors and the State or Province of Georol and employed by Hettrd Steam Boilerinsoecdton and Insurance Co. of Connectcut of Hadlord. Connecticut have inspected the components described In this Owner's Report during the period. 4e'V4 to Z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code. Section XlI By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concemning the examinations and corrective measures described in this owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any ma fer lor any personal injury or property damage or a loss of any kind arising from or connected with this Inst;< A Z Cornmisslons GA 3 Inspor's Signature National Board. State, Province and Endorsements Date_
UNIUI'4ML0 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl Traveler #1 04103 August 30.2006
- 1. Owner Southm Nuclar Oprating Company Date Natne 40 lnvem~ess Center Parkway.
ir nianhatm, AL Address
- 2.
Plant Vogtle Electric Geneting Plant Sheet Unit MWO# I of I 2 Plant Waynesboro, GA 30830 Address
- 3. Work Performed by Nuclear Operations Moaintenance 20401692 Repair Organization P.O. No.. Job No.. etc.
Plant Vootie Name Address 5 'wem 16011-t':I I. pjnt AIr Cxc!ing (FSF)
- 5. ji-.! Spolicaibl.: Construction Cod.- *;. "A SAEtdn il; S97.! Edii:on, Winter 1975 Addetoa, NlU.
Ctde Ca,_- (b)Applicable Edition of Section X; Utilized For Repairs Or
- i.
- ernents 1919
- 6. Identification Of Components Repairs Or Replacement _omponents NAME NAME MANUFACTURER NATIONAL.
- REPAIRED, ASME CODE OF OF SERLAL BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER NO.
NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) piping Pultnan Power NWA N/A
- VA 11UB REPLACEMENT YES
- 7. Description Of Work Fabricate and Instal blind pancake flange to stop leak In cooing colt.
- 8.
Tests Conducted: Hydrostatic O Pneumatic 0 Nominal Operating Pressure 1 NIA E Other El Pressure NIA PSI Test Ternp. NIA F CERTIFICATE OF COMPLIANCE We certify that the statements nmde in the report are correct and this trplacement conforms to the rules or the ASME Code. Section Xi. repair or replacement Type Code Symbol Stamp NIA Certificate of Authorization No, 4#VA Expiration Date NIA Signed /at/______ Team rnider Date __31 orf~wOrwner's besignee. Title CERTIFICATE OF INSERVICE INSPECTION 1 thc uneersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Harford Steam Boler Inspection and Insurance Co of Connecticut I oHanford Connecticut have inspected the components described In this Owner's Report during the period May 6 2004 to and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owners Report In accordance with the requirments of the ASME Code, Section Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Funhermore. neiher the Inspector nor his employer shall be liable In any ma r for any personal Injury or property damage or a loss of any kind arising from or connected with this _ Cornmissions - (!4-pp3 Inspestbrs Signature National Board, State. Province and Endorsements Date
. 2 ORIGINAL FORM NIS-.2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi TravelerS 04164
- 1.
Owner Southem Nuclear Operating Com7anY Date 01/06/05 Name 40 Inverness Center Parkway, Bimxingharm AL Address
- 2.
Plant Vogtie Electric Generating Planl Neme Waynesboro, GA 30830 Address Sheet I of 1 Unit 2 WOt 20403224 Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by
- 4.
Identification of System Maintenance Departmant Name Plant Voptle Type Cede Symbol Stamp Autrization No. Expirtion Datd WA WA N/A Address 1301 /Main Steam System
- 5.
(a) Applicable Construction Code ASME SEC /iI 19 77 Edition, Winter 1977 Addenda, (b)Apptikable Edition of Section Xt Utilized for Repairs or Replacements 1989
- 6.
Identificatlon Ot Compolents Repaired or Replaced end Replacement Components N/A Code Case National
- Repaired, AS-ME Code Name of Name of Manufacturer Board Other Year Replaced.
Stamped! Component Manufacturer Serial No. No. Identification Built or Replacement (Yes or No) VALVE CONTROL 23469-1-4 tWA 2PV-3030 1982 REPLACEMENT YES COMPONENTS
- 7.
Description of Work Valve ptug was replaced The reptaeetent vatvo ptug was oridgnally obtained under purchase order G-06834 and has been praoyusly Installed In the plant. The replacement pltug was subsequently reconditioned by Controf Components, Inc. tnder purchase order 70t29414 (M/R# 97-1045) prtor to this replacement activity, The ptug reconditloning did not require a code repair or replacement (stem replacementandhand polishino olplug pilotseat).
- 8.
Test Conducted: Hydrostatic E Pneumatic[] Nominal Operating PressurerO NWA [ Other Q Pressure NWA PSI
- Test Temp.
N/A OF
- 9.
Remarks See Item 7 Applicable Manufacturer's Date Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl. repair or replacement Type Code Symbol Stamp N/A Certificate of uthoription No. NVA Expiration Date N/A Signed WA7 Team Leader Date a 7 / C w O or Owner'if Designee, Title (_ CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georda and employed by -Hatford Steam Boiler Inspection and Insurance Co. of Connecticut of I Hantfrd, Conneciicut have Inspected the components described In this Owner's Report during the period O-Q3/04 to /^ 7-6.i-4 , and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASME
- Code, Section XI.
By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning ihe examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor hs employer shiall be liable In any mter for any personal Injury or property damage or a loss of any kind arising from or connected with this ,Commissions ,l-"A Inspctor's Signatwue National Board, State, Province and Endorsements Date /- 7-4
w u a U %we I FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASUE Code Section Xl Traveler# 05031
- 1.
Owner Southern Nuclear Operating Comrpany Name 40 Inveress Center Parhway, Birmingham. AL Address
- 2.
Plant Vogue Electric Generating Plant Name Waynesboro, GA 30830 Address Date Sheet Unit 10/07/05 t of t 2 WO# 2050240401 Repair Organization P.O. No., Job No., etc.
- 3.
Work Performed by _
- 4.
Identification of System Maintenance Department Name Plant Voglie Address Type Code Symbol Stamp Authorizatlon No. Expiration Dale NIA NVA NIA 1301 /Maln Steam System S. (a) Applicable Construction Code ASME SEC III 19 77 Edition. Winter 1977. Addends, (b)Applicable Edition of Section XI Utilized for Repairs or iplacements 1989
- 6.
IdentIfication Of Components Repaired or Replaced and Replacement Components NWA Code Case National
- Repaired, ASME Code Name of Name of Manufacturer Board Other Year
- Replaced, Stamped Cornponent Manufacturer Serial No.
No. Identification Built or Replacement (Yes or No) PIPE PULLMAN POWER INA N/A V2-1301-014--H006 7989 REPLACEMENT YES SUPPORT PRODUCTS
- 7.
Descriptlonof Work SnubberPSA-3, serIal#20211 wasroplaced withaPSA-3serial#25366 tosupportsurveiflancelesling.
- 8.
Test Conducted: Hydrostatic ] Pneumatic[] Nominal Operating Pressure[] NtA O3 Other D] Pressure JWA PSI Test Temp. I/A OF
- 9.
Remarks See Item7 Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPUANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASIE Code, Section XI. repair or replacement Type Code Symbol Stamp N/A Certificaft o I\\A Expiration Date N/A 5igned 7/** / Team Leader Date /d /7/ G Ovq6 r or Owner sZlaignee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the national Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georoia and employed by Hantord Steam Boiler Inspection and Insura1 Co of Connecticut Of Hafrdi ugnachcut have Inspected the components described in this Owner's Report during the period 0Si I to OA(Q3.S; . and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective meures dcribed In this Owners Report In accordance with the requirements of the ASME Code. Section Xl. By signing this certHficate, neither the Inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this I n*NIOF t Nota toCommissions Stt. i nd t National Board, State. Province and Endorsements Date 10Ag1Ahs
unlumaiitu FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xi 4 Traveler t 05036 October S. 2005 Owner Southern Nuclear OnereUno ComPanv Name 40 Inverness Center Parkway, Birmingham, AL Address
- 2. Plant VoatM Electric Geneatng Plant Plant Waynesboro, GA 30830 Date Sheet Unit MWO #
I of 4 2 2050241101 Address
- 3. Work Performed by Nucear Operations Maintenance Repair Organization P.O. No.. Job No., etc.
Plant Voqtte Name Address
- 4. Identification Of System 12041 Safety Injection
- 5.
(a) Applicable Construction Code ASME Section 111 1977 Edition, Winter 1977
- Addenda, N/A Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements I9M
- 6.
Identification Of Components Repairs Or Replacment Components NAME "AME MANUFACTURE NATIONAL
- REPAtRED, ASUE CODE OF OF A
BOARD OTHER YEAR REPLACED OR STAMPED COMPONENT MANUFACTURER SERIAL NO. IDENTIFICATION BUILT REPLACEMENT (YES OR NO) ~N O._ PIPE PULLMAN NVA N/A V2-1204-127.H007 19J9 REPLACEMENT Yes SUPPORT POWER PRODUCTS
- 7. Description Of Work Snubber PSA-35. serial #12326 woo replaced with PSA-35. serial #402to suport surveillance tesna.
- 1. Tests Conducted:
Hydrostatic 0 Pneumatic OJ Nominal Operating Pressure a NIA 0 Other 0 Pressure N/A PSI Test Temp. WA OF CERTIFICATE OF COMPUANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xl. repair or replacement Type Code Symbol Stamp WA Certificate Authorization No. W A Expiration Date NWA S igned./ < 4 9 /* * *
- Z K
- Z d
- IjjY
'Date
- wrwrorOwpo's Designeetle
",A,(# L.' A CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Gr and employed by Htfod Stam Boiler Insoection and Insurance Co of Connerticut of Na, Conneticut have Insected the components described in this Owner's Report during the period May 4,2005 to and d sta that to the best o my knowedge and belf, the Owner has performed examinations and tasts and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xl. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner lor any personal injury or property damage or a loss of any kind arising from or connected with this Commissions 6OA* 7S6 IndpEW'is Signsture National Board. State, Province and Endorsements 'ate O QS-
a I$ Mm 5 FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl (xi Tr avelerS 05041
- Owner Soutthem Nuclear Operating Company Name 40 Inverness Center Parkway, Birmingham, AL Address
- 2.
Plant Voglie Electric Generating Plant Plant Waynesboro, GA 3030 Address
- 3. Work Performed by Nucear Operations Maintenance Name Date October 12. 2005 Sheet I
of 4 Unit 2 MWO # 2050242001 Repair Organization P.O. No., Job No., etc. Plant Vogtle Address
- 4. identification Of Systemt 12041 Safety Injection
- 5. (a) Applicable Construction Code ASME Section Il 1977 Edition, Winter 7977 Addendas N/A Code Case (b)Applicable Edition of Section Xl Utilized For Repairs Or Replacements 19ft
- 6. Identification Of Components Repairs Or Replacement Components
- 7. Description Of Work Snubber AO41I. aeria
- 79 was reoleced withLisea srial #3050023029 to suDnort surveillanceytesting.
- t. Tests Conducted:
Hydrostatic a Pneumatic 0 NomInal Operating Pressure 0 N/A 0 Other 0 Pressure N/A PSI Test Temp. NIA F CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi. repair or replacement Type Code Symbol Stamp N/A Certificate ofphfthorizationNo. WA Expiration Date WA gned _= ltOwner 20wwne' De Iqevle CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Georgia and employed by Harttrd Steam Boiler Inspection and Insurance Co of Connecticut of d Conage!tkut have Inspected the components described in this Owner's Report during the period May 5, 2005 to //t/3I ( ;O? and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described In this Owners Report In accordance with the requirements of the ASME Code, Section Xi. By signing this certificate, neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examintionsand corrective measures described in this Owners Report. Furthermore. neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Commissions Got 756 'e Si~gnature National Board, State, Province and Endorsements 'latae Oe_ I Z., 2C__=}}