ML060110473
Jump to navigation
Jump to search
| ML060110473 | |
| Person / Time | |
|---|---|
| Site: | Browns Ferry |
| Issue date: | 01/09/2006 |
| From: | NRC/NRR/ADRO/DORL/LPLD |
| To: | |
| Brown Eva, NRR/DLPM, 415-2315 | |
| Shared Package | |
| ML060110296 | List: |
| References | |
| TAC MC8037, TAC MC8038 | |
| Download: ML060110473 (1) | |
Text
Control Rod Scram Times 3.1.4 SURVEILLANCE REQUIREMENTS NOTE---------------------
During single control rod scram time Surveillances, the control rod drive (CRD) pumps shall be isolated from the associated scram accumulator.
SURVEILLANCE FREQUENCY SR 3.1.4.1 Verify each control rod scram time is within Prior to the limits of Table 3.1.4-1 with reactor steam exceeding dome pressure 2 800 psig.
40% RTP after each reactor shutdown 2120 days SR 3.1.4.2 Verify, for a representative sample, each 200 days tested control rod scram time is within the cumulative limits of Table 3.1.4-1 with reactor steam operation in dome pressure 2 800 psig.
MODE 1 (continued)
I BFN-UNIT 3 3.1-13 Amendment No. 212, 226, 253