Slides - Electrical Grid Problems Identified at Palo Verde
ML053130108
Person / Time
Site: Palo Verde  
Issue date: 11/02/2005
From: Thomas Koshy
NRC/NRR/ADES/DE
To:
References
FOIA/PA-2004-0307
Download: ML053130108 (4)


Text

Electrical Grid Problems Identified at Palo Verde Thomas Koshy, EEIB (n

V..

, X o

M

. M.

CD 01 Division of Engineering Office of Nuclear Reactor Regulation

Purpose X Proposed by Richard Barrett, Director, DE X Information to understand grid vulnerabilities that could lead to loss of offsite power for long duration Success

  • ET & LT understand the grid centered problems Not For Public Release 2

Agenda

  • Description of the event
  • Root cause
  • Design Deficiency
  • Impact on 500KV Grid
  • Corrective Actions Not For Public Release 3

Event Description

  • On June 14, 2004 at 7:44 a.m. all three Palo Verde Units tripped. One EDG for unit #2 failed to run
  • Unit #2 went into an Alert because of one EDG and all offsite power unavailability

. All three units tripped from loss of load

  • Electrical fault remained for 39sec.,
  • Offsite power recovered by 8:18 a.m.
  • 9:51 a.m. safety buses energized from offsite power for unit#2 Not For Public Release 4