REACTIVITY CONTROL SYSTEMS 3/4.1.3 CONTROL RODS CONTROL ROD OPERABILITY LIMITING CONDITION FOR OPERATION 3.1.3.1 All control rods and scram discharge volume vent and drain valves shall be OPERABLE.

APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3***

ACTION:

a. With one withdrawn control rod inoperable due to being immovable, as a result of excessive friction or mechanical interference, or known to be untrippable:
1. Within 1 hour:

a) Verify that the inoperable withdrawn control rod is separated from all other inoperable withdrawn control rods by at least two control cells in all directions.

b) Disarm the associated directional control valves** either:

1) Electrically, or
2) Hydraulically by closing the drive water and exhaust water isolation valves.

Otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

2. Restore the inoperable withdrawn control rod to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
b. With one or more control rods trippable but inoperable for causes other than addressed in ACTION a, above:
1. If the inoperable control rod(s) is withdrawn, within 1 hour:

a) Verify that the inoperable withdrawn control rod(s) is separated from all other inoperable withdrawn control rods by at least two control cells in all directions, and b) Demonstrate the insertion capability of the inoperable with-drawn control rod(s) by inserting the control rod(s) at least one notch by drive water pressure within the normal operating range*.

May be rearmed intermittently, under administrative control, to permit testing associated with restoring the control rod to OPERABLE status.

OPERATIONAL CONDITION 3 is only applicable to the scram discharge volume vent and drain valves.

LIMERICK - UNIT I 3/4 1-3 Amendment No. 1-6B, 178

REACTIVITY CONTROL SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 4.1.3.1.2 When above the preset power level of the RWM, all withdrawn control rods not required to have their directional control valves disarmed electrically or hydraulically shall be demonstrated OPERABLE by moving each control rod at least one notch:

a. At least once per 7 days, and
b. Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from discovery that a control rod is immovable as a result of excessive friction or mechanical interference.

4.1.3.1.3 All control rods shall be demonstrated OPERABLE by performance of Surveillance Requirements 4.1.3.2, 4.1.3.4, 4.1.3.5, 4.1.3.6, and 4.1.3.7.

4.1.3.1.4 The scram-discharge volume shall be determined OPERABLE by demonstrating:

a.

The scram discharge volume drain and vent valves OPERABLE at least once per 24 months, by verifying that the drain and vent valves;

1.

Close within 30 seconds after receipt of a signal for control rods to scram, and

2.

Open when the scram signal is reset.

b.

Proper level sensor response by performance of a CHANNEL FUNCTIONAL TEST of the scram discharge volume scram and control rod block level instrumentation at least once per 92 days.

LIMERICK - UNIT 1 3/4 1-5 Amendment No. 74, 4, Ags Igl178

REACTIVITY CONTROL SYSTEMS 3/4.1.3 CONTROL RODS CONTROL ROD OPERABILITY LIMITING CONDITION FOR OPERATION 3.1.3.1 All control rods and scram discharge volume vent and drain valves shall be OPERABLE.

APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3***

ACTION:

a.

With one withdrawn control rod inoperable due to being immovable, as a result of excessive friction or mechanical interference, or known to be untrippable:

1.

Within 1 hour:

a)

Verify that the inoperable withdrawn control rod is separated from all other inoperable withdrawn control rods by at least two control cells in all directions.

b)

Disarm the associated directional control valves** either:

1)

Electrically, or

2)

Hydraulically by closing the drive water and exhaust water isolation valves.

Otherwise, be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

2.

Restore the inoperable withdrawn control rod to OPERABLE status within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

b.

With one or more control rods trippable but inoperable for causes other than addressed in ACTION a, above:

1.

If the inoperable control rod(s) is withdrawn, within 1 hour:

a)

Verify that the inoperable withdrawn control rod(s) is separated from all other inoperable withdrawn control rods by at least two control cells in all directions, and b)

Demonstrate the insertion capability of the inoperable with-drawn control rod(s) by inserting the control rod(s) at least one notch by drive water pressure within the normal operating range*.

    • May be rearmed intermittently, under administrative control, to permit testing associated with restoring the control rod to OPERABLE status.

LIMERICK - UNIT 2 3/4 1-3 Amendment No. 4-31,140

REACTIVITY CONTROL SYSTEMS 5URVEILLACLELREQUIREMENTS (Continued) 4.1.3.1.2 When above the preset power level of the control rods not required to have their directional electrically or hydraulically shall be demonstrated control rod at least one notch:

RWM, all withdrawn control valves disarmed OPERABLE by moving each

a.

At least once per 7 days, and

b.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from discovery that a control rod is immovable as a result of excessive friction or mechanical interference.

4.1.3.1.3 All control rods shall be demonstrated OPERABLE by performance of Surveillance Requirements 4.1.3.2, 4.1.3.4, 4.1.3.5, 4.1.3.6, and 4.1.3.7.

4.1.3.1.4 The scram discharge volume shall be determined OPERABLE by demonstrating:

I

a.

The scram discharge volume drain and vent valves OPERABLE at per 24 months, by verifying that the drain and vent valves:

least once

1.

Close within 30 seconds after receipt of.a signal for control rods to scram, and

2.

Open when the scram signal is reset.

b.

Proper level sensor response by performance of a CHANNEL FUNCTIONAL TEST of the scram discharge volume scram and control rod block level instrumentation at least once per 92 days.

LIMERICK - UNIT 2 3/4 1-5 Amendment No. 33, 34, £g, 4-4, 140