INDEX LIMITING CONDMIONS FOR OPERATION AND SURVEILLANCE REQUIREMENTS SECTION PAGE 3/4.6 CONTAINMENT SYSTEMS 3/4.6.1 PRIMARY CONTAINMENT Containment Integrity .......................... 3/46-1 Containment Leakage .......................... 314 6-2 Containment Air Locks ............................. 3/4 6-6 Internal Pressure . ................................ 3/4 6-7 Air Temperature . ................................ 3/46-8 Deleted............................ .......... 3/46-9 Containment Ventilation System .................... 3/4 6-10 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS Containment Spray System .................... 3/46-11 Containment Cooling System .................... 3/4 6-13 3/4.6.3 CONTAINMENT ISOLATION VALVES ................... 3/4 6-14 314.6A Deleted 3/4.6.5 SHIELD BUILDING Emergency Ventilation System ........................ 3/4 6-28 Shield Building Integrity ...... ...................... 3/4 6-31 Deleted ................... 3/46-32 DAVIS -BES SE, UNIT I VI Amendment No. 38,66, 135, 205, 265
INDEX BASES SECTION PAGE 3/4.6 CONTAINMENT SYSTEMS 3/4.6.1 PRIMARY CONTAINMENT ......................... B 3/4 6-1 3/4.6.2 DEPRESSURIZATION AND COOLING SYSTEMS .... ......... B 314 6-2 3/4.6.3 CONTAINMENT ISOLATION VALVES ................... B 3/4 6-3 3/4.6A Deleted 3/4.6.5 SHIELD BUILDING .............................. B 314 6-4 DAVIS-BESSE, UNIT I Xi Amendment No. 265
DELETED I DAVIS-BESSE, UNIT I 3/4 6-23 Amendment No. 167, 168, 265,
DELETED I DAVIS-BESSE, UNIT I 3/4 6-25 Amendment No. 183, 265,
DELETED I DAVIS-BESSE, UNrr I 3/4 6-26 Amendment No. 155,209,244, 265,
DELETED I DAVIS-BESSE, UNllr I 314 6-27 Amendment No. 155, 209,244, 265,
ADMINISTRATIVE CONTROLS 6.8.4 (Continued)
- e. Radiological Envirorn ehntal Monitoring Program (Continuiedj
- 3) Participation in an Interlaboratory Comparison Program to ensure that independent checks on the precision and accuracy of the measurements of radioactive materials in environmental sample matrices are performed as part of the quality assurance program for environmental monitoring.
- f. Ventilation Filter Testing Program (VFTP):
A program shall be established to implement the following required testing of safety related filter ventilation systems in accordance with Regulatory Guide 1.52, Revision 2*,
ANSI/ASME N510-1980, and ASTM D 3803-1989.
- 1. Demonstrate for each of the safety related systems that an in-place test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass
< 1%when tested in accordance with Regulatory Guide 1.52, Revision 2 and ANSIIASME N5IO-1980 at the system flowrate specified below, +1- 10%.
Safety Related Ventilation System Flowrate Shield Building Emergency Ventilation System 8000 cfm Control Room Emergency Ventilation System 3300 cfm
- 2. Demonstrate for each of the safety related systems that an in-place test of the charcoal adsorber shows a penetration and system bypass < 1% when tested in accordance with Regulatory Guide 1.52, Revision 2 and ANSIIASMEN510-1980 at the system flowrate specified below, +/-10%.
Safety Related Ventilation System Flowrate Shield Building Emergency Ventilation System 8000 cfm Control Room Emergency Ventilation System 3300 cfm
- 3. Demonstrate for each of the safety related systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, shows the methyl iodide penetration less than the value specified
- The periodic testing for the Shield Building Emergency Ventilation System and the Control Room Emergency Ventilation System are performed once each REFUELING INTERVAL. The need for testing following painting, a fire, or a chemical release in any ventilation zone communicating with the Shield Building Emergency Ventilation System or the Control Room Emergency Ventilation System is as specified by the VFTP. The method of testing is based on Regulatory Guide 1.52, Revision 2, except for charcoal laboratory testing which will be performed in accordance with ASTM D 3803-1989.
DAVIS-BESSE, UNIT I 6-14c Amendment No. 170, 244, 265,
ADMINISTRATIVE CONTROLS.
6.8.4 (Continued)
- f. Ventilation Filter Testing Program (VFTP) (Continued) below when tested in accordance with ASTM D 3803-1989 at a temperature of 300 C and the relative humidity (RH) specified below.
Safety Related Ventilation System Penetration RH Shield Building Emergency Ventilation System < 2.5% 95%
Control Room Emergency Ventilation System S 2.5% 70%
- 4. Demonstrate for each of the safety related systems that the pressure drop across the combined HEPA filters, the prefilters, and the charcoal adsorbers is less than the value specified below when tested in accordance with Regulatory Guide 1.52, Revision 2 and ANSIIASME N510-1980 at the system flowrate specified below,
+1- 10%.
Safety Related Ventilation System Delta P Flowrate Shield Building Emergency Ventilation System 6 inches Water Gauge 8000 cfM Control Room Emergency Ventilation System 4.4 inches Water Gauge 3300 cfm The provisions of SR 4.0.2 and SR 4.0.3 are applicable to the VFTP test frequencies.
I DAVIS-BESSE, UNIT I 6-14d Amendment No. 244, 265,