t -
N RQ.
Point Beach Nuclear Plant PBNP SHUTDOWN SAFETY ASSESSMENT AND FIRE CONDITION CHECKLIST Date:
April 18,2004 Time:
14()0 Preparer:
Jun Leiker U
I R
28 '
NOTE:
Refer to base procedure NP 10.3.6 for safety assessment checklist KSF definitions.
NOTE:
IWheneverfitel has been renzovedfroin the reactor vessel and refueling cavity, all key safety functions are GREEN except spent fitel pool cooling.
KEY SAFETY FUNCTION CRITERIA: No/False = 0, Yes/True = I through 4 REACTIVITY
- 1.
RCS Boron concentration = 2S92 pprn a.)
For RSD, RCS boron >Refueling boron concentration specified in unit-specific COLR (TRM 2.1) >2200 ppm b.)
For CSD and prior to RSD no fuel motion, RCS boron > boron concentration required by OP 3C (0-1)
]
- 2.
Number of boration paths (0-2) 2
- 3.
No fuel motion (0-1) 1
- 4.
SR instrumentation operable (0-1)
I Subtotal 0-1 2
6-Condition RED ORANGE
__E Subtotal =
CORE COOLING Subtotal Condition
- 1.
Number of SG available for DHR (0-2) 0 0-1 RED
- 2.
Refueling cavity filled (0-1) 0 2
- 3.
Number of trains RHR available (0-2) 2 (i)
- 4.
RCS level above REDUCED INVENTORY (0-1) 1 4-5 RCS Temperature derived from TICs TE04 and TE06.
RCS TEMI1' = 97"F; 15 dayssiutdlown; RCS 68%
Subtotal =
3 RCS Time to Boil 43 min (Applicable at Cold or Refueling Shutdown)
POWER AVAILABILITY Subtotal Condition I.
Independent off-site power sources I
RED available to A-05 and A-06 (totally 2
ORANGE independent at the 4160 V, 13.8 kV.
3 and 345 kV levels)
(0-2) 2 5GR
- 2.
G-01 or G-021A-05/B-03 available (0-1) 1 G-03 or G-041A-06/B-04 available (0-1) 1
- 3.
G-05 available, Reactor Cavity filled to Ž 23 ft above the top of the reactor vessel flange, upper internals removed and RCS time to boil 2 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
(0-1) 0 Subtotal =
4 INVENTORY Subtotal Condition
- 1.
Pressurizer level 220 percent wlhead on 0-1 RED (0-1) 0 2
- 2.
Refueling Cavity filled (see definition)
(0-3) 0
(
L
- 3.
RCS level above REDUCED INVENTORY (0-1) 1 4
- 4.
Makeup from VCT/BLENDER and/or RWST available (0-2) 2 Subtotal =
3
.6...,,lt iv tInllS record was deleted in accordance witht Freedom of Information PBF156 Act exPagteoof Revision 2X1J Page$I
-ng I of 9
References:
NP 10.3.6 NP 10.2.1 Al
Point Beach Nuclear Plant PBNP SHUTDOWN SAFETY ASSESSMENT AND FIRE CONDITION CHECKLIST CONTAINMENT
- 1.
Containment integrity (TS 15.1.D) (Containment Operable) (ITS TS 3.6.1) set
- 2.
Containment Closure CL-1 E maintained and closure < time to boil
- 3.
No fuel motion
- 4.
DHR Capability:
cavity flooded and internals out OR at least one SG available OR one fan cooler with Equip hatch installed and personnel hatches capable of being shut (O or 4) 0 (O or 2) 2 (0-I)
I Subtotal 0
2-3
@3-6 Condition RED ORANGE (0-1) 1 Subtotal =
4 SPENT FUEL POOL COOLING (ONLY APPLICABLE when starting AND during FULL CORE OFFLOADS)
NOTE:
Take credit for only one P-12 independent offsite power source during periods of single X-03 or X-04 availability (*).
Subtotal Condition I
'A" SFP cooling pump available 0-1 RED with power available from:
2 ORANGE G-02 or G-01 via 2B-32 (0-1) n/a 3
YELLOW
- (*) an independent off-site power 4-5 GREEN source different than that for Train B below
- 2.
WB" SFP cooling pump available with power available from:
G-03 or G-04 via IB-42
-() an independent off-site power source different than that for Train A above
- 3.
Temporary power available to one SFP cooling pump, G-05 available, and SFP time to boil > 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
(0-1) n/a (0-1) n/a (0-1) n/a (0-1) n/a SFP Temperatures:
NW n/a OF SE n/a OF SFP Average Temp n/a SFP Time to Boil n/a Subtotal =
n/a GIVE A BRIEF EXPLANATION OF ANY CHANGE IN SAFETY ASSESSMENT THAT TOOK PLACE:
(Jerry Strharskly) Changed time to boil based on conservative times provided by SEP-1 Attachment C for 314 pipe vessel level rather than interpolating data.
PBF-1562 Revision 2 10130/02
References:
NP 10.3.6 NP 10.2.1 Page 2 of 9
Point Bcach Nuclear Plant PBNP SHUTDOWN SAFETY ASSESSMENT AND FIRE CONDITION CHECKLIST OUTAGE SAFETY ASSESSMENT UNIT:
1 DATE:
April 18, 2004 TIME:
140(0 KEY SAFETY FUNCTIONS:
REACTIVITY:
CORE COOLING:
POWYER AVAILABLE:
INVENTORY:
CONTAINMENT:
SFP COOLING:
GREEN YELLOW GREEN YELLOW GREEN N/A PROTECTED EOUIPMENT:
Fire Protection Condition III: Crediting existing fire rounds as fire prevention contingency RCS Time to Boil is 43 minutes RCS is at 68 % Reactor Vessel level Hot leg vent path is the removed Pressurizer manway PBF-1562 Revision2 ioW3/0o2
References: