MONTHYEARML0514601422005-05-26026 May 2005 Notice of Meeting with Southern California Edison (SCE) to to Discuss the Licensees Proposed Exigent Technical Specification Amendment Request Regarding the 218kV Grid Voltage Setpoint at San Onofre Nuclear Generating Station Project stage: Meeting ML0514505852005-05-26026 May 2005 Agenda for Meeting with Southern California Edison (SCE) to to Discuss the Licensees Proposed Exigent Technical Specification Amendment Request Regarding the 218kV Grid Voltage Setpoint at San Onofre Nuclear Generating Station Project stage: Meeting ML0515805902005-06-0707 June 2005 6/7/05 SONGS - Exigent - Notice of Consideration of Issuance of Amd to Facility Operating License on Degraded Voltage Setpoints. Tacs. MC7189 & MC7190 Project stage: Other ML0516102282005-06-0707 June 2005 Additional Information Regarding Proposed Change Number (PCN) 561 Degraded Voltage Setpoints Project stage: Request ML0516404302005-06-10010 June 2005 Handouts for Meeting with Representatives of Southern California Edison Regarding San Onofre Nuclear Generating Station Project stage: Meeting ML0517902692005-06-24024 June 2005 Additional Information Regarding Proposed Change Number (PCN) 561 Degraded Voltage Set Points Project stage: Request ML0517902402005-06-24024 June 2005 Facility and Commitment Change Reports for May 1, 2003 Through June 15, 2005 Project stage: Request ML0517102262005-06-29029 June 2005 Notice of Meeting with Southern California Edison (SCE) to Discuss the Licensees Proposed Exigent Technical Specification Amendment Request Regarding the 218kV Grid Voltage Setpoint at San Onofre Nuclear Generating Station Project stage: Meeting ML0518702382005-07-0101 July 2005 TS Page (187) Degraded Voltage Setpoints (Tacs. MC7190/MC7191) Project stage: Other ML0518702392005-07-0101 July 2005 1 TS Page (196) Degraded Voltage Setpoints (Tacs. MC7190/MC7191) Project stage: Other ML0518604072005-07-0101 July 2005 License Amendments 196/187, Revise Degraded Voltage Setpoints (TACs MC7190/MC7191) Project stage: Other 2005-06-24
[Table View] |
Text
DG-Undervoltage Start 3.3.7 SURVEILLANCE REQUIREMENTS SURVEILLANCE FREQUENCY SR 3.3.7.1 Perform CHANNEL CHECK.
12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> SR 3.3.7.2 Perform CHANNEL FUNCTIONAL TEST.
24 months SR 3.3.7.3 Perform CHANNEL CALIBRATION wzith setpoint 24 months Allowable Values as follows:
- a. Degraded Voltage Function:
- i. Dropout 2 4123.0 V*
ii. Pickup s 4144.6 V*
SDVS (Sustained Degraded Grid Voltage Signal):
Time delay:
- i. 127D & 2.17 seconds.
ii.
162D z 78 seconds and < 128 seconds.
DGVSS (Degraded Grid Voltage with SIAS.
Signal):
Time delay:
- i. 127D z 1.83 seconds-and < 2.17 seconds.
ii. 162S k 4.16 seconds and s 4.44 seconds.
iii. 162T. 0.88 seconds and £ 1.62 seconds.
- b.
Loss of Voltage Function 2 3554 V and
< 3796 V Time delay: 2 0.75 seconds and s 1.0 seconds it 0 V.
I I
- Dropout and pickup values will be set to >4151.D V and respectively, until actions identified in SCE submittal are completed.
£4172.8 V.
dated May 27, 2005 I
SAN ONOFRE--UNIT 3 3.3 -34 Amendment No.
187