Calculation No. E4C-090, Revision 3, Auxiliary System Voltage Regulation
ML051530068
Person / Time
Site: San Onofre  
Issue date: 05/26/2005
From: James Kim, Lennartz W
Southern California Edison Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
E4C-090, Rev 3
Download: ML051530068 (65)


Text

Attachment N (Calculation E4C-090, ICCN C-130)

Proposed Interim Change (219.5 kV)

SONGS Units 2 and 3

Soulhem California Edison Company CALC NO.

PAGE TOTAL NO. OF INTERIM CALCULATION E4C-090 ICON NOJ PAGES CHANGE NOTICE (ICCN)I PRELIM. CCN NO. C - 130 1

64 CALCULATION CHANGE NOTICE (CCN)

BASE CALC. REV.

UNIT lCCN N

O CALO. REV.

COVER PAGE 3

3 COCN NO.

CCN-

-I

SUMMARY

CHANGE CALCULATION

SUBJECT:

[

NO E YES AUXILIARY SYSTEMAl VOLTAGE REGULATION CALCULATION CROSS-INDEX ENGINEERING SYSTEM NUMBERIPRIMARY STATION SYSTEM I Q-CLASS 0 New!Updated Index Included DESIGNATOR 1804 / PEA l

II D Existfng Index is Complete CONTROLLED PROGRAM OR PROGRAMIDATABASENAME(S)

VERSiONIRELEASENO.(S)

Site Programs I Proceduro Impact?

DATABASE ACCORDING TO El ALSO, LISTED BELOW

-0 NO E YES, AR No.

S23-lIV-5.1

_1OcFR5O.59/72.48aRevle

---- -0 PROGRAM-8-DATABASE-5.0..N AR No. N/A -See PCN 561 ETAP_____
1. BRIEF DESCRIPTION OF ICCN/CCN:

Purpose This summary change ICCN supports ECP 050500255 - 34 and provides the basis for the revised setting for the Degraded Grid Voltage (DGV) Relay Setpoint for Class 1E bus 3A04. NCDBMEL identification numbers for these relays are 3A0420-127D-1, 3A0420-127D-2, 3A0420-127D-3, and 3A0420-127D-4. This ICCN also supports PCN 561.

Specifically, this ICCN defines the design voltage limit at the 4.16kV bus 3A04 based on a postulated switchyard voltage of 219.5kV. This value is then utilized in the DGV relay setpoint calculation E4C-130: The analysis focuses on the Class 1E system only.

Acceptance Criteria For this ICCN, the Class 1E 4.16kV bus voltage is determined based on a postulated switchyard voltage of 219.5kV (see methodology on page 3). This value will be used to determine the maximum DGV relay reset (pickup) value indicated in calculation E4C-130 Rev. 1, ICCN C - 3. This value represents an output parameter of this calculation, and is not associated with a specific acceptance criterion.

For the study cases performed at the m-inimum DGV relay dropout setpoint, Class 1E loads are expected to have a minimum terminal voltage of 90% rated, consistent with the base calculation Section 1.3.

Results and Conclusions The resultant 3A04 bus voltage derived in this 1CCN is 4190V based on a postulated switchyard voltage of 219.5kV. In addition, all Class 1E loads experience a minimum terminal voltage greater than 90% rated, with 3A04 bus voltage at 4139V.

(continued on page 3)

INITIATING DOCUMENT ECP, OTHER ECP 050500255-34 Rev.

0

2. OTHER AFFECTED DOCUMENTS (CHECK AS APPLICABLE FOR CCN ONLY);

EI YES El NO OTHER EJECTED DOCUMENTS EXIST AND ARE IDENTIFIED ON ATTACHED FORM 26-503.

3. APPROVED BY:

D IPLINEIES ElectricalIDED d.P.RLennartz or

.A ORIGINATOR (Print name/sign/date)

/,nl FLS (Signature/da Approval requires POS TBEN64 Oualification VerIfied:

Approval requires P TN64 Qualification Verdfied:

.T./mg ts__5In"Ital J1. 1. Kim ni(.-. S/4o IRE (Print name/sign/date)

Approval requires POS T3EN64 Qualification Verified:

IC InItial

4. CONVERSION TO CCN DATE SCE CDM-SONGS SCE26-122-1 REV.8 4/05 [

REFERENCE:

SO123-XXIV.7.15]

e4c-O9O-130.-coverdoc I

ICCNCNO N

C-130IPAGE 2

OF 64 PRELIM. CCN NO.

CALCULATION CROSS-INDEX Calculation No.

E4C-090 Sheet of CCN CONVERSION:

CCN NO.

CCN-INPUTS OUTPUTS Does the oyuput Identify output Interface interface '

calc/document Calc. rev.

These Interfacing calculations and/or documents Results and conclusion of the subject calculation calc/docunient number and provide Input to the subject calculation, and If revised are used In these Interfacing calculations and/or require Change?

CCN, ECP, TCN/Rav., or responsible FLS may require revision of the subjcct calculation, documents.

tracking number.

initials and date Rv Calc I Document No.

Cac / Document No.

Rev. No.

YES / NO Rev. 3 ECP 050500255 - 34 0

E4C -130 1

YES ICCN C - 3 ICCN 90042, ECN A36442 10 C-130 E4C-130, ICCN C - 3 1

116>r II I

If I-SCE26-424 REV.5 4At5 (

REFERENCE:

S01234)0V-7.15]

e4 c-90Q_c-1 30_ccl.doc

E&TS DEPARTMENT ICON NO]-

C-130 I CALCULATION SHEET PREUM.CCN NO.

Page 3

of 64 CON CONVERSION:

Project or ECP ECP 050500255-34 Calc No.

E4C - 090 CCN NO. CCN Subject AUXILIARY SYSTEM VOLTAGE RtEGULATION Sheet of REV ORIGINATOR DATE IRE DATE REV ORIGINATOR DATE IRE DATE

=

=-

.=m

--- Assumptions"*-- --------.-

.. ~...--..

There are no specific assumptions associated with this ICCN.

Design Input The minimum DGV relay dropout setpoint is derived from calculation E4C-130 Rev. 1, ICCN C-3, Table 2.1.5.

This value is 4139.7V.

Relative to the base calculation study cases, the analysis included in this ICCN conservatively postulates that the Unit 3 Train A Emergency Diesel Generator ancillary loads are operating (as described in AR 050201584 - 4) while connected to the offsite source. Refer to base calculation case 3A12a for postulated loading, Otherwise,_.

the study case in this ICCN is similar to case 3A14 of the base calculation. This is the limiting study case for the accident scenario (see also methodology below) as described in the base calculation.

Methodoloev This ICCN includes accident scenario analyses only, similar to base calculation study case 3A14. However, only the affected safety train is analyzed (Unit 3, Train A) to support associated ECP. The included study case is designated as "3Al4aa".

This ICCN provides a resultant 4.16kV bus voltage level based on a postulated switchyard voltage of 219.5kV.

The 4.16kV bus voltage will then be utilized for DGV relay maximum reset (pickup) design limit included in calculation E4C-130 Rev. 1, ICCN C-3. This setpoint will then ensure that the 4.16kV bus remains connected to the normal preferred (offsite) power source during the post-accident, post-load-sequencing period.

The minimum DGV relay dropout setpoint (4139.7V) derived in E4C-130 Rev. 1, ICCN C-3, Table 2.1.5 is utilized in this analysis to confirm Class 1E equipment operability. The analysis in this ICCN utilizes a bounding (lower) value of 4139V.

Page 4 of this ICCN includes the one-line diagram of the analyzed system.

The case where the Class BE 4.i6kV buses are cross-tied to Unit 2 (alternate preferred source) is not analyzed in this ICCN because the cross-tie condition places the operating unit in an action statement due to the connection to the alternate preferred source. The alternate preferred source at 219.5kV may not be capable of providing adequate voltage at the 4.16kV bus immediately after the trip event.

Calculation ETAP load flow is utilized to ascertain the 4.16kV voltage level with a switchyard voltage of 219.5kV. The report is included in this ICCN on pages 5 through 34. The minimum DGV relay setpoint analysis is included on pages 35 through 64.

SCE 26-426 REV.3 4105

[

REFERENCE:

S0123-XXIV-7.15]

e4C-09Q_C 130.doc

I r-r CD ci,0 m

rTII N

a)

Co BUS ALIGNMENT AND LOADING DIAGRAM CASE 3A14aa SWITCHYARD co-a a0 10 m

0 I

I I

I I

3X81i Vi X XR

~~1 ry 41 I

51 3A0 3P0154 3po19 3POt7 3Pt1 sm301 3P504 1~~~

_ _3f_

)

~

B0 3B' EX1 43B )

3XR2 x T FTv 3A03 F--

3A08 3A07 3A09

.MI._

I I IT'I__'~

1303 3812 3513 3Pa75 3SV 3BC C443 3EF 3SLX2 3A001 358 112 P13 I3BB 3L1tR P117 P115 post P051 3P1X; 'T~

35,01 3802 510 re0 r1 r34 380 311' 3B14 W

3518 13508 3EBOB 3Et25 3333 3E123 3a II 3809 3B15 3(D93 Eli 3A353 A312 3E404A MM

£54040E 3BN

-Ar

- )Ii I'

3MA 3£t26 EP 3E397 3S124 P159 3P128 3S 4 2843 3Et22 B:

E245 or 39=

3m1a611 3E125tX1 3BRA 33D 3A071 3E401 3EE 3BY E418 3A074 2132o1X 1313

,3A072 438N IE419

'I391 9A073 3AW02 3A003 3c511 3DL 3<

Co03 3P138 3W 3MM 3BM 3P007(A)3P741 3B1 3P123 3A501 3W221 CX(

2P751 3,754 3868 SWB 09 tn" Ct N

Ul tAI w

46 0

O O

00 00 zz 00 zcn 0

z.

C')

m C !I r 0 m

z z

-I r)

,z z

3,

~30

..O a

t 0)

(0

.1v lr l IR MODES1-4 C-OAD I

10'I4 MODES 1-4 I

I P-I

\\~

THIS ICCN FIGURE 3Ai4 iI i

Ii i

i IIII co 0

a 0

REV INDICATOR a -

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2&3 5.0.0N Contract:

Engineer W.P. Lennart Study Case: 3A14aa Filename E4C090 Page 5. of ___

CCN No.

Page:

I Date:

05-25-2005 SN:

SCALEDISON Revision:

Dase Voelig,:

099-3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA Electrical Transient Analyzer Proeram Load Flow Analysis Loading Category (t):

Design-BHP Generation Cclegory (1):

Design Load Diversity Factor None Sfine V-Control Load 5

0 75 Number of Buses:

Number of Branches:

Matod ofSolution:

Maximum No. of Iteration:

Precision of Solution:

System Frequency 60]

Unit Systeun Eng Project Filenanm E4(

Output Filename:

C:l 80 XFMR2 XFMR3 Rnor LinHeCable Imoedance Tie PD 8

1 0

41 0

24 Total 74 Newton-Rapbson Method 10 0.001000 Hz glish CO9a UplfilesrETAPDATA\\086-088-00M\\3Al4aa29-5.lfr

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Pwnject:

E4C-090 REV.3 ICCN C-130 ETAP Locatian:

SONGS 2 & 3 5.0.0N Page 6 of ___

CCN No.

. I Contract:

Engir.ecr W. P. Lernartz Filemane:

E4CD90 Page:

Date:

SN:

Revision:

Config.:

2 05-25-2005 SCALEDISON Base 090-3A14aa Study Case: 3A14aa ECP0505Q0255-34 ICCN C-130 UNIT3 TRAINA Adfustments Apply Individual Tolerance Adjustnrents

/Global Transfcnner Impedance:

Yes bndividMaI Reactcrlmpedance:

Yes 2ndtvidual Ovcdoad Heate Resistance No Transmission line Length:

No Cable Length:

No Apply Individual Temperature Correction Adjustments IGlobal Percent Degree C Transmission Line Resistance:

Cable Resistance:

Yes YUs Individual Ibdividuad

ECP 050500255 - 34 Rev. 0 Cale. No. E4C-090 Rev. 3

  • AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 7

of.6 L CCN No. _

Pxjea:

E4C-090 REV,3 lCCN C-130 Location:

SONGS 2 & 3 Contract:

Eogineer:

W. P. Lennartz Filemme:

EAC090 ETAP 5.0.ON Page:

3 Date:

05-25-2005 SN:

SCAtEDISON Revision:

Base Confg.:

090-3A14aa Study Case 3A14aa ECPQ505255-34 ICCN C-130 UNIT3 TRAlNA BusInputData Bus ID 2G002-BUS 2G003-BUS 3A03 3A04 3A08 3B01 380XHIS 3B02 3302XHS 3B03 3B03XHS 3B04 3B04XHS 3B12 3B12XIlS 3B13 3B13XltS 3B16 3B16XHS 3B1611BP 3BA 3BB 311C 3BD 3BD18-HlRS 33DMM 3BDSM 3BE 33EMM 3BESM 3BF 3BHP01 3BHP02 3313P03 Load InItIal Voltage Cotmant WA Ccostant Z Ccnstant I Ger.a*

kV Sub-Sys

% Mas An&.

MW Myor mW Mnvr MW MYnr MW MyVr

4.160 2

4.160 3

4.160 1

4.160 I

4.160 1

0.480 1

4.160 1

0A40 1

4.160 1

A.83 1

4.160 1

0.480 1

4.160 1

OA80 1

4.160 1

0.480 1

4.160 1

CAWD I

4.J60 1

0.480 1

0.480 1

0.480 1

OAWO I

0.4AS 1

0.480 1

0.460 1

0.480 1

0.480 I

0A60 1

0.S0 1

0.480 1

0.480 1

0.480 1

0.4W0 1

1053 0.0 1053 0.0 97.8

-4.0 100.7

-1.6 97.8

  • 4.0 93.6

-5.4 972

.4.0 96.5

-6.8 97.8

-4.0 94.5

-69 97.8

-4.0 94.7

.5.9 100.7

-1.6 93.7

-7.7 97.8

-4.0 96.0

-5.9 97.S

-4.0 93.0

-7.6 97.8

  • 4.0 91.1

-7.7 93.3

-5.6 91.9

-7.5 94.9

-6.1 90.7

.6.4 90.7

-6.4 94.6

-6.4 90.7

  • 6.4 94.6

.5.9 9S8

-5.9 94.6

-5.9 92.8

-7.6 95.9

-7.0 96.1

-7.0 961

-7.0 lODOO 2.596 0.796 0.131 5.865 1.294 0.339.

0.07S 0.127 0.079 0.049 0.031 0.206 0.120 0.261 0.172 0.202 0.11 0.141 0.047 0.151 0.079 0.082 0.03f 0.089 0.043 0.084 0.07B 0.006 Q153 0.338 0.041 0.130 0.004 0.097 0.087 0.030 0.08 0.143 0.129 0.024 0.073 0.125 0.049 0.006 0.036 0.005 0.003 0.004 0.003 0.084 0.042 0.001 0.001 0.005 0.003 O.D04 0.104 0.052 D.156 0.157 0.210 0.21D O.W03 0.059 0.010 0.000 0.000

ECP 050500255-34 Rev. 0 Cal. No. E4C-090 Rev. 3 Page __

of __

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 CCN No.

Projea P4C-090 REV. 3 ICCN C - 130 ETAP Page:

4 Location:

SONGS 2 & 3 5.0.ON Date:

05-25-2005 Contract:

SN:

SCALEDISON Engineer.

W. P. 2mmaxtz StldyCase: 3A14aa Revision:

Base Filen e:

E4C090 Config.:

090-3A14aa ECP050500255-34 ICCNC-130 UN1r3 TRAINA Load Bus Initial Voltage Ccsnt WA Consimnt Z Cmnsnt I Geic ID kY Sub-sys

% Mar, An.

MW Myar MW Mvar MW Mvar MW Myar 3B3HP4 0.4S0 1

93.7

-6.6 021D 0.00D 3BLX 0.4S0 1

93.1

-7.9 DM36 0.023 0.018 0.o05 3BMX 0ASO 1

95.8 I5.9 0.035 0.022 0.0D 0.005 3sRA 0.480 I

94.7

.5.9 3BRANIM 0.460 1

9S.8

.5.9 0.005 0.003 3BRASM DA4o 1

94.7

-5.9 0.004 0.003 3DV 0.430 1

.7

-8.0 0.101 D.073 0.119 0.059 33X 0.480 1

91.5 4.2 0.107 0.070 0238 3 0.03 3BY 0.480 1

94.6

.6.0 0.139 0.082 0.061 0043 3BY39-5tf OAS0 1

94.6

-6.0 0.00 0.030 3BY40H7RS 0.Q40 1

94.6

.6.0 0.003 0.000 3BYMM 0.460 1

93.7

-6.0 0.005 0.003 3BYSM 0.480 1

94.6

-6.0 0.0o4 O.Q03 3D0043A0409 4.160 1

200.7

-1.6 3D104-3POIS 4.160 1

100.7

.1.6 0.408 0.174 3Go02-BUS 4.160 5

105.3 0.0 3GD03-BUS 4.160 4

105.3 0.0 32V9377-N 0.4S0 1

94.6

-5.9 0.002 0.001 3LIII 0.4DA 1

90.4

-8.6 0.125 0.049 0.062 0.024 3L707-3BRAD6 CAN0 1

94.6

-s.9 3PEXCCS 4.160 1

97.7

.4.0 1.770 0.907 3Qo0o 0.4O 0

1 90.7

.6.4 0.004 0.003 3Q039 0.4so 1

94.6

.6.0 0.017 0.011 3Q074 0.450 1

94.7

-5.9 0.004 D.003 3TD63 0.480 1

94.6

-5.9 0.021 0.013 3XPI-X 4.160 1

100.S 1.5 3XR1-Y 4.160 1

93.1 4.0 ASCI 4.160 1

97. S 4.0 0.232 0.115 B31 0A40 1

95.6

-6.5 ODG3 0.040 0.090 0.000 BIOXB1HS 4.160 1

97.3

.4.0 Do 0.4S0 1

95.1

-7.0 0.021 0.014 0.2S6 0.020 BP 0ASO I

94.5

.6.9 0.263 0.103 0.2 0.04D BQ 0A.3 1

93.9

.6.0 0.061 0.033 0.054 0.030 BQMM 0.460 1

93.0

.6.0 0.005 O.W03 BQSM 0.480 1

93.9 46.0 0.Dt4 0.0W3 BT 0.480 1

90.7

-S.0 0.163 0.100 0.246 0.127

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page _9 of__4_

CCN No.

Projea:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineecr W. P. Lennartz Filetame:

E¢OWO 5.0.0N Page:

5 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa Study Case: 3A14aa ECP 050500255 - 34 ICCN C -130 UNIT 3 TRAIN A Load Bus ID BT-3B1603 D007-3A0402 D007-E336 D645 DB0415-3B0418 DBO415-E418 Q033 SWTMCHYARD SWrrOIYARD-3 ZTB45 Initial Voltage Constant WVA Ccnsant Z Connant I Generi kV Sub-Sys

% )ag.

Ang.

MW Mar MW Mvar MW Mvrr NMW Mvar 0.480 1

90.7

-8.0 4.160 1

100.7

-1.6 4.160 1

100.7

-1.6 0.456 0.256 0.480 1

95.4

-6.6 0.009 0.000 OABO 1

93.9

-5.9 0.480 1

93.9

-5.9 0,111 0.071 0.4C0 1

93.9

-6.0 0.013 0.008 230.000 1

95A 0.0 230.000 1

95.4 0.0 CABo I

95A

.6.6 Total Number of Basers 8 19.72 10.655 3.245 1.015 O

O0W O.OO O.O 0.000 M

2GW02-BUS 20003-BUS 3GW02-BUS 3C003-BUS SWITCHYARD Generation Bus Voltage Generation Mvar Iimits ktV Type Sub-sys S Mpg.

Angle MW Myar

% PF Max Min 4.160 SwIng 2

105.3 0.0 4.160 Swing 3

105.3 0.0 4.160 Swing 5

105.3 0.0 4.160 Swing 4

1053 0.0 230.000 Swing I

95A4 0.0 0.000 0.000

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 10 Of 6 /

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 CCN No.

Projtc:

E4C-090 REV. 3 1CCN C - 130 Location:

SONGS 2 & 3 Contmct:

Enginetr W. P,Lenarz FRename.

E4C090 ETAP 5.0.ON Page:

6 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa Study Case: 3A14aa ECP050500255-34 lCCN C-130 UNIT3 TRAIN A Line/Cable IDVut Data Ohmns or Siesen'1)000 tl per Conductor (Cable) or per Phase (llnc)

LlnelCable tD b S(

%h Librzy size Adj. (ft)

% Tol.

  1. /Ph.-

T (-

R X

y OXB1002PI OXBtO14P]

OXBIOISPI OXB=015P2 3AA0402P]

3AA0409P) 3AA0417P1 3AB0403PI 3AB0407P1 3AB0414PI 3ABO41SPI 3AB0417PW 3A80418PI 3ABRA06PI 3XA0304PJ 3XA0309PI 3XA0310P1 3XA0321P) 3XA0312PI 3XA0801PI 3XAMso2PI 3XAOSOSPI 3XA0809PI 3X3D102PI 3XBOZ05PI 3XB0206PI 3XBO710PI,P2 3XB0306PI 3XC0314P]

3XB0402PI 3XB1202P1 3XB1203PI 3XB121 In 3XB1303PI 0.6MCUNI 0.6McUNI 0.6MCUJNI 0,6MCUNI tOMCUN3 t.OMCUN3 8.OMCUN3 Q6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCZtNI 0.6MCUN3 S.OMCUN3 1NICUN3 S.ChICUN3 8.0MCUN3 8.0MCUN3 t.OMCUN3 8.OMCUN3 S.OMCUN3 S.OMCUN3 0.6MCUNI 0.6MCUNI 0.6MCUN1 0.GMCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6VCUNI 0.6MCUNI 0.6MCUNI 0.CMCU91 750 750 6

250 250 350 350 350 750 350 310 10 250 250 250 250 350 250 250 250 250 750 47 4JO 210 750 500 350 750 500 350 500 175.0 0.0 I

75 0.02_OOO 0.043800 I

II i

131.

o.e 1

75 0.0Z8000 0.043S00 17S.0 0.0 1

75 0.131000 OD495D 20.0 0.0 1

75 0.49S000 0.059200 4S.0 0.0 I

- *75 0.054700 0.035600 78.0 0.0 1

75 0.054700 0.035600 70.0 0.0 1

75 0.054700 0.035600 31.0 0.0 1

75 0.0461O0 0.046900 165.0 0.0 1

75 0.046100 0.045900 31.0 0.0 1

75 0.046100 0.046900 31.0 0.0 1

75 0.028O00 0.043800 181,0 0.0 1

75 0.046100 0.046900 14E.0 0.0 1

75 0.086000 0.0486CO 125.0 0.0 1

75 1240000 0.044800 66.0 0.0 1

75 0.054700 0.035600 224.0 0.0 1

75 0.054700 0.035600 60D 0.0 1

75 0.054700 0.035600 40.0 0.0 1

75 0.054700 0.035600 240.0 0.0 1

75 0.040000 0.034S00 170.0 0.0 1

75 0.054700 0.035600 60.0 0.0 1

75 0.054700 0.035600 203.0 0.0 1

75 0.054700 0.035600 232.0 0.0 1

75 0.054700 0.035600 56.0 0.0 1

75 0.028000 0.043800 66.0 0.0 I

75 0.070000 0.048200 66.0 0.0 1

75 0.070000 0.048200 83.0 0.0 1

75 0.1060C0 0.049000 314.0 D.0 1

75 0.028000 0.043800 549.0 0.0 1

75 0.035900 0.045000 268.0 0.0 1

75 0.046100 0.046900 18.0 0.0 1

75 0.028000 0.043800 37.0 0.0 1

75 0.035900 0.04500O 605.0 0.O 1

75 0.046100 0.046900 189.0 0.0 1

75 0.035900 0Q045000

ECP 050500255 - 34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project E4C-90 REV. 3 ICCN C - 130 ETAP onmr.:c q 2 2I 5.0.ON Page I I of _I CCN No.

T al-u.

pVIM-

{ cs I

Conrac:

Engineer.

W. P.Lenanz Filernme:

E4C090 Page:

Date:

SN:

Revision:

Config.:

7 05-25-2005 SCALEDISON Base 090-3A14aa Study Case-. 3AI4aD ECP 050500255 - 34 JCCN C -130 UNIT 3 TRAIN A LinetCable ID 3XB1305PI 3X31602Pl 3XB2603P2.P2 3X)1611P]

3XXRI69PInP3 3XRI69P7.P8

  • . 33XRl69PA-PD.P9 lJbry 0.6MCUNI 06MICUm4 0.6MCUNI 0.6MCUNI 8.OMCUN3 8.0MCUN3 S

LOMCUN3 -

Olnis or SlemensfI000 ft per Conductor (Cable) or per rbnse (Une)

Lenagh S51e Adj. (1t)

%Tol.

E/2hase TCC) it X

500 380.0 0.0 1

75 0.035900 0.04 750 224.0 0.0 1

75 0.028000 0.04 350 371.0 0.0 2

75 0.046100 0.04 350 370.0 0.0 1

75 0.046100 0.04 750 631.0 0.0 3

75 0.0209M0 0.03 750 610.0 0.0 2

75 0.020o00 o0m 750 374.0

  • 0.0 5

75 0.020800.

. 0.

Y 15000 13800 46900 46900 30900 10900 10900.

lJb I Cable resistances arm l1med t gie specified temperatures.

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 Page 12 of CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer:

W. P. Lennartz Filenane:

E4C090 ETAP SD.ON Study Casc 3A14aa Page:

8 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

09003A14aa ECP050500255-34 lCCN C-130 1NIT3 lRAINA 2-Windine Transformer Input Data Transforiner Rating Z Variation

% TDp Setting Adjusted Phase Shift ID MVA Prinm.k Scc.kV

%Z X/R

+5%

-5%

bTol.

Pim.

Ses.

%z Type Anglc 3BOIX 1.500 4.160 0.480 9.09 6.30 0

0 0

2500 0

9.0900 Sid Pos. Seq.

0.0 3B02X 1.000 4.160 0.480 8o5 5.30 0

0 0

0 0

S-0500 Std Pos. Seq.

0.0 3B03X 1.000 4.160 0.480 8.09 10.92 0

0 0

0 0

S.0900 Sid Pos. Seq.

0.0 3B04X 1.500 4.160 0.480 10.07 6.64 0

0 0

0 0

10.0700 StdPos.Seq.

0.0 3B12X 1.000 4.160 OAO 8.14 11.03 0

0 0

0 0

8.1400 Std Pm Seq.

0.0 3B13X 1.000 4.160 0.4S0 3.13 10.96 D

0 0

0 0

8.1300 Std Pos. Seg.

0.0 3B16X 1.500 4.160 0.4S0 9.33 3.75 0

0 0

0 0

9.3300 StdPa&.Seq.

0.0 BIOX-B 1.500 4.160 0.430 9.17 6.72 0

0 0

D 0

9.1700 StdPas.Seq.

0.0 3-Winding Transformer Inpirt Data Transformer ID Rating Tap Impedance Z Variation Phase Shift Winding MV4 kV

%Z XIR MVAb

%Tol.

+5%

-5%

Type ngle Pimary 30.0D0 230.000

-2.50 Zps M4.40 20.67 30.ODO 0

0 0

Secondary:

10.00D 4360 0

Zpt-11.10 22.80 30.000 0

StdPos. Seg.

0.0 Tertialy

20.000 4.360 0

Zst-24.60 19.16 30.000 0

Sidtas. Seq.

0.0

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page 13 of _____

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 ltion:

SONGS 2 & 3 Contract:

Engineer W. P. Lenrmrtz Filenoa:e E4C090 ETAP 5.0.0N Page 9

Date:

05-25-200S SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa StudyCase: 3A14aa ECP050500255-34 ICCN C-130 UNrr3 TRAINA Branch Connections CXT/Branch Connected Bus ID ID 313lX 3B02X 3a03X 3B04X 3S12X 3B 13X 3316X BIOX-B 3XRI OXB1002PI 0X1014PJ OXEIoISPI OX\\31015P2 3AA0402PI 3AA0409PI 3AA0417PI 3AB0403PI 3AD3407P) 3AB0414PI 3AB30415P1 3AB0417PI 3ABO4 SPI 3ABRA06PI 3XA0304PI 3XA0309PI 3XA0310P2 3XA0311PI 3XA0312P1 3XAOSOIPI 3XA0O02PI 3XAOS8PI 3XAOSWP1 3X30 1021P1 3XB0205PI 3XBZ206PI Type 2W XFMR 2W XFMR 2WXFMR 2W Xl:MR 2WXFMR 2W XFMR 2W XFMR 2W XFMR 3WXemr 3W Xrmw 3W Xfnn Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cabl:

CabIC FmmBus 3BOWIaS 3B02XHS 3BO3XHS 3B04X}1S 3BI2XHS 3B 13XH1S 3B 16XH1S BIOXBHS SWITCHYARD-3 SWIrCHYARD-3 3XRI-X B10 B10 B10 ZTBS5 3A04 3A04 3A04 3B04 3B04 3104 31304 31304 31304 3BRA 3A03 SACS 3A03 3A03 3AO3 3A08 3A08 3AOS 3101 3B02 31302 To Bus 31B01 3802 3603 3BO4 3B812 31B13 3B 16 B10 3XRI-X 3XRI-Y 3XRI-Y BP BO ZTB45 D645 D007-3A0402 3DD04-3A0409 3BO4XHS 3BRA 3BD 3BE 3BY BQ D130415-3B041S 3L707-3BRA06 3B 13XHS ASCI 3B12XHS 3B03XiIS 3pEXCCS BIOXBHS 3B 16)XHS 3BOIXHS 3BD02XHS 310A 3BJIP02 3BHP03

% Impedance, POS. Scq, 100 MVA Base R

X Z

y S2.27 559A5 565.47 135.S7 720.13 732.84 67.16 733.41 736.48 91.02 604.34 611.16 66.61 73R.03 741.03 67.25 737.06 740.12 64.30 562.5S 56614 S1.92 550.47 556.53 2.0S 48.67 48.72 1.45 37.16 37.19 234.90 1143.83 1167.68 193.61 302.86 35946 144.93 226.71 269.08 1956.57 73931 2091.59 393.54 47.26 396.37 1.38 0.90 1.65 8.00 5.21 9.54 2.01 131 2.40 S6.47 57A.5 80.55 1393A6 1417.64 1987.82 56.47 57.45

£0.55 34.30 53.65 63.68 329.69 335.42 47032 502.91 284.20 577.66 6224.39 221.27 612839 1.90 1.24 2.27 6.45 4.29 7.69 2.73 1.12 2.06 1.35 0.75 137 5.05 4.39 6.69 4.89 3,18 5.84 1.73 1.12 2.06 5,S4 3.80 6.97 6.68 434 7.97 61.96 96.92 115.03 182.55 125.70 221.64 282.55 125.70 221.64

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN

-n -

s _

~ --..-.-

s ETAP Page I14f of___

CCN No.

C - 130 Project:

E4W-UJU KRV.3 ICCN C-1IU Locion:

SONGS 2 & 3 Contract:

Engineer.

W. P. Lennazz FMlename:

E4CM9M 5.0.ON Page:

10 Date:

05-25-2005 SN:

SCALEDISON Revision: Base Config.:

090-3AI4aa Study Case: 3A14aa ECP050500255-34 ICCN C-130 UNrr3 TRAINA CKTranch Connected Bus IW ID Typc From Bus To Bus 3XB0210PIXP2 3XB0306PI 3XBO314P]

3XE0402PI 3XS1202PI 3X;31203P1 3XB1211PI 3XB13C3PI 3XB130SPI 3XB1602PI 3XB1603PI.P2 3XB161 IPI 3OXXR169P1-P3 3XXR1 69P77Pt 3XXRlt69PA-? pP9 3BDIS 3BD26 3BDM 3BDS 3BE51 3BOEM 3BES 3BRA22 3BRAM 313RAS 3BY39 3BY40 3BY42 3BYM 3BYS BQ27 BQM BQS U3-SWYD0C3 3D004 30004 3L707X 8T XFRSW D007 DB04I5 Cable Cable Cable Cable Cable Cable cable Cable Cable Cable Cable Cable Cable Cable Cable l17 Breakl Tie Bretal rie Brcabr 77e Brcelr Tc Brallkr Tie Breab Me Breakr Tie 3realr Me Brealr 17e BmtCI lie BSnAL Tie Brren Tie Breakr Tie Breabr lie Break Tie Breala Tie Breakr Tee Brealn Tie Brenr Tie Switch Tie Switch lie Switch Me Switch le Switch 3B02 3B03 3B03 3B04 3B12 3B12 3312 3B13 3013 3B16 3B16 3B16 3XRI-X 3XRI-Y 3XRI-Y 311D 3BD 33D 3BD 3BE 3BE 3BE 3BRA 3BRA 3BRA 3BY 3BY 3BY 3BY 3BY BQ BQ BQ SWTrCHYARD-3 3D004-3POtS 3tlV9377N BT D007-336 DB0415-E3418 3BHPO1 3BF 3BB 3B13P04 3BV 3BLX 3LIII 3BMX 3BC 3BX 8T-3B 1 603 3B)61IBP 3A04 3A08 3AD3 3BDIS-HTrRS 3Q020 3BDMM 3BDSM 3T063 3BEMM 3BESM 3Q074 3BRAMM 3BRASM 3BY39-HlIRS 3BY40-H1TRS 3Q039 3BYMM 3BYSM Q033 BQMM BQSM SWYTOMYARD 3D004-3AW409 3L707.3BRA06 BT.3B1603 D007-3A0402 DB0415-3B0418

% ImpedanMe, Pos. Seq, 100 MIVA Base Rt X

Z.

Y 347.63 160.70 382.97 347.39 543.42 644.97 77175 976.15 1248.73 48817 496.64 696.39 200.25 313.24 371.75 534.77 67032 S57.50 1102.02 1121.14 I572.07 268.09 336.05 429.89 539.03 675.66 864.33 247.82 3S7.66 460.11 337.89 343.75 482.01 673.96 685.66 96lA3 2.30 3.42 4.12 3.34 4.96 5.98 0.82 1.22 IA7

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3.

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C Page 15 of ___

^ -130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Loction:

SONGS 2 & 3 Contract:

Engineer:

W. P. Iennartz Filename:

E4C090 ETAP 5.0.ON Swtdy Case: 3A14aa Page:

11 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa ECP050500255-34 ICCN C-130 UNIT 3 TRAIN A Eaulpment Cable Tnhut Data Ohms or SleinensfD000 ft per Conductor Equipment Cable ID Equipmcnt ID lcn~h Type lJbtuy Se Adj.'(t) 5Tol C0pb T'C R

OABQD7PI OABQOSPI OABQ05PI 3XBl0310PI,P2 3ABD409PIPP3 3A230419PI-P3 OABQI4PI 3AED12PI 3AfD13PlI 3ABYO7PI 3AtBY05PI 3ABY36PI 3ABYMPI 3ABE04PI 3XB1609P2 3X=0210P3-P5 3XBD206P2-W4 3XB0205P2,P3.PE 3XB0402P2,P3.P4 3XAD0I3PI OABQISPI 3ABY38PJ 3ABY39P6 3XB0209PI-P3 3XBO106PI-P3 3AB0410P1-F3 3ABY40r6,p7,P5 3AB0411PI-P3 3AIBY40P9,PA,P3 3ABY24PI 3ABY22PI 3ABY2DPI 3ABY21PI 3ABYIIPI 3ABY12PI 3ABY37PI 3AOY30PI 3ABY31PI 3Ai3E03PlP2 3ABY25PI 3ABD22PI 3ABD21PI 3ABE49PtP2 2A173 2E255 21270 3AOOI 3A071 3A074 3A173 3A274 3A275 3A370 3A373 3A394 3BOOI 3B003 3B035 3E122-HI 3E124-11 3E126-111 311128-411 EX]

3E202 3E255 3B70 3B37011 3E394 3M397 31399 3B399H 3E401 31140111 311417 311427 3E437 3E435 31439 311440 311441 3E453 3E454 3E464 311517 3E546 3E-550 3E=52 Ind. Motor 0.6MCJN3 Ind. Motor 0.6MCUN3 Stat. Load 0.6MClN3 Ind. Motor 0.6MCUNI Ind. Motor 0.6MCUNI WId.

Motor OAMCUNI Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 hnd. Motor 0.6MCUIN3 Ind. Motcr 0.6MCUN3 Ind. Motor 0.6MCUN3 Stat. Load 0.6MCUNI SUtL Loud 0.6MCUNI SIL Load 0.6MCUNI Stat. Load 0.6MCUN3 Stat. Lad 0.6MCUN3 Sut Load 0.6MCUZJ3 StaL Load 0.6MCUN3 lWd. Motor 8.DMCUN3 Wad.

Motor 0.6MCUN3 Ind. Motor O.6MCUN3 Stat. Load 0.6MCUN3 tnd. Motor 0.6MCUNI laL. Motor 0.6MCUNI Ind. Motor Q6MCUNI Stat. Lzad Q.6MCUN3 lId. Motor O.6MCUNI Stat. Load 0.6MCUN3 Wnd.

Motor 0.6MCUN3 lad. Motor 0.6MCUN3 Ind. Motor O.MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor O.6MCUN3 Ird. Motor Q.6MCUN3 Ind. Motor 0.6MCUN3 Icd. Motr 0.6MCUN3 Lid. Motor 0.6MCUN3 Stat. Lzad 0.6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor C.6MCUN3 Iri. Motor 0.6MCUN3 Stat. Load 0.6MCUN3 12 358.0 10 216.0 12 410.0 110 227.0 110 447.0 1)0 498.0 12 365.0 2

5R.0 2

123.0 12 403.0 12 520.0 10 628.0 PO 122.0 110 117.0 3)0 191.0 2

284.0 2

290.0 2

282.0 2

324.0 250 142.0 10 346.0 2

450.0 12 450.0 1)0 308.0 110 213.0 310 315.0 12 442.0 310 316.0 12 366.0 10 43D.0 10 120.0 12 370.0 12 370.0 12 330.0 12 330.0 12 460.0 12 374.0 12 309.0 2

464.0 12 354.0 2

148.0 2

178.0 12 500.0 0.0 1

0.0 I

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 0.0 1

C.0 1

0.0 1

0.0 1

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 t

0.0 1

0.0 1

0.0 2

0.0 1

75 1.97200 75 1.24000 75 1.7200 75

.13100 75

.13100 75

.13100 75 1.97200 75

.19700 75

.19700 75 1.97200 75 1.97200 75 1.24000 75

.13100 75

.13100 75

.0500 75

.19700 75

.19700 75

.19700 75

.19700 75

.D5470 75 1.24000 75

.19700 75 1.97200 75

.13100 75

.13100 75

.08600 75 1.97200 75

.08500 75 1.97200 75 124000 75 I.24000 75 1.97200 75 1.97200 75 1.97200 75 1.9720D 75 1.9-200 75 S97200J 75 37 o200 75

.19700 75 1.97200 75

.19700 75

.19700 75 i.sno J

OIL heater Rcntancc X

Y Adj.(ohm) S Tot 04560

.OOO0000

.ooD0 0.0 04480 DOOODO

.0ooo 0.0 04560 o00o00D

.0000 0.0 04950 0OOOD

.0000 0.0 04950 0000000 4000 0.0 04950

.0000000 Dooo 0.0 04560

.0000000

.0000 0.0 03440

.oooDooo-DOOO 0.0 03440

.0000000

.0000 0.0 04560

.OO000

.OO 00 0.0 04560

.0oo00000 DOO 0.0 04480 eoooo0o

.0000 0.0 04950

.0000Oo0

.0000

-0.

04950 oD00ooo OO00 0.0 04860

.0000000 ooo0 0.0 03440

.OOO00 DOD 0.0 03440

.0000000

.0000 0.0 C3440

.OOOOO0

.0000 0.0 03440

.0000000

.0000 0.0 03560 OO.00 00

.0O0 0.0

.0440

.0000000

.O00 0.0 03440

.0000000

.0000 0.0 04560

.0000000 oooo 0.0 04950 0ooooo0 0000 0.0 04950

.0OO000O

.0000 0.0 04860 COOO0OO D.0O 0.

04560

.0000000

.D00 0.0 04S60

.0000 0

.000 0.0 04560

.0D00000

.OOO o0.

0440

.000DOOO

.000 0.0 044SO

.0000000

.0000 0.0 04560

.OOOOO

.0000 0.0 04560

.0000000

.0D 0.0 04560

.ODO0OO

.0000 0.0 04560

.00000

.0000 0.0 04560 0D0OOO

.COOD 0.0 04560

.0000000 W000 0.0 04560

.0OD00

.0000 0.0 03440 OOOOOO DOOO 0.0 04560

.0000000

.0000 0.0 03440 0000000

.OOO 0.0 03440

.o00000 OO.O 0.0 04560

.0OOOO

.0OO0 0.0

ECP 050500255 - 34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN Page I6( of 6_

C-130 CCN No.

Psrcec.

E4CW-90 REV.3 ICCN C-130 Loftion:

SONGS 2 & 3 Corauct:

Engineer W. P. Lennartz Filenlame E4C090 ETAP 5.0.ON Page:

12 Date:

05-25-2005 SN:

SCALEDISON Reviein:

Base Config.:

090-3Al4aa Study Case: 3A14aa ECP 050500255 - 34 ICCN C - 130 UNrr 3 MRAIN A Ohmns or Slemens/1000 ft per Conductor Equipment Cable ID Equlp ent Adj. (ft)

% Tol #l/pb t CC)

R 1D 3A1E36P' 3XB1606?P.P2 3ABE42PI OABQO5PI 3XBY23PI 3ASY34Pl 3AAC403PI 3ADY40PI 3AA0407PI 3ABY39P1 3AA040SPI 3ABY39P2 3WADO04PI 3ABY39P3 3AA0405PI 3XA0308P1 3XA03D7PI 3XA0312P2 3X)0303PI 3ABD23PI 3A3D24?1 3ABYIOPI 3A3Y39P9 3A3Y39P4 3XA03O6PI SXA0305PI 3XA0313PI 3xBI206PI-3 32802!0PI 3XS1306PI 3AMA404PI 3ABY39PS 3ABY14PI 3ABY40P2 3ABYISPI 3ABY40P3 3AB3413PI 3ABY4OP4 3ABY40P5 3XBo309I'l 3AA041IPI 3A3Y39P5 3ABDIOPI 3A3DI IPI 3ABE41PI 3ABE02PI 3XI31210PI 31lV4731 31046 3266 3L270 3U1IIIX) 3P009 31`012 3P012H 3P015 31P015H 3P027 3PD17H 3P018 3POISBHA 32024 3P050 3PD51 3P058 3P075 3P093 3P096 3PIOIS 3PI01811 3P1 12H 3PliS 3P217 3P120 3P127 3P128 3P135 3P141 3P14111 3P174 3P174H 3P175 3P175H 3P190 3P19012 3P191IHA 3P290 3P307 3P307H 3996n3`1015 3P997/3P1014 3RU7804-1 3RU7S22-1 3TOII Type Librwy Size Ind. Motor 06MCUN3 12 Ind. Motor 0.6MCUN1 250 StaL Lod 0.6MCUN3 6

Stat. Load 0.6MCUN3 12 Stat. Load O.fMCUN3 12 Ind. Motor Q.6MCUN3 2

Ind. Motor LOMCUN3 250 Sltat. Lod 0.6MCUN3 12 WId.

Motor E.OMCUN3 250 Stat. Load 0.6MCUN3 12 Ind. Motor S OMCUN3 250 StaL Load 0.6MCUN3 12 Ind. Motor S.OMCUN3 250 Stat Load 0.6MCUN3 12 2rd. Molor S.OMCUN3 250 Ird. Motor BOMCUN3 750 Ind. Motor 8.OMCUN3 750 hd. Motor 5.OMCUS1 350 Ind. Motor 0.6MCUNI 1/0 Ind. Motor 0.6MCUN3 12 Ind. Motor 0.6MCUN3 12 Ind. Motor 0.6MCUN3 10 Slat. Load 0.6MCUN3 12 Stat. Load 0.6MCUN3 12 Ind. Motor E.CMCUN3 500 ld. Motor S.OMCUN3 500 lad. Motor S.MCU1N3 250 Ind. Mctor 0.6MCUN1 Soo Ind. Motor 0.6MCUN1 210 bad. Motor 0.6MCUNt 4)0 Ind. Motor B.OMCUN3 250 Stat. Load 0.6MCUN3 12 Ind. Motor 0.6MCUN3 6

StaL Load 0.6MCUN3 12 bd. Motor 0.6MCUN3 6

SLat.Load 0.6MCUN3 12 Ind. Motor 0.6MCUN1 310 Smt. Load 0.6MCUN3 32 Stat. Load 0.6MCUN3 12 Wnd.

Motor 0.6MCUN1 110 lInd. Motor 8.OMCU3 250 Stat. Lcad 0.6MCUN3 12 Ind. Motor 0.6MCUN3 12 lnd. Motor 0.6MCUN3 12 Stat. Load 0.6MCUN3 12 Stat. Load 0.6MCUN3 12 Stat. Load 0.6MCUNI 350 562.0 416.0 360.0 650.0 377.0 470.0 332.0 372.0 33S.0 369.0 364.0 548.0 36.0 400.0 328.0 73.0 107.0 36.0 166.0 170.0 170.0 370.0 370.0 432.0 30S.0 340.0 678.0 563.0 314.0 701.0 540.0 779.0 330.0 420.0 330.0 3W0.0 316.0 420.0 336.0 198.0 431.0 466.C 106.0 60.0 230.0 500.0 294.0 0.0 1

0.0 2

0.0 2

0.0 1

0.0 1

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 I

0.0 I

0.0 1

0.0 I

0.0 1

0.0 1

0.0 I

0.0 1

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 I

0.0 I

0.0 I

0.0 I

0.o I

0.0 I

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 I

0.0 1

0.0 I

0.0 I

75 I-7200 75

.06080 75 A9300 75 1.97200 75 1.97200 75

.19700 75

.05470 75 1.972D 75

.05470 75 1.97200 75

.05470 75 1.97200 75

.05470 75 1.97200 75

.05470 75

.02080 75

.02080 75

.04610 75

.13100 75 1.97200 75 1.97260 75 1.24000 75 1.97200 75 1.97200 75

.02920 75

.02920 75

.05470 75

.03590 75

.10600 75

.07000 75

.05470 75 1.97200 75 A9300 75 1.9720D 75 A9300 75 1.9720 75

.0D6S 75 1.97200 75 1.97200 75

.13100 75

.05470 75 1.972CO 75 1.97200 75 1.97200 75 1.97200 75 1.97200 75

.04610 x

.04560

.04800

.03910

.04560

.03440

.03560

.04560 W3560

.04560

.03560

.04560 D3560

.04560

.03560

.03090

.03090

.05140

.04950

.04560

.04560

.04480

.04560

.04560

.03340

.03340

.03560

.04500 D4900

.04W20

.03560 D4560

.03910 D4560

.03910

.04550 4860

.04560

.04560

.04950

.03560

.04560

.W4560

.04560

.04560

.04560

.04690 y

£0000000

£D000000

.0000000 C0000000

.0000000

.000000O

.0000000

.D00000

.0000000

.0000000

.0000000

.0000000

.0000000

.00CWODO O0000 woc0000

.0000000

.0000000

.OD0000

£000000

£ooo000 ODOOWOO DW00000 DWOOOO0

.0000000 DOOOCOO

.00D0000

.0000000

.0000000 D000000 D000000

£000000

.0000000

.0000000

.W00000 D000D0 D000000

.0000000

.0000000

.0000000 D000000 C00000 D000000

.0000000

.0000O0

.00000W D000WOO O/L Hleiter ReSlMaaen Adj.(cltm) % TJI

.0000 0.0

.0000 OD

.000 0.0

£000 0.0

.0000 0.0

.O000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0 DOO0 0.0 mOODO 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.DOC 0.0

.0000 0.0

.0D00 0.0

.000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 C.C

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.00DO 00

.0000 0.0

.00D0 0.0

.0000 0.0

.0000 0.0

.0000 0.0 0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

.0000 0.0

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION lCCN Pro~ect:

E4C-00 REV.3 ICCN C-130 Loca.ion:

SONGS 2 & 3 Contract:

Engineer W.P.Lennartz Filenme:

E4C090 ETAP 5.0.0N Page 17 of ____

C-130 CCN No.

Page:

J3 Date:

05-25-2005 SN:.

SCALEDISON Revision:

Base Confg.:

090-3AI4aa Study Case: 3A14aa ECP 0505025 - 34 ICCN C-130 UNIT 3 TRAIN A Equipment Cable Equnpmeent ID ID Type Ohms or Siemens11000 ft per Conductor Length ibrmary Size Ad4.()

% Tol ph T (C)

R 3XA0412PI 3XBY33P2.P3 OADQ22PI 0A8Q23PI OArQC9P2 OXACIOIP2 OABQO4PIJP2 OAADC07PI OABD41SPI OXSIOIIPI OXE 101573 0ABQ13PI CABQ26PI OXBQII!p 3XBY19PI 3XB1307PI cXBIW06PI OABQ24PI 0ABQ20P]

OABQ25PI 3T0141X]

3TII0/3Q071PXI A053 A056 A207 C443 E297 E336 E41B 1643 E645 L211-1 L211-4 LA371X1 LP35AIXJ N002 P159 P162 P445 W310 Stat Load Stat. Load lnd.Motor Ind. Motor mnd.

Motor lad. Motor Stat. Load Wn. Motor Ind, Motor SMtL Load Stat. Load StaL Lotd Stat. Load Stat. 1.0d Stat. Load Stat. Lad Ind. Motor Ind. Maoor Ind. Motor Ind. Motor 8.MCUN3 0W6MC(NI 0.6MCUN3 0.6MCUN3 0.6MCUN3 S.OMCUN1 0.6MCUN3 LOMCUN3 0.6MCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUIN3 0.6MCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 250 462.0 2

949.0 12 472.0 12 472.0 20 640.0 250 90.0 12 518.0 250 216.0 310 415.0 500 18.0 10 10.0 6

90.0 6

120.0 10 300.0 6

339.0 10 824.0 110 402-0 2

468.0 12 584.0 12 584.0 0.0 1

0.0 I

0.0 I

0.0 I

0.0 I

0.0 1

0.0 I

0.0 1

0.0 I

0.0 1

0.0 1

0.0 I

0.0 1

0.0 I

0.0 1

0.0 1

0.0 1

0.0 I

0.0 I

0.0 I

75

.05470

.4 75

.20300 75 1.7200 75 1.97200

.1 75 1.24000 75

.06090

.4 75 1.97200

.1 75

.05470 J

75

.08600

.D 75

.03590

.1 75 124000

.1 75 A9300

.1 75

.49300

.J 75 1.24000 75 A9300 J1 75

.13100

.1 75

.13100 75

.19700 75 1.97200 75 1.972CO OJL Hseter Reasstance X

Y Adj.fohm) % Tot D3560 DOOOOOO *°0°° 0.0 D5130 D000000

.O0OC 0.0 04560

.OOOOOO

.0000 0.0 D4560

.0000000

.0000 0.0 D4480

.0000000

.0000 0.0 05250

.0000000

.0000

.0 D4560

.0OOO0

.000 0.0 03560

.0000000 WO0 0.0 D0460

.00000

.0000 00 04500

.OOOOOOD.0000 0.0 04480

.0000000

.0000 0.0 03910

.0000000

.0000-0.0 D3910

.0000000

.00 0.0 24480

.0000000

.0000 0.0 03910

.OOOOO0

.0000 0.0 24950

.000000

.0000 0.0 D4950

.0000000

.0000 0.0 23440

.OOO0OOO DOO 0.0 04560

.0000000

.0000 0.0 04560

.000000

.0000 0.0

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 Page I - of &4q CCN No.

Project:

E4C-090 REV.3 JCCN C-130 Location:

SONGS 2 & 3 Ccnracl:

Engineer.

W. P. Lennanz Filename:

E4C090 ETAP 5.0.ON Study Czse, 3A14aa Page:

14 Date 05-25-2005 SN:

SCALEDISON Revision:

Bzse Conflig.:

090-3A14aa ECP050500255-34 ICCNC-130 UN1T3 TRAINA LOAD FLOW REPORT Bus-113 Voltage Generaton Load kV kV Ana.

MW MWr MW Mvar 4.160 4.070

-4.0 0

0 10.000 5.865 3B13XHS ASCI ID 3A03 3A04 3AOS 31B01 31331XIIS 4.16D 4.190

-1.6 4.160 4.070

.4.0 0.480 CA49 5.4 4.160 4069

.4.0 0.480 0.463

-6.B 4.160 4.06S

  • 4.0 0.4S0 0.453

-6.9 4.160 4.069

-4.0 0A40 0.455

-5.9 31B12XIS 3BO3XIIS 3PEXCC5 3XRI-Y 0

0 2.725 1374 D007-3A0402 3D004-3A0409 3B04XHS 3XR1-X 0

0 0.796 0339 BIOXBHS 31BJ6XIS 3BOIXHS 3BD2XHS 3XRJ-Y 0

0 0.131 0.07S 3BA 3BDlXlIS 0

a 0

0 3AOS 3BDI 0

0 0.049 0.031 3BHlP02 3MmP03 3BIIPOI 3BO2XHS 0

0 0

0 3A08 3BD2 0

0 0.206 0.120 3BF 3BB 3BD3XHS 0

0 0

0 3A03 31803 0

0 0.261 0.172 3BRA 31113 3DE 3BY BQ DB0415-3DD41S Load Flow XFIMR MW Mmr Amp

%PF

%Tap 0388 0.186 61.0 90.2 0.232 0.115 36.8 89.5 0.769 0.453 126.6 86.1 0.612 0.366 1012 15.8 1.713 0.909 2S2.6 B9.0

-13.773

-7.894 2252.2 B6.8 0.456 0.256 72.0 87.2 0.40B 0.174 61.1 92.0 1.200 0.763 195.9 84A

-4.7S9

-2.S67 741.6 88.1 0.716 0.260 108.0 94.0 0.988 0.671 169.4 82.7 0399 0.233 65.5 B63 0.589 0.062 84.0 99.4

-3.4S7

-1.565 542.1 91.2 0.266 0.141 386.9 883

-0396 40.219 581.8 87.5

-0399

-0.233 65.5 863 0399 0.233 65.5 863 2.500 0.195 0.O0I 242.6 100.0 0.195 0.001 242.6 100.0 0.145 0.001 281.0 100.0

-0.583 40.033 728.1 99.8

-0.59 40.062 84.0 99A 0.589 0.062 84.0 99.4 0.241 0.108 336.8 913 0.161 0.095 238.2 86.0

-0.608

-0.323 8773 883

-0.612 40.366 101.2 85.8 0.612 0366 101.2 85.8 0.014 0.009 20.6 84.9 0.147 0.101 226.9 82.4 0.104 0.056 150.1 87.8 0.27 0.140 3383 85.0 0.129 0.078 190.9 8S.5 0.112 0.072 169.0 84.1 31302 3BW021IS 3B03 3B03XHS 3804

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

. E4C-090 REV. 3 ICCN C - 130 Locaton:

SONGS 2 & 3 Contracl:

Engineer.

W. P. Lennatz hilename:

M4090 ETAP 5.0.ON StudysCse 3A14aa Page 19 of ___

CCN No.

Page:

15 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa ECP050500255-34 ICCNC-130 UNIT3 TRAINA

t....--.-

lus ID Voltage Generation Load kV kV gAn.

MW Mar MW Mvr ID 3B04XHS 3B12 3B 12Xt3S 3B13 3B 13XHS 3B16 4.160 4.189

-1.6 0.4S0 0.450

-7.7 4.160 4.069

-4.0 0.480 0.461

-5.9 4.160 4.069

.4.0 0.4S0 0.447

-7.6 4.160 4.C69

.4.0 0.420 0.437

-7.7 0.480 0.445

-5.6 O4A0 0.441

-7.5 0.450 0.455

.6.1 0.480 0.435

.6.4 0ABO OA35

.6.4 0.460 C.435

-6.4 0.4W0 0.435 46.4 0.4S0 0.454

-5.9 311HP04 3B04XHS 0

0 0

0 3A04 3B04 0

0 0.325 0.159 3BV 3BLX 3L111 3B 12XHS 0

0 0

0 3A03 3B12 0

0 0.27 0.080 3BMX 3BlC 3B13XHS 0

0 0

0 3A03 3B13 0

0 0.162 0.111 3BX BT-3B1603 3B1611BP 3B16XHS O

0 0

0 3ACS 3B16 O

0 0.125 0.108 3B16 0

0 0265 0.140 3B01 0

0 0.158 0.091 3803 0

0 0.107 0.063 31B13 0

0 0.130 0.088 3B04 3BDIS 111RS 3Q020 3DDMM 3BDSM 0

0 0

0 38D 0

0 0.005 0.003 31B1) 0 0

0.003 0.002 38D Load Flow XFMR MW Mvar Anmp

%PP P

Tap 0.1I6 0.002 236A 100.0

-1.179

.0.631 1698.0 8S.2

-1.199

-0.763 195.9 S4A 1.199 0.763 195.9 84.4 0.205 0.126 308.8 S53 0.052 0.027 75.2 88.5 0.180 0.073 2.50.1 92.6

  • 0.762

-03S6 1097.0 89.2

-0.768

-0.453 126.6 86.1 0.763 0A53 126.6 S6.1 0.052 0.026 72.4 89.2 0.10 0.064 157.1 86.0

-0.386

  • 0.170 528.5 91.5

-03tS

-0.186 61.0 90.2 0.388 0.186 61.0 90.2 03D9 0.145 441.7 90.6 0379 0.212 561.2 872 0.127 0.110 217.7 75.5

-0.977

-0.579 1467.B S6.0 40.9S7

-0.671 169.4 87 0.987 0.671 169.4 827

-0.125

-0.108 217.7 75.6

-0.265 40.140 386.9 88.4

-0.158

-0.091 238.2 86.5

-0.107 40.063 157.1 863 40.142

-0.096 226.9 82.8 0.000 0.000 0.0 0.0 0.003 0.002 5.5 85.0 0.005 0.C03 73 S3.0 0.003 0.002 5.5 85.0 0.000 0.000 0.0 0.0

-0.005

-0.003 73 83.0

-0.003

.0.002 5.5 85.0 40.104

.0.056 150.1 87.9 0.019 0.012 28.5 85.0 M.05 0.003 7.0 83.0 0.004 0.002 5.7 85.0

-. 005

.0.003 7.0 83.0 3BI6XJIS 3B1611BP 3BA 313B 3BC 3BD 3BDIS.llTRS 3BDMM 3BDSM 3BE 0

0 0.076 0.039 3B04 3T063 3BEMM 3BESM 313EMM 0.460 0.454

-5.9 O

a O C05 0.003 3BE

ECP 050500255-34 Rev. 0 Cal. No. E4C-090 Rev. 3 Page ZO of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Projec:

E4C-090 REV. 3 ICCN C -130 Location:

SONGS 2 & 3 Conttact:

Engineer W. P. Lnantz Filen2me:

E4090 ETAP 5.0.0N Page:

16 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14as Study Case: 3A14aa ECP05050Q255 -34 ICCN C-130 UNIT3 TRAINA Bus ID 3BESM 3BF 3BIIPol 3BHP02 3BIIP03 3BtS01 3BLX 3BMX 3ERA Voltage Gcncratoln Load kV kV Ang.

MW Mar MW Mnr 0.480 0.454

-5.9 0

0 0.004 0.002 0.480 0.445

-7.6 0

0 0.238 0.103 0.4W0 0.460

.7.0 0

0 0.IU 0.000 0.480 0.461

-7.0 0

0 0.194 OD00 0.4E0 0.461

-7.0 0

0 0.194 0.000 0.40 OA50

-6.6 0

0 0.1I4 0.000 0.480 OA47

-7.9 0

0 0.052 0.027 0.480 0.460

-5.9 0

0 0.051.

0.026 ID 0.480 0.455

-5.9 3BRAMM 3BRASM 3BV 3BX 3BY 3BY39-IRS 3BY40-1ITRS 3BYMM 3BYSM 3D004-3A04"9 3D004-3P01B 31HV93n7-N 3LIII 3L707-3BRA06 3PEMCC5 3Q020 3Q039 3Q074 0.460 0.455

-5.9 0.4S0 0.455

-5.9 0.4W0 0.445

-8.0 0.480 0.439 4.2 0.400 0.454

-6.0 0.480 0.454

-6.0 0.40 0Q454

-6.0 0.460 0.454 46.0 0.480 0.454

-6.0 4.160 4.188

  • .6 4.160 4.1BS

-1.6 OAEO 0.454

-5.9 0.480 0.434

-8.6 0.4W0 0.454

5.9 4.160 4.064

.4.0 0.4SD 0.435

-6.4 0.480 0.454

.6.0 0.480 0.455

-5.9 0

0 0

0 3B04 3L707-3BRAOG 3Q074 3BRA.M 3BRASM 0

0 0.005 0.003 3DRA O

0 0.004 0.002 3BRA 0

0 0.204 0.123 3B12 0

a 0.306 0.139 3B 16 0

0 0.193 0.125 3B04 3BY39-HTRS 3BY40-HTRS 3Q039 33YMM 3BYSM 0

0 0.007 0.000 3BY 0

0 0.003 0.000 3BY 0

0 0.005 0.003 3BY 0

0 0.004 0.002 3BY Load Flow XFMR MW Mvzr Amp IXPP

%Tap

-0.004

-0.C02 5.7 85.0

.0.23B

.t003 336.S 91.7

-0.144 0.000 I81.0 100.0

.0.194 0.000 242.6 100.0

-0.194 0.000 242.6 100.0

-0.184 0.00D 236.4 100.0

.0.052

-4.027 752 88.6

-0.051 0.02M 72.4 89.2 40.014

-0.C09 20.6 84.9 0.002 0.001 2.3 90.0 0.004 0.002 5.7 85.0.

0.005 0.003 7.0 83.0 0.004 0.002 5.7 85.0 4.0005

-0.003 7.0 83.0 40.004

-0.002 5.7 85.0

-0.204 40.123 30a8 85.5 40.306

-0.139 441.7 91.0

-0.226

.0.140 33.3 85.1 0.007 0.000 8.9 100.0 0.003 0.000 3A 100.0 0.015 0.009 22.7 t5.0 0.OOS 0.003 7.0 83.0 O004 0.002 5.7 85.0

-0.007 0.000 8.9 100.0

-0.003 0.000 3.4 100.0 40.005

-0.003 7.0 83.0

.0.004

-0.002 5.7 85.0

-0.40E 0.174 61.1 92.0 0.408 0.174 61.1 92.0

-0.408

.0.174 6t.l 92.0

-0.002 40.001 2.3 90.0

-0.175

-0.068 250.1 93.2

-0.002

-0 M1 2.3 90.0 o02 0.001 2.3 9D0

-1.770

-0.907 282.6 890

-4.003

-0.002 5.5 85.0

-0.015

-0.009 22.7 85.0

-0.004 4.0002 5.7 85.0 0

0 0

0 3A04 3D004-3P0IB 0

0 0.408 0.174 3D004-3A0409 0

0 0.002 0.001 3L707-3BRA06 0

0 0.175 0.068 31312 0

0 0

0 3BRA 3HV9377-N 0

0 1.770 0.907 3A03 0

0 0.003 0.002 33D 0

0 0.015 0.009 3BY 0

0 0.004 0.002 3BRA

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page 2 1 of___

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV. 3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer:

W. P. Leinartz Filenaimr F4C090 ETAP 5.0.ON Study Case: 3A14aa Page:

17 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa ECP050500255-34 lCCN C-130 UNIT3 TRAINA Bus ID 3T063 3XR1-X Voltage Generation Lond kV kV An.

MW M

Mvar mw mvar ID Load Flow XFMR MW Mar Amp

%PP

% Tap A8D 0.454

-5.9 4.160 4.199

-1.5 3XRI-Y 4.160 4.030

.4.0 ASCI 131D 4.160 4.069

  • 4.0 0.480 0.459 46.5 0

0 0.019 0.012 3BE 0

a 0

0 3A04 3XRI-Y

& SWCHIYARD-3 0

0 0

0 3A08 3A03 SWITCHYARD-3

&3XRI-X 0

0 0.232 0.115 3A03 0

0 0.145 0.041 BP BO ZTB45 BIOXBHS 0

0 0

0 3AOS B10 O

0 0279 0.033 B10 0

0 0.274 0.144 B10 0

0 0.108 0.065 3K04 Q033 BQMM BQSM BIOXBHS BP BQ BQMM BQSM BT BT-3B1I603 D007-3A0402 DW7-E336 D645 DB0415-3B0418 DB30415mE41S Q033

  • SWnrl'YARD SWTrTIHYARD.3 4.160 4.068 4.0 0.480 0.456

-7.0 0.480 0.454

-6.9 0.420 OA51

-6.0 0.460 0.451

.6.0 0.480 0.451 46.0 0.480 0.43S

-4.0 0.480 0.435 4.0 4.163 4.190

-1.6 4.160 4.190

.1.6 0.480 4A5S

-6.6 0.480 0.450

.5.9 0.480 0.450

-5.9 0.4S0 0.451

.6.0 230.000 219.5CO 0.0 230.000 219500 0.0

-Q0I09

-0.012 4.796 2.578

.4.796

-2.57 3.492 1.5m 13.797 7.930

-17.290

.9.503

-0.232

-0.115 0.276 0.147 0.250 0.035 0.00 0.000 40.710 40.223

.0.715

-04259 0.71S 0.259

-0.279 40.033

-0.274

-0.144

-0.123

-0.077 0.013 0.007 0.005 0.003 0.004 0.002

-0.005

-0.003

-0.004

.0.002

-0370

-0.204

-0.370

-0.204 0.370 0.204 40.456 0256 0.456 0.256

-0.456

-0.256

-0.00S 0.000

.0.111

-0.071 0.111 0.071

-0.111

-0.071

.0.011

-0.007 22.161 13.913

-22.161

.13.913 22.161 13.913 2B.5 85.0 748.6 82.1 748.6 E5.1 542.1 912 2252.2 86.7 2792.2 87.6 36.B 89.5 394.0 B8.2 355.3 99.2 103 100.0 935.9 95.4 I302 94.0 108.0 94.0 3553 99.3 394.0 88.5 190.9 85.6 16.9 B5.0 7.0 83.0 5.6 85.0 7.0 23.0 5.6 85.0 561.2 87.6 561.2 87.6 561.2 87.6 72.0 87.2 72.0 87.2 72.0 87.2 103 10.0 169.0 84.1 169.0 54.1 169.0 84.1 16.9 85.0 68.8 84.7 6S.8 84.7 68.8 84.7

-2.500 0

0 0.005 0

0 0.004 a

0 0370 0

0 0

0.003 BQ 0002 BQ 0.24 BT-3B31603 0 3B16 D3171 BT 0 3A04 D007-E336 0.256 D007-3A0402 0.0O0 ZTB45 D 33D4 0

0 0

0 0

0 0

0.456 0.008 0

0 22.161 0

0 13.913 0

0.111 0.0I 0

0 DB0415-E418 0.071 D30415-3B0418 0.007 BQ 0 SWITCHYARD-3 O SWICIIYARD 3XRI-X

&3XRI-Y

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130

.EAP Page 22. of __f CCN No.

rrojcct:

4AL-UoJU Kr-V.

Location:

SONGS 2 & 3 Concac:

Engineer W. P. Lennartz Filename E4C09Q.

31 KIUN u-ij5u 5.0.0N StudyCase 3Al4aa Page:

Date:

SN:

Revision:

Conlig.:

18 05-25-2005 SCALEDISON Base 090-3A14aa ECP05;0500255-34 ICCN C-130 UNrr3 TRAINA BlUs ID Zfl45 voltagc Genration Load kV kV An.

MW Mnr MW MWar 0.480 0.458

-6.6 0

0 0

0 B10 DD45 ID Load nFow XFMR MW Mar Amp

% Pr

% Tap

-0.008 D.DOO 10.3 100.0 0.00 0.0o0 103 100.0

  • Wnuicates a voltage regulated bus (voltage controlled or swing type aacmihim connected to Ii)

Jodicuatcs a bus wilt a load nisunatdi of ro I*b3 0.1 MVA

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 23 of 6L AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 lCCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer W. P. Lennartz Filename; E4C090 ETAP 5.0.ON Study Case: 3A14aa Page:

19 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Conlig.:

090-3Al4aa ECP 050500255 - 34 ICCN C -130 UNrr 3 RAIN A DivS Loadinix Summarv Report Directly Connected Load Total Bus Load Bus Conubat VA CmasiutZ Constuntl Genemic ID kW PWed Amp MW My=

MW Mar MW Wvar

.nv MWar MVA

%PF Amp Loading 2W002-BUS 2GC03-BUS 30002-BUS 3G}03-BUS 3Ao3 3AM4 3AO8 3B01 3BCXHIS 3B02 3BO2XHS 3B03 3303XHS 3B04 3B04X}1S 3B12 3B12XHS 3813 3B13XIIS 3B16 3B16X1HS 31B161tBP 3BA 3BB 313C 3BD 3BD18-TlMRS 3BDMM 3BDSM 3BE 3BEMM 3BESM 3B' 3HIP1o 3BH)P02 3BH0C3 4.160 0

0 0

0 4.160 0

0 0

0 4.160 a

0 0

0 4.163 0

0 0

0 4.160 3C00.0 10.000 5.S65 00 0 0 4.160 3000.0 2.596 1.294 0.129 0.0BO 4.160 1200.0 0.796 0.339 0

0 0.4B0 2000.0 0.131 0.078 0

0 4.160 0

0 0

0 0.480 1600.0 0.049 0.031 0

0 4.160 0

0 0

0 0.4S0 1600.0 0.206 0.120 0

0 4.160 0

0 0

0 0.480 2X00.0 0.261 0.172 0

0 4.160 0

0 0

0 0.4B0 1600.0 0.202 0.118 0.123 0.041 4.160 0

0 0

0 0.4S0 1600.0 0.151 0.079 0.075 0.001 4.160 0

0 0

0 0.480 2000.0 0.09 0.043 0.073 0.06 4.160 0

0 0

0 0.480 100.0 0.006 0.004 0.119 0.104 0.4S0 600.0 0.153 0.097 0.112 0.043 0.450 600.0 0.138 0.087 C.020 MS05 0.480 600.0 0.041 0.030 0.066 0.033 0AS0 600.0 0.130 0.088 0

a 0.480 0

0 0

0 0A60 0.005 0.0O3 0

0 0.480 0

0 0.003 0.002 0.4S0 6C0.0 0.001 0.001 0.075 0.03S 0.460 0.005 0.003 0

0 0.4S0 0

0 0.004 0.002 0.480 600.0 0.104 0.052 0.134 0.051 0.480 0

0 0.144 0

0.4B0 0

0 0.194 0

0.480 0

0 0.194 0

0 0

0 0

0 0 0

0 0

0 0

0 0

0 a

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 a

0 0

0 0

0 0

0 0

a 0

0 0 0

0 0

C a

a 0

0 0

C a

0 0

0 0

a 0

0 0

0 0

a 0

0 0

0 0

0 0

0 0

0 0

0 0.0 0.0 0

0 0

0.0 0.0 0

0 0

0.0 0.0 0

0 0

0.0 0.0 00 0 0 15.875 86.8 2252.2 75.1 0

0 5A33 81.1 74S.6 25.0 0

0 3.822 91.2 542.1 45.2 0

0 OA53 17.5 581.8 29.1 0

0 0.462 16.3 65.5 0

0 0.5S4 99.8 728.

45.5 0

0 0.592 99A S4.0 0

0 0.689 88.3 877.3 54.8 0

0 0.713 85.8 101.2 0

0 1337 S8.2 1698.0 84.9 0

0 lA21 84.4 195.9 0

0 0.854 B92 1097.0 68.6 0

0 0.S92 86.1 126.6 0

0 0.422 91.5 528.5 33.0 0

0 0.430 90.2 61.0 0

0 1.135 86.0 1467.8 73.4 0

0 1.194 82.7 169.4 0

0 0.165 75.6 217.7 27.2 0

0 030 88.4 386.9 64.5 0

0 0.182 25.5 231.2 39.7 0

0 0.124 26.3 157.1 26.2 0

0 0.171 82,8 226.9 37.8 0

0 0

0.0 0.0 0

0 0.006 83.0 73 a

0 0.004 85.0 5.5 0

0 0.113 97.9 150.1 25.0 0

a 0.006 83.0 7.0 0

0 0.004 85.0 5.7 0

0 0.260 91.7 336.8 56.1 0

0 0.144 I1D.0 181.0 0

0 0.194 I10.0 242.6 0

0 0.194 100.0 242.6

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page ZfIf of 6__

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 CCN No.

Projc:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contmct:

Engineer W. P. Len=ar Filename:

E4CW9O E: TAP 5.0.ON Page:.

20 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case: 3Al4an ECP 050500255 - 34 ICCN C -130 UNIT 3 TRAJN A Directly Connected Load Total Bus Load Buns Constant kVA Constunt Z COnSmnt I Generic ID kV Rated Amp MW MWar MW MWVr MW Mvar MW Mvr MVA

%PF Arp Looing 3BHP04 3BLY 3BMX 3BRA 3BRAMM 3BRASM 3BV 3BX 3BY 3BY39-HTRS 3BY40-llRHS 3BYM?6M 3BYSM 3D004-3A0409 30004-3P013 311V9377-N Wiut 3L707-3B3RA06 3PEXCCS 3Q020 3Q039 3Q074 3TC63 3XRl-X 3XRI-Y ASCI B10 BIOXBIIS no BP BQ BQMM BQSM BT BT-3131603 D007.3AO402 D007-E336 D645 0.4S0 0

0 0.184

. 0 0.480 600.0 0.036 0.023 0.015 0.004 0.480 600.0 0.035 0.C22 0.016 0.004 0.430 600.0 0

0 0

0 0.460 0.005 0.003 0

0 0.430 0

0 0.004 0.002 0.460 600.0 0.101 0.073 0.102 0.051 0.4W 600.0 0.107 0.070 0.199 0.069 0.480 600.0 0.139 0.082 0.054 0.043 0.480 0

0 0.007 0

0.4S0 0

0 0.003

.0 0.460 0.005 0.003 0

0 0.480 0

0 0.004 0.002 4.160 0

0 0

0 4.160 0.408 0.174 0

0 0.480 0

0 0.002 0.001 0.480 0.125 0.049 0.050 0.020 0.48D 0

0 0

0 4.160 1.770 0.907 0

0 0.480 0

0 0.003 0.002 0.480 0

0 0.015 0.009 0.480 0

0 0.004 0.002 0.430 0

0 0.019 0.012 4.160 0

0 0

0 4.16D 0

0 0

0 4.160 400.0 0.232 0.115 0

0 0.480 200O.0 0.063 0.040 0.082 0

4.160 0

0 0

0 0.480 600.0 0.021 0.014 0.258 0.01O 0.480 600.0 0.163 0.103 0.111 0.036 0.4S0 600.0 0.061 0.038 0.047 0.026 0.460 0.005 0.003 0

0 0AO 0

0 0.004 0.002 0.480 600.0 0.168 0.100 202 0.105 0.480 0

0 0

° 4.160 0

0 0

0 4.160 CA56 0.256 0

0 0.4S 0

0 0.008 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0

  • 0 0

0 0

0 0

0 a

0 0

0 a

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0.184 100.0 236.4 0

0 0

0.05S 88.6 75.2 12.5 0

0 0

0.058 392 72.4 12.1 a

0 0

0.016 84.9 20.6 3.4 0

0 0

0.006 83.0 7.0 0

0 0

0.004 85.0 5.7 0

0 0

0.238 85.5 303.8 51.5 0

0 0

0.336 91.0 441.7 73.6 0

0 0

0.266 85.1 3383 56A 0

0 0

0.007 100I 3.9 0

0 0

0.003 IC0.0 3.4 0

0 0

0.006 83.0 7.0 0

0 0

0.004 35.0 5.7 0

0 0

0.443 92.0 61.1 0

0 0

0.443 92.0 61.1 a

0 a

0.002 90.0 2.3 0

0 0

0.1BS 93.2 250.1 0

0 0

0.002 90.0 2.3 0

0 0

1.939 89.0 282.6 0

0 0

0.004 85.0 5.5 0

0 0

0.018 S5.0 22.7 0

0 0

0.D04 35.0 5.7 0

0 0

0.022 15.0 28.5 0

P 0

5.445 68.1 743.6 0

0 0

19.729 57.6 2792.2 0

0 0

0.259 B9.5 36.8 9.2 0

0 0

0.744 95.4 935.9 46.8 0

0 0

0.761 94.0 IS.0 0

0 0

0.281 99.3 355.3 59.2 0

0 0

0310 38.5 394.0 65.7 0

0 0

0.149 85.6 190.9 31.8 0

0 0

0.006 83.0 7.0 0

0 0

0.004 35.0 5.6 0

0 0

0.423 37.6 561.2 935 0

0 0

0.423 87.6 561.2 a

a 0

0.523 97.2 72.0 0

0 0

0.523 87.2 72.0 0

0 0

0.00 200.0 10.3

ECP 050500255 -34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 255 of G,4 CCN No.

Project:

E4C090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer:

W.P.Lernanz Filename.

E4CWDI ETAP 5.0.0N Study Catse 3A14aa Page:

21 I'ale:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

09D-3A14aa ECP050500255-34 ICCN C-130 UN]r3 TRAINA Directly Connected Load Total Bus Load Bus Constont LVA CwStant Z Constant I GenerPc ID kV Rated Arp MW Mnir MW MTV MW MvWr MW Mvvr MVA

%PF Amp Loading DB04154"B0418 0.480 0

0 0

0 0

0 0

0 0.132 84.1 169.0 DB3415-E418

.O80 0.111 0.071 0

0 0

a 0

0 0.132 B4.1 169.0 Q033 0.4AO 0

a 0.011 0.007 a

0 0

0 0.013 85.0 16.9 SWrrCHYARD 230.000 0

0 0

0 0

0 0

0 26.167 84.7 63.8 SWTrClIYARD-3 It0.000 0

0 0

0 0

0 0

0 26.167 14.7 68.8 ZTB45 0ABO 0

0 0

0 0

0 0

a O

.OOBJ00.0 I0.3

  • Indicatetoopezting lod of abes exceeds iM but cdticn1limit ( 5 of the Qm tinuous Ampere rating).

4 lndicatcs operatins load ofs t us exceeds the bus marginal grait ( % of the Continuous Amipcrt rating).

ECP 050500255-34 Rev. 0 Cal. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 Page Z C4 of W CCN No.

Projed:

E4C090 REV.3 ICCN C-130 lcaion:

SONGS 2 & 3 Corr.act:

Engineer:

W. P. Lemnnz Filea=se:

E4cM9M ETAP 5.0.0N Study Casc 3A14aa Page:

22

  • -Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa ECP 050500255 -34 ICCN C-130 UNIT 3 TRAIN A Branch lUadine Summary Report CKT I Brastch ID 3BOIX 3B02X 3B03X 3B04X 3B12X 3B13X 3B16X BIOX-B 3XR1 Transrormer Catbe & Reactor AnIr-eity Lmading Caybility Loadicg (input)

Loading (output)

(Anmp)

Amp (MVA)

MVA MVA Trasrnrwrcr 12500 0.462 30.8 0.453 30.2 Thmsrormer l.000 0.592 59.2 0.534 58.4 Transfoner 1.000 0.713 713 0.6S9 63.9 Transformer 13500 IA21 94.8 1.337 89,2 Tranfernifer 1.500 0.S92 59.5 0.854 57.0 Tmnsfortwr 3.000 0.430 43.0 0.422 42.2 Trarstormer 1.5I0 1.194 79.6 1.135 75.7 Trsformer 1.500 0.761 50.7 0.744 49.6 3W XFiRp 40.000 26.167 65.4 3WXrMRs 13.300 5.445 40.9 3W XFMR t 26.700 19.729 73.9

  • Indicates a branch with operating load exceeding the branch capabnlity.

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 3Z7 of G0 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

4C-O90 REV. 3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer W. P. Lenna1iz Flename; E4C090 ETAP 5.0.ON Page:

23 Date 05-25-2005 SN:

SCALEDISON Revision:

Base Conlig.:

090-3Al4aa Study Case: 3A14aa ECP 050500255 - 34 ICCN C -130 UNlT 3 TRAIN A Branch Losses Stnnmarv Report CKTIBranch ID Vd From-TofBus Flow To-From Bus Flow Losscs

% Bus Voltage

% Drop MW Mvar MW Uva-r lW kvar Frrm To hn Vm; 3XA03D4Pl 3XAD309Pl 3XA0310P3 3XA031 IU 3XA03 12PI 3XXR169PA-PDX9 3AA0402P1 3AA0409P1 3AA0417P]

3xOP169P]-P3 3XA09o0PI 3XAOS2PI 3XA0808PI 3XAO090P]

3XXR1691'7.Ps 3XBOI02PI 3BOIX 3XBO2OSPI 3X10206P1 3XB0210PIP2 3B02X 3XB0306P]

3XB0314PI 3D03X 3AD0403P?

3AB0407PI 3ABD414PI 3AB041.5P 3AB0417PI 3AD0418PI 3XB0402P]

3BWX 3XB 1202PI 3XB1203P1 3X3121 1P 0.388 0.136

-0.383

-0.186 0.0 C.a 972

97.

0.01 0.32 0.769 0.612 1.773

.13.773 0.456 OA0O 1.2DO 4.789 D.716 0.933 0.399 0.589

-3.487 0.266

-0.396 0.195 0.195 0.145

.0533 0.241 0.161

.0.608 0.014 0.147 0.104 0.227 0.129 0.112 0.186

-1.179 C.205 0.052 0.180 0.115

.0.232 0.453

.0.768 0.366

.0.612 0.909

-1.770 J7.s94 13.797 0o256

-CA56 0.174

.0.408 0.763

-1.199

.2.567 4.796 0.260

.0-715 0.671

.0.987 0.233

.0.399 0.062

.0.5s9

-13565 3.492 0.141

-0.265

.0.219 0.399 0.001

-0.194 0o01

-01.94 0.001

-0.144

.0.033 0.589 0.108

-0.238 0.095

.0.158

.0.323 0.612 0.009

-0.014 0.101

-0.142 0.056

.0.104 0.140

.0.226 0.078

.0.123 0.072

.0.111 0.002

.0.184

-0.631 1.199 0.126

.0.204 0.027

-0.052 0.073

.0.175

.0.115

.4A53

.0366

.0.907 7.930 4.256

-0.174

-0.763 2.57s

.0.259

.0.671

-0.233

.0.062 I.573

.0.140 0.233 0.000 0.000 0.000 0.062

.0.103

.0.091 0.366 40.00c

-0.096

.0.056

.0.14D

.0.077 40.071 0.000 0.763

.0.123

.0.027

.0.063 0.0 0.2 0.1 2.3 23.7 0.0 0.2 0.4 7.4 0.3 0.3 0.1 0.3 5.6 0.7 2.1 0.8 0.8 0.9 5.5 3.0 3.4 3.9 0.0 5.4 0.1 0.3 0.9 1.1 2.1 19.9 IA 0.2 52 0.0 97.S 97.8 0.02 0.1 97.3 97.3 0.02 0.0 97.8 97.S 0.01 2.0 97.8 97.7 0.15 35.2 97.8 98.1 0.23 0.0 100.7 100.7 0.01 0.2 100.7 100.7 0.05 0.3 100.7 100.7 0.04 10.9 200.7 100.9 0.22 0.2 97.8 97.8 0.05 0.2 97.8 97.8 0.03 0.1 97.8 97.8 0.04 0.2

97.

97.8 0.05 8.3 97.8 98.1 0.22 1.1 93.6 933 0.35 14.0 93.6 97.3 4.19 0.6 96.5 96.1 0.40 0.6 96.5.

96.1 0.40 0.4 96.5 95.9 0.58 29.0 96.5 97.8 1.29 4.7 94.5 92.8 1.65 42 94.5 91.9 2.53 42.9 94.5 97.S 3.36 0.0 94.7 94.7 0.01 5.5 94.7 90.7 4.04 0.1 94.7 94.6 0.11 0.5 94.7 94.6 0.18 0.9 94.7 93.9 079 0.6 94.7 93.8 0.S9 2.1 94.7 93.7 1.06 132,3 94.7 100.7 5.95 2.3 93.7 92.7 0.94 03 93.7 93.1 0.54 53 93.7 90.4 3.29

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 23 of Qf AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 ETAP Page:

24 Location:

SONGS 2 & 3 S.0.ON Dale:

05-25-2005 Contract:

SN:

SCALEDISON Engineer W. P. Lennartz StudyCase: 3A14aa Revision:

Base Filenane:

E4C Conig.:

090-3A14aa ECP050500255-34 ICCN C-130 UNIr3 TiAINA CKTlBranch From-To Bus Flow To-From Bus Flow Lnsss

% Bus Voltage 5 Dp ID MW Mvar MW Mvar kW kywr Frun TO In Vma 3B12X 0762

-0.386 0.76S 0.453 6.1 67A 93.7 97.8 4.14 3XB1303P1 0.052 0.026

-0.051

.0.026 0.1 0.1 96.0 95.1 0.26 3XB1305P1 0.108 0.064 40107

.0.063 1.0 13 96.0 94.9 1.16 3B13X

-0.3B6

.0.170 0383 D.1S6 14 15.6 96.0 97.8 1.7S 3XB1602P1 0309 0.145 40306

.0.139 3.7 5.7 93.0 91.5 156 3XB1603P2.P2 0.379 0.212

-0.370

.0.204 8.1 S2 93.0 9Q.7 2.37 3)C31611P1 0.127 0.110

-0.125

-0.108 2.4 2.5 93.0 91.1 1.91 3Bl6X

.0.977

-0.579 0.9S7 0.671 10.5 92.0 93.0 97.3 4.77 3ABRA06rI 0.002 0.001

.0.002

-0.001 0.0 0.0 94.7 94.6 0.12 OXBIOC2PI 0.276 0.147 0274

-0.144 23 3.6 95.6 94.5 1.13 OXB1014P1 020 0.035

-0.279

.0.033 1.4 2.2 95.6 95.1 0.55 OX1IISPI 0.008 0.000

-0008 0.000 0.0 0.0 95.6 95A 0.11 BOX-B

-0.71D

.223 0.715 0.259 5.4 36.6 95.6 97.8 217 OXB1015P2 40.008 0.000 0.008 0.0D 0.0 0.0 95.4 95.4 0.04 3XR1 22.161 13.913

-4.796

-2.578 75.5 2832.6 95.4 100.9 0.E8 217290

.9.503 95.4 93.1 1.87 216.7 2372.9

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page -2+/-Z9 of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Consntc Engineer.

W. P. Lennanrtz Flename:

E4CO90 rTAP 5.0.ON Page:

25 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case: 3A14aa ECP 050500255-34 ICCN C-130 UNrr3 TRAINA

quipment Cable and Heater Losses Sunmnary Report Connected Loetd ID Cablellleater Type

% Voltoge Losses Terminalan

% Vd

%V1 kW kVtr B3u5 Bus kV Lod LV Opersting SlteIng 3.9 4.5 97.83 97.61 97.61 0.22 96.S7 ID Ubrary 3PI 17 3P 15 3P051 3P050 3P120 3P307 3P012 3PC24 3P017 3P141 3P015 3E202 3POIS 3POS5 C443 B336 3E397 3P128 3E394 3P075 3P290 3AOCJ 3A074 3A071 3E399 3E401 3P190 3P127 3P135 3L046 3A274 3A275 3ESSO 3E546 Ino. Motor 3XA0305PI hd. Motor 3XA0306PI Ind. Motor 3XA0307PI Ind. Motor 3XA030BPI Ind. Motor 3XA0313PI Wd. Motor 3AA0411PI Ind. Motor 3AA043PI Ind. Motor 3AA0405PI Ind. Motor 3AA040BPI Ind.Motcr 3AA0404PI Ind. Motor 3AAC407PI Ind. Motor 3XAOS03PI bnd. Motor 3WAD004P1 Ind. Motor 3XAW312P2 Wnd.

Motor OXACIOIP2 Ind. Motor OAAD007PI Ind. Motor 3X30106PI-P3 ILn Motor 3XB0110PI hid. Motor 3XB0209PI-P3 Ind. Motor 3XD03MP1 Ind. Motor 3XB0309PI Ind. Motor 3XB032tOPl.P2 Ind. Motor 3AB0419Pl-P3 Ind. Motor 3ABC409PI-P3 Ind. Motor 3ABC410PI-P3 Ld. Motor 3AB0411PI-P3 lad. Motor 3AB0413PI Ind. Motor 3XB1206PI-P3 Wed.

Motor 3XB1306P1 Ind. Motor 3XB31606P1 P2 Ind. Motor 3ABD12P1 Ind.Motor.

3ABD13PI Ind. Motor 3ABD21PI Ind. Motor 3ABD22PI SD.MCUN3 S.OMCUN3 S.OMCUN3 SD.MCUN3 6.0MCUN3 B.OMCUN3 S.OMCUN3 S.OMCUN3 S.0MCUN3 E.OMCUN3 8.OMCUN3 60MCUN3 B.OMCUN3 5.0MCUS1 S.OMCUNI S.OMCUN3 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI Q.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 Q6MCUN3 3.5 4.1 97.83 97.63

.0 1.A 97.83 97.78 0.7 1.0 97.83 97.79 3.1 2.0 97.3 97.52 0.2 0.1 ID0.73 I00.66 0.1 0.1 200.73 100.68 0.3 0.2 100.73 100.67 02 0.1 100.73 100.67 1.0 0.6 t00.73 100.57 02 0.1 100.73 100.67 0.4 0.2 97.85 97.80 0.0 0.0 100.63 I1.6S 0.4 0.4 97.69 97.66 0.0 0.0 97.81 97.80 0.2 0.1 I2W.72 100.68 0.5 0.2 93.62 92.84 1.5 0.7 93.62 92.03 0.6 0.2 96.51 95.41 0.7 0.3 94.46 93.60 a05 0.2 94.46 93.67 1.3 0.5 94.46 93.12 0.9 0.4 94.74 93.03 0.8 03 94.74 93.21 0.6 03 94.74 93.78 0.6 0.3 94.74 93.77 0.6 0.3 94.74 93.78 5.5 6.8 93.67 90.41 6.7 4.6 96.04 91.4S 0.6 0.5 93.05 9232 0.1 0.0 90.70 9052 0.2 0.0 90.70 9032 0.3 0.1 90.70 90.0S 0.2 0.0 90.70 90.19 97.63 97.78 97-79 97.52 100.66 100.68 100.67 100.67 100.57 100.67 97.80 100.68 97.66 97.S0 300.68 96.8E 96.03 99.56 97.67 97.75 97.17 97.08 97.26 97.85 97.85 97.85 94.34 95.46 96.33 94A5 94.25 94.00 94.11 0.20 96.96 0.05 97A4 0.04 97.56 031 96.77 0.06 100.45 0.04 100.48 0.06 100.43 0.06 I0.40 0.1 100.00 0.05 1O0A8 0.05 97.63 0.01 100.65 0.03 9754 0.01 97.74 0.04 100.55 0.78 90.68 1.59 87.51 1.10 92.13 0.87 91.75 0.79 92.08 1.35 90.15 1.71 87.23 153 87.99 0.96 S8.47 0.97 U.45 0.96 90.11 3.26 7S.23 4.56 79AS 0.73 87.01 0.1 90.20 0.37 89.65 0.62 89.03 0.51 8932

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 23° of (64 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer W. P. Lennartz Etlenate:

E4090 ETAP 5A.ON Page:

26 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case 3A14aa ECP 050500255-34 ICCN C-130 UNTI 3 TRAINA Equdpment Cable and Heater Losses Sumnmrv Report Connected Load ID Type 3P093 Ind. Mtewr CabIck~mlaer

% Voltagc Losses Terirnnl on

% W

% W kW kyor DUs BuskV iood CkV Operating S=ting 0.0 0.0 90.70 90.58 94.52 0.12 90.48 ID Ubrary 3A3D23PI 3P096 3`99713P1014 3P996W3P1015 311V4731 3A373 3A370 3PW108 3E439 3E3440 3P174 3P175 3E437 3E438 3E427 3E417 3E1517 3i 453 3E.454 3P009 3A394 3E441 3E370 P159 P162 2A173 2E3255 A207 3A173 3EZ55 P445 A053 A056 W310 Ird. Motor 3ABD24PI Ind. Motor 3A13DIIPI Ind. Motor 3ABDIOPI lhd. Motor 3ABE36PI Ind. Motor 3ABY08PI nd. Motor 3ABY07Pt Wd. Motor 3SAYIOPI tnd. Motor 3ABYIIPI

}nd. Motor 3ABY12PI ind. Motor 3ABY14PI btd. Motor 3ABY15PI Ind. Motor 3A1lY20P1 lId. Motor 3AIY21PI led. Motor 3ABY22PI Ind. Matcr 3ABY24P1 ird. Motor 3ABY25PI lnd. Motor 3ADY30PI Ind. Motor 3ABY31PI Lid. Motor 3ABY34PI lnd. Motor 3ABY36PI tnd. Motor 3ABY37PI ind. Motor 3A3Y38PI ind. Motor OXB1006PI Ind. Motor OABQ24PI Ind. Motor 0ABQ07PI Ld. Motor OABQ08PI Ind. Motor CABQ09P2 IdL Motor OABQ14PI ind. Motor OABQISPI ind. Mator OADQ20PI led. Motor OABQ22PI ind. Motor OABQ23PI ind. Motor OA1IQ25PI 046MCUN3 0.6MCUN3 0.6MCUiS3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0Q6MCUN3 0.6MCiDN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 Q.tMCUN3 O.GMCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6McuN3 Q.6MCUN3 0,6MCUN3 0.6MCUN3 0.6MCUN3 0.0 0.0 90.70 90.58 94.52 0.0 0.0 90.70 90.59 94M3 0.0 0.0 90.70 90.50 94.44 0.0 0.0 94.63 94.00 98.09 0.1 0.0 94.56 93.01 97.05 0.1 0.0 94.56 93.37 97.42 0.1 0.0 94.56 93.12 97.17 0.0 0.0 94.56 94.50 9361 0.0 0.0 94.56 94.50 98.61 0.5 0.0 94.56 92.84 96.87 05 0.0 94.56 92.84 96.87 0.0 0.0 94.56 94.46 9857 0.0 0.0 94.56 94.46 9357 0.0 0.0 94.56 94.25 9835 0.1 0.0 94.56 93.20 97.26 0.0 0.0 94.56 94.28 9838 0.0 0.0 94.56 94.33 98.43 0.0 0.0 94.56 94.35 98.45 0.3 0.0 94.56 9353 97.60 0.1 0.0 9456 92.85 96.89 0.0 0.0 94.56 94.27 93.37 1.0 0.2 94.56 92.74 96.77 1.4 0.5 95.63 93.76 97.14 0.4 0.1 93.95 92.72 96.75 0.0 0.0 93.95 93.10 97.15 0.1 0.0 93.95 93.09 97.14 0.4 0.0 93.95 90.60 94.54 0.0 0.0 93.95 93.07 97.11 0.3 0.0 93.95 92.57 96.60 0.0 0.0 93.95 93.15 97.20 0.1 0O.

93.95 92.74 96.77 0.0 0.0 93.95 93.53 97.60 0.0 0.0 93.95 92.92 96.96 0.12 90.48 0.11 90.51 0.20 90.36 0.64 93A1 1.55 89.71 1.20 90.97 1.44 91.92 0.06 93.94 0.06 93.94 1.73 91.27 1.73 91.27 0.10 93.87 0.10 93.87 031 93.51 1.36 91.12 0.29 9334 0.24 93.57 0.21 93.75 1.03 91.71 1.71 8S.91 0.29 93.70 1.83 89.62 3.S7 89.55 1.23 90.32 0.S4 90.91 0.85 91.67 3.34 86.93 0.88 90.81 1.37 90.05 0.80 92.49 1.21 89.86 0.41 91.80 1.02 92.11

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 31.L of 6'0II AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 &l 3 Contract:

Engineer:

W. P. LnaLtz Filenare:

E4CO90 ETAP 5.0.ON Page:

27 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case 3A14aa ECP 050500255-34 ICCN C -130 UNIT 3 TRAIN A Eartniment Cable and Heater Losses Summamy Report Connected Load ID Twe Cablelflenter ID U braiy OABD41SPI 0.6MCUNI

% Voltage Losses Terminal on

%Vd

% VJI kW kvar Bus Bus LV Load kV Opeating Siarting 3.1 1.7 93.85 91.35 95.33 2.50 81.87 E41B 2L27D 3BD01 3B003 3B005 3E122-HI 3EI24-NIl 3E126-HI 3E12t-HI [XI 3E370H 3E399H 3E401H 3E464 3E652 3L266 3U270 3LAIICIX 3rpo11 3POISH 3P017H 3POIStA 3P11211 3P14111 3P17411 3P17511 3Pl90H 3PJ91HA 3P30711 3PI01811 3RU7l041 3RU7822-I 37011 370141X1 3T1 1O/3Q071Ptl 2nd. Motor Si. Load OABQ05PJ SL. Load 3ABY03PI Si. Load 3ABEO4PI St. Lod 3XB1609P2 St. Load 3XBO210P3-PS SL Load X30BM2O6-P4 St. Load 3XBC201P2.P3,PE SL. Load 3XB0402Pl.P3.P4 SL Load 3ABY39P6 St. Load 3ABY40P6.P7.P8 St. Ld 3ABY40P9,PAPB SL Lond 3ABE03PIP2 St. Load 3ABE49PI.P2 St. Load 3ABE4V1 Si. Load OABQ06PI St. L=d 3XBY23P1 Si. load 3ABY40Pi SL Load 3ABY39P1 SL. Load 3ABY39P2 St. Load 3ABY39P3 SL Load 3ABY33P4 St. Lod 3ABY39P8 SL Load 3ABY40P2 St. Load 3ABY40P3 SL Load 3ABY40P4 SL load 3ABY40PS St.Load 3ABY39P5 Si. Load 3ABY39P9 St. Lad 3ABE41PI St. Load 3ABE02PI SL Load 3XB1210PJ SL Load 3XA0412PI S. Load 3XBY33P2.P3 0.6MCUN3 O.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 O.61MCN3 O.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 O.6MCUNJ S.OMCUN3 0.6MCUNI 0.1 0.0 93.95 0.1 0.0 94.56 0.1 0.0 94.63 O.A 0.5 93.05 0.6 0.1 95.94 0.6 0.1 96.11 0.6 0.1 96.31 0.6 0.1 93.68 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.3 0.0 94.63 0.1 0.0 94.63 02 0.0 94.63 02 0.0 93.95 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.6 0.0 0.0 94.56 0.0 0.0 94.56 0,0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.56 0.0 0.0 94.63 0.0 0.0 94.63 J.)

1.2 93.67 0.0 0.0 100.73 0.9 0.2 94.56 92.27 9427 94.35 9119 94.73 94.87 94.90 92.3S 94.32 943S 94.41 93.57 93.12 93A8 9130 94A44 93.37 9338 92.82 93.28 94.25 93.74 94.48 94.50 94.4S 9450 94.26 94.48 94.00 9325.

92.64 92.27 9427 94.35 92.19 94.73 94.87 94.90 923S 94.32 943S 94.41 93.57 93.12 93.48 91.30 94A4 93.37 93.38 92.82 93.28 94.25 93.74 94.4S 94.50 94.48 94.50 94.26 94.4S 94.00 93.25 92.64 1.68 0.00 0.29 0.00 0.22 0.00 0.5 0.00 1.21 0.00 1.24 0.00 120 0.00 130 0.00 0.25 0.00 0.19 0.00 0.15 0.00 1.07 0.00 1.51 0.00 1.16 0.00 2.64 0.00 0.12 0.00 1.19 0.00 1.l8 0.00 1.74 0.00 1.2S 0.OO 0.31 0.00 0.S2 0.OO 0.0 0.00 0.06 0.00 0.08 0.00 0.07 0.QO 030 0.0O 0.0 0.00 0.64 0.03 1.32 0.00 1.04 0.00 0.03 0.00 3.74 0.00 100.70 100.70 90.82 90.82

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 3Z of CCN No.

Project.

E4C-090 REV.3 ICCN C-130 Location SONGS 2 & 3 Contract:

Engineer W. P. Lennanz Filiamme E4C090 ETAP 5.0.ON Study Case: 3A14aa Page:

28 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Confi;.:

090-3A14aa ECP 050500M5 - 34 ICCN C-130 UNIT3 TRAIN A Eardtinment Cable and Heater Losses Sumnmrv Report Connected TA ID

,ad Cable/Hleater E297

£643 E645 L211-1 L21 1-4 L437LX1 LP35A(X)

N002 Type SLLmad OABQ04Pl.P2 SLL.ad

=x132011P1 SL Load CXB1015P3 St. ld OABQ13PI St. Load OABQ26PI SL Load OXBQ11PI SL Load 3XBY19P1 SL Lad 3XB1307P1 ID 0.6 uUy 0.6MCUN3 0.6MCUNI Q.6MCUN3 0.6MCUN3 0.6MCUN3 Q6MCUN3 Q6MCUN3 0.6MCUH1

% Voltage Losscs Thinnal en

%Vd S Vst kW kyar Bus Bus kV Load kV Operatn:

Starting 0.1 0.0 93.95 91.99 91.99 1.96 0.00 0.2 0.3 95.63 9533 9538 0.25 0.00 0.0 0.0 95.41 9535 9536 0.05 0.00 0.1 0.0 93.95 93.64 93.64 031 0.00 0.1 0.0 93-95 93.54 9354 0.41 0.00 0.1 0.0 93.95 92.94 9Z.94 1.01 0.00 0.1 C.0 94.56 93.65 93.65 0.91 0.00 2.9 1.1 96.04 9235 92.35 3.69 0.00

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130

'roject:

E4C-090 REV. 3 ICCN C-130 ETA}

_5.0.0N I

Page 33 of 6.

CCN No._

Page:

29 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Location:

zUNUw A ec Cortract:

Engineer W. P. Lennanz Filenamm:

E4C090 Smtdy Case 3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA Alert Sunmnary Report

% Alert Settings Critical Loading Bus Cable Reactor Line Transformer Panel Protective Device Geneator Bus Voltatee OverVoltage UnderVoltage Generator Excitalon OverExcited (Q Max.)

UnderExcited (Q Mi.)

0.0 0.0 0.0 100.0 0.0 100.0 0.0 0.0 0.0 0.0 0.0 95.0 0.0 95.0 0.0 0.0 130.0 70.0 1000.0

-100.0 0.0 0.0 ID 20002 2GY03 30002 30003 Device Type Geetwr Geneialto Gentrator Genetor Critical Report lIstin 11nlt CakoLled

%eMag.

Condition 0.000 MW 0.00 UnderPower 0eo0o MW 0.000 UnderPower 0.000 MW 0.000 UndlerPower 0.000 MW 0.000 UnderPower

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION lCCN C - 130 Project:

E4C-090 REV.3 ICCN C-130 EAP Location:

SONGS 2&3 5.0.ON Contract:

Engineer W. P. Lenrxu Study Case: 3AI4aa Fileame:

E4C090 Page sqf of 64L CCN No._

Page:

30 Date:

05-25-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Ai4aa ECP 050500255-34 ICCN C -130 UNIT 3 TRAIN A

SUMMARY

OF TOTAL GENERATION, LOADING & DEMAND Source (Swing Buses):

Source (Non-Swintg Buses):

Totat Denand:

Total Motor Load:

Total Static Load.

Apparent Losses:

MV 22.161 0.000 22.161 19.072 2.972 0.217 Myar 13.913 0.000 13.913 10.655 0.885 2.373 MVA 26.167 0.000 26.167 21.847

% PF 94.69 Lagging 100.00 Lagging 94.69 Lagging 87.30 Lnggir.g System Mismattdu 0.000 0.000 NurnberotIterations: I

ECP 050500255 -34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

E4C-090 REV. 3 ICCN C -130 FrAP Location:

SONGS 2 & 3 5.0.0N Contracl:

Engincere W.P. Lewanz StudyCase. 3A14aa Filename:

E4CO09 Page 3 of CCN No.

Page:

1 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa ECP050500255-34 ICCN C-130 UNrr3 TRAINA Electrical Transient Analyzer Propram Load Flow Analysis Loading Category (1):

Generation Category (1):

Load Diversity Factor.

Design-BHP Design None Swinm V-Contrcl Load 5

0 75 Total go Number of Buses:

Number of Branches:

Method of Solution:

maximun No. ofIteration:

Precision of Solulion:

Systesn Rquency 601 Unit System:

Eni Project Fler.me:

E44 Output Filenaree C:A XFMR2 XFMR3 Reactor linelCable Imnedanee Tie PD 8

1 0

41 0

24 Total 74 Newton-Raphson Method I0 0.0010M0 Hz Oish

!wplfiles\\ErAPDATA\\08-0S8-09-O\\A14aasfr

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 "roject:

E4C-090 REV. 3 ICCN C-130 ETAP

.Location:

SONGS 2 & 3 5.0.ON Page 3 of (tf CCN No.

I Contract:

Engineer.

W. P. Lennartz Filenw=e E4C090 Page:

Date:

SN:

Revision:

Config.:

2 05-24-2005 SCALEDISON Base 090-3Al4aa StudyCase: 3A14aa ECP050500255 -34 ICCN C-130 UNIT3 TRAIN A Adiustments Tolerance Transformer Impedance:

Reactr Impedance:

Overload Heater Resistance:

Transmission Line Length:

Cable Length Apply Individual Adjustments

/Global Percent Yes ndividual Yes Individual No No No Apply Individual Adjuments

/Global Degree C Yes Individual Yes Indivldual Temperrture Correction Trm msson Line Resistance:

Cable Resistance:

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 0S7 of L.

CCN No.

ProjeCt:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contrat:

Engine-e.

W. P. Lenr.aMZ Filenamr E4C090 ETAP 5.0.ON Page 3

Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case: 3A14aa ECP050500255-34 ICCN C-130 UNrr3 TRAINA BuS TWPUt DO ta Load BUS JD 2G002-BUS 2G003-BUS 3A03 3AC4 3A0O 3BO I 3BO1 XHS 3B02lII 3B02XHS 3B03 3BO3XHS 3B04 3B04XHS 3B12 3B12XHS 3B13 3013X11S 3B13XH 3Bt60S 3B1611BP 3BA 3DB 3DC 33D 3BDIS-IrrTRS 3DDMM 3BDSM 3BE 3B£MM 3BESM 3BF 3BIIPOI 3B1H02 3BHPS3 Initial Voltage Consiant WA kV Sb-sys

% Mag.

Amg.

MW Mvr 4.160 2

105.3 0.0 Constant Z ConsatDI I Genetic MW MWar MW Mr MW MWar 0.127 0.079 4.160 3

4.160 1

4.160 3

4.160 1

0.4B0 1

4.160 1

D.4S0 I

4.160 1

0.460 1

4.160 1

0.480 1

4.160 1

.ASO 1

4.160 1

0.4B0 1

4.160 1

0.480 1

4.160 1

0.480 I

0.460 1

0.480 1

0.480 1

0.483 1

0.480 0.460 1

0.4E0 1

0.4t0 1

0.460 1

0.4B0 1

0.460 I

0.480 1

0.480 I

0.4t0 1

1053 0.0 96.5

.4.1 99.5

-1.6 96.6

.4.1 92.4

-5.5 96.5 4.1 95.2

.6.9 96.5

-4.1 93.1

-7.1 96.5

-4.1 93.4 6.0 99.4

-1.6 92A

.7.9 96.5

.4.1 94.7

-6.0 95.5

-4.1 91.B

-7.7 96.5

.4.1 89.9

-7.S 92.0

-5.7 90.6

-7.7 93.6

-6.2 89.3

-6.5 S9.3

-6.5 93.2

.6.5 89.3

-65 933 46.0 97A 46.0 93.3

.6.0 91.5

-7.7 94.7

-7.1 94.8

-7.1 94.6

-7.1 10.000 5.865 2.596 1.294 0.796 0.339 0.131 0.078 0.049 0.031 0.206 0.120 0.261 0.172 0.202 0.118 0.152 0.079 0.09 0.043 0.006 0.004 0.153 0.097 0.136 0.087 0.041 0.030 0.130 0.0S 0.141 0.047 0.0C2 0.001 0.084 0.07 0.143 O.IZ5 0.129 0.049 0.024 0006 0.073 0.036 0.005 0.003 0.00Q 0.001 0.005 0.003 0.104 0.052 0.004

.003 0.04 0.042 0.004 0.003 0.156 0.059 0.157 0.000 0.210 0.000 0.210 0.000

ECP 050500255 - 34 Rev. 0 Cale. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer W. P. Lennnnz Filename:

E4C090 ETAP 5..ON Page

  • 3 c of _4_

CCN No.

Page:

4 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

09D-3A]4aa Study Cast: 3A14aa ECP 050500255 - 34 1CCN C -130 U

3 TRAIN A Load Bus ID 3B11104 3BLX 3BMIX 313PLA 3ORAMM 3BRASM 3BV 3BX 3BY 3BY39-HTRS 3BY41?TRS 3BYMM 3BYSM 3D004-3AD409 3D004-3P038 3GO02-BUS 3G003-BUS 3HV937-N 3L1 II 3L707-3BRA06 3PEXCCS 30020 3Q039 3Q074 3T063 3XRI.X 3XRI.Y ASCI B10 BIOXBHS DO BP BQ BQMM DQSM BT InItd Voltnge Constant WA Conrstan Z Consrtan I Geneti kV Sub-sys

% Mag.

Ang.

MW MWar MW M Yar MW MYWr MW Mvzr 0ASO 1

92.4

-6.7 0.210 0.000 0.4S0 1

91.S

-. 0 0.036 0.023 0.01 0.005 0.480 1

94,5 46.0 0.035 0.022 0.01 0.005 ABO0 1

93.4

.6.0 OA60 1

97.5

-6.0 0.005 0.003 0.4W0 I

93.4

-6.0 0.004 0.003 0.480 91.4

-8.1 0.101 0o73 0.119 0.059 0.480 1

902 4.3 0.107 0.070 0.23S 0.083 0.480 1

933

.6.1 0.139 0.082 0.061 0.048 0.480 1

933 46.1 0.008 0.000 0.4S0 1

933

-6.1 0J003 0.000 0A60 1

973

.6.1 0.005 0.003 0.4B0 1

93.3

.6.1 0.004 0.003 4.160 1

99A

-1.6 4.160 1

99A

.1.6 0.408 0.174 4.160 5

1053 0.0 4.160 4

1053 0.0 0.48O

  • 1 933

-6.0 0.002 0.001 OA80 1

89.0 4.8 0.125 0.049 0.062 0.024 0.4S0 1

933

.6.0 4.160 1

95A

.4.1 1.770 0.907 0.4W0 1

893 46.5 0.004 0.003 0.480 1

93.3

.6.1 Q0.17 0.011 0.40S 1

93.4 4.0 0.004 0.003 0.480 1

93.3

.6.0 0.021 0.013 4.160 1

§9.7

-1.6 4.160 1

96.8

.4.0 4.160 1

96.5

-4.1 0.232 0.115 0.4S0 1

943

.6,7 0.063 0.040 0.090 0.000 4.160 1

96.5

-4.1 0.4S0 1

93.8

-7.1 0.021 0.014 0.286 0.020 0.4BD 1

93.2

-7.0 0.163 0.108 0.125 0.040 0.480 1

92.6

.6.2 0.D61 0.038 0,054 0.030 0.460 1

96.7

.6.2 0.005 0.003 0.480 1

92.6

-6.2 0.004 0.003 0.4S0 1

89A.

4.1 0.168 0.103 0.246 0.127

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Prject:

E4C-090 REV.3 ICCN C-130 ETAP Location:

SONGS 2 & 3 S.AON I

Page 2

of k CCN No.

Page:

5 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config4 090-M3Al4aa Contract:

Engineer.

W. P. Lennartz Filenarme:

E4C090 Study Case: 3A14aa ECP050500255-34 lCCN C-130 UNIT13 TRAINA Leand Bos ID BT-3BJ603 DC07-3Ao402 D007-E336 D645 D110415-3B0418 DBO415-E418 Q033 SWTrCHYARD SWl0c11YAP.D-3 ZTB45 kV Sub-sys 0.480 1

4.160 1

4.160 1

OASO I

OAS0 I

.O48 I

0.480 1

230.000 1

230.00 1

0.460 1

Initial Voltage 9, Mag.

Aeg.

89.4 4.1 99.5

-1.6 99.5

-1.6 94.1 45.7 92.5

-6.0 925

-6.0 92.6

-6.2 943 0.0 943 0.0 94.2

-67 Constant IVA MW Mvar Consbtnl Z Cxistuit I Genetic MW Mvar MW MWar MW Wvar 0.456 0.256 0.009 0.000 0.111 0.071 0.013 0.008 Toma Nuiber of Bust 80 19.073 10.656 3.245 L.O1S 0.000 0.000 O.OW 0.0O 2G002-BUS 2G003.BUS 3Gom-BUS 3G003-BUS SWvrrCHYARD Generation Bus kV Type Sub-sys 4.160 Swing 2

4.160 Swlng 3

4.160 Swing 5

4.160 Swing 4

230.000 Swing 1

Voltage Generation MyarIln-lts

% Mag.

Angle MW MWar

% PF Max Mn 1053 0.0 1053 0.0 1053 0.0 1053 0.0 943 0.0 0.000 o0oo

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page AO of 6Cff..

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV. 3 ICCN C -130 Locatin:

SONGS 2 & 3 Contract:

Engineer.

W.P.Lennartz Filename:

E4CM9M ETAP 5.0.ON Page:

6 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3AI4aa Study Cas 3A14aa ECP050500755-34 lCCN C-130 UNIT3 TRAINA m

0 0 7- -

Linc/Cable Input Data Ohms or SiemensfiODO ft per Conductor (Cable) or per Phase (lne)

LUnlth Linc/Cable ID DXB31002P1 OXD1014PI 0O31015PI OXB1015P2 3AA04A0PI 3AA0409P1 3AA0417P3 3AB0403PI 3AB0407P1 3AB0414P1 3ABO415PI 3ABO417P7 3AB041SP1 3ABRA06P1 3XA0304P]

3XA0309P1 3XA0310PI 3XA031lPl 3XA03 12PI 3XA0O01Pl 3XAOS02PI 3XA8OOSPI 3XAOS09P1 3XD00102P1 3XBO2051P 3XB0206PI 3XD0210Pl.P2 3XB0306P1 3XB0314P1 3XB0402PI 3XB1202P1 3X)31203P1 3XB1211PI 3X13B303P1 Ubrary 0.6McuNI 0.6MCUN1 0.6MCUNI C.6MWNI SOMCUN3 B.OMCIUN3 LOMCUN3 0.6MCUN1 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUN3 S.0MCUN3 S.CMCUN3 S.OMCUN3 LOMCUN3 B.OMCUN3 8.OMCUN3 S.OMCUN3 S OMCUN3 B.OMCUN3 0.6McWNI C.6MCUNI 0.6MCltNl 0.6MCUNI 0.6MCUNI 0.6McWNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI Size 750 750 110 6

250 250 250 350 350 350 750 350 3/0 10 250 250 250 250 350 250 250 250 250 750 410 40 2/0 750 500 350 750 500 350 5CO Adj. (ft)

%Tol.

t.'Pbase T(C)

R X

Y 175.0 0.0 1

75 0.02B000 0.043800 131.0 0.0 378.0 0.0 20.0 0.0 48.0 0.0 273.0 0.0 70.0 0.0 31.0 0.0 765.0 0.0 31.0 0.0 31.0 0.0 11.0 0.0 148.0 0.0 2.0 0.0 66.0 0.0 224.0 0D0 60.0 0.0 40.0 0.0 240.0 0.0 170.0 0.0 60.0 0.0 203.0 0.0 232.0 0.0 56.0 0.0 66.0 0.0 66.0 0.0 S3.0 0.0 314.0 0.0 549.0 0.0 268.0 0.0 l81.0 0.0 377.0 0.0 605.0 0.0 189.0 0.0 1

75 0.028000 0.043S00 1

75 0.131000 0.049500 1

75 0.49000 0.059800 1

75 0.054700 0.035600 1

75 0.054700 0.03560D 1

75 0.054700 0.035600 1

75 0.046100 0.046900 1

75 0.046100 0.046900 1

75 0.046100 0.046900 1

75 0.028000 0.043800 1

75 0.046100 0.046900 1

75 0.086C00 0.048600 1

75 1.240000 0.044BOO 1

75 0.054700 0.035600 1

75 0.054700 0.035600 1

75 0.054700 0.035600 1

75 0.054700 0.03560D 1

75 0.040000 0.034800 1

75 0.054700 0.035600 1

75 0.054700 0.035600 1

75 0.054700 0.035600 1

75 0.054700 0.035600 1

75 0.028000 0.043800 1

75 0.070000 0.048200 1

75 0.070C0O 0.048200 1

75 0.10600D 0.049000 1

75 0.028000 0.043800 1

75 0.035950 0.045000 1

75 0.0461CO O.C46900 1

75 0.028000 0.043800 1

75 0.035900 0.04500o 1

75 0.046100 0.046900 1

75 0.035900 0.045000

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 EI"AP Page 4 '

of+/-¶ CCN No.

Project:

E4C4)90 REV. 3 ICCN C - 13U Location.

SONGS 2 & 3 Commrat:

Engineer.

W. P. L=nnaz Filene:

MMwO 5.0.ON Study Case 3Al4aa Page:

Date:

SN:

Revision:

Config.:

7 05-242005 SCALEDISON Base 090-3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAIN A Ohnis or Slemeas1OO0^ ft per Conductor (Cable) or per Phase (Lne)

Linc/Cable ID 3XB1305PI 3XB1602PI 3XIE603P1.P2 3XB161ZP2 3XXR169PI-P3 3XXR169P7.PS 3XX0R169PA-PDP9 Libmry St=e 0.6MCJNI 500 0.6MCUN1 7SO 0.6.MCU41 350 0.6MCVNI 350 B.OM mUN3 750 8.OMCUN3 750 S.OMCUN3 750 Adj. (f)

% Tot.

380.0 0.0 224.0 0.0 371.0 0.0 370.0 0.0 631.0 0.0 610.0 0.0 374.0 0.0 I

1 2

3 2

5 T ('C R

X Y

75 0.035900 0.045300 75 0.02lOC 0.043800 75 0.046100 0.046900 75 0.046100 0.046900 75 0.02&000 0.030900 75 0.02000 0.030900 75 0.D20800 0.030900 Linc I Cable esismmnes on listed at the speeified temp1cntus.

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 42-of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C -130 CCN No.

Prmject:

E4C4090 REV. 3 ICCN C-130 Lomtion:

SONGS 2 & 3 CotarscL Engineer W.P. Lennartz Filerame:

E4C090 ETAP 5.0.ON Page:

S Date:

05-24-2005 SN:

SCALEDISON Revision: Base Config.:

090-3Al4aa SwtdysCasc 3AI4aa ECP050500255-34 ICCN C-130 UNIT3 TRATNA 2-Winding Transrormer Input Datn Transfanrer ID 3BOIX 3B02X 3B03X 3B04X 3B12X 3B13X 3B16X B1OX-B Rating Z Variation S7a Top Setting Adjusted Phase Shift MVA PdFmikV Sce.kV

%IZ X/R

+5%

-5%

  • Td.

Ptin.

Szc.

%5Z Type Angle 1.500 4.160 0.480 9.09 6.10 0

0 0

2.500 0

9.0900 Std Pos.Seq.

0.0 1.000 4.160 0.4S0 8.05 5.30 0

0 0

0 0

8.0500 S9d os. Seq.

0.0 I.000 4.160 0.480 S.09 10.92 0

0 0

0 0

1.0900 Std Pas. Seq.

0.0 1.500 4.160 0.480 10.07 6.64 0

0 0

0 0

10.0700 SidPos.Seq.

0.0 1.000 4.160 0.4S0 S.14 11.0l 0

a 0

0 0

S.1400 Sid Pos. Seq.

0.0 1.000 4.160 OA4O B.13 10.96 0

0 0

0 0

5.1300 Sid Pos.Seq.

0.0 1.500 4.160 0.480 933 8.75 0

0 0

0 0

9.330 Sid Pos. Seq.

0.0 1500 4.160 0.480 9.17 6.72 0

0 0

0 0

9.1700 SidPos.Seq.

0.0 3-Winding Transformer Input Data Rating Tap Impedance Z Variation Phase Shift Winding MVA kV I.Z XIR MVAb

% Tol.

+5%

-5%

Type Angle PAi:ary:

3000 230.000

-250 Zps -

14.40 20.67 30.000 0

0 0

Secondmrq 10.000 4.360 0

Zpl..

11.10 22.S0 30.000 0

Std Pos. Seq.

0.0 Tenimvy

20.0M0 4360 0

Zst*

24.60 19.16 30.000 0

Scd Pcs Seq.

0.0 Transfonter ID

ECP 050500255-34 Rev. 0 Cac. No. E4C-090 Rev.3 Page 43 of &

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Loaition:

SONGS 2 & 3 Ccntradc:

Engineer W. P. Lennanz Filenane:

E4C090 ETAP 5.0.ON StudyCase 3A14aa Page-9 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA Branch Connections CKT/Branch Connected Bus ID ID 3BOIX 3B02X 3B03X 3BD4X 3B12X 3B13X 3B16X DIDX-B 3XRI 0XBf002r1I OXBlOl4PI OXB1015IP OXI31015P2 3AA0402P1 3AAD409PI 3AA0417PI 3A80403PI 3A30407PI 3AD0414PI 3ABo415P1 3AB04 17PI 3A30418PI 3A3RA06PI 3XA0304P) 3XA0309PI 3XA0310'P 3XA3 1I1PI 3XA0312PI 3XA080 13 3XA0302PI 3XA0808P1 3XA0S091' 3X130102P1 3XB0205PI 3XBD206PI Type 2W XhMR 2W XFM4R 2W XPMR 2W XFPMR 2W XFMR 2W XFMX 2W XFMR 2W XFMR 3W Xfnr 3W Xfn 3W Xfr Cable Cable Cable Cable Ceblt Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cnble Cable GCabl:

Cable Cable Cable Prom Bus To Bus 3BOlXtlS 3B02XHS 3B03XHS 3Bo4XHS 3BI2XHS 3B13XltS 3B16XHS DICXBHS SWITCHIYARD-3 SWrTCHYARD-3 3XRI-X Bla B10 B10 MZa45 3A04 3A04 3A04 3Bo4 3304 3D304 3Bo4 3Bo4 3n04 3sRA 3A03 3A03 3A03 3A03 3A03 3A08 3AOS 3A08 3A0D 3B01 3B02 3B02 3BOI 3302 3803 3Bo4 3B12 3B13 3B16 B30 3XRI-X 3XRI-Y 3XRI-Y BP BO ZTB45 D645 D007-3A0402 3D004-3A04C9 3304XHS 3BRA 331B 3BE 3BY BQ DB0415-330418 3L7D7-3BRAD6 3B13XBS ASCI 3BI2XHS 3B03XHS 3PIEXCC5 BIOXDHS 3B16XHS 3130BIXi4S 3B02XHS 3BA 3BHP02 3BHP03

% Impedance, Pos. Seq., 100 MVA Base R

X z

y 87.27 559.45 56547 135.87 720.13 732.24 67.16 733.41 736.4S 91.02 604.34 611.16 6.61 738.03 741.03 67.25 737.06 740.12 64.30 562. 53 66.24 81.92 550.47 556.S3 2.05 48.67 48.72 1.45 37.t6 37.19 234.S0 1143.83 1167.68 193.61 302.86 359.46 144.93 226.71 269.08 1956.57 73931 2091.59 393.54 47.26 39637 1.38 0.90 1.65 8.00 5.23 9.54 2.01 1.31 2.40 56.47 57.45 80.55 1393A6 1417.64 1987.t2 56A7 57.45 80.55 34.30 53.65 63.68 329.69 335A2 47032 502.91 284.20 577.66 6124.39 221.27 612839 1.90 1.24 2.27 6.45 4.19 7.69 1.73 1.12 2.06 1.15 0.75 1.37 5.05 4.39 6.69 4.89 3.18 5.84 1.73 1.12 2.06 5.84 3.S0 6.97 6.68 4.34 7.97 61.96 96.92 115.03 182S5 125.70 221.64 182.55 125.70 221.64

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION lCCN C - 130 Page f 1/4. of 64 CCN No.

Project:

E4C-090 REV. 3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer:

W. P. Lennartz Filename:

E4C090 ETAP S.0.ON Study Case: 3A14aa Page:

10 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Cornlg.:

090-3A14aa ECP050SO52S5-34 1CCN C-130 UNMMS TRAIN A CKT/Branch Connected Bus ID ID 3XB0210P1,P2 3X80306PI 3XB0314PI 3XB0402PI 3XB1202PI 3XB1203PI 3XB121 1P 3XB 1303PI 3XCB1305PI 3XB1602PI 3XB1603PI,P2 3X3161 IPI 3X)XR169PI-P3 3XXR169,Pt7, 3XXR169PA-PD.W9 3BD18 3BD26 3BDM 35DS 3BE51 3BEM 3BES 3BRA22 3BRAM 3BRAS 3BY39 3BY40 3BY42 3BYM 3BYS BQ27 BQM BQS U35WYD-Cl 3D004 3L707X BTXFRSW D007 DM4 15 Type Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Cable Tie Brakr Mie B3lxea ie BraT Tic BDakr Te Brcakr rjeBrealT Tle Breakr Me Brealr nc MBna Tie Brck Tle Brelck TlIe Ereab Tiflrea er Tic Breali Tie Brenkr 17e Br-lb Tie Breakr Me Break Tie Brealk Me Swtc3 Tie Switch TM Switch Tie Switch Tie Switch FramBus To Bus 3B02 3303 3B03 3B04 3B12 3B12 3B12 3B13 3B13 3B16 3B16 3B16 3XRI-X 3XRI-Y 3XR1-Y 3BD 3BD 3BD 3BD 3BE 3BE 3BE 3BRA 3BRA 3BRA 3BY 3BY 3BY 311Y 3BY B3Q BQ BQ SWllcUYARD-3 3D004-31P018 311V9377-N BT D007-2336 DB0415-E418 3BHPOI 3BF 3BB 3BIHP04 3BV 3BLX 31.111 3BMX 3BC 3BX BT-3B1603 3B1 61IBP 3A04 WAS 3A03 3BDM8-rrRS 3Q020 3BD.M.M4 3BDSM 37,N6 3BEMM 3BESM 3Q074 3BRAMM 3BRASM 3BY39-HTStS 3BY40-ITRS 3Q039 3BYMM 3BYSM Q033 BQMM BQSM SWItnHYARD 3D004-3A0409 3L707-3BRA06 BT-3B1603 D007-3AW402 DB0415-300419

% Imipedance, Pos. Seq., 100 MVA Base R

X Z

Y 347.63 150.70 332.97 347.39 543.42 644.97 778.75 976.15 1248.73 438.17 496.64 69639 200.25 31324 371.78 534.77 670.32 857.50 11D2.02 1121.14 15MO7 26S.09 336.05 429.89 539.03 675.66 86433 247.U2 387.66 460.11 337.89 343.75 482.01 673.96 6B5.66 963.43 2.30 3.42 4.12 3.34 4.96 5.98 0.S2 1.22 1.47

ECP 050500255 - 34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page L of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 MEV.3 ICCN C-130 Location SONGS 2 & 3 Contimc:

Engineer.

W. P. Lcmartz Filename:

E4CO90 ETAP 5.0.0N Page:

11 Date:

05-24-2005 SN:

SCALEDISON Revision.

Base Confil.:

090-3A14aa StudyCase. 3AI4a ECP 050500255-34 ICCN C-130 UNIT 3 TRAIN A Erulpnment Cable Input Data Ohms or Sicmenstll000 ft ner Conductor OIL l-ett Equipment Cable ID Equirrpient ID Length RIesise Type LA-7U SIs M. (M)

%Tol #Iph T( C)

R X

Y AdJ.(ohm) %Tol OABQO7PI OABQOSPI OABQOSPI 3XB03IOPI.P2 3AB0409PI -P 3AB0419PI-P3 OABQ14PI 3ABD12PI 3Ai3D13PI 3ABY07P1 3ABYOSPI 3ABY36PI 3ABYO3PI 3ABE04PI 3Xi 1609P2 3XB0210P3-P5 3XB0206P2P4 3XB0205P2' P13 3xB0402P2P3,I`4 3XAOS03PI OABQI5PI 3AB1Y3PI 3ABY39P6 3XBC205P1-P13 3XBOIC6PI-P3 3AB0410PI-P3 3ABY40P6,7"PS 3AB041 IPI-P3 3A3Y40P9,PAP13 3ABY24PI 3ABY22PI 3ABY20PI 3ADY21PI 3ABYIIPI 3ABY12PI 3ABY37PI 3ABY30PI 3AB.Y3PI 3ABE-03P2.92 3ABY2SPI 3ABD22PI 3ABD21PI 3ADE49PI.P2 2A173 2E255 2t.270 3AOOI 3A071 3A074 3A173 3A274 3A275 3A370 3A373 3A394 3BOOI 313003 3B005 3E122-HI 3E124-14 3E126-HI 3E128-Hi PX]

3E202 3U255 3E370 3E370H4 3E394 3E397 3E399 3399H 3E401 3E401H 31E417 3E427 3E437 3E43B 3E439 3E440 31E441 3E453 3E454 3E464 3E517 3E546 3E550 3f-652 tnd. Motor 0.6MCUN3 Irnd.Motor 0.6MCUN3 Stcat. Lad 0.6MCUN3 lod. Motor 0.6MCUNI Wd. Motor 0.6MCUNI tnd. Motor 0.6MCUNI Wnd.

Moawr 0.6MCUN3 lad. Motor 0.6MCUN3 lad. Motor 0.6MCUN3 tnd. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 lnd. Motor 0.6MCUN3 Stat. Lcad 0.6MCUNI Stt. Load 0.6MCUNI StaL Load 0.6MCUN1I Stat. Load 0.6MCUN3 StUt. LEad Q6MCUN3 Stit. Load 0.6MCUN3 Stat. Load 06MCUN3 Wad.

Motor B.OMCUN3 tad. Motor 0.6MCUN3 lod. Motor 0.6MCUN3 SUL LAd 0.6MCUN3 hnd. Motor OAMCUNI Ind. Motor 0.6MCUNI Ind. Motor 0.6MCUNI Stat. Load 0.6MCWN3 hnd. Motor Q.6MCUN2 Stai. Load 0.6MCUN3 Ind. Motor O.6MCUN3 lId. Motor O.6MCUN3 Lhd. Motor 0.6MCUN3 lnd. Motor 0.6MCUN3 tad. Motor Q.6MCUN3 Ind. Motor 0.6MCUN3 ld, Motor OQ6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCWN3 Stat. Load 0.6MCUN3 Ind. Motor 0.6MCUNO3 Ind. Motor Q.6MCUN3 lad. Motor 0.6MCUN3 StatL Load 0.6MCUN3 12 358.0 10 216.0 22 410.0 II0 227.0 I/D 447.0 110 49B.0 12 368.0 2

58.0 2

120.0 12 403.0 12 520.0 10 62B.0 1V 322.0 1/0 117.0 310 191.0 2

284.0 2

290.0 2

282.0 2

314.0 250 142.0 10 346.0 2

450.0 12 460.0 UD0 308.0 1/0 213.0 3m 315.0 12 442.0 3Ja 316.0 12 366.0 to 430.0 10 120.0 12 370.0 12 370.0 12 330.0 12 330.0 12 460.0 12 374.D 12 309.0 2

464.0 12 354.0 2

148.0 2

178.0 12 SCO.0 0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 i

0.0 1

0.0 1

0.0 1

0.0 1

0.0 I

0.0 2

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

0.0 1

75 1.97200 75 124000 75 IS970 75

.13100 75

.13100 75

.13100 75 1.97200 75

.19700 75

.19700 75 1.97200 75 1S9720 75 124000 75

.13100 75

.13100 75 08600 75

.19700 75

.19700 75

.19700 75

.19700 75

.05470 75 1.24000 75

.19700 75 1.97200 75

.13100 75

.13100 75 CU600 75 1.97200 75

.08600 75 1.97200 75 1.24000 75 1.24000 75 1.97200 75 1.97200 75 1.97200 75 1.97200 75 1.97200 75

1. 72O 75 1.972c0 75

.19700 75 1.97200 75

.19700 75

.19700 75 1.97200 D4560

.04480

.04560

.04950

.04950

.04950

.04560

.03440

.03440

.04560

.04560

.04480

.04950

.04950

.04860

.03440

.03440

.03440

.03440

.03560

.04480

.03440

.04560

.04950

.04950

£4860

.04560

.04860

.04560

.04480

.044s0 X4560

.04560

.04560

.04560

£04560

.04560

.04560

.03440

.04560 e3440

.03440

£4560

£000000

.0000000

£000000 zoomoo

£000000

.0000000

.000DDO0

.0000000

.0000000 eooooo

.0000000 Dooooo

.0000000

£000000

.COOOODCO

.0000000

£000000

.0000000

.000000o

£000000 4000000

.0000000 DOWDDOO ooooooo

.00100000

.000000

-oooooo XOOODGD

.0000000

.0000000

£000000

£000000

£000000

.0000000

£000000

.0000000

.0000000

£0030OO

£000000 Zoom

.000000

.00100000

.0000000

.0000000

.0000000

£000

.000

.0000 0001

£O0 l D000

£000

.0000

.0000

.D000

.OWO0 OWO

.OOOC

.0000

,ooo 000 DOOO

.0000

.0000

.0000

.0000

.000 owo0 ODOO WOO

.0300

.0000

.0000 DOOO

.0000

.000

.0000

.0000

.0000

.0WO

.0000

.000

.OOO

.0COO

.0000

.0000

£000

.0000 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 OD 0.0 0.0 0.0 0.0 OD 0.0 OD OD 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.o 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 Project:

B4Ct090 REV.3 lCCN C-230 Ltion:

SONGS 2 & 3 Contrac Engineer.

W. P. Lennnz FilenaMe:

E4C090 ETAP 5.0.ON Page LI of of CCN No.

Page:

12 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case: 3AI4aa ECPQ505Ot)055-34 ICCN C-130 UNIT3 TRAINA Ohmis or Slemnens/I1OO ft per Condudor OIL heater Erquipment Cable Equipmcnt Length Restatmce ID ID Type Wbntry Sie Adj.{(T)

Il 7ol

'Ipb T C R

X y

AdJ.Cchru) %Tot 3ABE36PI 3XB1606Pl.P2 3ABE42PI OA3QO6Pl 3XBY23PI 3ABY34PI 3AA04MP1 3ABY40PI 3AA0407PI 3ABY39PI 3AA040SPI 3ABY39PZ 3WAD004PI 3ABY39P3 3AA0405P1 3XA0308P) 3XA0307PI 3XA0312P2 3XB0303PI 3ABD23PI 3ABD24PI 3ABYIOPI 3ABY39P9 3ABY39P4 3XA03C6PI 3XA0305PI 3XA0313PJ 3XB1206P1-P3 3XBOIIOPI 3XB1306PI 3AA0404PI 3ABY39PS 3ABY14P2 3ABY40P2 3ABY15PI 3ABY40P3 3ABW413PI 3ABY40D4 3ABY40P5 3XBo3091' 3AA041 IPI 3ABY39P5 3ABDIOPI 3ABDIIPI 3ABE41PI 3AB0102P]

3XB1210PI 31!V4731 3L046 3L266 3L270 3L411LXI 31,009 3P012 3P012H 3P015 3P015H 3P017 3PO718 3POIS 3POISH1A 3r024 3P050 3P051 3P058 3P075 3PO93 3PO96 3PIO]S 3PIOISH 3PI115 3P117 3P120 3711271 3P125 3P128 3P135 3P141 3P141H 3P174 3P174H 3P175 3P17511 3P190 3P19011 3PI9111A 3n290 3P307 3P307H 3P996/3P1028 3P997/311014 3RU7t34-1 3RTOI822I 3701 II Ind. Motor 0.6MCUN3 Ind. Motor DhMCUNI Stat. Load D.CMCUN3 Stat. Load 0.6MCUN3 Sat. Load 0.6MCUN3 Ind. Motor C.6MCUN3 lrd. Motor 8.OMCUN3 Stat Load 0.6MCUN3 bad. Motor LOMCUN3 Stat. Load Q.6MCUN3 lrd. Motor 8.OMCUN3 Stnt. Load Q.6MCUN3 Ind. Motor B.OMCUN3 Stat. Load 0.6MCUN3 Ird. Motor 8.OMCUN3 rAd. Mosor 8.OMCN3 Ind. Motor 8.0MCUN3 bd. Motor 5.0MCUSI Ird. Motor C.6MCUNI lnd. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Stat. Load 0.6MCUN3 StaL Load 0.6MCUN3 lod. Motor S.OMCUN3 Ind. Motor 8.0MCUN3 lad. Motor S.OMCUN3 IAd. Motor 0.6MCJNI Ind. Motor 0.6MCUNI Ina. Motor 0.6MCUNI Ind. Motor 8.OMCUN3 Stat. Load 0.6MCUN3 lId. Motor 0.6MCUN3 StaLLond 0.6MCUN3 bnd. Motor 0.6MCUN3 Stat. Load 0.6MCUN3 Ind. Motor 0.6MCUNI Stat LoLad 0.6MCUN3 Stat Load 0.6MCUN3 Ind. Motor 0.6MCUNI Ind. Motor BOMCVN3 Stat. Lond 0.6MCUN3 lnd. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Stat. Load 0.6MCUN3 Stat. Load 0.6MCUN3 Stat. Load 0.6MCUNI 12 250 6

12 12 2

250 12 250 12 250 12 250 12 250 750 750 350 1m0 12 12 20 12 12 500 500 250 2)0 410 250 12 6

12 6

12 31D 12 12 1/0 250 12 12 22 12 12 350 562.0 426.0 360.0 650.0 177.0 470.0 332.0 372.0 338.0 369.0 364.0 s4s.0 36.0 400.0 328.0 73.0 207.0 36.0 166.0 170.0 170.0 370.0 370.0 48.0 308.0 340.0 678.0 563.0 324.0 701.0 540.0 779.0 330.0 420.0 330.0 3W0.0 326.0 420.0 336.0 198.0 430.0 466.0 106.0 60.0 230.0 500.0 294.0 0.0 1

0.0 2

0.0 1

0.0 I

0.0 1

0.0 I

0.0 1

0.0 I

0.0 I

0.0 1

0.0 1

0.0 1

0.0 I

0.0 I 0.0 0.0 1

0.0 1

0.0 1

0.0 I

0.0 I

0.0 I 0.0 I

0.0 I

0.0 I 0.0 I 0.0 I

0.0 1

0.0 1

0.0 I

0.0 I 0.0 I

0.0 2 0.0 1 0.0 0.0 I

0.0 I

0.0 I

0.0 I

0.0 I

0.0 1

0.0 1

0.0 1

0.0 2

0.0 1

0.0 1

0.0 I

0.0 I

75 1.97200

.04560 75

.06080

.04800 75 A9300

.03910 75 1.97200

.04560 75 1.97200

.04563 75

.29700 03440 75

.05470

.03560 75 1.97200

.04560 75

.05470

.03550 75 1.97200.04560 75

.05470

.03560 75 1.97200

.04560 75

.05470

.03560 75 1.97200

.04560 75

.05470

.03560 75

.02080

.03090 75

.02080 75

.04610 75

.13100 75 1.97200 75 1.97200 75 1.24000 75 1.97200 75 2.97200 75

.02920 75

.02920 75

.05470 75

.03590 75

.10600 75

.07000 75

.05470 75 1.97200 75 A9300 75 1.9720 75 A9300 75 1.97200 75

.08600 75 1.972CO 75 1.97200 75

.13100 75

.05470 75 1.97200 75 1.97200 75 1.97200 75 2.97200 75 1.97200 75

.04610

.03090

.05140

.04950

.04560

.04560 D4489

.04560

.04560

.03340

.03340

.03560

.04500

.04900

.04820 035150

.04560

.03910

.04560

.03910

.04560

.04860

.04560

.04560

.04950

.03560

.04560

.04560

.04560

.04560

.04560

.04690

.000000

.0000000

.000D000

.0000000

.0000D00

.0000000

.0000000

.00DD0000

.0000000

.0000000

.0000000

.0000000

.0000000

.0000000 DOOOOOO

.0000000

.00o0000

.0000000

.00ooo

.0000000

.00000DO

.0000000

.000000D

.0000000

.c00oooo

.000000

.0000000

.9000WO ooooooo

.0000000

.000000

.0OOOO

.00000oo

.00000DO

.00300000

.0CD0000

.0000000

.0000000

.0000000 xooooDs

.0000000

.QDOODO

.000DO00 D00OCOO

.00DO000

.00000DD D03WOO0 DooaaOO0

.CDD0

.0000

.0000

.0000

.0000

.0000

.0000

.00D0

.0000

.0000

.0000

.0000

.0000

.0000

.0000

.0000

.00DD

.0000

.0000

.0000

.O0DO

.0000

.0000

.0000

.0000

.0000

.0000 wow

.0000

.ooo0

.oooo 0300

.0000

.0000

.0000

.0000 D0o0 0.o 0.0 0.0 0.0 00 0.0 0.0 0.0 0.0 0.o 0.0 0.0 0.0 0.0 0.0 O.

0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Qo 0.0 0.O 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page - 7 of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer.

W. P. Lennartz Filename E4CO90 ETAP 5.0.0N Page:

13 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case: 3AI4aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA Ohms or Slemens/t000 ft per Conductor Equipment Cable ID Equipment ID Length Type LUbrary Size Adj. (n)

% Tol J/th T ()

R OIL Heater Resist2ace X

Y Adj.(oltm) % Tol 3XA0412PI 3XDY33P2MP3 CABQ22PI OABQ23PI OABQ09P2 OXACIOID2 OABQO4PI.P2 OAAD007PI OABD41SPI OXBIOIIPI 0%X1015P3 OABQ13Pl OADQ20p1 0xIQIIPI 3XBY19PI 3XB13S7I OXB1006PI OABQ24PI CABQ20PI 0ABQ25PI 37D141X1 3TI0nQmIo j

A053 AD56 A207 C443 E297 E336 E415 E643 E645 Ull-l L211t4 LA371X1 LP35AIX)

N002 P159 P162 P445 W310 Stmt Lad 8.0MCUN3 Stat. Load 0.6MCUNI hd. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 ld. Motor B.OMCUNI Stat Load C.6MCUN3 lad. Motor E.CMCUN3 Ind. Motor 0.6MCUNI Stat. Load 0.6MCUNI Stat. Load 0.6MCUN3 StatL Load 0.6MCUN3 Stat. Lad 0Q6MCUN3 Stat. Load 0.6MCUN3 Stat. Load 0.6MCUN3 Stat. Load 0.6MCUNI Ind. Motor 0.6MCUNI lad. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 Ind. Motor 0.6MCUN3 250 2

12 12 10 250 12 250 310 Soo 10 6

6 10 6

2o 110 2

12 12 462.0 949.0 472.0 472.0 640.0 90.0 51O.0 216.0 415.0 188.0 10.0 90.0 120.0 300.0 339.0 824.0 402.0 468.0 554.0 584.0 0.0 I

0.0 I

0.0 I

0.0 1

0.0 I

0.0 I

0.0 I

0.0 I

0.0 1

0.0 I

0.0 1

0.0 I

0.0 I

0.0 1

0.0 1

0.0 I

0.0 1

0.0 I

0.0 1

0.0 1

75

.05470

.03560

.0ODOOO 75

.20300

.05130

.0000000 75 1.97200

.04560

.0000000 75 1.97200

.04560

.000000 75 1.24000

.04480

.0000000 75

.06090

.05250

.0000000 75 1.97200

.04560

.OOOOOO 75

.0547

.03560

.0000000 75

.08600

.04860

.OOOOO0 75

.03590

.04500

.000000 75 124000

.04480

.0000000 75 A9300

.03910

.0000000 75

.9300

.03910 OOOO 75 12400C

.04480

.ooo000 75 A9300

.03910

'.0000000 75

.13100

.04950

.0000000 75

.3100 A4950

.0000000 75

.19700 03440

.OOO0 75 1.97200

.04560

.00OO0 75 1.97200

.04560

.00OOOOO 100

.emo

.oooo

.0000

.0000

.oooo

.0000

.OOO0 ODOO

.0oc0

.0000 DOOOO

.Ooco

.0000 A00 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 Proje:

E4C-090 REV.3 ICCN C-130 Lcation:

SONGS 2 & 3 Contrac:

Engineer W. P. Lennarl Filename:

E4C090 ETAP 5.0.ON Study Case: 3A14aa Page Li' of CCN No.

Page:

14 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa ECP050500255-34 ICCNC-130 UNIT3 TRAINA LOAD FLOW REPORT Bus 10 3AM Voltage Generation Ioad kV kV JAm2 MW Mvar Mw MWar 4.160 4.017

  • 4.1 0

0 10.000 5.E65 ID 3AD4 3A08 3OI 3BOIXHS 4.160 4.139

-1.6 4.160 4.017

-4.1 0.4S 0.443

-5.5 4.160 4.016

-4.1 0.480 OA57

-6.9 4.160 4.05

-4.1 0.480 0.447

-7.1 4.160 4.016 4.1 A480 0.449

-6.0 31312XHS 3B103XHS 3PEXCCs 3XRI-Y 0

0

.722 1372 D007-3A0402 3D004-3A0409 3004X1S 3XR1-X 0

0 0.796 0339 BIOXT311S 3B 16XHS 3BOIXHS 3B02XHS 3XRl.Y 0

0 0.131 OD7S 3BA 31301XHS 0

0 0

0 3A0S 3101 0

0 0.049 0.031 3BHP02 31B1P03 3BHPOI 3B02XHS 0

0 0

0 3AOS 31302 0

0

.206 0.120 3BF 3BB 31303X1HS 0

0 0

0 3A03 3B03 0

0 0.261 0.172 3BRA 311B 3BE 3BY BQ D1B0415-3B041S Load nlowv XFMR MW Mvar Amp

%PF

% Tap 0.384 0.185 6.2 90.1 0.232 0.315 373 89.5 0.761 0.451 127.1 86.o 0.60s 0365 102.0 85.7 1.773 0.909 286A 19.0

-13.758

-7.891 2279.8 36.7 0.456 0.256 72.9 87.2 0.40S 0.174 61.8 92.0 1.18 0.761 196.8 E4.2

-4.774

-2.562 755.8 8s 1 0.703 0.25s 107.7 93.9 0.971 0.661 168.6 8.7 0.396 0.232 65.9 a63 0.575 0.062 83.1 99.4

-3.441

-1.552 542.5 91.2 0.263 0.140 386.1 88.2

.0.394

-0.218 5s5.7 87.5

-0.396

.0.232 65.9 86.3 0.396 0.232 65.9 86.3 2500 0.190 O.001 239A I00.0 0.290 0.001 239.4 100.0 0.141 0.000 178.6 300.0

.0.569

.0.033 720.2 99.8

-0575 0.062 83.1 99.4 0575 0.062 83.1 "A

0.230 0.107 3363 91.2 0.160 0.095 240.9 85.9

.0.604

-0322 884.0 88.3

-0.60

.0.365 102.0 85.7 0.608 0365 102.0 85.7 0.014 0.008 20.5 84.9 0.147 0.101 230.0 323 0.101 0.055 1483 87.8 0.224 0.139 339.6 85.1 0.127 0.0o77 91.1 85.5 0.112 0.072 171.5 B4.1 3302 3BO2XHS 31103 3B03XHS 3B04

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page !9.

of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-00 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contrac1:

Engineer W. P. Lennarlz FCnam E4M090 ETAP 5.0.ON Page:

15 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3AI43:

Study Case: 3A14aa ECP0505002S5-34 lCCN C -130 UNMr3 TRAINA Bus Voliage Generation Load kV kV Ang MW MWar MW MWar ID ID 3B04XHS 3B12 3BI2XHS 4.160 4.137

.1.6 0.4S0 0.443

.7.9 4.160 4.016

-4.1 0.450 OA55

-6.0 4.160 4.016

-4.1 0.4ED 0.441

-7.7 3BHP04 3BC4XHS 0

0 0

0 3A04 3B04 0

0 0.322 0.158 3BV 3BLX 3LIII 3B12XHS 0

O 0

0 3AC3 3B12 0

0 0.225 0.080 3BMX 33C 3BI3XHS 0

0 0

0 3A03 3B13 0

0 0.160 0.109 3BX BT-3B1D603 3B1611BP 3B 16XH1S a

0 0

0 3AOS Load Flow 2MIR MW MWr Amp

%PF

%Trp 0.181 0.002 233.2 100.0

-1.168

-0.627 1705.9 88.1

-1.18S 40.760 196.S S4.2 1.I88 0.760 196.E 842 0.202 0.124 309.0 85.2 0.051 0.027 75.7 S8.4 0.179 O.D73 251.7 92.6 40.754 40.3U3 1101.6 89.2

-0.761

-0451 127.1 86.0 0.761 0.451 127.1 S6.0 0.051 0.026 72.9 89.1 0.106 0.063 156.8 86.0 40.382

.0.169 530.6 91A

-0.3B4 40.185 61.2 90.1 0.384 0.185 61.2 90.1 0.304 0.143 440.2 90.5 0.373 0.210 560.6 87.2 0.124 0.I08 215.0 75.5

-0.961

-0.569 1463.3 16.0 3313 3B13XHS 31B16 3BI6XHS 4.160 4.016

  • 4.1 3B2611BP 3DA 3BB 3BC 3BD 0ASD 0.432

-7.S e.480 0.442

-5.7 0.480 0.435

-7.7 0.480 OA49

.6.2 0ABO 0.429

-6.5 0.48D 0.429

-6.5 0.4460 0.429 46.5 0.480 0.429

-4.5 0.480 0.448

-6.0 0.460 0.448

-6.0 0

0 0.121 0

0 0.262 0

0 0.157 0

0 0.105 0

0 0.130 0

0 0

0 0

0.005 0

0 0.003 0

0 0.074 3B16 0.105 31B16 0.139 31B02 0.091 3103 0.062 31B13 0.08 31B04 3BDI E-IITRS 3QC20 3BDMM 3BDSM 0 3BD 0.003 3BD 0.002 3B13 0.03W 3B04 3T063 3BE2MM 40.971

-0.661 0.971 0.661

-0.121

-0.105

  • 0.262

-0.139

.-0.57 40.091 40.105

.0.062

.0.142

-0.096 0.000 O.0W0 0.003 0.002 0.005 0.003 0.003 0.002 0.000 O.CW0

-0.005

-4W3

-0.003

-0.002

-0.102

-0.05S 0.019 0.01D O.C0s 0.003 0.004 0.002

-0.0a5

  • 0.003 168.8 82.7 168.8 82.7 215.0 75.6 388.2 8S4 240.9 86.5 156.8 86.2 230.0 828 OD 0.0 5.4 85.0 7A 83.0 5A4 5.0 0.0 0.0 7.4 E3.0 5.4 85.0 148.3 87.9 2S1 85.0 7.1 83.0 5.6 85.0 7.1 83.0 3BD28-)iTRS 313DMM 3BDSM 3BE 3BESM 0

0 0.005 0.003 3BE 3BEMM

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page S5O of (4 t

AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV. 3 ICCN C - 130 Locaticn:

SONGS 2 : 3 Contmct:

Engineer:

W. P. Lennanz Filename:

E4C090 ErAP 5.0.ON Study Case: 3AM4aa Page:

16 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Conig.:

090-3A14aa ECP 050500255 - 34 ICCNC-130 UNrT3 TRAINA Bus Voltage Generation Load ID LV kV Ang.

MW Mvu MW Myr ID 3BESM 0.4C0 0.448

.6.0 0

0 0.04 0.002 3BE 3sF 0,450 OA39

-7.7 0

0 0235 0.102 3B03 3BHPOI 0.43 0.454

-7.1 0

0 0.141 o0o0o 3B02 3sHP02 0.430 0.455

.7.1 0

0 0.189 o.o0 3B02 3BHP03 0.480 0.455

-7.1 0

0 0.189 0.000 3002 3BHP04 0.480 0.444

.6.7 0

0 0.179 0.000 3B04 3BLX 0.480 0.441 4.0 0

0 0.051 0.027 3312 3BMX 0.4O0 OA54

-6O a

0 0.050 0.026 31313 3BRA 0A80 0.449 46.0 0

0 0

0 3B04 3L707-3DRA06 3Q074 3BRAMM 3BRAMM 3BRASM 3BV 3BX 3BY 30Y39-HTIS 3BY40-iTRS 3BYMM 3BYSM 3DC04.3A0409 3D004-31`018 32iV9377-N 3L1.II 3L707-3BRA06 3PEXCC5 3Q020 3Q039 3Q074 0.460 0.449

.6.0 0.480 0.449

.6.0 OA&O 0.439

.8.1 0.480 OA33

.8.3 0.480 0.448 46.1 0AW0 0.448

-6.1 0.483 0Q448 6.

0.460 0.448

.6.1 0.480 0.448 46.1 4.160 4.137

.-. 6 4.160 4.137

-1.6 0.450 0.448

.6.0 D.480 CR27

-8.

0.480 0443

.6.0 4.160 4.010

.4.1 0.4S0 0.429

-6.5 0.4SD 0.448

.6.1 0.480 0.449

.6.0 3BRASM 0

0 0.005 0.003 3BRA 0

0 0.004 0.002 3BRA o

0 0.201 0.122 3012 0

0 0.300 0.137 3316 0

0 0.192 0.124 3BD4 3BY39.-ITRS 3BY40-HTRS 3QO39 3B1YMM 3BYSM 0

a O.O7 0.000 3BY 0

0 0.0 0.000 o3BY 0

a 0.005 0.003 3BY 0

0 0.004 0.002 3BY 0

0 0

0 3A04 3D004-3P018 Load Flow GMR MW Nivar Amp SPF

% Tap 40.004 40.002 5.6 85.0

-0.235 4.102 336.3 91.7

.0.341 0.000 178.6 100.0 4.189 0OOO 239A 300.0

-0.189 0.000 239A 100.0 4.179 ow.0 233.2 100.0

-0.051 2 0.027 75.7 88.6 40.051 40.026 72.9 89.1

-0.014

-0.008 20.5 84.9 0.002 0.001 2.2 90.0 0.004 0.002 5.6 85.0 0.005 0.C03 7.1 83.0 0.004 0.002 5.6 85.0

.0.005

.0.003 7.1 83.0 4.004 4.002 5.6 85.0 4.201 4.022 309.0 85.5 40.300 40.137 440.2 91.0 40.224 4.138 339.6 85.1 0.007 0.000 1.8 100.0 O.D03 0.000 3.3 ICO.0 0.015 0.009 22.4 s5.0 0.005 0.003 7.1 83.0 0.004 0.02 5.6 85.0

.0.007 0.0O0 8.W 100.0

-0.003 0.000 33 100.0

.0.005 40.003 7.1 83.0 40.004 4.002 5.6 85.0

.0.408 4.174 6O.

92.0 0.408 0.374 61.8 92.0 4.408

.0.174 61.S 92.0

.0.002

.0.001 2.2 90.0

-0.174 4.068 253.7 93.2 40.002 4.003 2.2 90.0 0.002 0.001 2.2 90.0

-1.770

.0.907 286.4 89.0 4.003 40.002 5.4 85.0 4.035

.0.009 22.4 85.0

.0.004

.0.002 5.6 85.0 0

0 0.408 0

0 0.002 0

0 0.174 0

a 0

a 0

1.770 0

0 0.003 0

0 0.015 0

0 O.0W4 0.174 3DOD4-3A0409 0.01 3L707-3BRA06 0.68 3B 12 0 3BRA 311V9377-N 0.907 3A03 0.002 3BD 0.009 3BY 0.002 31RA

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 Page.L of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Cortract:

Engine-.

W. P. Lemnart ilenan=.e E4C090 ETAP 5.0.ON Study Case: 3A14aa Page:

17 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa ECP 050500255 - 34 ICCN C -130 UNIT 3 TRAIN A

~~~

Bus ID Vollage Generation Load IV IV Ang.

MW Meazr MW Mvar OAS0 0.4S 46.0 0

0 0.019 0.011 3BE 4.160 4.142

-1.6 0

0 0

0 3A04 ID 37T63 3XRI-X Load FMor XFV R MVW Mvar AmIP

% PF

%Top

-0.039

.0.CI 2a:

85.0 4.782 2.573 755.8 S3.1

-4.782

.2.573 755.8 88.J 3XRI-Y

& SWITCHYARD-3 0 3A08 3XRI-Y 4.160 4M6

-4.0 0

0 ASCI B10 3A03 SWnTCHYARPD3

&3XRI-X 4.160 4.016

-4.1 0

0 0.232 0.215 3A03 Q.4SD OA53

  • 6.7 0

0 0.143 0.041 BP BO ZT145 8DOXBHS 4.160 4.015

-4.1 0

0 0

0 3A0S B10 0.480 0.450

.7.1 0

0 0.272 0.032 B10 04Eo 0.447

-7.0 0

0 0.271 0.143 310 3.447 13.782

-17.229 BIOX8HS 80 BP DQ 1.560 542.5 91.1 7.927 2279.8 86.7

-9.487 2820.2 87.6 OAS3 0.445

-6.2 0

0 0.107 0.064 3B04 Q033 BQMM BQSM 0.03 BQ 0.002 BDQ 0.201 BT-3B11603 0 3B 16 BQMM BQSM BT BT-3B1603 D007-3AW402 D307-E336 D645 D804 15-3B30418 DB0415-E41S Q033

-SWMTCHYARD SWrTCIIYARD-3 0.460 0.445 0.480

.A45 0.480 0.429 0.480 0.429

-6.2

-6.2

-8.1 4.1 0

0 0.005 0

0 0.004 0

0 0.365 0

0 0

  • 0.232

-0.115 0.273 0.147 0.273 0.034 0.00 0.000

.0.698

  • 0.221

-0.703 40.25a 0.703 0.25S 40.272

-0.032

.0.271

-0.143

-0.126

-0.076 0.01g 0.00`7 0.005 0.003 O.O4 0.002 40.005

-0.003 40.004

-0.002

.0.365

-0.201

-0365

-0.201 0365 0.201

-oA56

-0.256 0.456 0.256

  • 0.456

-0256

-0.008 0.000

-0.11I

-0.071 0.111 0.071

-0.11 1

-0.071

-0.011

-0.007 22.0SS 13.930

-22.088

-13.930 22 08 13.930 373 89.5 395.5 S6.1 3513 99.2 10.2 100.0 933.1 95.3 107.7 93.9 107.7 93.9 351.3 99.3 395.5 88.5 191.1 85.6 16.7 85.0 7.1 B3.0 5.6 85.0 7.1 83.0 5.6 85.0 560.6 87.6 560.6 87.6 560.6 87.6 72.9 87.2 72.9 872 72.9 87.2 10.2 100.0 171.5 84.1 171.5 84.1 171.5 84.1 16.7 S5.0 69.5 84.6 69.5 14.6 69.5 84.6

-2500 BT 4.160 4.138

-1.6 0

0 0

0 3AD4 D007-E336 4.160 4.138

-1.6 0

0 0.456 0.256 D007-3A0402 0.4S3 0.452

-6.7 0

0 0.008 0.000 ZTB45 0.430 0.444 0.460 0.444 0.4S0 0.445 230.000 216.190 230.000 216.S90

-6.0

-6.0 0

46.2 0

0.0 22.0SS 0.0 0

0 0

0 31104 DBD415-E418 0

0.11 0.071 DBO415-31B0418 0

0.011 0.007 BQ 13.930 0

0 SWrrCHYARD.3 0

0 0 SWITCHYARD 3XRI-X

&3XRI-Y

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 rtojed:

E4C-090 REV.3 ICCN C-130 ETAP I

  • p,

P. '

5.0.0N I

Page $2 of (a' CCN No.

Page:

18 Date:

05-24-200S SN:

SCALEDISON Revision:

Base Confir.:

090-3Al4aa LocUoLn:1 auilua A c o

Contract:

Engineer W. P. Lennarz FM!ena=e E4C090 Study Case 3A14aa ECP0505002M5-34 ICCN C-130 UNIT3 7RAIN A Dos VoLtye Generattion Load Ik kV kV Ang.

MW Mrar MW Mvrer ZTE45 0.4S0 0.452

.6.7 0

0 0

D B10 D645 ID Load Flow XFER MW Mvar Amp

% PF

% Tap 4.0Cs 0.000 10.2 100.0 0.001 0.000 10.2 100.0

  • Indicates a yoltmpe resulated bus C voltle cotrolled cr snwir, type machire connected to Ist)
  • Indicatesa bums with a load Wtds t~C ofznore ts 0.1 UVA

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 53 of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E,4C-090 REV. 3 ICCN C -130 Locific:

SONGS 2 & 3 Contract:

Engineer.

W. P. Lenniuiz Filename:

E4COO0 E TAP 5.0.0N Page:

19 Dale:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Smdy Carse: 3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA Bus Loading Summary Report Directly Connected Load ToW Bus Load Btus Constant kVA ConstantZ Constur.t I Ge ric rent ID kV Rated Aryp MW MWnr MW Myar MW Myar MW Mnar MVA

% PF Anmp Loading 2GOO2-BUS 2GO03-BUS 3G002-BUS 3GC03-BUS 3A03 3A04 3A08 3BOl 3BOIXHS 3BO2 3BOZXHS 3303 3BO3XE7S 3B04 3D041015 3B12 3B12XlIS 3B13 3B13XH1S 3B16 3B3I36XS 3B161 1BP 3BA 3BB 3BC 13D 3BD1 8I-IItS 3BDMM 3BDSM 3BE 3BEMM 3DESM 3BF 3BHPOI 3BH1M02 3DHP03 4.160 0

0 0

0 0

0 0

0 0

0.0 0.0 4.160 0

0 0

0 4.160 0

0 0

0 4.160 0

0 0

0 4.160 3000.0 I0OCOO 5.865 0 0 00 4.160 3000.0 27596 1.294 0.126 0.078 4.160 1200.0 0.796 0339 0

0 0.4S0 2000.0 0.131 0.07S e

0 4.160 0

0 0

0 0.4S0 1600.0 0.049 0.031 0

0 4.160 0

0 0

0 0.480 1600.0 0.206 0.120 0

0 4.160 0

0 0

0 0.480 2000.0 0.261 0.172 0

0 4.160 0

0 0

0 0.4O0 1600.0 0.202 0.1I8 0.120 0.040 4.160 0

0 0

0 0.480 16000 0.152 0.079 0.073 0.001 4.160 0

0 0

0 0.480 2000.0 0.09 0.043 0.071 0.066 4.160 0

0 0

0 0.4S0 800.0 0.006 0.004 0.116 0.101 0.4O0 500.0 0.153 0.097 0.109 0.042 0.4S0 600.0 0.138 0.087 0.019 0.005 0.4O0 600.0 0.041 0.030 0.064 0.032 0.450 600.0 0.130 0.088 0

0 0.480 0

0 0

0 0.460 0.005 0.003 0

0 0.480 0

0 0.003 0.002 0.480 600.0 0.001 0.001 0.073 0.037 0.460 0.005 0,003 0

0 0.480 0

0 0.004 0.002 0.480 600.0 0.104 0.052 0.131 0.050 0.4S0 0

0 0.141 0

0.480 0

0 0.189 0

0.480 0

0 0.189 0

0 0

0 0

0 0.0 0.0 0

0 0

0 0

0.0 0.0 0

0 0

0 0

0.0 0.0 00

0) 0 0 00 15.860 85.7 2279.S 76.0 0

0 a

0 5.41S 88.1 755.8 25.2 0

0 0

0 3.775 91.2 542.5 45.2 0

0 0

0 0.450 U7.5 585.7 293 0

0 0

0 0.459 863 65.9 0

0 0

0 0.70 99.8 720.2 45.0 0

0 0

0 0.578 99.4 83.1 0

0 0

0 0.685 883 884.0 55.2 0

0 0

0 0.709 85.1 102.0 0

0 0

0 1.325 S8.1 1705.9 853 0

0 0

0 IAI0 84.2 196.8 0

0 0

0 0.846 89.2 1101.6 68.8 0

0 0

0 0.884 86.0 127.1 0

0 0

0 0.418 91.4 530.6 33.2 0

0 0

0 0.426 90.1 61.2 0

0 0

0 1.117 86.0 34633 73.2 0

0 0

0 1.175 82.7 168.8 0

0 0

0 0.161 75.6 215.0 26.9 0

0 0

0 0.297 88.4 3S8.1 64.7 0

0 0

0 0.181 86.5 240.9 40.2 0

0 0

0 0.122 86.2 156.8 26.1 0

0 0

0 0.171 82.8 230.0 38.3 0

a 0

0 0

0.0 0.0 a

0 0

0 0.006 83.0 7A O

0 0

0 0.004 85.0 5.4 0

0 0

0 0.115 87.9 148.3 24.7 0

0 0

a 0.A06 83.0 7.1 0

0 0

0 0.004 85.0 5.6 0

0 0

0 0.256 91.7 3363 56.1 0

0 0

0 0.141 100.0 178.6 0

0 0

0 0.189 100.0 239.4 0

0 0

0 0.189 100.0 239.4

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 57 of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3

Contact:

Engimeer.

W.P.Lennma.lz Filenarne:

E4C090 ETAP 5.0.ON Sludy Cesc 3A14aa Page:

20 Date:

05-24-2005 SN:

SCALEDISON Revision: Base Config.:

O90-3A14aa ECP050500255-34 ICCN C-130 UNT13 TRAINA Directly Connected Load Total Bus Load Bus Constant LVA Consunn Z Consant I Generic Punt ID kV Raed Amp MW Mar MW War MW Mvr MW MWar MVA S PP Amp Loading 3BHP04 3BLX 3BMX 3BRA 3BRAMM 3BRASM 3BV 3DX 3BY 3BY39-HTRS 3BY40-11RS 3BYMN 3BYSM 3D004-3A0M 3DC04-3POIS 311V9377-N 3L2 11 3L707-38RA06 3PEXCCS 30020 3Q039 3Q074 3TO63 3XRI-X 3XRI-Y ASCI B10 BIOXBHS BO BP DQ BQMM BQSM BT BT-3B 1 603 D007-3AO402 D007-E336 D645 0.480 0

0 0.179 0

0.480 600.0 0.036 0.023 0.015 0.004 0.480 6000 0.035 0.022 0.016 0.04 0.4S0 600.0 0

0 0

0 0.460 0.005 0.003 0

0 0.480 0

0 0.004 0.002 0.4S0 600.0 0.101 0.073 0.100 0.049 0.4SO 600.0 0.107 0.070 0.194 0.067 0.480 600.0 0.139 0.082 0.053 0.041 0.480 0

0 0.007 0

0.480 0

0 0.003 0

0.460 0.005 0.003 0

0 0.480 0

0 0.004 O.002 4.160 0

0 0

0 4.160 0.408 0.174 0

0 0.480 0

0 0.002 0.001 0.480 0.125 0.049 0.049 0.019 0.480 0

0 a

0 4.160 1.770 0.907 0

0 0.480 0

0 0.003 0.032 0.4S0 0

0 0.015 0.009 CA4O 0

0 0.004 0.002 0.4S0 0

0 0.019 0.011 4.163 0

0 0

0 4.160 0

0 0

0 4.160 400.0 0.232 0.115 0

0 0.4C0 2000.0 0.063 0.040 0.080 0

4.160 0

0 0

0 0.4S0 600.0 0.021 0.014 0.251 0.018 0.480 600.0 0.163 0.108 0.108 0.035 0.480 6DO.0 0.061 0.03S 0.046

.06 0.460 O.C05 0.003 0

0 0.480 0

0 0.004 0.002 0.480 600.0 0.16S 0.100 0.197 0.102 0.480 0

0 0

0 4.16D a

0 0

0 4.160 0.456 0.256 0

0 CO80 0

0 0.008 0

0 0

0 0

0.179 100.0 233.2 0

0 0

0 0.058 88.6 75.7 12.6 0

0 0

a 0.057 89.1 72.9 12.1 0

0 0

0 D.016 84.9 20.5 3.4 0

0 0

0 0.006 83.0 7.1 0

0 0

0 0.004 85.0 5.6 0

0 0

0 0.235 85.5 309.0 51.5 0

0 0

0 0.330 91.0 440.2 73.4 0

0 0

0 0.263 85.1 339.6 56.6 0

0 0

0 0.007 100.0 3.8 0

0 0

0 0.003 100.0 3.3 0

0 0

0 0.006 83.0 7.1 0

0 0

0 0.004 85.0 5.6 0

a 0

0 0.443 92.0 61.8 0

0 0

0 0.443 92.0 61.8 0

0 0

0 0.002 90.0 2.2 0

0 0

0 0.186 93.2 251.7 0

0 0

0 0.002 90.0 2.2 0

a 0

0 1.989 19.0 286A 0

0 0

D 0.004 15.0 5A 0

0 0

a 0.017 85.0 224 0

0 0

0 0.004 85.0 5.6 a

0 a

0 0.022 85.0 28.1 0

a 0

0 5.430 18.1 755.8 0

0 0

0 19.668 87.6 2820.2 0

0 0

0 0.259 19.5 37.3 93 0

0 0

0 0.732 95.3 933.1 4&7 0

0 0

0 0.749 93.9 107.7 0

0 0

0 0.274 993 351.3 58.5 0

0 0

0 0.306 88.5 395.5 65.9 0

0 0

0 0.147 85.6 191.1 31.8 0

0 0

0 0.006 83.0 7.1 0

0 0

0 O.C04 85.0 5.6 a

0 0

0 0.417 87.6 560.6 93A 0

0 0

0 0.417 87.6 560.6 0

0 0

0 0.523 87.2 72.9 0

0 0

0 0.523 87.2 72.9 0

0 0

0.008 100.0 10.2

ECP 050500255 - 34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 i'rojeca:

E4C-090 REV. 3 ICCN C -130 ETA 5.0.0N Page 55of.6 CCN No.

I Location:

SUNGS z &3 Contract:

Engineer I W. P. Lenna&tz Filename:

E4C090 Page:

Date:

SN:

Revision:

Confis.:

21 05-24-2005 SCALEDISON Base 090-3A14aa Study Case: 3A14aa ECPi050500255-34 ICCN C-130 UNIT3 TRAINA Bus ID DB0415-3BO418 DB0415-E418 Q033 SWTrCHYARD SWrrCHYARD-3 ZTB45 Consnt kVA IN Rlted Amp MW MWar 0.4R0 0

0.48D 0.11!

0017 0.480 0

230.000 0

230.000 0

0.480 0

Directly Connected Load Cons=ut Z Constaut I MW Mrur MW MWar Generk MW 0

0 0

C Total Bus Load a

0 0.011 0

0 0

0 0

0.007 0

0 0

o o

o 0

0 0

0 0

o o

o a

Mynr MVA 0

0 0.132 O

0 0.132 0

0 0.013 0

0 26.113 O

0 26.113 0

0 0.006

% PF Amp 84.1 171.5 U4.1 171.5 85.0 16.7 84.6 693 84.6 69.5 100.0 10.2 PeLodnt Lording

' Indicates operating load or a bus exereds the bus itictal imHit

( % of tibe Continous Ampere rating).

4 Indicates operating load of t bus exceeds the bus marginal linSIl C % of de Constinuus Ampere radn.

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 56 of f

CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Loction:

SONGS 2 & 3

Contract, Engineer W. P. Lc amt Filenmne:

E4CO90 hETAP 5.0.ON Study Case: 3A14aa Page:

22 Dale:

05-24-2005 SN:

SCALEDISON Revision:

Base Config,:

090-3Al4aa ECP 050O0055-34 ICCN C-130 UNIT3 TRAINA Branch Londina Sunmmary Rcport CKT/Branrh ID 3BOIX 3B02X 3803X 3004X 3B12X 3B 13X 3B16X B IOX-11 3XR1 Transformer Cable & Reactor Ampradty Liading Capability Loading (Input)

Loading (output)

(Amp)

Anmp (MVA)

Tvae MVA MVA h

Thnsfonner 3.500 OA59 30.6 OA50 30.0 Transforme?

1.DOO 0.57

57.

0.570 57.0 Thouronner 1.000 0.709 70.9 0.6S5 68.5 TV rfornwr 1500 1.410 94.0 1.325 88.4 Transfontr 1500 0.884 58.9 0.846 56.4 Trsfunzw 1.000 0.426 42.6 0.418 41.8 Tansrcrr 150W 1.175 783 1.1t7 74.4 Tnmrsfonner 1.500 0.749 49.9 0.732 48.8 3W XFMRp 40.000 26.113 653 3W XFMR s 13300 5.430 40.8 3WXFMRt 26.700 19.668 73.7

  • Indicntes bmnch sith operating ad exceedin^ thc b=raoh cupubiUty.

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Page 57 of &k CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer.

W. P. Lernanz Elename:

E4CD90 ETAP 5.0.0N Page:

23 Date:

05-242005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa Srudy Case 3A14aa ECPO50500255-34 iCCN C-130 UNU 3 TRAINA Branch Losses Sumnmary Report CRT/Branch From.ToBnsFlow To-FromnBus Flow Losses

%BusVoltage

, D-p iD MW' Mvar MW Mnn kW ar From To in Vana 3XA0304P1 3XA0309P]

3XA0310PI 3XA031 IPI 3XA0312P1 3XXR169PA-PD,P9 3AA0402PI 3AA0409P1 3AA0417PI 3XXR169PI-P3 3XA080tPI 3XAOS02PI 3XAOE08PI 3XAO809P1 3XXR169P7.PS 3XB0102P1 3BOIX 3XBO205PI 3XB0206PI 3XB0210P1,P 3B02X 3X80306PI 3XB0314P]

3B03X 3AB0403PI 3ABD407PI 3A110414PJ 3ABO41SPI 3ABWD 17P1 3AB04 1P1 3XB0402P1 3B04X 3XB 1202PI 3XB1203PI 3XB1211P1 0384 0.I85 403t4 4.1t5 0.0 0.0 9.6 96.5 0.01 0.232 0.761 0.60S 1.73

-13.758 0.456 0.408 1.l88 4.774 0.703 0.971 0.396 0.575

  • 3.441 0.263

-0394 0.190 0.190 0.141

-0.569 0.238 0.160 40.604 0.014 0.147 0.101 0224 0.127 0.112 0.181

-1.16B 0.202 0.051 0.179 0.S15

.232 D.451 4.761 0.365 40.608 0.909

.1.77D

-7.891 13.782 0256

.0.456 0.174

-0.408 0.761

.1.1 SB

.2-562 4.7S2 0258

  • .Q703 0.661

.0.971 0.232 40.396 0.062 4.575

-1.552 3.447 0.140 40.262

.0.218 0396 0.001

.0.189 0.001

.0.1S9 0.000

.0.141 4.0033 0.575 0.107

.0.235 0.095 40.157 4.322 0.608 0.008

.0.014 0.101

-0.142 0.05S

.0.101 0.139 4.224 0.077 0.126 0.072 40.111 0.002

-0.179

-0.627 1.18l 0.124

.0201 0.027

.0.051 0.073 40.174 40.115

-0.451 40.365 40.907 7.927 40.256

  • 0.174

-0.760 2573 40.25B

-0.661 40.232 4.062 1.560 40.139 0.232 0.000 0.000 0.0O 0.062 40.102 4.091 0.365 40.008

.0.096

.0.055

-0.138 0.076 40.071 0.000 0.760 4.122

.0.027 40.06S 0.1 0.0 96.6 96.5 0.02 0.2 0.1 96.6 96.5 0.02 0.1 0.0 96.6 96.5 0.01 2.4 2.1 96.6 96.4 0.15 24.3 36.0 96.6 96.8 0.24 0.0 0.0 99.5 99.5 0.01 0.2 0.1 99.5 99A 0.05 0.4 03 99.5 99.4 0.04 7.5 11.1 99.5 99.7 0.22 03 0.2 96.6 96.5 0.05 0.3 0.2 96.6 965 0.03 0.2 0.1 96.6 96.5 0.04 03 0.2 96.6 96.5 0.05 5.6 8.3 96.6 96.8 0.22 0.7 1.1 92.4 92.0 036 2.1 14.2 92.4 96.5 4.17 0.8 0.5 95.2 94.8 0AO 0O C.5 95.2 94.8 OAO 0.8 0.4 95.2 94.7 0.57 5.4 28.4 95.2 96.5 128 3.0 4.7 93.2 91.5 1.65 3A 43 93.2 90.6 2.57 4.0 43.5 93.2 96.5 3.39 0.0 0.0 93.5 93.4 0.01 5.6 5.7 93.5 S9.4 4.10 0.1 0.1 93.5 93.4 0.10 0.3 0.5 93.5 93.3 0.28 0.9 0.9 93.5 92.7 0.80 1.1 0.6 93.5 92.6 0.90 tO 2.0 93.5 92.4 1.05 20.1 233.5 93.5 99.4 5.99 1.5 2.3 924 91A 0.94 0.2 0.3 92.4 91.8 0.54 53 5.4, 92.4 89.1 331

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page 8

of 9 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C-130 CCN No.

Project:

E4C-090 REV.3 1CCN C-130 Page:

24 Location:

SONGS 2 & 3 5.0.0N Date:

05-24-2005 Cont.zce SN:

SCALEDISON Engincer.

W. P. L.-nrafLz Study Cese: 3A14aa Revision:

Base Filename-E4CC90 Config.:

090-3A14an ECP050500255-34 lCCN C-130 UNIT3 TRAIN A Vd CKTIBranch From-ToBusFlomv To-From BusFlow Losses

% Bus Voltage Drop ID MW Mvar MW Mar kW kvar Prorm To In Vrng 3B12X 40.754

-0383 0.761 0.451 6.1 68.0 92A 96.5 4.16 3XB1303P1 0.051 0.026 40.051

.0.026 0.1 0.1 94.7 94.5 0.26 3XB1305P1 0.106 0.063 40.105

.0.062 1.0 1.3 94.7 93.6 1.16 3813X

-0382

.0.169 0.3B4 0.185 IA 15.8 94.7 96.5 1.79 3XB1602PI 304 0.143 4300 40.137 3.6 5.7 91.8 90.2 1.56 3XB1603PI,P2 0373 0.210

-0365 40.201 B.l 8.2 91.8 B9.4 237 3XiI611PI 0.124 0.108

-0121

-0.105 2A 2.4

91. S 9.9 1.B8 3B16X 4.961

-0.569 0.971 0.661 10C5 91.5 91.S 96.5 4.76 3ADRA06PI 0.002 O.COI

.0.002

.0.001 0.0 0.0 93A 933 0.12 OX1002PI 0.273 0.147

-0.271

.0.143 23 3.6 943 932 1.13 0X31014P1 0.273 0.034

.0.272

.0.032 IA 2.1 943 93.8 0.55 CXB1015PI 0.008 0.000

.0,00E 0.000 0.0 0.0 94.3 94.2 0.18 BIOX-B

.0.698

.0.221 0.703 025S 5A 36.4 943 96.5 2.18 CXBIOISP2

-0.00S 0.000 0.008 0.000 0.0 0.0 94.1 94.2 0.04 3XR1 22.0S5 13.930 4.7B2

-2.573 77.1 169.5 94.3 99.7 0.B3

-17229

-9.487 943 96.8 1.95 219.2 2412.4

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page of &Li AUXILIARY SYSTEM VOLTAGE REGULATION

  • ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract Engineer:

W. P. Lennartz Filenamne E4C090 ETAP 5.0QON Page:

25 Datl:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa Study Case 3AI4aa ECP050500255-34 lCCN C-130 tWT3 TRAINA Equipment Cable and Heater Lomes Sunmnarv Report Connected Load ID Type Cable/Heater

% Voltge Losses Tenninal on

%Vd

% Vst kW kyar Bus Bus kV Lcad kV Operautlg Swaitni 4.0 4.6 96.55 96.33 9633 0.22 95.60 ID Ubuy 3PI17 3PI 15 3ro05 3PC50 3P120 3P307 3P012 3P024 3P017 3P141 3POIS 3E02 3POIl 3P058 C443 E336 3B97 3P228 3B94 3P075 3?290 3ACOt 3A074 3A071 3E399 3E411 3P190 39227 3PJ35 3L046 3A274 3A275 3E550 3E546 IWd.Motor 3XA0305PI Ind. Moor 3XA0306PI nd. Matrr 3XA0307PI Ind. Motor 3XA300SPI Ind. Motor 3XA0313PI Ind. Motor 3Mk0411PI lnd. Motor 3AA0403M1 Wnd.

Motor 3AA04057P ad. Molor 3AA040SP1 Ind. Motor 3AM0404PI lod. Motor 3AA0407P1 Iad. Maor 3XACE03PI kd. Motor 3WAD004PI Ind. Motor 3XA0312P2 lWd. Motor OXACIOIP2 Ind. Maor OAADOO7PI Ind. Motor 3X301C6PI-P3 nd. Maor 3XBOIIOPI kad. Motor 3XB0209P1-P3 ked. Motor 3X103 1PI Ind. Motor 3XBC309PI Ind.Motor 3XBQ310PIP2 hnd. Motor 3AB0419PI-P3 Ind. Maor 3A8C409PI-P3 kd. Motor 3A130410P1.P3 Ind. Motor 3AB0411PI-P3 Ind. Motor 3ABC413PI Ird. Maor 3XB 1206P-1'3 ktd. Moiar 3XB13D6PI Ind. Motor 3Xi31606PI.P2 Ind. Motor 3ABD12PI Ind. Moor 3ABD13P1 Ind. Motor 3ABD2JPJ Ind. Molor 3ABD22PI 8.OMCUN3 S.OMCUN3 B.OMC1JN3 S.OMCUN3 S.OMCUN3 S.OMCUN3 B.OMCUN3 S.OMCUN3 8.0MCUN3 S.OMCUN3 S.OMCUN3 1LOMCUN3 8.OMCUN3 5.0MCUSI E.OMCUNI E OMCUN3 O.6MCUNI 0.6MCUN1 0.6MCUN1 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUNI OhMCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 3.6 4.2 95.55 1.0 1.5 96.55 0.7 1.0 96.55 3.2 2.1 96.55 0.2 0.1 99.49 0.1 0.1 99A9 03 0.2 99.49 0.2 0.1 99.49 L.0 0.7 99.49 0.2 0.1 99.49 0.4 02 6.57 0.0 0.0 99.44 0.4 0.5 96.43 0.0 0.0 96.53 0.2 0.1 99AS 0.5 0.2 9236 1.5 0.7 92.36 0.7 0.2 95.24 0.7 03 93.15 0.5 0.2 93.15 13 0.5 93.15 1.0 0.4 93.46 0.9 03 93A6 0.6 0.4 93.46 0.6 0.4 93.46 0.6 0.3 93.46 5.6 7.0 9237 6.9 4.8 94.75 0.6 0.5 91.73 0.1 0.0 8936 0.2 0.0 8936 03 0.1 8936 D.2 0.0 E936 9635 96.50 96.51 96.24 99.42 99.44 99.42 99A3 9933 99.43 96.52 99.44 9638 96.52 99A3 91.57 90.75 94.13 92.27 9235 91.78 91.72 91.90 92.48 92.47 92.48 89.05 90.12 91.05 89.1S 88.98 B8.73 88.84 96.35 96.50 96.51 96.24 99.42 99.44 99AZ 99.43 9933 g9.43 96.2 99.44 9638 96.52 99.43 95.55 94.69 98.22 96.28 9636 95.78 95.71 95.90 96.50 96.50 96.50 92.92 94.04 95.00 93.05 92.85 92.59 92.70 0.20 0.05 0.04 031 0.06 0.04 0.06 0.06 0.16 0.06 0.05 0.01 0.03 0.01 0.04 0.79 1.62 1.22 0.t8 0.80 137 1.73 1.55 0.9S 0.98 0.98 331 4.63 0.74 0.IS 038 0.62 0.52 95.69 96.16 96.29 95.51 99.21 99.24 59.19 99.16 9S.77 99.24 9635 99A 96.26 96.47 9931 89A6 8633 90.91 90.47 90.80 8S.90 86.05 S6.80 t7.27 E7.25 88.89 77.14 78.41 85.83 t8.87 U833 S7.72 88.00

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

E4C-090 REV.3 ICCN C-130 L[c-ion:

SONGS 2 & 3 Commta:

Engineer.

W. P. Lernnarz Filename:

E4C090 ETAP 5.0.ON Page 60 ofA5L CCN No.

Page:

26 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3A14aa Study Case: 3AI4aa ECP050500255-34 ICCN C-130 UNIT3 TRAIN A Equipment Cable and Heater Losses Summnury Report Connteded Load ID Cable/}eater

% Voltage Losscs Terminal on

%Vd

%Vs Llbrry kW hyar Bus Bus IV Load kV Operatiing Starting Type ED 3P093 3P096 3P997t3P1014 3P996i3P)0t5 3HV4731 3A373 3A370 3P1018 3E439 3E440 3P174 3PI5 3E437 3E438 3E427 3E417 3E517 3B453 3E454 3P009 3A394 3E441 3E370 P159 P162 2Am73 2155 A207 3A173 3E255 P445 AC53 A056 W310 lid. Motor 3ABD23PI bdL Motor 3ABD24PI Ind. Motor 3ABDIIPl Ind. Motor 3ABDIOPI Wo. Motor 3ABE36PI Wad.

Motor 3ABYOSPI Ind. Motor 3ABY07PI lnd. Motor 3ABYIOPI nd. Motor 3ABYIPI Ind. Motor 3A'3Y12PI lrk Motor 3ABY14PI lad. Motor 3ABYISPI Ind. Motor 3ABY2OPI Ind. Motor 3ABY21PI Ind. Motor 3ABY22PI Lnd. Motor 3A'Y24PI lad Motor 3ADY25PI Ad. Motor 3ABY3OPI Ind. Motor 3ABY31PI Ind. Motor 3ABY34PI lad. Motor 3ABY36PI Ind. Motor 3ABY37PI Wrd.

Motor 3ABY3SPI lnd. Motor OXIQOO6PI lad. Mator OABQ24PI hW. Motor OABQ07PI Ind. Motor OABQOSPI Wnd.

Motor OABQO9P2 WId.

Motor OASQ14PI Ind. Motor OABQ15PI Lid. Motor OABQ20PI Ind. Motor OABQ22PI Ird. Motor OABQ23PI Ind. Motor OABQ25PI 0.6MCUN3 0.6MCUN3 O.6MCUN3 0.6MCUN3 0.6MCUN3 Q6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUJN3 0.6MCUN3 Q6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 Q6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUNI O.6MCUN3 O.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 OAMCUN3 C.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.0 0.0 89.36 89.24 0.0 0.0 89.36 89.24 0.0 0.0 B9.36 29.25 0.0 0.0 89.36 S9.16 0.0 0.0 9335 92.71 0.1 0.0 93.2S 91.70 0.1 0.0 93.28 92.06 0.1 0.0 93.2S 91.81 0.0 0.0 93.23 93,22 0.0 0.0 93.23 93.22 0.5 0.0 93.28 91.53 0.5 0.0 93.28 91.53 0.0 0.0 93.28 93.18 0.0 0.0 93.28 93.18 0.0 0.0 93.2 92.96 0.1 0.0 93.28 91.90 0.0 0.0 93.28 92.99 0.0 0.0 93.28 93.04 0.0 0.0 93.23 93.06 0.3 0.1 93.28 92.23 0.1 0.D 93.28 91.54 0.0 0.0 93.28 92.98 1.0 0.2 93.28 91.42 IA 0.5 94.34 92.45 0.4 0.1 92.66 91AI 0.0 0.0 92.66 91.8D 0.1 C.0 92.66 91.80 OA 0.0 92.66 89.27 0.0 0.0 92.66 91.71 0.1 0.0 92.66 91.27 0.0 0.0 92.66 91.85 0.1 0.0 92.66 91.43 0.0 0.0 92.66 92.24 0.0 0.0 92.66 91.62 93.12 0.12 89.15 93.12 93.13 93.04 96.74 95.69 96.07 95.80 97.27 97.27 95.50 95.50 97.23 97.23 97.01 95.90 97.03 97.08 97.11 96.24 95.52 97.03 95.40 96.47 95.39 95.79 95.19 93.15 95.76 95.24 95.84 95.41 96.25 95.60 0.Q2 89.15 0.11 89.17 0.20 S9.02 0.64 92.15 1.57 88.49 1.21 89.73 A.6 90.67 0.06 92.67 0.06 92.67 1.75 90.03 1.75 90.03 0.10 92.59 0.10 92.59 0.31 92.24 1.33 89.88 0.29 92.07 0.24 92.30 0.21 92.48 1.04 90A6 1.74 87.70 0.29 92.42 1.85 88.40 1.89 S8.35 1.25 89.09 0.86 89.65 0.86 90A.1 3.39 85.74 0.89 89.57 139 88.82.

0.81 91.23 1.23 S8.63 0.42 90.54 1.04 90.85

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 Page C/

of AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 CCN No.

Project:

E4C-090 REV.3 ICCN C-130 Location:

SONGS 2 & 3 Contract:

Engineer W. P. Lernarnz Filename:

E4C090 ErAP 5.0.ON Page:

27 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3AI43a Study Case: 3A14aa ECP 050500255-34 ICCN C-130 NIT3 TRAINA Equipment Cable and Heater Losses Sumnmar Report Connected Load ID Cable/Heater

% Voltage Losses Tenninal on

% Vd

% VW kW kvr Bus Bus kV Load kV Opesating Siarting Type ID Ll~bny E41S 2lL270 31B001 3BOCol 3B005 3E122-HI 3B124-HI 3E126-HI 3E 284-31 IXI 3E37CH 3E39911 3E40111 3E464 3E652 31.266 3L270 3L41I(XI 3P012H 3P01511 3P017H 3PKtlIA 3?1 12H 3P14114 3P174H 3P175H 3P99031 3919]HA 3P307H 3P1018H 3RU7S04-1 3RUM22-1 3T'10I 3T0141X1 3T310/3Q071JX1 ed. Motor OABD415PI StLoad OABQOSPI SL Load 3ABY03PI St. Leod 3ABEo4PI SL lad 3XB1609P2 St. Load 3XBCZ101`3-P5 St. Load 3XB0206P2-P4 SL Load 3XB0205P2,P3,PE St. Load 3XB0402P2.P3.1p4 St. Load 3ABY39P6 St. Lead 3ABY40P6.P7.P8 SL Lead 3ABY40P9.PAPB SL Load 3ABE03PI.P2 SL Load 3ABE49PIP2 St. Load 3ABE42PI St. Load OABQ06PI SL Lad 3XBY23PI SL Load 3ABY40PI SL Load 3ABY39PI SL Lead 3ABY39P2 St. Lead 3ABY39P3 St. Load 3ABY39P4 St. Load 3ABY39P8 St. Load 3ABY40P2 St. Load 3ABY40P3 SL Load 3ABY4CP4 St. Load 3ABY40PS St. Load 3ABY39r5 St. Lond 3ABY39P9 SL Load 3AIIE41PI St. Land 3ABEo2PI St.Lood 3XB1210PI St. Lad 3XA04 12P1 SL Load 3XDY33rMP3 0.6MCUNI 0.6MCUN3 0.6MCUNI 0.6MCUNI 0.6MCUNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 O.6MCUN3 Q.6MCUN3 0.6MCUN3 Q.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 O.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 Q6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6.MCUNI t.0MCUN3 0.6MCU1N1 3.1 3.8 92.55 90.02 0.1 0.0 92.66 91.00 0.1 0.0 93.2S 92.99 0.1 0.0 93.35 93.07 O.B 0.4 91.78 90.94 0.6 0.1 94.68 93.4S 0.6 0.1 94.84 93.62 0.6 0.1 94.84 93.66 0.6 0.1 92.41 91.12 0.0 0.0 93.28 93.04 0.0 0.0 9328 93.09 0.0 D.0 93.2S 93.13 0.3 0.0 93.35 9230 0.1 0.0 9335 91.E6 0.2 0.)

9335 92.21 0.2 0.0 92.66 90.06 0.0 0.0 93.28 93.16 0.0 0.0 93.28 92.10 0.0 0.0 93.28 92.11 0.0 0.0 93.23 91.56 0.0 0.0 93.2 92.02 0.0 0.0 9328 92.97 0.0 0.0 932S 92.46 0.0 0.0 93.2S 93.20 0.0 0.0 93.28 93.22 0.0 0.0 93.28 93.20 0.0 0.0 93.28 93.21 0.0 0.0 93.28 92.98 0.0 0.0 93.2S 93.19 0.0 0.0 9335 92.72 0.0 0.0 93.35 91.99 1.'

3.1 92.37 91.34 0.0 0.0 99.49 99.46 0.8 0.2 93.23 89.59 93.93 2.53 80.74 91.00 92.99 93.07 90.4 93AS 93.62 93.66 91.12 93.04 93.09 93.13 9230 91.85 92.22 90.06 93.16 92.10 92.11 91.56 92.02 92.97 92.46 93.20 93.22 93.20 93.21 92.98 93.19 92.72 91.99 91.34 99.46 89.59 1.66 0.00 0.9 0.00 0.28 0.00 0.S4 D.00 1.19 0.00 1.22 0.00 1.19 0.00 1.28 D.00 0.24 0.00 0.18 0.00 0.15 D.00 1.05 0.00 1.49 0.00 1.14 0.00 2.60 0.00 0.12 0.00 1.17 0.00 1.16 0.00 1.72 0.00 1.26 0.00 031 0.00 0.81 0.00 0.08 0.00 0.06 0.00 0.08 0.00 0.06 0.00 0.30 0.00 0.08 0.00 0.63 0.00 1.36 0.00 1.02

.0oo 0.03 0.00 3.69 0.00

ECP 050500255-34 Rev. 0 CaIc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Projec:

E4C490 REV. 3 ICCN C - 130 Location:

SONGS 2 & 3 Cortract:

Engineen W. P. Lennartz Filenamc E4C090 ETAP 5.0.ON Study Case: 3Al4aa Page 62 of / LI CCN No._

Page:

28 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Config.:

090-3Al4aa ECP050500255-34 ICCNC-130 UNIT3 TRAINA Eanqnment Cable and Heater Losses Sumnmarv Report Connected Load TD Cable/lfeater E297 E643 E645 L21 1-I L-2 1-4 L4371XJ LP35AIXI N002 Type SL Load OABQ04PI.P2 SLLoad OXIIIOI1PI SLt Lad OXBl0ItP3 SL Load OASBQI3PI St. Load CABQ26PI SL Load OXdQIIPI St. thd 3XBY19PI St. Loid 3XB1307P1 ID Ubriry 0.6MCUN3 0.6MCuNI 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUN3 0.6MCUNI

% Voltage Losses

__m_

an S_ Vd

7. Vst kW khar Bus Bus kV Load kV Operating StattIng 0.1 0.0 92.66 90.73 90.73 1.93 0.00 0.2 03 94.34 94.10 94.10 0.25 0.00 0.0 0.0 94.13 94.08 94.08 0.05 0.00 0.1 0.0 92.66 9236 92.36 030 0.00 0.l 0.0 92.66 92.26 92.26 0.40 0.00 0.1 0.0 92.66 91.67 91.67 0.99 0.00 0.1 0.0 93.28 923B 92.38 0.90 O.

2.8 I.1 94.75 91.11 91.11 3.64 0.00

ECP 050500255 - 34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130

,reject:

E4C-090 REV.3 ICCN C-130 E:TAP ev

.15.0.0N T

Page 63 of 6 CCN No.

Page:

29 Dale:

05-24-2005 SN:

SCALEDISON Revisiorn Base Conflig.:

090-3Al4aa iocalion:

aUNU4 M&

.2 Cor.tract:

Engineer W. P. Lennantz Filename:

E4C090 Study Case: 3A14aa ECPO50500255-34 ICCN C-130 UNlT3 TRAINA Alert Summary Rcport

% Alert Settings Critical Loadine Bus Cable Reactor Line Transforiner Panel Protective Device Generator Bus Voltage OverVoltnee UnderVoltage Generator Excitation OyerExcited (Q Max.)

UnderExcited (Q Mim) 0.0 0.0 0.0 100.0 0.0 100.0 0.0 0.0 0.0 0.0 0.0 95.0 0.0 95.0 0.0 0.0 130.0 70.0 1000.0

-100.0 0.0 0.0 ID 2000 30002 3G003 Critical Report DecTkeype Ratlng Unit Cakulated SfNg.

Condition Genertor 0.000 MW 0.000 UmderPower Generator 0.eo MW 0.000 UnderPower Geunetor 0.000 MW o000 UnderPower Ger.n tor 0.000 MW O o00 UnderPower

ECP 050500255-34 Rev. 0 Calc. No. E4C-090 Rev. 3 AUXILIARY SYSTEM VOLTAGE REGULATION ICCN C - 130 Project:

E4C-090 REV.3 lCCN C-130 ETAP location:

SONGS 2 & 3 5.0.0N I

I Page A

of C't CCN No.

Page:

30 Date:

05-24-2005 SN:

SCALEDISON Revision:

Base Colxig,:

090-3Al4aa Contract:

Engineer W. P. Lennartz Filenamre:

E4C090 Study Case: 3A14aa ECP050500255-34 ICCN C-130 UNIT3 TRAINA

SUMMARY

OF TOTAL GENERATION, LOADING & DEMAND Source (Swing Buses):

Source (Non-Swing Buses):

Total Demand:

Total Motor Load:

Total Static Load:

Apparent Losses:

MW 22.08B O.OW0 22.088 19.073 2.795 0.219 Mvar 13.930 0.000 13.930 10.656 0.861 2.412 MVA 26.113 0O0 26.113 21.S48

% Pr 8458 Lagging 100.00 Lagging 84.58 Lagging 87.30 Lagging Systern Mismatch:

0.000 0Q000 Number of Iterations: I