,1 Richard Emch - FW: Whiteville to Fayetteville Page 1 Richard Emch - FW: Whiteville to Fayetteville Page 1 tI I

From:

To:

Date:

Subject:

"Kozyra, Jan" <jan.kozyra~pgnmail.com>

"Richard Emch" <RLE@nrc.gov>

Wed, Mar 30, 2005 1:53 PM FW: Whiteville to Fayetteville I have received the following from Tetra tech regarding the induced shock issue for the Whiteville-to-Fayetteville transmission line:

Tetra Tech NUS examined the plan and profile drawings (TD-1 1680, sheets 30A to 63) for the Whiteville-to-Fayetteville spans of the Brunswick-to-Fayetteville transmission line, identifying 30 paved road crossings. Almost all crossings had clearances greater than 40 feet at either 200 degrees Fahrenheit or 212 degrees Fahrenheit, depending on the specific drawing. Three exceptions had clearances as follows:

NCSR 2023 at 2900+76 NCSR 1134 at 3380+371 NCSR 119 at 3807+61 39 feet 36 feet 36 feet The spans used the standard medium tangent H-frame used by all the Brunswick transmission lines.

These specific road crossings were compared with previous analyses for Brunswick transmission lines, the lowest clearances of which had the following induced current.

Line Location Road Clearance Induced Current Whiteville 816+53 US 17

Richard Emch - FW: Whiteville to Favetteville

-Page 2 i Richard Emch - FW: Whiteville to Favetteville Pane 2 ii 35 feet 1.8 ma Jacksonville 1000+10 US 17 28 feet 1.9 ma Delco West 1431+38 SR 1849 27 feet 2.8 ma Delco East 1551+88 US 74/76 30.5 feet 1.8 ma Tetra Tech NUS concludes that given the similar construction, the clearances for the Whiteville-to-Fayetteville spans, ranging from 36 to 39 feet, would have lower induced current than those analyzed with clearances from 27 to 35 feet. Accordingly, the analysis results presented in Progress Energy's Environmental Report, Operating License Renewal Stage, Brunswick Steam Electric Plant would bound the impacts of the Whiteville-to-Fayetteville spans.

CC:

'Moore, Philip' <MooreP~ttnus.com>

c:\\termp\\qW)00001.TMP Page11 Mail Envelope Properties (424AF5B9.CBA: 9: 36026)

Subject:

FW: Whiteville to Fayetteville Creation Date:

Wed, Mar 30, 2005 1:53 PM From:

"Kozyra, Jan" <jan.kozyra@pgnmail.com>

Created By:

jan.kozyra@pgnmail.com Recipients nrc.gov OWGWPOO2.HQGWDO01 RLE (Richard Emch) ttnus.com MooreP CC (Philip Moore)

Post Office Route OWGWPO02.HQGWDO01 nrc.gov ttnus.com Date & Time Wednesday, March 30, 2005 1:53 PM Files MESSAGE TEXT.htm Mime.822 Options Expiration Date:

Priority:

Reply Requested:

Return Notification:

Concealed

Subject:

Security:

Size 1675 17070 1

None Standard No None No Standard