TABLE TS 4.1-1 MINIMUM FREQUENCIES FOR CHECKS, CALIBRATIONS AND TEST OF INSTRUMENT CHANNELS CHANNEL DESCRIPTION CHECK CALIBRATE TEST REMARKS
- 18. a. Containment Each shift Each refueling cycle Monthly(a)
(a) Isolation Valve Signal Pressure (SIS signal)
- b. Containment Each shift(a)
Each refueling cycle(a)
Monthly(a)
(a) Narrow range containment pressure Pressure
(-3.0, +3.0 psig excluded)
(Steamline Isolation)
- c. Containment Each shift Each refueling cycle Monthly Pressure (Containment Spray Act)
- d. Annulus Pressure Not applicable Each refueling cycle Each refueling (Vacuum Breaker) cycle
- 19. Radiation Monitoring Daily (a,b)
Each refueling cycle (a)
Quarterly (a)
(a) Includes only channels R1 1 thru R1 5, R1 9, System R21, and R23 (b) Channel check required in all plant modes
- 20. Deleted
- 21. Containment Sump Level Not applicable Not applicable Each refueling cycle
- 22. Accumulator Level and Each shift Deleted Not applicable Pressure
- 23. Steam Generator Each shift Each refueling cycle Monthly Pressure I
Page 4of 7 heondnt iNb. 182
TABLE TS 4.1-1 MINIMUM FREQUENCIES FOR CHECKS, CALIBRATIONS AND TEST OF INSTRUMENT CHANNELS CHANNEL DESCRIPTION CHECK CALIBRATE TEST REMARKS
- 24. Turbine First Stage Each shift Each refueling cycle Monthly Pressure
- 25. Deleted
- 26. Protective System Logic Not applicable Not applicable Monthly Includes auto load sequencer Channel Testing
- 27. Deleted
- 28. Deleted
- 29. Seismic Monitoring Each refueling Each refueling cycle Not applicable System cycle
- 30. Fore Bay Water Level Not applicable Each refueling cycle Each refueling cycle
- 31. AFW Flow Rate (a)
Each refueling cycle Not applicable (a) Flow rate Indication will be checked at each unit startup and shutdown
- 32. PORV Position Indication Monthly Each refueling cycle Not applicable
- a. Back-up Monthly Each refueling cycle Not applicable (Temperature)
- 33. PORV Block Valve Monthly Each refueling cycle Not applicable Position Indicator I
Amendment No.
182 Page 5 of 7