Permit NC0007064 STATE OF NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF WATER QUALITY PERMIT TO DISCHARGE WASTEWATER UNDER THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES)
In compliance with the provision of North Carolina General Statute 143-215.1, other lawful standards and regulations promulgated and adopted by the North Carolina Environmental Management Commission, and the Federal Water Pollution Control Act, as amended, Progress Energy Carolinas, Inc.
is hereby authorized to discharge wastewater from outfalls located at the Brunswick Steam Electric Plant NC Highway 87, Southport Brunswick County to receiving waters designated as the Atlantic Ocean below the Cape Fear River Basin in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts I, H, III, IV and V hereof.
This permit shall become effective August 1, 2003.
This permit and authorization to discharge shall expire at midnight on November 30, 2006.
Signed this day June 30, 2003.
an Klimek, P.E., Dir ctor if7 Division of Water Quality By Authority of the Environmental Management Commission
SUPPLEMENT TO PERMIT COVER SHEET Progress Energy Carolinas, Inc. is hereby authorized:
- 1. to continue operating a 1,900 MGD cooling water system consisting of an intake structure, 9.6 miles of intake and effluent canals connected via internal Outfalls 00land 002, circulation pumps, siphons under the intra-coastal waterway, a discharge pump station at Oak Island, and final discharge conduits terminating 2,000 feet off shore; all necessary appurtenances to withdraw cooling water from the Cape Fear River near Snow Marsh, and thereby to discharge cooling water into the Atlantic Ocean; and
- 2. to continue operating and discharging via internal Outfall 004 (see attached map), a 0.055 MGD domestic wastewater treatment plant (WWTP) consisting of influent pumps, bar screen, flow measuring device, aeration tank, secondary clarifier and chlorination chamber; and
- 3. to continue discharging via internal Outfall 010 (see attached map), and continue operating the existing 0.036 MGD Support Services domestic W'bVTP (previously permitted under NC0083895) consisting of an influent duplex pump station, manually cleaned bar screen, flow EQ basin, flow splitter box, two (2) aeration basins, two (2) clarifiers, two (2) tertiary filters, aerobic sludge digestor with airlift sludge pump, baffled chlorine contact chamber with two (2) tablet chlorinators, and an effluent flow v-notch weir measuring device; and
- 4.
to begin operating additional "helper' cooling facilities and begin discharging 0.187 MGD of cooling tower blowdown (if installed) to Outfall 011, then to Outfall 005 to the Intake Canal (see attached map); and
- 5.
to continue to discharge treated metal cleaning wastes (Outfall 006), treated low-volume wastes and stormwater (Outfall 005) to the Intake Canal; and
- 6. to continue operating a diversion fence located at the mouth of the intake canal; and
- 7.
to continue operating fine-mesh screens, as described under Part 1, A.(L.) Outfalls 00land 002 at intake pump bays; and
- 8. to continue to operate an intake pump system to minimize intake flow rate; and
- 9.
to discharge stormwater from Outfalls 007, 008, and 009 (see attached map) into Nancy's Creek, classified as Class SC-Sw-HQW waters within the Cape Fear River Basin; and
- 10. to discharge stormwater, wastewater, and cooling water via internal outfalls from said treatment works, Intake Canal, and Discharge Canal (see Attachment 1) into the Atlantic Ocean, Class SB waters; located at the Brunswick Steam Electric Plant on NC Highway 87, Southport, Brunswick County.
All discharges shall conform to the attached schedules:
Part 1:
Wastewater Monitoring, Controls and Limitations for Permitted Discharges Part 11:
Stormwater Monitoring, Controls and Limitations for Permitted Discharges Part III:
Standard Conditions for NPDES Permits Part IV:
Other Requirements Part V:
Annual Administering and Compliance Monitoring Fee Requirements This permit does not relieve the permittee from responsibility to comply with any other applicable federal, state or local law, rule, standard, ordinance, order, judgement or decree.
Brunswick Steam Electric Plant Facility Location Intake and Discharge Infrastructure I
4nti tudle:
33° 53 31" N I ongludle:
Atlantic Ocean SB State Gridlairln:
L 26 NE / Southport. NC 4
78 03' 22" W P-rrnittel FFl-: 190 SIG Drainage Basin:
Cape Fear River Basin Sub-Basin:
03-06-17 l
nt t scle x
I
- ..T*
INI PDES Permit No. NC0007064.
N~o rt l j Brunswick County Reeriving Stremrn:
Sit re I
CasvI
Sludge.
I.
t~~~~meqenq~releaseto
_.Ya
- Imat, dischartage (001) 1 Puming
~...
(to 1 900MNGD).
(011)
Proposed "helper (002)
Coollng Condensate
.owdon_
Unit 2 Service lJ (010)
Low Volume (005)(0.187 MD es)
Retention Pond
.Support Fadilities Sewage Treatment"*
Unit 2 Condenser
'ear River 1
Cooling WVater 0.036 MGD Diversion Structure Intake Csnal
-1,600 NMGD Outfall Flow Chart -- Permit Attachment 1 Brunswick Steam Electric Plant NPDES Permit NC0007064
- Radwaste Treatment Facility emuent (non-radioactive) at Internal Outfall 003 may be combined with either Unit I or Unit 2 coolinig/service water Modified after BSEP Renewal Application.
Form 2C - Item 11 - A New Internal outfall (previously permitted under NC0083895 - to be rescinded)
Flows, Sources of Pollution, (001)
Internal Oultal Number (typical). Stonmwater outtalls discharging to Nancy's Creek (007, 008, and 009) are not included.
and Treatment Technologies Page 1 of J lune 2003
Brunswick Steam Electric Plant Internal Outfalls 001 through 006, 010 and 011 I.fLtitt(ie:
33° 53' 31 N
L~oneituj(k Receivin2 Strein:m Atlantic Ocean Stream ('iass:
SB State CGri(VItimd:
78 03' 22 W
Drainage Basin:
SuhbBasin:
L 26 NE f Southport, NC Permitted Flow:
19C Cape Fear River Basin 03-06-17
Brunswick Steam Electric Plant Stormwater Outfalls 007, 008 and 009 Latitudle:
33 53' 31" N Lonoithdle:
Receiving Stream:
Atlantic Ocean Stre-an (Ilass:
SB State Crid/Ouad:
78° 0 22" W Drainage Basin:
Sub-B:-icin:
L 26 NE / Southport. NC Permitted Flow:
19C Cape Fear River Basin 03-06.17
Permit NC0007064 A. (1.)
EFFLUENT LIMITATIONS AND MONITORING REQUIRENENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge once-through cooling and non-contact service water through Outfalls 001 and 002. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent Characteristics Di; cha Lftit iatfons.;t":
- o* --
nit ihg'R qui em s Monthly Weekly Daily Maximum Measurement Sample Type Sample Average Average Frequency Location 1 Cooling Water Flow 2 Continuous Pump Logs /
Recording For April - November 1105 cf6 / unit 3,4 For December - March 922 cfs / unit
- 1. Unless otherwise specified, the permittee shall sample the effluent of each individual generating unit prior to mixing with other waste streams. During periods of refueling and other outages at zero reactor power, the Permittee shall maintain minimum unit flows required for the safe and efficient operation & maintenance of plant systems.
-2. During a generating-unit outage (one unit not in operation), the Permittee may increase flow to the remaining operating unit as needed, provided that the total cooling water flow does not exceed the maximum flow limit for two-unit operation.
- 3. During the months of July, August and September, one unit only may increase its flow to 1230 cfs. At times when the system demand is within 200 IvIW of available system reserves, the Permittec may suspend flow limitations upon notice to the Regional Supervisor. Notice shall include anticipated flow rates and an estimate of the duration of flow rates in excess of those otherwise allowed. Excursions up to eight hours per week are allowed to clean debris from filters. Three hours per week are allowed for testing of backup pumps and related equipment.
- 4. cfs/unit = cubic feet per second per generating unit NOTE: Part m A.7.a. identifying low limits as Monthly Averages is not applicable to flow requirements for 001 and 002.
Part I Page I
Permit NC0007064 A. (1.) EFFLUENT LIMITATIONS AND MONITORING REQUIRE, MENTS -- Cofitinued FINE MESH SCREENS - Two and a half (21/2) fine mesh screens shall be maintained on the plant intake structure such that intake cooling water flowing into three (3) pump bays per generating unit will continuously pass through the two and a half (21/2) fine mesh screens. The fourth bay will be maintained with'one half (1/2) fine mesh screens such that, if this fourth pump bay is put in service, cooling water will pass through'one half (1/2) fine mesh screen in this bay only. If the Circulating Water Intake Pumps are in jeopardy of tripping as a result of high differential pressure across the traveling screens, the fine mesh screens may be temporarily removed to prevent or mitigate unplanned decreases in power or plant trips. The fine mesh screens will be reinstalled when conditions permit the Circulating Water Intake Pumps to sustain continuous operation. Should the use of at least two and a half (21/2) fine-mesh pumped bays be impossible as a result of screen failure or other malfunction, the Permittee shall provide explanation in the monthly report stating the cause(s) of the malfunction, duration and corrective action(s) taken by the plant. For testing purposes, pumps may be operated when not in compliance with the fine mesh screen requirements.
Preventative maintenance of the fine mesh screens is allowed during periods when the generating unit is operating, if such work is accomplished in the time.between one hour after sunrise and one hour before sunset. Preventative maintenance as requir4d at other times is allowed; however, the Permittee shall report monthly the total time that screens are out of service for such maintenance. CP&L'shall maintain a record of fine-mesh screen total maintenance outages.
DIVERSION FENCE - A diversion fence located at the mouth of the intake canal shall be continuously operated and maintained in such a manner as to minimize impingement. A biological monitoring program shall be continued which will provide sufficient information to allow for a continuing assessment of the impact of the Brunswick Steam Electric Plant on the Cape Fear estuary, with particular emphasis on the marine fisheries. Data shall be reported annually and shall include an interpretive summary report assessing the effectiveness of the diversion fence, and the effectiveness of flow minimization and fine mesh screens to curtail organism impingement and entrainment. The Director of the Division of Water Quality shall approve any major changes in the biological monitoring program.
CHLORINE -There shall be no discharge of Total Residual Chlorine (total residual oxidants) at the ocean outfall. Total Residual Chlorine or total residual oxidants are to be measured weekly at the Caswell Beach Pump Station by multiple grab samples.
Part I Page 2
Permit NC0007064 A. (1.)
EFFLUENT LIMITATIONS AND MONITORING REQUIRE MENTS -- Continued TEMPERATURE - Cooling-water system facilities shall be effectively maintained and operated so as to 'meet the temperature standards assigned to the Atlantic Ocean: 0.80C (1.440F) increase above ambient water temperature during the months June through August; 2.20C (3.960F) increase above ambient water temperature during the months September through May. In no case should the temperature exceed 320C (89.60F) due to the discharge of heated liquid measured three (3) feet below the water surface except within the following defined mixing zones:
(a).
The temperature increase above ambient water temperature shall not exceed 70F outside an area of 120 acres included within the plume extending from the point of discharge.
(b).
The temperature increase above ambient water temperature shall not exceed 0.80C (1.440F) increase above ambient water temperature during the months of June through August; 2.20C (3.96°F) increase above ambient water temperature during the months of September through May. In no case should the temperature exceed 321C (89.60F) outside an area of 2000 acres.
- (c).
The temperature increase above ambient water temperature at the bottom (defined as one foot above the ocean floor) shall not exceed 70F for more than 1000 feet from the point of discharge, nor for an area of more than four (4) acres.
Temperature monitoring at the ocean discharge shall be conducted semiannually, once during the months of April - November and once during the months of December -March. Reactor power levels should be at least 85% for each unit on the date of monitoring. If it is determined by this Division that the water quality standards or conditions of this permit are being violated or being threatened (within 90% of the limitations or standards), additional monitoring may be required.
Temperature shall be monitored within a 2320-acre rectangular mixing zone defined by two (2) sampling grids; one near the ocean surface (three feet below the water surface) and the second near the bottom (one foot above the ocean floor). Temperatures shall be recorded at locations sufficient in number to establish compliance with Water Quality Standards. If sufficient temperature variation exists, the permittee shall plot 1PF isotherms to report surface and bottom conditions. The permittee shall likewise establish and report ambient temperatures beyond each grid by averaging four (4) temperature measurements -- each measurement to be taken approximately 1500 feet beyond a different mixing-zone corner on a baring approximately 1350 relative to each sampling grid.
The Permittee shall discharge no polychlorinated biphenyl compounds such as those used for transformer fluid.
Discharge at the ocean outfall shall contain no floating solids or foam visible in other than trace amounts.
Part I Page 3
Permit NC0007064 A. (2.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS.
During the period beginning on the effective date of the permit and lasting~until expiration, the Permittee is authorized to discharge Radwaste Treatment System effluent through Outfall 003. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent Characteristics Disceiai'gEim'iita ions.,.,
oiiitorixigRcquircmcnts Monthly Weekly Daily Measurement Sample Sample Average Average Maximum Frequency Type Location 1 Flow Annually Instantaneous I or E Total Suspended Solids 30.0 mg/L 100.0 mgfL Annually Grab E
Oil and Grease 15.0 mgfL 20.0 mg/L Annually Grab E
- 1. To determine permit compliance, the Pernittee shall collect samples of Radwaste Treatment discharge prior to mixing with other sources of wastewater.
Explanation:
I E
mg/L
= influent
= effluent
= milligrams per-liter Part I Page 4
Permit NC0007064 A. (3.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Pernittee is authorized to discharge treated domestic wastes from the onsite Wastewater Treatment Plant through Outfall 004. Such discharges shall be limited and, monitored by the Permittee as specified below:
EfuenflChardi ct-i'd tsrrcs'
.Io i
.f.
'l'2Monit in
_i,___________
Monthly Weekly Daily Measurement Sample Type Sample Average Average Maximum Frequency Location 1 Flow 0.055 MGD Weekly Instantaneous I orE BOD, 5-Day, 20'C 30.0 mg/L 45.0 mg/L
- Weekly, Grab E
Total Suspended Solids 30.0 mg/LL 45.0 mg/L Weekly Grab E
- 1. To determine permit compliance, the Permittee shall sample plant effluent prior to mixing with other waste streams.
Explanation:
I E
MGD BOD mg/L influent effluent million gallons per day-biochemical oxygen demand milligrams per liter Part I Page 5
Permit NC0007064 A. (4.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge stormwater, metal cleaning wastes, low-volume wastes, and cooling tower blowdown. (if installed), through Outfall 005. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent-Ch'arcteri tics H
>or'~sltr ifntat n i.r,-:s:t^!.
M ir
- etiee Monthly Weekly Daily Measurement Sample Sample Average Average*
Maximum Frequency Type Location Flow
_Weekly Instantaneous E
Total Suspended Solids 30.0 mg/L 45.0 mg/L Weekly Grab E
Oil and Grease 15.0 mg/L 45.0 mg/L Weekly Grab E
Explanation:
E
=
mg/L =
effluent milligrams per liter Part I Page 6
Permit NC0007064 A. (S.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge Metal Cleaning Wastes through Outfall 006. Such discharges shall be limited and monitored by the Permittee as specified below:
EffluentCharacteristics' 9.
e Re ifiiure ents - '
Monthly Weekly Daily Measurement Sample Sample Average Average Maximum Frequency Type Location Total Suspended Solids 30.0 mg/L 100.0 mg/L Episodic Grab E
Oil and Grease 15.0 mg/L 20.0 mg/L Episodic Grab E
Total Copper 1.0 mg/L 1.0 mg/L Episodic
'Grab E
Total Iron 1.0 mg/L 1.0 mg/L Episodic Grab E
Explanation:
E mg/L effluent milligrams per liter Part I Page 7
Permit NC0007064 A. (6.)
EFFLUE NT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective-date of the permit and lasting until expiration, the Permittee is authorized to discharge stormwater from the Trash Separation Area through Outfall 007. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent:Chateistics:. '
i r
e i Monthly Weekly Daily Measurement Sample Sample Average Average Maximum Frequency Type Location 1 Flow2 E
Total Rainfall2 (inches)
Event Duration 2 (minutes)
Total Suspended Solids Annual Grab E
Oil and Grease Annual Grab E
Table Footnotes:
- 1) Sample location: E - Effluent
- 2) For each representative storm event, the Permnittee shall monitor total precipitation, storm duration, and total flow.
Total flow shall be either; (a) measured continuously; (b) calculated based on the surface area draining to the outfall, the built-upon (impervious surface) area, and the total rainfall; or (c) estimated by measuring flow at the outfall every 20 minutes during each rain event.
Discharge at the outfall shall contain no floating solids or foam visible in other than trace amounts.
Part I Page 8
Permit NC0007064 A. (7.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge stormw"atcr from the Sivitchyard Area through Outfall 008 -. Such discharges shall be limited and monitored by the Permittee as specified below:
EffWug tCiiarafer stics h-art ifbrinReii
__a;__
Monthly Weekly Daily Measurement Sample Sample Average Average Maximum Frequency Type Location 1 Flow2 E
Total Rainfall 2 (inches)
Event Duration2 (minutes)
Total Suspended Solids Annual Grab E
Oil and Grease
- _I_
_Annual Grab E
1)
Sample location: E - Effluent
- 2)
For each representative storm event, the Permittee shall monitor total precipitation, storm duration, and total flow. Total flow shall be either; (a) measured continuously; (b) calculated based on the surface area draining to the outfall, the built-upon (impervious surface) area, and the total rainfall; or (c) estimated by measuring flow at the outfall every 20 minutes during each rain event.
Discharge at the outfall shall contain no floating solids or foam visible in other than trace amounts.
Part I Page 9
Permit NC0007064 A. (8.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge stormwater through Outfall 009. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent Clacis'ct k'5' i- -R-uiet ts Monthly Weekly Daily Measurement Sample Sample Average Average Maximum Frequency Type Location 1 Flojv2 E
Total Rainfall 2 (inches)
Event Duration2 (minutes)
Total Suspended Solids Annual Grab E
Oil and Grease Annual Grab E
- 1. Sample location: E-Effluent
- 2. For each representative storm event, the Permittee shall monitor total precipitation, storm duration, and total flow.
Total flow shall be either; a) measured continuously; b) calculated based on the surface area draining to the outfall, the built-upon (impervious surface) area, and the total rainfall; or c) estimated by measuring flow at the outfall every' 20 minutes during each rain event.
Discharge at the outfall shall contain no floating solids or foam visible in other than trace amounts.
Part I Page 10
Permit NC0007064 A. (9.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee.is authorized to discharge treated domestic wastes from the onsite Support Facilities Wastewater Treatment Plant through Outfall 010. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent. CliaractcristiesF.
n i
Linit ti
-Monitof i
eguiremr ts Monthly Weekly Daily Measurement Sample Type Sample Average Average Maximum Frequency Location 1 Flow 0.036 MGD Weekly Instantaneous I or E BOD, 5-Day, 200C 30.0 mg/L 45.0 mg/L Weekly Grab E
Total Suspended Solids 30.0 mg/L 45.0 mgJL Weekly Grab E
- 1. To determine permit compliance, the Permittee shall sample plant effluent prior to mixing with other waste streams.
Explanation:
I influent E
effluent BOD
=
biochemical oxvyen demand
- MGD =
mg/L =
million gallons per day milligrams per liter
- Part I Page 11
Permit NC0007064 A. (10.)
EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge Cooling Tower blowdown (if installed) through Outfall 011. Such discharges shall be limited and monitored by the Permittee as specified below:
Effluent Characteristics' Di-charge:.Li'iitaiti'6n so.;
M'IIi'tring Requirements Monthly Weekly Daily Measurement Sample Type Sample Average Average Maximum Frequency Location EPA Priority Pollutants1 Annually Grab E
Total Chromium
.200.0
_g/L 200.0 ptg[L_
Weekly Grab E
Total Zinc 1.0 mg__L 1.0 mg/L Weekly Grab E
Explanation:
mg/L E
milligrams per liter micrograms per liter effluent I
These parameters [required under 4OCFR 423.13 (d)(1)] apply only if the permittee adds these materials for cooling tower maintenance. There shall be no detectable amounts of the 126 priority pollutants (40CFR 423, Appendix A) contained in chemicals added to the cooling towers except for Total Chromium and Total Zinc.
Part I Page 12
PART I (continued)
Section B. Schedule of Compliance
- 1. The permittee shall comply with Final Effluent Limitations specified for discharges in accordance with the following schedule:
Permittee shall comply with Final Effluent Limitations by the effective date of the permit unless specified below.
- 2. Permittee shall at all times provide the operation and maintenance necessary to operate the existing facilities at optimum efficiency.
- 3.
No later than 14 calendar days following a date identified in the above schedule of compliance, the permittee shall submit either a report of progress or, in the case of specific actions being required by identified dates, a written notice of compliance or noncompliance. In the latter case, the notice shall include the cause of noncompliance, any remedial actions taken, and the probability of meeting the next schedule requirements.
Permit NC0007064 PART II STORMWATER MONITORING, CONTROLS AND LIMITATIONS FOR PERMITTED DISCHARGES SECTION A: FINAL LIMITATIONS AND CONTROLS FOR STORMWATER DISCHARGES During the period beginning on the effective date of the permit and lasting until expiration, the permittee is authorized to discharge wastewater and stormwater associated with industrial activity. Such discharges shall be controlled, limited and monitored as specified below.
- 1.
Stormwater Pollution Prevention Plans The permittee shall develop a Stormwater Pollution Prevention Plan, herein after referred to as the Plan.
The Plan shall be considered.public information in accordance with Part m, Standard Conditions, Section E.10. of this permit. The Plan shall include, at a minimum, the following items:
- a.
Site Plan: The site plan shall provide a description of the physical facility and the potential pollutant sources which may be expected to contribute to contamination of regulated stormwater discharges. The site plan shall contain the following:
(I) A general location map (USGS quadrangle map, or appropriately drafted equivalent map), showing the facility's location in relation to transportation routes and surface waters, and the name of the receiving water(s) to which the stormwater outfall(s) discharges. If the discharge is to a municipal separate storm sewer system, the name of the municipality and the ultimate receiving waters, and accurate latitude and longitude of the point(s) of discharge must be shown.
(2) A narrative description of storage practices, loading and unloading activities, outdoor process areas, dust or particulate generating or control processes, and waste disposal practices.
(3) A site map (or series of maps) drawn to scale with the distance legend indicating location of industrial activities (including storage of materials, disposal areas, process areas, and loading and unloading areas), drainage structures, drainage areas for each outfall and activities occurring in the drainage area, building locations and impervious surfaces, the percentage of each drainage area that is impervious. For each outfall, a narrative description of the potential pollutants which could be expected to be present in the regulated stormwater discharge.
(4) A list of significant spills or leaks of pollutants that have occurred at the facility during the 3 previous years and any corrective actions taken to mitigate spill impacts.
(5) Certification that the stormwater outfalls have been evaluated for the presence of non-stornwater discharges. The certification statement will be signed in accordance with the requirements found in Part III, Standard Conditions, Section B.1 1.
- b.
Stormwater Management Plan: The stormwater management plan shall contain a narrative description of the materials management practices employed which control or minimize the exposure of significant materials to stormwater, including structural and non-structural measures.
The stormwater management plan, at a minimum, shall incorporate the following:
Part 11 Page 1
Permit NC0007064 (1)
A study addressing the technical and economic feasibility of changing the methods of operations and/or storage practices to eliminate or reduce exposure of materials and processes to stormwater.
Wherever practicable the permittee should consider covering storage areas, material handling operations, manufacturing or fueling operations to prevent materials exposure to stormwater. In areas where elimination of exposure is not practicable, the stormwater management plan shall document the feasibility of diverting the stormwater runoff away from areas of potential contamination.
(2)
A schedule to provide secondary containment for bulk storage of liquid materials, storage of Section 313 of Title III of the Superfund Amendments and Reauthorization Act (SARA) water priority chemicals, or storage of hazardous materials to prevent leaks and spills from contaminating stornwater runoff. If the secondary containment devices are connected directly to storrnwater conveyance systems, the connection shall be controlled by manually activated valves or other similar devices [which shall be secured with a locking mechanism] and any stormwater that accumulates in the containment area shall be at a minimum visually observed prior to release of the accumulated stormwater. Accumulated stormwater shall be released if found to be uncontaminated. Records documenting the individual making the observation, the description of the accumulated stormwater and the date and time of the release shall be kept for a period of five years.
(3)
A narrative description of Best Management Practices (BMPs) to be considered such as, but not limited to, oil and grease separation, debris control, vegetative filter strips, infiltration and stormwater detention or retention, where necessary. The need for structural BMPs shall be based on the assessment of potential of sources contributing significant quantities of pollutants to storrnwater discharges and data collected through monitoring of stormwater discharges.
(4)
Inspection schedules of stormwater conveyances and controls and measures to be taken to limit or prevent erosion associated with the stormwater systems.
- c.
Spill Prevention and Response Plan: The Spill Prevention and Response Plan shall incorporate a risk assessment of potential pollutant sources based on a materials inventory of the facility.
Facility personnel (or team) responsible for implementing the plan shall be identified in the plan.
A responsible person shall be on-site at all times during facility operations that have the potential to contaminate storrnwater runoff through spills or exposure of materials associated with the facility operations.
- d.
Preventative Maintenance and Good Housekeeping Program: A preventative maintenance program shall be developed. The program shall document schedules of inspections and maintenance activities of stormwater control systems, plant equipment and systems. Inspection of material handling areas and regular cleaning schedules of these areas shall be incorporated into the program.
- e.
Training schedules shall be developed and training provided at a minimum on an annual basis on proper spill response and cleanup procedures and preventative maintenance activities for all personnel involved in any of the facility's operations that have the potential to contaminate stormwater runoff. Facility personnel (or team) responsible for implementing the training shall be identified in the plan.
- f.
The Stormwater Pollution Prevention Plan shall identify a specific position(s) responsible for the overall coordination, development, implementation, and revision to the Plan. Responsibilities for all components of the Plan shall be documented and position(s) assignments provided.
- g.
Plan Amendment: The permittee shall amend the Plan whenever there is a change in design, construction, operation, or maintenance which has a significant effect on the potential for the Part I1 Page2
Permit NC0007064 discharge of pollutants via a point source to surface waters. The Stormwater Pollution Prevention Plan shall be reviewed and updated on an annual basis.
The director may notify the permittee when the Plan does not meet one or more of the minimum requirements of the permit. Within 30 days of such notice, the permittee shall submit a time schedule to the Director for modifying the Plan to meet minimum requirements. The permittee shall provide certification in writing (in accordance with Part m, Standard Conditions, Section B.1 1.) to the Director that the changes have been made.
- h.
Facility Inspections: Inspections of the facility and all stormwater systems shall occur at a minimum on a semiannual schedule, once in the fall (September - November) and once during the spring (April - June). The inspection and any subsequent maintenance activities performed shall be documented, recording date and time of inspection, individual(s) making the inspection and a narrative description of the facility's stormwater control systems, plant equipment and systems. Records of these inspections shall be incorporated into the Stormwater Pollution Prevention Plan.
Visual monitoring as required in Part II, Section A.3.b. shall be performed in addition to facility inspections.
- i.
Implementation: Implementation of the Plan shall include documentation of all monitoring, measurements, inspections, maintenance activities and training provided to employees, including the log of the sampling data. Activities taken to implement BMPs associated with the industrial activities, including vehicle maintenance activities, must also be recorded. All required documentation shall be kept on-site for a period of five years and made available to the Director or his authorized representative immediately upon request.
- 2.
Minimum Monitoring and Reporting Requirements Minimum monitoring and reporting requirements are as follows unless otherwise approved in writing by.
the Director of the Division of Water Quality:
- a.
If a facility has multiple discharge locations with substantially identical stormwater discharges that are required to be sampled, the permittee may petition the Director for representative outfall status. If it is established that the stormwater discharges are substantially identical and the permittee is granted representative outfall status, then sampling requirements may be performed at a reduced number of outfalls.
- b.
Visual monitoring for.color, odor, solids, foam, outfall staining, visible sheens and dry weather flow shall be performed at all stormwater discharge outfall locations. All visual monitoring shall be documented and records maintained with the Stormwater Pollution Prevention Plan. The initial visual monitoring event shall be performed simultaneously with the first analytical monitoring event and documentation of only this initial visual monitoring event shall be submitted along with the required analytical monitoring submittal.
- c.
For purposes of the stormwater sampling required in this perrnit, all samples shall be collected from a discharge resulting from a representative storm event (See definitions in Part m, Standard Conditions). Failure to monitor storm events in accordance with the specified frequency shall constitute a violation of this permit. If the stormwater runoff is controlled by a detention pond, the following sampling requirements shall apply:
Part I1 Page 3
Permit NC0007064 (1)
If the detention pond detains the runoff generated by one inch of rainfall for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, visual observations for color, foam, outfall staining, visible sheens and dry weather flow are required, but analytical sampling shall not be required.
(2)
If the detention pond discharges only in response to a storm event exceeding a 25-year, 24-hour storm (See Part II, Standard Conditions, Section A), the pond shall-be considered a non-discharging stormwater control system and not subject to NPDES requirements, unless the discharge causes a violation of water quality standards.
- d.
Samples analyzed in accordance with the terms of this permit shall be submitted on forms approved by the Director no later than January 31 for the previous year in which sampling was required to be performed.
- e.
Analytical results from sampling during the final year of the permit term shall be submitted with the permit renewal application.
- f.
This permit regulates stormwater discharges associated with industrial activity. Non-storrnwater discharges which shall be allowed in the stormwater conveyance system are:
(1)
All other discharges that are authorized by an NPDES permit.
(2)
Foundation drains, air-conditioner condensate without added chemicals, springs,
\\waterline and fire hydrant, water from footing drains, flows from riparian habits and wetlands, fire-fighting training and fire system testing.
(3)
Discharges resulting from fire-fighting.
If the storm event monitored and reported in accordance with this permit coincides with a non-stormwater discharge, the permittee shall separately monitor and report all parameters as.
required under the non-stormwater portion of this permit and provide this information with the stormwater discharge monitoring report.
- b.
Visual Monitoring Visual monitoring requires a qualitative visual inspection of each stormwater outfall, regardless of representative outfall status, for the purpose of evaluating the effectiveness of the Stormwater Pollution Prevention Plan and assessing new sources of stormwater pollution. No analytical tests are required.
Visual monitoring of stormwater outfalls does not need to be performed during a representative storm event.
Stormwater Discharge Characteristics.
Frequency' Monitoring Type2 Monitoring Location3 Color Semi-annual Visual SDO Odor Semi-annual Observation SDO Clarity Semi-annual Visual SDO Floating Solids Semi-annual Visual SDO Suspended Solids Semi-annual Visual SDO Foam Semi-annual Visual SDO Oil Sheen Semi-annual Visual SDO Other obvious indicators of stormwater Semi-annual Visual SDO pollution Part 11 Page 4
Permit NC0007064 1 Frequency: The first visual monitoring event during the term of the permit must be performed during the initial analytical monitoring event. All subsequent visual monitoring will be performed twice per year, once in the spring and once in the fall.
2 Monitoring Type: Monitoring requires a qualitative observation of each stormwater outfall.
No analytical testing or sampling is required.
3 Sample Location: Stormwater Discharge Outfall (SDO).
SECTION B:
SCHEDULE OF COMPLIANCE
- 1.
The permittee shall comply with stormwater monitoring requirements and controls specified for stormwater discharges in accordance with the following schedule:
The Stormwater Pollution Prevention Plan shall be developed and implemented within 12 months of the effective date of this permit and updated thereafter on an annual basis. -Secondary containment, as specified in Part m, Section A.19. of this permit, shall be accomplished within 12 months of the effective date of this permit.
- 2.
The permittee shall at all times provide the operation and maintenance necessary to operate the permitted stormwater controls at optimum efficiency.
Part 11 Page 5
PART III STANDARD CONDITIONS FOR NPDES PERPviTS Schedule of Compliance
- 1. The permittee shall comply with Final Effluent Limitations specified for discharges in accordance with the following schedule:
Permittee shall comply with Final Effluent Limnitations by the effective date of the permit unless specified below.
- 2. Permittee shall at all times provide the operation and maintenance necessary to operate the existing facilities at optimum efficiency.
- 3. No later than 14 calendar days following a date identified in the above schedule of compliance, the permittee shall submit either a report of progress or, in the case of specific actions being required by identified dates, a written notice of compliance or noncompliance. In the latter case, the notice shall include the cause of noncompliance, any remedial actions taken, and the probability of meeting the next schedule requirements.
SECTION A. DEFINITIONS
- l.
Permit Issuing Authority:
The Director of the Division of Water Quality.
- 2. DWO or "the Division" Means the Division of Water Quality, Department of Environment and Natural Resources.
- 3. E`IC Used herein means the North Carolina Environmental Management Commission.
- 4.
Act or "the Act" The Federal Water Pollution Control Act, also known as the Clean Water Act, as amended, 33 USC 1251, et. seq.
- 5.
MIass/Day Measurements
- a.
The "monthly average discharge" is defined as the total mass of all daily discharges sampled and/or measured during a calendar month on which daily discharges are sampled and measured, divided by the number of daily discharges sampled and/or measured during such month. It is therefore, an arithmetic mean found by adding the weights of the pollutant found each day of the month and then dividing this sum by the number of days the tests were reported. The limitation is identified as "Monthly Average" in Part I of the permit.
- b. The "weekly average discharge" is defined as the total mass of all daily discharges sampled and/or measured during the calendar week (Sunday - Saturday) on which daily discharges are sampled and measured, divided by the number of daily discharges sampled and/or measured during such week. It is, therefore, in arithmetic mean found by adding the weights of pollutants found each day of the week and then dividing this sum by the number of days the tests were reported. This limitation is identified as "Weekly Average" in Part I of the permit.
- c. The "maximum daily discharge" is the total mass (weight) bf a pollutant discharged during a calendar day. If only one samn'ple is taken during any calendar day the weight of pollutant calculated from it is.the "maximum daily discharge." This limitation is identified as "Daily Maximum," in Part I of the permit.
- d. The "average annual discharge" is defined as the total mass of all daily discharges sampled and/or measured during the calendar year on which daily discharges are sampled and measured, divided by the number of daily discharges sampled and/or measured during such year. It is, therefore, an arithmetic mean found by adding the weights of pollutants found each day of the year and then dividing this sum by the number of days the tests were reported. This limitation is defined as "Annual Average" in Part I of the permit.
Permit NC0007064 - Parts III-V Page 2 of 12
- 6. Concentration Measurement
- a. The "average monthly concentration," other than for fecal coliform bacteria, is the sum of the concentrations of all daily discharges sampled and/or measured during a calendar month on which daily discharges are sampled-and measured, divided by the number of daily discharges sampled and/or measured during such month (arithmetic mean of the daily concentration values).
The daily concentration value is equal to the concentration of a composite sample or in the case of grab samples is the arithmetic mean (weighted by flow value) of all the samples collected during that calendar day. The average monthly count for fecal coliform bacteria is the geometric mean of the counts for samples collected during a calendar month. This limitation is identified as "Monthly Average" under "Other Limits" in Part I of the permit.
- b.
The "average weekly concentration," other than for fecal coliform bacteria, is the sum of the concentrations of all daily discharges sampled and/or measured during a calendar week (Sunday/Saturday) on which daily discharges are sampled and measured divided by the number of daily discharges sampled and/or measured during such week (arithmetic mean of the daily concentration values). The daily concentration value is equal to the concentration of a composite sample or in the case of grab samples is the arithmetic mean (weighted by flow value) of all the samples collected during that calendar day. The average weekly count for fecal coliform bacteria is the geometric mean of the counts for samples collected during a calendar week. This limitation is identified as "WVeekly Average" under "Other Limits" in Part I of the permit.
- c. The "maximum daily concentration" is the concentration of a pollutant discharge during a calendar day. If only one sample is taken during any calendar day the concentration of pollutant calculated from it is the "Maximum Daily Concentration". It is identified as "Daily Maximum" under "Other Limits" in Part I of the permit.
- d. The "average annual concentration," other than for fecal coliform bacteria, is the sum of the concentrations of all daily discharges sampled and/or measured during a calendar year on which daily discharges are sampled and measured divided by the number of daily discharges sampled and/or measured during such year (arithmetic mean of the daily concentration values).
The daily concentration value is equal to the concentration of a composite sample or in the case of grab samples is the arithmetic mean (weighted by flow value) of all the samples collected during that calendar day. The average yearly count for fecal coliform bacteria is the geometric mean of the counts for samples collected during a calendar year. This limitation is identified as "Annual Average" under "Other Limits" in Part I of the permit.
- e. The "daily average concentration" (for dissolved oxygen) is the minimum allowable amount of dissolved oxygen required to be available in the effluent prior to discharge averaged over a calendar day. If only one dissolved oxygen sample is taken over a calendar day, the sample is considered to be the "daily average concentration" for the discharge. It is identified as "daily average" in the text of Part I.
- f. The "quarterly average concentration" is the average of all samples taken over a calendar quarter. It is identified as "Quarterly Average Limitation" in the text of Part I of the permit.
- g. A calendar quarter is defined as one of the following distinct perioas: January through March, April through June,July through September, and October through December.
- 7.
Other Measurements
- a.
Flow, (MGD): The flow limit expressed in this permit is the 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> average flow, averaged monthly. It is determined as the arithmetic mean of the total daily flows recorded during the calendar month.
- b. An "instantaneous flow measurement" is a measure of flow taken at the time of sampling, when both the sample and flow will be representative of the total discharge.
- c.
A "continuous flow measurement" is a measure of discharge flow from the facility which occurs continually without interruption throughout the operating hours of the facility.
Flow shall be monitored continually except for the infrequent times when there may be no flow or for infrequent maintenance activities on the flow device.
Permit NC0007064 - Parts III-V Page 3 of 12
- 8. Types of Samples
- a.
Composite Sample: A composite sample shall consist of:
(1) a series of grab samples collected at equal time intervals over a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period of discharge and combined proportional to the rate of flow measured at the time of individual sample collection, or (2) a series of grab samples of equal volume collected over a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period with the time intervals between samples determined by a preset number of gallons passing the sampling point. Flow measurement between sample intervals shall be determined by use of a flow recorder and totalizer, and the present gallon interval between sample collection fixed at no greater than 1/24 of the expected total daily flow at the treatment system, or (3) a single, continuous sample collected over a 24-hour period proportional to the rate of flow.
In accordance with (1) above, the time interval between influent grab samples shall be no greater than once per hour, and the. time interval between effluent grab samples shall be no greater than once per hour except at wastewater treatment systems having a detention time of greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. In such cases, effluent grab samples may be collected at time intervals evenly spaced over the 24-hour period which are equal in number of hours to the detention time of the system in number of days. However, in no case may the time interval between effluent grab samples be greater than six (6) hours nor the number of samples less than four (4) during a 24-hour sampling period.
- b. Grab Sample: Grab samples are individual samples collected over a period of time not exceeding 15 minutes; the grab sample can be taken manually.
Grab samples must be representative of the discharge or the receiving waters.
- 9.
Calculation of Means a
Arithmetic Mean: The arithmetic mean of any set of values is the summation of the individual values divided by the number of individual values.
- b. Geometric Mean: The geometric mean of any set of values is the Nth root of the product of the individual values where N is equal to the number of individual values. The geometric mean is equivalent to the antilog of the arithmetic mean of the logarithms of the individual values. For purposes of calculating the geometric mean, values of zero (0) shall be considered to be one (1).
- c.
Weighted by Flow Value: Weighted by flow value means the summation of each concentration times its respective flow divided by the summation of the respective flows.
- 10. Calendar Day:
A calendar day is defined as the period from midnight of one day until midnight of the next day.
However, for purposes of this permit, any consecutive 24-hour period that reasonably represents the calendar day may be used for sampling.
- 11. Hazardous Substance:
A hazardous substance means any substance designated under 40 CFR Part 116 pursuant to Section 311 of the Clean Water Act.
- 12. Toxic Pollutant:
A toxic pollutant is any pollutant listed as toxic under Section 307(a)(1) of the Clean Water Act.
SECTION B. GENERAL CONDITIONS
- 1. Duty to Comply The permittee must comply with all conditions of this permit. Any permit noncompliance constitutes a violation of the Clean Water Act and is grounds for enforcement action; for permit termination, revocation and reissuance, or modification; or denial of a permit renewal application.
- a.
The permittee shall comply with effluent standards or prohibitions established under section 307(a) of the Clean Water Act for toxic pollutants and with standards for sewage sludge use or disposal established under
Permit NC0007064 - Parts III-V Page 4 of 12 section 405(d) of the Clean Water Act within the time provided in the regulations that establish these standards or prohibitions or standards for sewage sludge use or disposal, even if the permit has not yet been modified to incorporate the requirement.
- 1. b. The Clean Water Act provides that any person who violates a permit condition is subject to a civil penalty not to exceed $25,000 per day for each violation. Any person who negligently violates any permit condition is subject to criminal penalties of $2,500 to $25,000 per day of violation, or imprisonment for not more than 1 year, or both. Any person who knowingly violates permit conditions is subject to criminal penalties of
$5,000 to $50,000 per day of violation, or imprisonment for not more than 3 years, or both. Also, any person who violates a permit condition may be assessed an administrative penalty not to exceed $10,000 per violation with the maximum amount not to exceed $125,000. [Ref: Section 309 of the Federal Act 33 U.S.C.
1319 and 40 CFR 122.41 (a))
- c.
Under state law, a civil penalty of not more than ten thousand dollars ($10,000) per violation may be assessed against any person who violates or fails to act in accordance with the terms, conditions, or requirements of a permit. [Ref: North Carolina General Statutes § 143-215.6A]
- d. Any person may be assessed an administrative penalty by the Administrator for violating section 301, 302, 306, 307, 308, 318, or 405 of the Act, or any permit condition or limitation implementing any of such sections in a permit issued under section 402 of the Act. Administrative penalties for Class I violations are not to exceed $10,000 per violation, with the maximum amount of any Classi penalty assessed not to exceed
$25,000. Penalties for Class II violations are not to exceed $10,000 per day for each day during which the violation continues, with the maximum amount of any Class II penalty not to exceed $125,000.
- 2. Duty to Mitigate The permittee-shall take all reasonable steps to minirize or prevent any discharge or sludge use or disposal in violation of this permit which has a reasonable likelihood of adversely affecting human health or the environment.
- 3. Civil and Criminal Liability Except as provided in permit conditions on "Bypassing" (Part II, C-4) and "Power Failures" (Part II, C-7),
nothing in this.permit shall be construed to relieve the permittee from any responsibilities, liabilities, or penalties for noncompliance pursuant to NCGS 143-215.3, 143-215.6 or Section 309 of the Federal Act, 33 USC 1319.
Furthermore, the permittee is responsible for consequential damages, such as fish kills, even though the responsibility for effective compliance may be temporarily suspended.
- 4.
Oil and Hazardous Substance Liability Nothing in this permit shall be construed to preclude the institution of any legal action or relieve the permittee from any responsibilities, liabilities, or penalties to which the permittee is or may be subject to under NCGS 143-215.75 et seq. or Section 311 of the Federal Act, 33 USG 1321. Furthermore, the permittee is responsible for consequential damages, such as fish kills, even though the responsibility for effective compliance may be temporarily suspended.
- 5.
Property Rigthts The issuance of this permit does not convey any property rights in either real or personal property, or any exclusive privileges, nor does it authorize any injury to private property or any invasion of personal rights, nor any infringement of Federal, State or local laws or regulations.
- 6.
Onshore or Offshore Construction This permit does not authorize or approve the construction of any onshore or offshore physical structures or facilities or the undertaking of any work in any navigable waters.
- 7. Severability The provisions of this permit are severable, and if any provision of this permit, or the application of any provision of this permit to any circumstances, is held invalid, the application of such provision to other circumstances, and the remainder of this permit, shall not be affected thereby.
Permit NC0007064 - Parts II-V Page5 of 12
- 8.
Dutv to Provide Information The perrnittee shall furnish to the Permit Issuing Authority, within a reasonable time, any information which the Permit Issuing Authority may request to determine whether cause exists for modifying, revoking and reissuing, or terminating this permit or to determine compliance with this permit. The permittee shall also furnish to the Permit Issuing Authority upon request, copies of records required to be kept by this permit.
- 9. Duty to Reapply If the permittee wishes to continue an activity regulated by this permit after the expiration date of this permit, the permittee must apply for and obtain a new permit.
- 10. Expiration of Permit The permittee is not authorized to discharge after the expiration date. In order to receive automatic authorization to discharge beyond the expiration date, the permittee shall submit such information, forms, and fees as are required by the agency authorized to issue permits no later than 180 days prior to the expiration date. Any permittee that has not requested'renewal at least 180 days prior to expiration, or any permittee that does not have a permit after the expiration and has' not requested renewal at least 180 days prior to expiration, will subject the permittee to enforcement procedures as provided in NCGS 143-215.6 and 33 USC 1251 et. seq.
- 11. Signatory Requirements All applications, reports, or information submitted to the Permit Issuing Authority shall be signed and certified
[40 CFR 122.41 (k)].
- a.
All permit applications shall be signed as follows:
(1) For a corporation: by a responsible corporate officer. For the purpose of this Section, a responsible corporate officer means:
(a) a president, secretary, treasurer or vice president of the corporation in charge of a principal business function, or any other person who performs similar policy or.decision making functions for the corporation, or (b) the manager of one or more manufacturing, production, or operating facilities, provided, the manager is authorized to make management decisions which govern the operation of the regulated facility including having the explicit or implicit duty of making major capital investment recommendations, and initiating and directing other comprehensive measures to assure long term environmental compliance with environmental laws and regulations; the manager can ensure that the necessary systems are established or actions taken to gather complete and accurate information for permit application requirements; and where authority to sign documents has been assigned or delegated to the manager in accordance with corporate procedures.
(2) For a partnership or sole proprietorship: by a general partner or the proprietor, respectively; or (3) For a municipality, State, Federal, or other public agency: by either a principal executive officer or ranking elected official [40 CFR 122.22].
- b. AU reports required by the permit and other information requested by the Permit Issuing Authority shall be signed by a person described in paragraph a. above or by a duly authorized representative of that person. A person is a duly authorized representative only if:
- 1. The authorization is made in writing by a person described above;
- 2. The authorization specified either an individual or a position having responsibility for the overall operation of the regulated facility or activity, such as the position of plant manager, operator of a well or well field, superintendent, a position of equivalent responsibility, or an individual or position having overall responsibility for environmental matters for the company. (A duly authorized representative may thus be either a named individual or any individual occupying a named position.); and
- 3. The written authorization is submitted to the Permit Issuing Authority [40 CFR 122.22]
- c. Changes to authorization: If an authorization under paragraph (b) of this section is no longer accurate because a different individual or position has responsibility for the overall operation of the facility, a new autho'rization satisfying the requirements of paragraph (b) of this section must be submitted to the Director prior to or together with any reports, information, or applications to be signed by an authorized representative [40 CFR 122.22]
Permit NC0007064 - Parts III-V Page 6 of 12
- d.
Certification.
Any person signing a document under paragraphs a. or b. of this section shall make the following certification [40 CFR 122.22]:
'I certify, under penalty of law, that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gather and evaluate the information submitted. Based on my inquiry of the person orpersons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fines and imprisonment for knowing violations.'
- 12. Permit Actions This permit may be modified, revoked and reissued, or terminated for cause. The filing of a request by the permittee for a permit modification, revocation and reissuance, or termination, or a notification of planned changes or anticipated noncompliance does not stay any permit condition.
- 13. Permit Modification. Revocation and Reissuance. or Termination The issuance of this permit does not prohibit the permit issuing authority from reopening and modifying the permit, revoking and reissuing the permit, or terminating the permit as allowed by the laws, rules, and regulations contained in Title 40, Code of Federal Regulations, Parts 122 and 123; Title 15A of the North Carolina Administrative Code, Subchapter 2H.0100; and North Carolina General Statute 143-215.1 et. al.
- 14. Previous Permits All previous National Pollutant Discharge Elimination System Permits issued to this facility, whether for operation or discharge, are hereby revoked by issuance of this permit. r[he exclusive authority to operate this facility arises under this permit. The authority to operate the facility under previously issued permits bearing this number is no longer effective. ] The conditions, requirements, terms, and provisions of this permit authorizing discharge under the National Pollutant Discharge Elimination System govern discharges from this facility.
SECTION C. OPERATION AND MAINTENANCE OF POLLUTION CONTROLS
- 1. Certified Operator Pursuant to Chapter 90A-44 of North Carolina General Statutes, and upon classification of the facility by the Certification Commission, the permittee shall employ a certified wastewater treatment plant operator in responsible charge (ORC) of the wastewater treatment facilities. Such operator must hold a certification of the grade equivalent to or greater than the classification assigned to the wastewater treatment facilities by the Certification Commission. The permittee must also employ a certified back-up operator of the appropriate type and any grade to comply with the conditions of Title 15A NCAC Chapter 8G.0200. The ORC of the facility must visit each Class I facility at least weekly and each Class II, 111, and IV facility at least daily, excluding weekends and holidays, and must properly manage and document daily operation and maintenance of the facility and must comply with all other conditions of Title 15A, NCAC Chapter 8G.0200.
- 2. Proper Operation and Maintenance The permittee shall at all times properly operate and maintain all facilities and systems of treatment and control (and related appurtenances) which are installed or used by the permittee to achieve compliance with the conditions of this permit. Proper operation and maintenance also includes adequate laboratory controls and appropriate quality assurance procedures. This provision requires the operation of back-up or auxiliary facilities or similar systems which are installed by a permittee only when the operation is necessary to achieve compliance with the conditions of the permit.
- 3. Need to Halt or Reduce not a Defense It shall not be a defense for a permittee in an enforcement action that it would have been-necessary to halt or reduce the permitted activity in order to maintain compliance with the condition of this permit.
- 4. Bypassing of Treatment Facilities
- a. Definitions (I) "Bypass" means the intentional diversion of waste streams from any portion of a treatment facility including the collection system, which is not a designed or established or operating mode for the facility.
Permit NC0007064 - Parts III-V Page 7 of 12 (2) "Severe property damage" means substantial physical damage to property, damage to the treatment facilities which causes them to become inoperable, or substantial and permanent loss of natural resources which can reasonably be expected to occur in the absence of a bypass. Severe property damage does not mean economic loss caused by delays in production.
- 4. b. Bypass not exceeding limitations.
The permittee may allow any bypass to occur which does not cause effluent limitations to be exceeded, but only if it also is for essential maintenance to assure efficient operation. These bypasses are not subject to the provisions of Paragraphs c. and d. of this section.
- c.
Notice (1) Anticipated bypass. If the permitted knows in advance of the need for a bypass, it shall submit prior notice, if possible at least ten days before the date of the bypass; including an evaluation of the anticipated quality and affect of the bypass..
(2) Unanticipated bypass. The permittee shall submit notice of an unanticipated bypass as required in Part II, E. '6. of this permit. (24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> notice).
- d. Prohibition of Bypass (I) Bypass from the treatment facility is prohibited and the Permit Issuing Authority may take enforcement action against a permittee for bypass, unless:
(A) Bypass was unavoidable to prevent loss of life, personal injury or severe property damage;'
(B) There were no feasible alternatives to the bypass, such as the use of auxiliary treatment facilities, retention of untreated wastes or maintenance during normal periods of equipment downtime. This condition is not satisfied if adequate backup equipment should have been installed in the exercise of reasonable engineering judgment to prevent a bypass which occurred during normal periods of equipment downtime or preventive maintenance; and (C) The permittee submitted notices as required under Paragraph c. of this section.
(2) Bypass from the collection system is prohibited and the Permit Issuing Authority may take enforcement.
action against a Permittee for a bypass as provided in any current or future system-wide collection system permit associated with the treatment facility.
(3) The Permit Issuing Authority may approve an anticipated bypass, after considering its adverse affects, if the Permit Issuing Authority determines that it will meet the three conditions listed above in Paragraph
- d. (1) of this section.
- 5. Upsets
- a.
Definition: "Upset" means an exceptional incident in which there is unintentional and temporary noncompliance with technology based permit effluent limitations because of factors beyond the reasonable control of the permittee. An upset does not include noncompliance to the extent caused by operational error, improperly designed treatment facilities, inadequate treatment facilities, lack of preventive maintenance, or careless or improper operation.
- b. Effect of an upset:
An upset constitutes an affirmative defense to an action brought for noncompliance with such technology based permit effluent limitations if the requirements of paragraph c. of this condition are met. No determination made during administrative review of claims that noncompliance was caused by upset, and before an action for noncompliance, is final administrative action subject to judicial.review.
- c.
Conditions necessary for a demonstration of upset:
A permittee who wishes to establish the affirmative defense of upset shall demonstrate, through properly signed, contemporaneous operating logs, or other relevant evidence that:
(1) An upset occurred and that the permittee can identify the cause(s) of the upset; (2) The permittee facility was at the time being properly operated; and (3) The permittee submitted notice of the upset as required in Part 11, E. 6. (b) (B) of this permit.
(4) The permittee complied with any remedial measures required under Part II, B. 2. of this permit.
Permit NC0007064 - Parts III-V Page 8 of 12
- d. Burden of proof:
in any enforcement proceeding the permittee seeking to establish the occurrence of an upset has the burden of proof.
- 6. Removed Substances Solids, sludges, filter backwash, or other pollutants removed in the course of treatment or control of wastewaters shall be utilized/disposed of in accordance with NCGS 143-215J and in a manner such as to prevent any pollutant from such materials from entering waters of the State or navigable waters of the United States. The permittee shall comply with all existing federal regulations governing the disposal of sewage sludge. Upon promulgation of 40 CFR Part 503, any permit issued by the Permit Issuing Authority for the utilization/disposal of sludge may be reopened and modified, or revoked and reissued, to incorporate applicable requirements at 40 CFR Part 503.
The permittee shall comply with applicable 40 CER Part 503 Standards for the Use and Disposal of Sewage Sludge (when promulgated) within the time provided in the regulation, even if the permit is not modified to incorporate the requirement. The permittee shall notify the Permit Issuing Authority of any significant change in its sludge use or disposal practices.
- 7. Power Failures The permittee is responsible for maintaining adequate safeguards as required by 1SA NCAC 2H.0124 (Reliability) to prevent the discharge of untreated or inadequately treated wastes during electrical power failures either by means of alternate power sources, standby generators or retention of inadequately treated effluent.
SECTION D. MONITORING AND RECORDS
- 1. Representative Sampling Samples collected and measurements taken, as required herein, shall be characteristic of the volume and nature of the permitted discharge. Samples collected at a frequency less than daily shall be taken on a day and time that is characteristic of the discharge over the entire period the sample represents. All samples shall be taken at the monitoring points specified in this permit and, unless otherwise specified, before the effluent joins or is diluted by any other wastestream, body of water, or substance.
Monitoring points shall not be changed without notification to and the approval of the Permit Issuing Authority.
- 2. Reporting Monitoring results obtained during the previous month(s) shall be summarized for each month and reported on a monthly Discharge Monitoring Report (DMR) Form (DWQ No. MR 1,1.1, 2, 3) or alternative forms approved by the Director, DWQ, postmarked no later than the 30th day following the completed reporting period.
The first DMR is due on the last day of the month following the issuance of the permit or in the case of a new facility, on the last day of the month following the commencement of discharge. Duplicate signed copies of these, and all other reports required herein, shall be submitted to the following address:
NC DENR / Division of Water Quality / Water Quality Section A=TENTION: Central Files 1617 Mail Service Center Raleigh, North Carolina 27699-1617
- 3.
Flow Measurements Appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to ensure the accuracy and reliability of measurements of the volume of monitored discharges. The devices shall be installed, calibrated and maintained to ensure that the accuracy of the measurements is consistent with the accepted capability of that type of device. Devices selected shall be capable of measuring flows with a maximum deviation of less than 10% from the true discharge rates throughout the range of expected discharge volumes.
Once-through condenser cooling water flow monitored by pump logs, or pump hour meters as specified in Part I of this permit and based on the manufacturer's pump curves shall not be subject to this requirement.
Permit NC0007064 - Parts III-V Page 9 of 12
- 4. Test Procedures Test procedures for the analysis of pollutants shall conform to the EMC regulations published pursuant to NCGS 143-215.63 et. seq, the Water and Air Quality Reporting Acts, and to regulations published pursuant to Section 304(g), 33 USC 1314, of the Federal Water Pollution Control Act, as Amended, and Regulation 40 CFR 136; or in the case of sludge use or disposal, approved under 40 CFR 136, unless otherwise specified in 40 CFR 503, unless other test procedures have been specified in this permit.
To meet the intent of the monitoring required by this permit, all test procedures must produce minimum detection and reporting levels that are below-the permit discharge requirements and all data generated must be reported down to the minimum detection or lower reporting level of the procedure. If no approved methods are determined capable of achieving minimum detection and reporting levels below permit discharge requirements, then the most sensitive (method with the lowest possible detection and reporting level) approved method must be used.
- 5. Penalties for Tampering The Clean Water Act provides that any person who falsifies, tampers with, or knowingly renders inaccurate, any monitoring device or method required to be maintained under this permit shall, upon conviction, be punished by a fine of not more than 510,000 per violation, or by imprisonment for not more than two years per violation, or by both. If a conviction of a person is for a violation committed after a first conviction of such person under this paragraph, punishment is a fine of not more than S20,000 per day of violation, or by imprisonment of not more than 4 years, or both.
- 6. Records Retention Except for records of monitoring information required by this permit related to the permittee's sewage sludge use and disposal activities, which shall be retained for a period of at least five years (or longer as required by 40 CFR 503), the permittee shall retain records of all monitoring information, including all calibration and maintenance records and all original strip chart recordings for continuous monitoring instrurrentation, copies of all reports required by this permit, for a period of at least 3 years from the date of the sample, measurement, report or application. This period may be extended by request of the Director at any time.
- 7. Recording Results For each measurement or sample taken pursuant to the requirements of this permit, the permittee shall record the following information:
- a.
The date, exact place, and time of sampling or measurements;
- b. The individual(s) who performed the sampling or measurements;
- c.
The date(s) analyses were performed;
- d.
The individual(s) who performed the analyses;'
- e.
The analytical techniques or methods used; and
- f.
The results of such analyses.
- 8.
Inspection and Entry The permittee shall allow the Director, or an authorized representative (including an authorized contractor acting as a representative of the Director), upon the presentation of credentials and other documents as may be required by law, to;
- a.
Enter upon the permittee's premises where a regulated facility or activity is located or conducted, or where records must be kept under the conditions of this permit;
- b.
Have access to and copy, at reasonable times, any records that must be kept under the conditions of this permit;
- c.
Inspect at reasonable times any facilities, equipment (including monitoring and control equipment), practices, or operations regulated or required under this permit, and
- d.
Sample or monitor at reasonable times, for the.purposes of assuring permit compliance or as otherwise authorized by the Clean Water Act, any substances or parameters at any location.
Permit NC0007064 - Parts 11I-V Page10of 12 SECTION E REPORTING REQUIREMENTS L
Change in Discharge All discharges authorized herein shall be consistent with the terms and conditions of this permit. The discharge of any pollutant identified in this permit more frequently than or at a level in excess of that authorized shall constitute a violation of the permit.
- 2. Planned Changes
'The permittec shall give notice to the Director as soon as possible of any planned physical alterations or additions to the permitted facility. Notice is required only when:
- a.
The alteration or addition to a permitted facility may meet one of the criteria for determining whether a facility is a new source in 40 CFR Part 122.29 (b); or
- b. The alteration or addition could significantly change the nature or increase the quantity of pollutants discharged. This notification applies to pollutants which are subject neither to effluent limitations in the permit, nor to notification requirements under 40 CFR Part 122.42 (a) (I).
- c. The alteration or addition results in a significant change in the permittee's sludge use or disposal practices, and such alternation, addition or change may justify the application of permit conditions that are different from or absent in the existing permit, including notification of additional use or disposal sites not reported during the permit application process or not reported pursuant to an approved land application plan.
- 3.
Anticipated Noncompliance The permitee shall give advance notice to the Director of any planned changes in the permitted facility or activity which may result in noncompliance with permit requirements.
- 4. Transfers This permit is not transferable to any person except after notice to the Director. The Director may require modification or revocation and reissuance of the permittee. and incorporate such other requirements as may be necessary under the Clean Water Act.
- 5.
Monitoring Reports Monitoring results shall be reported at the intervals specified elsewhere in this permit.
- a.
Monitoring results must be reported on a Discharge Monitoring Report (DMR) (See Part II. D. 2 of this permit) or forms provided by the Director for reporting results of monitoring of sludge use or disposal practices.
- b. If the permittee monitors any pollutant more frequently than required by the permit, using test procedures specified in Part II, D. 4. of this permit or in the case of sludge use or disposal, approved under 40 CFR 503, or as specified in this permit, the results of this monitoring shall be included in the calculation and reporting of the data submitted in the DMR.
- c.
Calculations for all limitations which require averaging of measurements shall utilize an arithmetic mean unless otherwise specified by the Director in the permit.
- 6.
Twenty-four Hour Reporting
- a.
The permittee shall report to the central office or the appropriate regional office any noncompliance which may endanger health or the environment. Any information shall be provided orally within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from the time the permittee became aware of the circumstances. A written submission shall also be provided within 5 days of the time the permittee becomes aware of the circumstances. The written submission shall contain a description of the noncompliance, and its cause; the period of noncompliance, including exact dates and times, and if the noncompliance has not been corrected, the anticipated time it is expected to continue; and steps taken or planned to reduce, eliminate, and prevent reoccurrence of the noncompliance.
- b.
The following shall be included as information that must be reported within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> under this paragraph:
(1) -Any unanticipated bypass that exceeds any effluent limitation in the permit.
(2) Any upset which exceeds any effluent limitation in the permit.
Permit NC0007064 - Parts III-V Page 1 1of 12 (3) Violation of a maximum daily discharge limitation for any of the pollutants listed by the Director in the permit to be reported within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
- c.
The Director may waive the written report on a case-by-case basis for reports under paragraph b. above of this condition if the oral report has been received within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
- 7.
Other Noncompliance The permittee shall report ill instances of noncompliance not reported under Part II. E. 5 and 6. of this permit at the time monitoring reports are submitted. The reports shall contain the information listed in Part II. E. 6. of this permit.
- 8.
Other Information Where the permittee becomes aware that it failed to submit any relevant facts in a permit application, or submitted incorrect information in a permit application or in any report to the Director, it shall promptly submit such facts or information.
- 9. Noncompliance Notification The permittee shall report by telephone to either the central office or the appropriate regional office of the Division as soon as possible, but in no case more than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or on the next working day following the occurrence or first knowledge of the occurrence of any of the following:
- a.
Any occurrence at the water pollution control facility which results in the discharge of significant amounts of wastes which are abnormal in quantity or characteristic, such as the dumping of the contents of a sludge digester; the known passage of a slug of hazardous substance through the facility; or any other unusual circumstances.
- b. Any process unit failure, due to known or unknown reasons, that render the facility incapable of adequate wvastewater treatment such as mechanical or electrical failures of pumps, aerators, compressors, etc.
- c.
Any failure of a pumping station, sewer line, or treatment facility resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility.
Persons reporting such occurrences by telephone shall also file a written report in letter form within 5 days following first knowledge of the occurrence.
- 10. Availability of Reports Except for data determined to be confidential under NCGS 143-215.3 (a)(2) or Section 308 of the Federal Act, 33 USC 1318, all reports prepared in accordance with the terms shall be available for public inspection at the offices of the Division of Water Quality. As required by the Act, effluent data shall not be considered confidential.
Knowingly making any false statement on any such report may result in the imposition of criminal penalties as provided for in NCGS 143-215.1 (b)(2) or in Section 309 of the Federal Act.
- 11. Penalties for Falsification of Reports The Clean Water Act provides that any person who knowingly makes any false statement, representation, or certification in any record or other document submitted or required to be maintained under this permit, includinrg monitoring reports or reports of compliance or noncompliance shall, upon conviction, be punished by a fine of not more than $10,000 per violation, or by imprisonment for not more than two years per violation, or by both.
PART IV OTHER REQUIREMENTS A. Construction No construction of wastewater treatment facilities or additions to add to the plant's treatment capacity or to change the type of process utilized at the treatment plant shall be begun until Final Plans and Specifications have been submitted to the Division of Water Quality and written approval and Authorization to Construct has been issued.
Permit NC0007064 - Parts III-V Page 12 of 12 B. Groundwater Monitoring The permittee shall, upon written notice from the Director of the Division of Water Quality, conduct groundwater monitoring as may be required to determine the compliance of this NPDES permitted facility with the current groundwater standards.
C. Changes in Discharges of Toxic Substances The permittee shall notify the Permit Issuing Authority as soon as it knows or has reason to believe:
- a.
That any activity has occurred or will occur which would result in the discharge, on a routine or frequent basis, of any toxic pollutant which is not limited in the permit, if that discharge will exceed the highest of the following "notification levels";
() One hundred micrograms per liter (100 1g/L);
(2) Two hundred micrograms per liter (200 jLg/L) for acrolein and acrylonitrile; five hundred micrograms per liter (500 Ssg/L) for 2.4-dinitrophenol and for 2-methyl-4.6-dinitrophenol; and one milligram per liter (1 mg/L) for antimony, (3) Five (5) times the maximum concentration value reported for that pollutant in the permit application.
- b. That any activity has occurred or will occur which would result in any discharge, on a non-routine or infrequent basis, of a toxic pollutant which is not limited in the permit, if that discharge will exceed the highest of the following "notification levels";
(I) Five hundred micrograms per liter (500 jg/L);
(2) One milligram per liter ( mg/L) for antimony; (3) Ten 00) times the maximum concentration value reported for that pollutant in the permit application.
D. Requirement to Evaluate Alternatives to Wastewater Discharges If the facility is in substantial non-compliance with the terms and conditions of the NPDES permit or governing rules, regulations or laws, the permittee shall submit a report in such form and detail as required by the Division evaluating these alternatives and a plan of action within sixty (60) days of notification by the Division.
PART V ANNUAL ADMINISTERING AND COMPLIANCE MONITORING FEE REQUIREMENTS A. The permittee must pay the annual administering and compliance monitoring fee within 30 (thirty) days after being billed by the Division. Failure to pay the fee in a timely manner in accordance with 15A NCAC 2H
.0105(b)(4) may cause this Division to initiate action to revoke the permit.