Review of License Renewal Application for Brunswick Units 1 & 2, Calculation Package for Brunswick Transmission Lines Induced Current Analysis
ML050630188
Person / Time
Site: Brunswick  
Issue date: 12/13/2002
From: Connor S
Tetra Tech NUS
To:
Office of Nuclear Reactor Regulation, Progress Energy Carolinas
Emch R, NRR/DRIP/RLEP, 415-1590
References
Download: ML050630188 (72)


Text

.

I I -

I r-I 1

RCT 0

IJ Calculation Package for Brunswick Transmission Lines Induced Current Analysis December 13,2002 Prepared for:

Progress Energy Raleigh, North Carolina Prepared by:

Steven J. Connor Tetra Tech NUS Aiken, South Carolina

I.

Purpose These calculations were performed in support of Applicant 's Environmental Report. Operating License Renewal Stage, BrunswickSteam Electric Plant, specifically section 4.13 on induced current. Section 4.13 provides the requirements for the calculation.

II.

Selection of Locations to Model In general, the profile drawings for each line were used to identify two types of locations where clearances were low. (1) at paved roads with low clearances and (2) any location with low clearance, regardless of terrain or structures beneath. For type I locations (i.e., at roads), all US Highways and North Carolina State Roads were identified as candidates for analysis. Dirt Toads were specifically excluded. The least clearance of all the road crossings was selected. For type 1 locations, either the least clearance location or a representative for a set of least clearance locations was selected for analysis. The candidate locations are cataloged in the attached notes.

The locations analyzed are thought to represent bounding conditions on the transmission line. However, it is possible that some logging roads could have lower clearances. However, a large sampling of roads was considered for each transmission line: It is believed that they represent well the design conditions throughout the length of the trawsmission line. Given that no analyzed location was near the 5 millamp lmit, it seems unlikely than any missed road would exceed the standard either. All the high usage roads were included.

M. Inputs The plan and profile drawing identified in the attached notes were used to obtain the following information:

structure numbers of the two towers in the span of interest, structure type, sag for the span (at 200 degrees Fahrenheit), span, elevation of conductors at the towers, elevation of the location of interest, clearance at the location of interest,-and distance from the nearest tower to the'location of interest. Given that the sags at 200 degrees were used instead of the'120-degree sags, the inputs to the model are very conservative.

Using other engineering drawings identified in the notes, tower dimensions were obtained for horizontal and vertical dimensions of the three conductors, horizontal and vertical dimensions for the static wires, specification of the conductors (e.g. 1272 MCM 45/7 ACSR), specifications of the static wire, and phasing of conductors.

ACDCLINE uses conductor bird names as inputs. The transmission line drawings did not contain bird names, but did provide specifications. Using the ACDCLINE Appendix A, bird names were selected. The selection was based on the type (e.g. ACSR) and the stranding (e.g. 45/7) and not on the circular mills. No unique bird.

name selection was possible, so one was selected at raedom from the list of those that matched type and stranding. The results are not expected to be affected by an improper choice.

See attached notes and the model run printouts for details.

IV.

Methods In most cases the elevation of the two towers of a span of interest were different and the elevation of the location of interest was different than the nearest tower base. Because ACIDCLINE does not accommodate non-level geometries, a surrogate geometry was constructed that uses weighted average height for conductor attachments above the location of interest. The surrogate geometry had the two towers -at the same elevation. This surrogate geometry would not have identical impact with that of the actual geometry, but it should be close.

The code was first run to give electric field with no coupled objects to find the transverse location with the highest electric field strength. The code was then rerun with a long box coupled object with dimensions of the largest tractor-trailer truck that is'allowed on North Carolina roads. Where analyses were at non-road locations, a tractor trailer truck was still used (instead of something like a combine) for simplicity and conservatism.

2

Each transmission line was considered in isolation; however, as many as eight transmission lines run down a corridor, spaced in two groups of four, 75 feet apart within a group and 180 feet separation between the groups.

To test.whether adjacent transmission lines can significantly affect the outcome for a given line, tests were run with one, two, and three adjacent transmission lines (ACDCLINE does not work well with more lines.). For the ABC/ABC/ABC phasing used by the Brunswick lines, the results showed interesting variations in the shapes of the electric fields, but no significant change in the induced current. Results of these tests are provided in the attached ACDCL1NE printouts.

V.

Results Analytical results for each analysis is provided in the table below to two significant digits. In reporting in the Environmental Report, the highest value per transmission line will be reported. The reported values will be provided as "less-than" values because of the conservative input of 200-degree sag.

Transmission Line Castle Hayne East Castle Hayne East Castle Hayne West Castle Hayne West Delco East

.Delco East Delco West Delco West Jacksonville Jacksonville Wallace Wallace Weatherspoon Weatherspoon Whiteville Whiteville Survey Location Description 196+60 center span 703+80 NC HWY 133 197+90 representative low point 703+70 NC HWY 133 835+05 1551+19 199+50 1431+28 537+30 1000+16.20 365+80 615+30 836+56 1430+14 209+77 816+53 representative low point US 74/1US 76 representative low point State Route 1849 representative low point US 17 representative low point NSCR 1518 representative low point SR 1849 representative low point US 17

.Induced Current (millamps) 2.8 1.7 3.3 1.7 3.2 1.8

  • 3.1
  • 2.8 3.0 1.9 3.7 1.8 2.9 1.7 2.9 1.8

.3.

Brunswick Steam Electric Plant Castle Hayne East Transmission Line Analysis Data Sources Castle Hayne East Plan and Profile Drawing TD-1 1300, sheets 1-10; TD-1 1300 sheets 11-18 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1 Castle Hayne East One-Line TD-1 1300; 111 System Phasing Diagram, Wilmington Area, TF,12606, sheet 4 of 5 General Data length: 16.27 miles to Barnard Creek; 9.87 miles to Wrightsville Beach; 8.56 miles to Castle Hayne; Total = 34.7 miles ROW widths:

Brunswick to 68+75 no ROW-on CP&L property 68+75 to 621+29 = 310' 621+29 toBarnard Creek SS = 170' Conductor: 2515 MCM 76/19 ACSR; spaced -18, 0, 18 at equal height OHGW: one 7#10 AW (3/8'); 14.75' above conductor; +/- 19' from centerline of tower Phasing ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. A typical representative of the least clearance low point was selected as a candidate.

200° Clearance 600 Clearance Structure Location Name (feet)

(feet) 16-17 107+20 State HWY 87 40 43 94-95 613+98??

NCSR 1513 39 43 108-109 703+80 NC HWY 133 38 41 30-31 196+60 center span 28 34 94-95 892+90 US 421 south 53 94-95 891+60 US 421 north 54 Ignored spans with single steel poles because all the clearances were high and a test run with ACDCLINE indicated no difficulties.

Selection of Locations to Analyze The least clearance overall, irrespective of presence of a road is between Structures 30-31. The least clearance road is HWY 133 at 703+80. These two locations will be analyzed.

Specific Data for 196+60 span = 199+90 - 193+30 = 660 feet sag = 22 feet @ 200 degrees and 15 feet at 60 degrees Str 30: 90 feet elevation of conductor connection distance to point of interest is 660/2 = 330 feet 4.-

Str 31: 92 feet elevation of conductor connection distance to point of interest is 660 - 330 - 330 feet elevation of ground at point of interest - 42 feet elevation of OHGW = (90+92)12 + 14.75 = 105.75 Surrogate Geometry Use 200 degree sag. Place low point exactly in center span (almost is anyway) at 330 feet.

Relative height of conductor connections is 28 feet clearance + 22 feet sag 50 feet.

Relative height of OHGW is 50 + 14.75 64.75 feet.

Sketch:

4.

ACDCLINE Run Attached 5

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR30 Date: 12/ 9/2002 Time: 13:43 STR30 Center Span between Str 30-31 BUNDLE INFORMATION VOLTAGE I

CURRENT I I I BUNDLE COORDINATES I

IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG.I PH I I.1 4 I (kV) l(DEG)I (A) I(DEG)ICONDI (feet) I (feet)l(feet)l I

I 1 1 1 1 230.01 0.-1 500.1 0.l 1 1

-18.01 50.01 22.01 A I

I 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 50.01 22.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1.

18.01 50.01 22.01 C I 1

4 1 1 1

.01 0.1 0.1 0.1 1 l

-19.01 64.81 10.01 GND 1 I 5 I 1 1

.01 0.1 0.1 0.1 1 1 19.01 64.81 10.0lIGND I MINIMUM GROUND CLEARANCE -

28.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES

                                                              • s*********************************

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I.i I NAME I (inch)

I (inch)

I (ohm/mile)l (ohm/mile) l (ohm/mile) 2 1

]THRASHER I

1.800 1 18.000 1

.0400 1

.0450 1

.3420 1 1 2 ITHRASHER I

1.800 I 18.000 1

.0400 1

.0450 1

.3420 1 I. 3 1THRASHER I

1.800 1 18.000 l

.0400 1

.0450 I

.3420 1 1 4 17#10AW I

.310 1 18.000 1 3.8100 1 3.8800 1

.7770 1 1

5 I7I1OAW I

.310 1 18.000 I 3.8100 1 3.8800 I

  • .7770 1 0

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 330.00 feet LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL, (feet)

(meters)

(kV/m)

(ratio)

(kV/m)

.(ky/m)

(kV)

-50.0

-15.24 1.317

.000 1.305

.179 1.313

-45.0

-13.72 1.622

.002 1.607

.217 1.615

-40.0

-12.19 1.982

.006 1.966

.248 1.970

-35.0

-10.67 2.375

.013 2.361

.255 2.357

-30.0

-9.14 2.742

.024 2.734

.214 2.714

-25.0

-7.62 2.976

.044 2.975

.151 2.935

-20.0

-6.10 2.955

.081 2.953

.272 2.900

-15.0

-4.57 2.630

.147 2.611

.496 2.563

-10.0

-3.05 2.115

.257 2.085

.650 2.047

-5.0

-1.52 1.672

.390 1.658

.687 1.612 6

.0

.00 1.515

.447 1.515

.677 1.455 5.0 1.52 1.672

.390 1.658

.687 1.612 10.0 3.05 2.115

.257 2.085

.650 2.047 15.0 4.57 2.630

.147 2.611

.496 2.563 20.0 6.10 2.955

.081 2.953

.272 2.900 25.0 7.62 2.976

.044 2.975

.151 2.935 30.0 9.14 2.742

.024 2.734

.214 2.714 35.0 10.67 2.375

.013 2.361

.255 2.357 40.0 12.19 1.982

.006 1.966

.248 1.970 45.0 13.72 1.622

.002 1.607

.217 1.615 50.0 15.24 1.317

.000 1.305

.179 1.313 100.0 30.48

.222

.000

.221

.021

.222 150.0 45.72

.069

.001

.068

.004

.068 100.0 30.48

.222

.000

.221

.021

.222 150.0 45.72

.069

.001

.068

.004

.068 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR30 Date: 12/ 9/2002 Time: 13:43 0

DATE: 12/ 9/2002 TIME: 13:43 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE) 4 EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 330.00 feet AC SHORT CIRCUIT CURRENT -

2.82 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

2996. V 1% AC VOLTAGE TO GROUND -

1684. V 50% AC VOLTAGE TO GROUND -

249. V 7

Specific Data for 703+80 span =706+70 - 702+30 = 440 feet sag 10 feet @ 200 degrees and 7 feet at 60 degrees Str 108: 53 feet elevation of conductor connection distance to road is 703+80 - 702+30 = 150 feet Str 109: 61 feet elevation of conductor connection distance to road is 440 - 150 290 feet elevation of ground at road - 10 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductor is a weighted average of 53 and 61 feet.

(290/450X53-10) + (150/450X61-10) = 44.7 feet Relative height of OHGW is 44.7 + 14.75 59.5 feet..

Sketch:

I_

00 qq ACDCLINE Run Attached 8

D Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR108 Date: 12/10/2002 Time: 12:40 STRI08 NC HWY 133 at 703+80 BUNDLE INFORMATION i

I I

VOLTAGE I

CURRENT I I I

BUNDLE COORDINATES I

I

..IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I

  1. I I I (kV)

I(DEG)I (A)

I(DEG)ICONDI (feet)

I (feet)l(feet)l I 1 1 1 1 230.01 0.1 500.1

0.

1 I1

-18.01 44.71 10.01 A

I 1 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 44.71 10.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 44.71 10.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.l 1 1

-19.01 59.51 5.01 GND I I 5 1 1 l

.01 0.1 0.1 0.l 1 I 19.01 59.51 5.01 GND I MINIMUM GROUND CLEARANCE -

34.70 feet

-POWER SYSTEM FREQUENCY

60.

Hz.

SOIL RESISTIVITY 100.

ohm meter SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I 4 I NAME I (inch)

I (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)l I

1 ITHRASHER I

1.800 I

.000 1

.0400 1

.0450 1

.3420 1 1 2 ITHRASHER I

1.800 I

.000 1

.0400 1

.0450 1

.3420 1 1 3 ITHRASHER I

1.800 1

.000 1

.0400.l

.0450 1

.3420 1 1 4 17f10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1 5 17t10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1

0

                        • +****************

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 150.00 feet *
                                                          • ~

LATERAL MAXIMUM MINOR/MAJOR

'SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/n)

(kV)

-50.0

-15.24 1.166

.004 1.160

.121 1.162

-45.0

-13.72 1.361

.007 1.355

.131 1.355

-40.0

-12.19 1.564

.012 1.558

.131 1.556

-35.0

-10.67 1.752

.019 1.748

.113 1.740

-30.0

-9.14 1.888

.030 1.887

.082 1.872

-25.0

-7.62 1.928

.047 1.928

.093 1.907

-20.0

-6.10 1.834

.075 1.831

.179 1.806

-15.0

-4.57 1.599

.121 1.586

.280 1.562

-10.0

-3.05 1.262

.203 1.238

.356 1.218

-5.0

-1.52

.914

.366

.890

.395

.869 9

.0

.00

.724

.560

.724.

.405

.701 5.0 1.52

.914

.366

.890

.395

.869 10.0 3.05 1.262

.203 1.238

.356 1.218 15.0 4.57 1.599

.121 1.586

.280 1.562 20.0 6.10 1.834

.075 1.831

.179 1.806 25.0 7.62 1.928

.047 1.928

.093 1.907 30.0 9.14 1.888

.030 1.887

.082 1.872 35.0 10.67 1.752

.019 1.748

.113 1.740 40.0 12.19 1.564

.012 1.558

.131 1.556 45.0 13.72 1.361

.007 1.355

.131 1.355 50.0 15.24 1.166

.004 1.160

.121 1.162 100.0 30.48

.248

.000

.247

.022

.248 150.0 45.72

.081

.001

.080

.005

.081 100.0 30.48

.248

.000

.247

.022

.248 150.0 45.72

.081

.001

.080

.005

.081 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC. 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR108 Date: 12/10/2002 Time: 12:40 0

DATE: 12/10/2002 TIME: 12:40 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND 2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 150.00 feet AC SHORT CIRCUIT CURRENT -

1.69 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1795. V 1% AC VOLTAGE TO GROUND -

1009. V 50% AC VOLTAGE TO GROUND -

149. V 10

Brunswick Steam Electric Plant Castle Hayne West Transmission Line Analysis (to Wilmington Corning only)

Data Sources Castle Hayne West Plan and Profile Drawing, TD-1 1327, sheets 1-10; CT-46421 sheet 1 of 1; TD-1 1327 sheets 11-28 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1 Castle Hayne West One-Line TD-11327; 112 System Phasing Diagram, Wilmington Area, TE-12606, sheet 4 of 5 General Data length: 16.32 miles to Barnard Creek; 9.91 miles to Coming tap; 0.93 miles of tap to Corning, Total =

27.16 miles ROW widths:

Brunswick to 75+88 no ROW-on CP&L property 75+88 to 621+28 = 3 10' 621+28 to Barnard Creek SS =170' Conductor: 2515 MOM 76/19 ACSR; spaced -18, 0, 18 at equal height OHGW: two 7#10 AW (3/8'j); 14.75' above conductor, +1-19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. A typical representative of the least clearance low point was selected as a candidate.

2000 Clearance 600 Clearance Structure Location Name (feet)

(feet) 15-16 107+01 State HWY 87 urndctaminable undetaminmble 74-75 498+60

  • NCSR 21 (dirt) 40 43 92-93 614+41 NCSR 1513 40 42 105-106 703+70 NC HWY 133 37 42 29-30 197+90 center span 26 34 Ignored spans with single steel poles because all the clearances were high and a test run with ACDCLMN indicated no difficulties.

Selection of Locations to Analyze The least clearance overall, irrespective of presence of a road is between Structures 29-30. The least clearance road is HWY 133 at 703+70. These two locations will be analyzed.

Specific Data for 197+90 span = 201+45 - 194+00 = 745 feet sag = 27 feet @ 200 degrees and 20 feet at 60 degrees Str 29: 95 feet elevation of conductor connection 11 '

distance to point of interest is 745/2 373 feet Str 30: 97 feet elevation of conductor connection distance to point of interest is 373 feet elevation of ground at point of interest -42 feet Surrogate Geometry Use 200 degree sag. Place low point exactly in center span at 373 feet.

Relative height of conductor connections is 26 feet clearance + 27 feet sag 53 feet.

Relative height of OHGW is 53 + 14.75 = 67.75 feet.

Sketch:

ACDCLINE Run Attached 12

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR29 Date: 12/10/2002 Time: 12:26 STR29 midspan at STR 29 BUNDLE INFORMATION I

I VOLTAGE I

CURRENT I $

I BUNDLE COORDINATES I

IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I I

i I I (kV)

I(DEG)I (A)

I (DEG)ICONDI (feet) I (feet) I (feet)I I

I 1

    • 1 230.01 0.1 500.1
    • 0.1 1 I

-18.01

  • 53.01 27.01 A

I I 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 53.01 27.01 B

I I 3 1 1 1 230.01 120.1 500.1 120.1 1.1 18.01 53.01 27.01 C

I 1 4 1 1 1

.01 0.1

.0.1 0.l 1 1

-19.01 67.81 10.01 GND I 1 5 1 1 1.

.01 0.1 0.1 0.l 1 I1 19.01 67.81 10.01 GND I MINIMUM GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY

.100.

ohm meter

        • 4*******
  • &**A************

SUBCONDUCTOR INFORMATION - REGULAR BUNDLES A*****

    • ** * ********** ** *A******** A***
  • A
    • &A**********A**

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I

I I

NAME I

(inch)

I (inch)

I (ohm/mile) I (ohm/mile) I (ohm/mile) I I ******A*******************************************************************

I 1 ITHRASHER I

1.800 I

.000 1

.0400 1

.0450 1

.3420 1 I 2 ITHRASHER I

1.800 1

.000 1

.0400 1

.0450 1

.3420 1 1

3 ITHRASHER I

1.800 i

.000 I

.0400 1

.0450 1

.3420 1 1 4 17#10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1

5 17#10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1

    • A**A***AA *******A****A************AA****A*AA*****A****************
  • A*****A**

0 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground longitudinal distance: 373.00 feet

  • A AA*****A *********
    • A****A***
                      • A****

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.347

.001 1.333

.195 1.342

-45.0

-13.72 1.683

.001 1.665

.243 1.676

-40.0

-12.19 2.095

.004 2.075

.289 2.082

-35.0

-10.67 2.565

.010 2.546

.312 2.544

-30.0

-9.14 3.031

.021 3.019

.277 2.998

-25.0

-7.62 3.362

.042 3.359

.187 3.312

-20.0

-6.10 3.388

.081 3.385

.303 3.319

-15.0

.- 4.57 3.026

.154 3.005

.588 2.946

-10.0

-3.05 2.435

.277 2.403

.781 2.360

-5.0

-1.52 1.983

.395 1.974

.806 1.916 13

.0

.00 1.864

.420 1.864

.777 1.785 5.0 1.52 1.983

.395 1.974

.806 1.916 10.0 3.05 2.435

.277 2.403

.781 2.360 15.0 4.57 3.026

.154 3.005.

.588 2.946 20.0 6.10 3.388

.081 3.385

.303 3.319 25.0 7.62 3.362

.042 3.359

.187 3.312 30.0 9.14 3.031

.021 3.019

.277 2.998 35.0 10.67 2.565

.010 2.546

.312 2.544 40.0 12.19 2.095

.004 2.075

.289 2.082 45.0 13.72 1.683

.001 1.665

.243 1.676 50.0 15.24 1.347

.001 1.333

.195 1.342 100.0 30.48

.214

.000

.213

.020

.214 150.0 45.72

.065

.001

.065

.004

.065 100.0 30.48

.214

.000

.213

.020

.214 150.0 45.72

.065

.001

.065

.004

.065 0

Results of AC/DCLINE program COUPLE (EPRI/KVTRC 7-93.) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR29 Date: 12/10/2002 Time: 12:26 0

DATE: 12/10/2002 TIME: 12:26

+*******~******w**************,********I***

ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED. RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

20.00 373.00 feet AC SHORT CIRCUIT CURRENT -

3.34 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3549. V 1% AC VOLTAGE TO GROUND -

1994. V 50% AC VOLTAGE TO GROUND -

295. V 14

Specific Data for 703+70 span =705+05 - 697+05 = 800 feet sag = 30 feet c 200 degrees and 20 feet at 60 degrees Str 105: 57 feet elevation of conductor connection distance to road is 703+70 - 697+05 = 665 feet Str 106: 63 feet elevation of conductor connection distance to road is 800 - 665 - 135 feet elevation of ground at road - 9 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductor is a weighted average.

(135/800X57-9) + (665/800)(63-9) = 53 feet Relative height of OHGW is 53 + 14.75 = 67.8 feet.

Sketch:

6 &S' ACDCLINE Run Attached 15

0 Results of AC/DCLINE program EFION (EPRIViWTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR105 Date: 12/10/2002 Time: 12:21 STRI05 NC HWY 133 BUNDLE INFORMATION I

I I

VOLTAGE I

CURRENT. 1 1 BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI -LOAD IANGLEI OF I X

I Y

I SAG I PH I

I # I f I (kV)

I(DEG)

(A) f(DEG)ICONDI (feet)

' (feet)j(feet)

I 1 1 I 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 53.01 30.01 A I

1 2 1 1 1 230.01 240.l 500.1 240.1 1 1

.01 53.01. 30.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 53.01 30.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 67.81 10.01 GND I 1 5 1 1 1

.01 0.1 0.l 0.1 1 1 19.01 67.81 10.01 GND I MINIMUM GROUND CLEARANCE -

23.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter

    • &****** **********+****************************************************&*****

SUBCONDUCTOr, INFORMATION -

REGULAR BUNDLES t

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I NAME I (inch)

I (inch)

I (ohm/mile) I (ohm/mile) I (ohm/mile) I

                  • I*********************************

1 1

ITHRASHER I

1.800 I

.000 1

.0400 1

.0450 1

.3420 1 1

2 ITHRASHER I

1.800 I

.000 1

.0400 1

.0450 1

.3420 1 1 3 ITHPASHER I

1.800 1

.000 I

,.0400 I

.0450 1

.3420 1 1 4 17#I1AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 I 5 17#10AW I

.310 1

.000 I 3.8100 1 3.8800.1

.7770 1

    • *+******* ** * ***********************I********

0 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 135.-00 feet LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kY/m)

(kV/m)

(kY)

-50.0

-15.24 1.193

.004 1.187

.123 1.189

-45.0

-13.72 1.391

.007 1.384

.133 1.385

-40.0

-12.19 1.596

.012 1.591

.132 1.588

-35.0

-10.67 1.786

.018 1.782

.114 1.774

-30.0

-9.14 1.923

.029 1.922

.082 1.906

-25.0

-7.62 1.962

.046 1.962

.093 1.940

-20.0

-6.10 1.864

.074 1.861

.182 1.835

-15.0

-4.57 1.623

.119 1.610

.283 1.566

-10.0

-3.05 1.278

.201 1.253

.361 1.232

-5.0

-1.52

.919

.366

.893

.400

.873 16

.0

.00

.721

.571

.721

.411

.698 5.0 1.52

.919

.366

.893

.400

.873 10.0 3.05 1.278

.201 1.253

.361 1.232 15.0 4.57 1.623

.119 1.610

.283 1.586 20.0 6.10 1.864

.074 1.861

.182 1.835 25.0 7.62 1.962

.046 1.962

.093 1.940 30.0 9.14 1.923

.029 1.922

.082 1.906 35.0 10.67 1.786

.018 1.782

.114 1.774 40.0 12.19 1.596

.012 1.591

.132 1.588 45.0 13.72 1.391

.007 1.384

.133 1.385 50.0 15.24 1.193

.004 1.187

.123 1.189 100.0 30.48

.256

.000

.255

.022

.256 150.0 45.72

.083

.002

.083

.005

.083 100.0 30.48

.256

.000

.255

.022

.256 150.0 45.72

.083

.002

..083

.005

.083 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW3D\\ACDCLINE\\DATA\\ACSTR105 Date: 12/10/2002 Time: 12:21 0

DATE: 12/10/2002 TIME: 12:21 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

.25.00 135.00 feet AC SHORT CIRCUIT.CURPENT -

1.71 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1814. V 1% AC VOLTAGE TO GROUND -

1019. V 50% AC VOLTAGE TO GROUND -

151. V 17

Brunswick Steam Electric Plant Delco East Transmission Line Analysis Data Sources Delco East Plan and Profile Drawing, TD-1 1368, sheets 1-19 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1 Delco East One-Line TD-1 1368; 127 System Phasing Diagram, Wilmington Area, TE-12606, sheet 4 of 5 General Data length: 31.134 miles ROW widths:

Brunswickto,2324+70 = 310' 232+70 to 1297+94 = 240' 1298+05 to 1566+65 = 100' 1567+16 to end = 240' Conductor 1272 MCM 45n ACSR; spaced -18,0, 18 at equal height 011GW: two 7#10 AW (318"); 14.75' above conductor, +/- 19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. The least clearance center span was selected as candidate and it coincidentally had a farm road very near lowest point.

200° Clearance 60° Clearance Structure Location Name (feet) 15-16 87+56 NC Hwy 87 42 45 90-91 603+70 SR 1513 37 42 102-103 694+62 NCSR 1514 40 44 103 - 103-1 700+09 US 17 44 46 112-113 761+38 SR 1406 42 44 120-121 817+98 SR 1406 (dirt) 39.5 41.5 225-226 1551+19 US 74 & 76 ;

30.5 41 225-226 1551+88 US 74 & 76 38 42 232-233 1598+89 NCSR 1818 39 43 232-233 1599+81 NC HWY 87 39 43 122-123 835+05 least clearance 26 35 center span but has farm road Selection of Locations to Analyze Selected 835+05 as the least clearance location to analyze. There were other locations with identical clearance, but this one was selected because there is coincidentally a farm road there. The least clearance road is US 74 & 76 at 1551+19. These two locations will be analyzed.

18

Specific Data for 835+05 span =838+55 -831+30 = 725 feet sag=24 feet 200 degrees and 16 feet at 60 degrees Str 122:

100 feet elevation of conductor connection V

distance to point of interest is 835+05-831+30 = 375 feet Str 133:

100 feet elevation of conductor connection distance to point of interest is 725-375 350 feet elevation of ground at point of interest - 50 feet elevation of OHGW= 100 + 14.75= 114.75 Surrogate Geometry Use 200 degree sag. Place low point exactly in center span (almost is anyway) at 363 feet.

Relative height of conductor connections is 26 feet clearance + 24 feet sag= 50 feet.

Relative height of OHGW is 50+ 14.75 64.75 feet Sketch:

ACDCLINE Run Attached 19

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR122 Date: 12/ 5/2002 Time: 13: 3 STR122 Brunswick Delco East Sti 122, center span

                                                            • &*************+*******

BUNDLE INFORMATION

        • i********.**************.**4*************~*******

I I

VOLTAGE I

CURRENT I 4 1 BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I

  • I f I (kV)

I(DEG)l (A)

I(DEG)ICONDI (feet) I (feet)l(feet)l I

I 1 I 1 1 230.01 0.1 500.1 0.1 1 I

-18.01 50.01 24.01 A

I 1 2 1 1 l 230.01 240.1 500.1 240.1

1.

.01 50.01 24.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 50.01 24.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.1 1 I

-19.01 64.81 10.01 GND I 1 5 1 1 1

.01 0.1 0.1 0.1 1 1 19.01 64.81 10.01 GND I MINIMUM GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES 4************************4***4*****4****4***********

  • 444*4*4*4 IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I I NAME I

(inch)

I (inch)

I' (ohm/mile) I *ohm/mile) l (ohm/mile) l

    • 4*********************4*44**4***********************************

1 2

IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1

1 2 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1

I 3

IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1 I

4 17#10AW I

.310 1 18.000 l 3.8100 1 3.8800 1

.7770 1 1 5 17tlOAW I

.310 1 18.000 1 3.8100 1 3.8800 1

.7770 1

      • 44***4********************************4*****4**4444*44**4****************4***
  • 44444*4***444**4*4**44*4**4444**4444*

AC ELECTRIC FIELD PROFILE at 3.28 feet-above ground longitudinal distance: 350.00 feet *

  • 4444*44 ***4***********44*4**444******

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.276

.001 1.263

.185 1.272

-45.0

-13.72 1.596

.001

.1.579

.231 1.588

-40.0

-12.19 1.986

.004 1.967

.275 1.975

-35.0

-10.67 2.433

.010 2.415

.296 2.414

-30.0

-9.14 2.876

.021

.2.865

.264 2.845

-25.0

-7.62 3.191

.042 3.189

.178 3.144

-20.0

-6.10 3.217

.081 3.215

.287 3.153

-15.0

-4.57 2.876

.154 2.856

.557 2.800

-10.0

-3.05 2.317

.276 2.287

.740 2.245

-5.0

-1.52 1.887

.394 1.878

.766 1.823 20

.0

.00 1.772

.427 1.772

.739 1.698 5.0 1.52 1.887

.394 1.878

.766 1.823 10.0 3.05 2.317

.276 2.287

.740 2.245 15.0 4.57 2.876

.154 2.856

.557 2.800 20.0 6.10 3.217

.081 3.215

.287 3.153 25.0 7.62 3.191

.042 3.189

.178 3.144 30.0 9.14 2.876

.021 2.865

.264 2.845 35.0 10.67 2.433

.010.

2.415

.296 2.414 40.0 12.19 1.986

.004 1.967

.275 1.975 45.0 13.72 1.596

.001 1.579

.231 1.588 50.0 15.24 1.276

.001 1.263

.185 1.272 100.0 30.48

.202

.000

.202

.019

.202 150.0 45.72

.062

.001

.062

.004

.062 100.0 30.48

.202

.000

.202

.019

.202 150.0 45.72

.062

.001

.062

.004

.062 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93). for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR122 Date: 12/ 5/2002 Time: 13: 3 0

DATE: 12/ 5/2002 TIME: 13: 3 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

                          • .******************I**********

EQUIVALENT COUPLED OBJECT AREA 2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

20.00 350.00 feet AC SHORT CIRCUIT CURRENT -

3.18 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3369. V 1% AC VOLTAGE TO GROUND -

1893. V 50% AC VOLTAGE TO GROUND -

280. V 21

Specific Data for 1551+19 span =1 553+60 - 1547+20 - 640 feet sag = 18 feet @ 200 degrees and 12 feet at 60 degrees Str 225: 112 fet elevation of conductor connection distance to road is 1551+19 - 1547+20 399 feet Str 226: 115 feet elevation of conductor connection distance to road is 640 - 399 = 241 feet elevation of ground at road - 62 feet elevation of OHGW (112+115)/2 + 14.75 128.25 Surrogate'Geometry Use 200 degree sag.

Relative height of conductor is 113.5 feet average elevation of conductor - 62 feet elevation of road =

51.5 feet. (Terrain is level; equal height towers so did not do weighted average)

Relative height of OHGW is 51.5 + 14.75 - 66.25 feet.

Sketch:

J.

Irz,

UO

.N ACDCLINE Run Attached 22

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR225 Date: 12/ 5/2002 Time: 13: 8 STR225 Brunswick Delco East Str 225, US 74 & 76 4************4************4*************4********

                    • ~****4************

BUNDLE INFORMATION 4***********************44*44*4********44***4******4*4*****44************&

I I

I VOLTAGE I

CURRENT I I I BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH' I

I I

I #

( (kV)

I(DEG)l (A) l(DEG)!CONDI (feet)

I (feet)I(teet)I I

I*************************************************************************

I1 1 1 1 230.01 0.1 500.1 0.1 1 I

-18.01 51.51 18.01 A 1 2 1 1 1 230.01 240.1

.500.1 240.1 1 I

.01 51.51 18.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 51.51 18.01 C I I 4 I 1 I

.01 0.1 0.1 0.1 1 I1

-19.01 66.31 10.01 GND I

'I 5 1 1

.01 0.1 0.1 0.I 1 1 19.01 66.31 10.01 GND I MINIMUM GROUND CLEARANCE -

33.50 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter 4*4*4***************4******4*************4**********4*********4**.******4*4*4 SUBCONDUCTOR INFORMATION -

REGULARiBUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I NAME I

(inch).

I (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)l i *

[*********************

            • 4*4**4*4*4*030*44******.******************

I 1 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1 I 3 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1 1 4 17#10AW I

.310 1 18.000 1, 3.8100 1 3.8800 1

.7770 1 1 5 17#10AW I

.310 1 18.000 1 3.8100 1 3.8800 1

.7770 1 4*4**********************44******4******44*************44***

  • 44*4*44*444*4**

0 4*4***************4*4***4**********4**

4 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 350.00 feet 4*4*4*4
    • 4*444*4444*******4****44*4*444*

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.162

..003 1.155

.130 1.159

-45.0

-13.72 1.374

.006 1.366

.145 1.368

-40.0

-12.19 1.602

.010 1.595

.149 1.593

-35.0

-10.67 1.822

.018 1.817

.135 1.809

-30.0

-9.14 1.994

.029 1.992

.100 1.976

-25.0

-7.62 2.064

.047 2.064

.097 2.039

-20.0

-6.10 1.982

.077 1.979

.191 1.951

-15.0

-4.57 1.738

.126 1.725

.307 1.698

-10.0

-3.05 1.381

.214 1.356

.394 1.333

-5.0

-1.52 1.019

.373

.997

.434

.973 23

.0

.00

.834

.542

.834

.443

.807 5.0 1.52 1.019

.373

.997

.434

.973

-10.0 3.05 1.381

.214 1.356

.394 1.333 15.0 4.57 1.738

.126 1.725

.307 1.698 20.0 6.10 1.982

.077 1.979

.191 1.951 25.0 7.62 2.064

.047 2.064

.097 2.039 30.0 9.14 1.994

.029 1.992

.100 1.976 35.0 10.67 1.822

.018 1.817

.135 1.809 40.0 12.19 1.602

.010 1.595

.149 1.593 45.0 13.72 1.374

.006 1.366

.145 1.368 50.0 15.24 1.162

.003 1.155.

.130 1.159 100.0 30.48

.233

.000

.232

.021

.233 150.0 45.72

.075

.001

.075

.005

.075 100.0 30.48

.233

.000

.232

.021

.233 150.0 45.72

.075

.001

.075

.005

.075 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR225 Date: 12/ 5/2002 Time: 13: 8

.0O DATE: 12/ 5/2002 TIME: 13: 8 4*****.***.**********

                      • 4~*&**~*I********~*****

ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

          • {******************************

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 241.00 feet AC SHORT CIRCUIT CURRENT 1.81 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1916. V 1% AC VOLTAGE TO GROUND -

1077.

V 50% AC VOLTAGE TO GROUND -

159. V 24

Brunswick Steam Electric Plant Delco West Transmission Line Analysis Data Sources Delco West Plan and Profile Drawing, TD-1 1636, sheets 1-19 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1 Delco West One-Line TD-11636; TD-11150; 142 System Phasing Diagram, Wilmington Area, TE-12606, sheet 4 of 5 General Data length: 31.64 miles ROW widths:

Brunswickto87+43 NC87=370' 87+43 to 1298+05 240' 1298+05 to 1642+97 = 170' Conductor: 1272 MCM 45/7 ACSR; spaced -18,0, 18 at equal height OHGW: one 7#10 AW (3/8"); 14.75' above conductor; - 19' from centerline of tower Phasing: ABC looking from' plant Candidate Locations to Analyze Ignored dirt roads unless they were-identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. The least clearance and another representative of the next least clearance were selected as candidates.

2000 Clearance 600 Clearance Structure Location Name (feet)

(feet) 13-14 87+43 NC Hwy 87 49 51 87-88 603+64 SR 1513 41 44.5 99-100 695+14 NCSR 1514 40 43.5 100-100-1 699+67 US 17 43.5 45.5 109-110 761+56 SR 1406 41 45 147-148 1027+21 NCSR 1413 (dirt) 38 42 205-206 1431+28 SR 1849 27 34 223-224 1559+72 SRJ1824 42.5 45.5 228-229 1594+26 US 74 & 76*

36 41 22-23 150+40 low point (marsh 25.5 33.

+below) 29-30 199+50 low point (woods 26 35 below)

Selection of Locations to Analyze The least clearance location is over a marsh. Therefore, selected 199+50 as the least clearance location to analyze. There is no road there, just forest. The least clearance road is SR 1849 at 1431+28. These two locations will be analyzed.

25

Specific Data for 199+50 span = 203+35 - 196+00 735 feet sag 25 feet © 200 degrees and 17 feet at 60 degrees Str 29: 94 feet elevation of conductor connection distance to point of interest is 199+50 - 196+00 350 feet Str 30: 96 feet elevation of conductor connection distance to point of interest is 735-350 -385 feet elevation of ground at point of interest - 44 feet elevation of OHGW = (94+96)/2 + 14.75 = 109.75 Surrogate Geometry Use 200 degree sag. Place low point exactly in center span (almost is anyway) at 368 feet.

Relative height of conductor connections is 26 feet clearance + 25 feet sag 51 feet.

Relative height of OHGW is 51 + 14.75 65.75 feet.

Sketch:

ACDCLINE Run Attached 26*

0 Results ofAC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR29-Date: 12/ 4/2002 Time: 16: 9 STR29-Brunswick Delco West; Str 29-30; low point, no road BUNDLE INFORMATION

                • i********************4**************6********4******~********4*****

I I

I VOLTAGE I

CURRENT I I I

BUNDLE.COORDINATES I

1BNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

f Y

I SAG I PH I

I # I # I (kV) 1(DEG)l (A) I(DEG)ICONDI (feet) I (feet)l(feet)l I

  • **********2*************************************************************

I 1 1 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 51.01 25.01 A I 1 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 51.01 25.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.l 1 1 18.01 51.01 25.01 C I 1 4 1 1 1

.01 0.1 0.1 0.1 1 I

-19.01 65.8]

10.01 GND I

                          • +*************4**********************t*********************

MINIMUM GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm mete'r SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST l AC RESIST I AC REACT 1 I I I NAME I

(inch)

I (inch)

I (ohm/mile)I (ohm/mile) I (ohm/mile) I I 1 IBITTERN I

1.350 I 18.000 I

.0730 I

.0760 I

.3780 I I 2 IBITTERN I

1.350. 1 18.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 l 18.000 1

.0730 1

.0760 1

.3780 1 1 4 17I10AW I

-.310 1 18.000 1 3.8100 1 3.8800 1

.7770 1

                                                        • +*********************************************

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 520.00 feet
  • LATERAL DISTANCE (feet) (meters)

-50.0

-15.24

-45.0

-13.72

-40.0

-12.19

-35.0

-10.67

-30.0

-9.14

-25.0

-7.62

-20.0

-6.10

-15.0

-4.57

-10.0

-3.05

-5.0

-1.52

.0

.00 5.0 1.52 MAXIMUM I

FIELD I

(kV/m) 1.208 1.465 1.756 2.058 2.321 2.465 2.408 2.126 1.696 1.297 1.147 1.355 MINOR/MAJOR ELLIPSE AXES (ratio)

.002

.004

.008

.015

.027

.046

.080

.140

.243

.396

.485

.371 VERTICAL (kV/m) 1.19B 1.454 1.745 2.050 2.317 2.4 64 2.405 2.110 1.668 1.280 1.147 1.335 HORIZONTAL (kV/m)

.154

.179

.196

.191

.151

.118

.229

.394

.512

.554

.557

.554 SPACE POTENTIAL (kV) 1.204 1.458 1.746 2.043 2.298 2.433 2.366 2.073 1.638 1.245 1.105 1.301 27

10.0 3.05 1.776

.229 1.748

.513 1.718 15.0 4.57 2.212

.134 2.197

.395 2.160 20.0 6.10 2.497

.078 2.494

.230 2.454 25.0 7.62 2.554

.045 2.554

.117 2.522 30.0 9.14 2.410

.025 2.407

.150 2.388 35.0 10.67 2.148

.014 2.139

.191 2.133 40.0 12.19 1.844

.007 1.833

.197 1.834 45.0 13.72 1.550

.003 1.540

.181 1.544 50.0 15.24 1.291

.000 1.281

.156 1.287 100.0 30.48

.253

.001

.252

.022

.253 150.0 45.72

.084

.000

.084

.005

.084 100.0 30.48

.253

.001

.252

.022

.253 150.0 45.72

.084

.000

.084

.005

.084 D

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C: \\TLW30\\ACDCLINE\\DATA\\ACSTR29-Date: 12/ 4/2002 Time: 16: 9 DATE: 12/ 4/2002 TIME: 16: 9 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

                                            • I**************************

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (It RESISTANCE. VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER 25.00 368.00 feet AC SHORT CIRCUIT CURRENT -

3.09 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3283. V It AC VOLTAGE TO GROUND -

1845. V 50% AC VOLTAGE TO GROUND -

272. V 28

Specific Data for 1431+28 span =1434+50 - 1427+10 = 7io feet sag - 23 feet @ 200 degrees and 16 feet at 60 degrees Str 205:

110 feet elevation of conductor connection distanceto road is 1431+28-1427+10=418 feet Str 206: 109.5 feet elevation of conductor connection distance to road is 710 - 418 = 292 feet elevation of ground at road - 60 feet elevation of OHGW = 11 0 + 14.75 124.75 Surrogate Geometry Use 200 degree sag.

Relative height of conductor is 110 feet elevation of conductor - 60 feet elevation of road 50 feet.

(Terrain is level; equal height towers)

Relative height of OHGW is 50 + 14.75 '64.75 feet.

Sketch:

.SC ACDCLINE Run Attached 29

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR205 Date: 12/ 4/2002 Time: 16:49 STR205 Brunswick Delco West; Str 205, SR 1849

                        • ~**********+*********~************+*****4~***********~*****,***

BUNDLE INFORMATION

,*********.*+************i*****+********************,**********i**,******4***

I I

I VOLTAGE I

CURRENT I f I

BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I

  1. I

$ I (kV)

I(DEG)I (A)

I (DEG) ICONDI (feet) I (feet) I (feet) I I

I 1 1 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 50.01 23.01 A

I I 2 1 1 1 230.01 240.l 500.l 240.l 1 *l

.°l 50.01 23.01 B

I 1 3 1. 1 1 230.01 120.1 500.1 120.1 1 1 18.01 50.01 23.01 C I 1 4 1 1 1

.01 0.1 0.l 0.1 1 1

-19.01 64.81 10.01 GND I

    • .********************************i*;********************,****

MINIMUM GROUND CLEARANCE -

27.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter.

                                                                                          • +***************4*******&****
                  • +*****************************4****4***********

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES

                                  • 4,***********~***********

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

f I

NAME I

(inch)

I (inch)

I (ohm/mile) I (ohm/mile) I (ohm/mile) I

        • *1**********0********************************,**************4*********

I 1 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1 18.000 1

.0730 1

.0760 1

.3780 1

I 3 IBITTERN 1.350 I 18.000 I

.0730 1

.0760 1

.3780 1 1 4 17110AW I

.310 1 18.000 1 3.8100 1 3.8800 1

.7770 1

        • t****.*********-*********k*****************i**************
                • ***** *.&i*

0

                              • d**4 ********.***,,*********

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground longitudinal distance: 292.00 feet LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.239

.001 1.227

.172 1.234

-45.0

-13.72 1.532

.003 1.518

.209 1.525

-40.0

-12.19 1.881

.006 1.865

.241 1.870

-35.0

-10.67 2.264

.013 2.250

.249 2.246

-30.0

-9.14 2.624

.024 2.617

.211 2.597

-25.0

-7.62 2.858

.045 2.857

.147 2.818

-20.0

-6.10 2.842.

.082 2.839

.263 2.788

-15.0

-4.57 2.526

.150 2.508

.484 2.461

-10.0

-3.05 2.026

.264 1.997

.636 1.960

-5.0

-1.52

.1.608

.400 1.596

.672 1.550

.0

.00 1.486

.445 1.485

.661 1.427 5.0 1.52 1.665

.381 1.650

.672 1.605 30

10.0 3.05 2.108

.252 2.078

.637 2.041 15.0 4.57 2.614

.144 2.597

.485 2.549 20.0 6.10 2.932

.079 2.930

.263 2.878 25.0 7.62 2.949

.043 2.948

.146 2.909 30.0 9.14 2.716

.023

. 2.709

.210 2.689 35.0 10.67 2.355

.011 2.342

.249 2.338 40.0 12.19 1.971

.004 1.956

.242 1.960 45.0 13.72 1.619

.001 1.606

.211 1.613 50.0 15.24 1.322

.001 1.311

.175 1.318 100.0 30.48

.240

.001

.239

.021

.239 150.0 45.72

.079

.000

.079

.005

.079 100.0 30.48

.240

.001

.239

.021

.239 150.0 45.72

.079

.000

.079

.005

.079 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR205 Date: 12/ 4/2002 Time: 16:49 DATE: 12/ 4/2002 TIME: 16:49.

ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND. ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 292.00 feet AC SHORT CIRCUIT CURRENT -

2.78 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

2945. V 1% AC VOLTAGE TO GROUND -

1655. V 50% AC VOLTAGE TO GROUND -

244. V 31

Brunswick Steam Electric Plant Jacksonville Transmission Line Analysis Data Sources Jacksonville Plan and Profile Drawing, TD-1 1617, sheets 1-46 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1 Jacksonville One-Line TD-11617; 129 System Phasing Diagram, Wilmington Area, TE-12606, sheets 4 and 5 of 5 General Data length: 75.213 miles ROW widths:

no data Conductor. 1272 MCM 45n ACSR; spaced-18, 0,18 at equal height OHGW: two 7#10 AW (3/8'); 14.75' above conductor, +1-19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt toads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. A representative of the least clearance low points was selected as a candidate.

2000 Clearance Structure Location Name (feet) 6-7 46+65 paved road 29 16-17 106+93?

paved road 42 35-36 246+77 NC HWY 133 35 70-71 498+58 NCSR 1521 40 87-88 614+86 NCSRI518 41 135-136 1000+16.20 US HWY 17 28 152-153 1110+41 NCSR437 36 154-155 missing US 74/76 49 158-159 1150+42 US 74 42 178-179 1280+17 NCSR 1430 37 214-215 1530+48 US 421 39 223-224 1600+54.40 NCSR 1109 35 266-267 1914+54 US 117 45 288-289 2060+00 approx 1-40 South 37 @ 212 degrees 288-289 2061+70 approx 1-40 North 29 @ 212 degrees 288-289 2065+60 access road 46 ( 212 degrees 292-293 2093+30.16 SR 1517 37 301-302 2150+07 NC 210 42 305-306 2178+84 NCSR 15?6 40 321-322 2296+38 ShawHighwayRoad 36 462-463 3276+35 NCSR ??04 44 484-485 1708+94 NCSR?09?

30 499-500 1814+16 NCSRI118 38 32

501-502 1824+73 lNCSRIIO9 41 514-515 1907+58 NC 53 1

43 528-529 1995+80 H

HWY 1214 38 534-535 2037+05 HWY 23 42 535-536 j 2039+91

-HWVY 212 46 75-76 537+30 representative low point 27 Selection of Locations to Analyze The least clearance location is over a tnarsh. Therefore, selected 199+50 as the least clearance location to analyze. There is no road there, just forest. The least clearance road is SR 1849 at 1431+28. These two locations will be analyzed.

33

I Specific Data for 537+30 span =537+30-530+00= 730 feet sag = 24 feet @ 200 degrees Str 75: 100 feet elevation of conductor connection distance to point of interest is 730/2 = 365 feet Str 76: 100 feet elevation of conductor connection distance to point of interest is 365 feet elevation of ground at point of interest - 50 feet Surrogate Geometry Use 200 degree sag. Place low point exactly in center span (almost is anyway) at 3 65 feet.

Relative height of conductor connections is 27 feet clearance + 24 feet sag 51 feet.

Relative height of OHGW is 51 + 14.75 65.75 feet.

Sketch:

ACDCLINE Run Attached 34

.3 0

Results of AC/DCLINE program EFION (EPRI/RVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR75 Date: 12/12/2002 Time: 10: 1 STR75 Brunswick-Jacksonville - lowest clearance -at STR 75

  • 4444*444*444*4444444444
  • 4*4**+*************44****44*444444444*4***444444*

BUNDLE INFORMATION

.4****4*************************************************************4******

I I

I VOLTAGE I

CURRENT I f I

BUNDLE COORDINATES l

IBNDLICIRCIVOLTAGEIANGLEI LOAD JANGLE! OF I X

I Y

I SAG I PH I

I I

I I I (kV) l(DEG)l (A) I(DEG)ICONDI (feet) I (feet)l(feet)l I

I**44444444230401*4

              • 4**4444*4*44444*44 4******44444***4*44*44*4***20 I 1 1 1 I 230.01 0.1 500.1 0.1 1 I

-18.01 51;01 24.01 A I 1 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 51.01 24.01 B

I I

3 1 1 I 230.01 120.1 500.l 120.1 1 1 18.01 51.01 24.01 C

I

.1 4 I 1 1

.01 0.1 0.1 0.1 1 1

-19.01 65.81 10.01 GND I 1 5 1 1 1

.01 0.1 0.!

0.1 1 1 19.01 65.81 10.01 GND I

                • 4*****
                                                                                • 4******************

MINIMUM GROUND CLEARANCE -

27.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter

  • *4**4*4**444*4*4 4*4444444444*4*****444*4*+4444444444***4**4*4
  • 4*44**444*
              • 4******4*44444444444444444*4*4*4444444*4*****
  • 44*4444*4444*44******4*

SSUBCONDUCTOR INFORMATION -

REGULAR BUNDLES 444***444*44******4*4*4+*44*44*44***4*************************4 4*444444*4*

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I I NAME (inch)

I (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)l

  • 4*4************

1 1 2

BITTERN I

1.350 1

.000 l

.0730 1

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1

1 3 IBITTERN I

1.350 1

.000 I

.0730 1

.0760 1

.3780 1 1 4 17flOAW I

.310 1

.000 1 3.8100 1

.3.8800 1

.7770 1 1

5 17#10Aw I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 0

                • 44********4**********4*44444*44*************d***.****
  • 4 4

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground longitudinal distance: 365.00 feet LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/n)

(kV)

-50.0

-15.24 1.270

.000 1.257

.178 1.265

-45.0

-13.72 1.575

.001 1.560

.219 1.568

-40.0

-12.19 1.942

.005 1.925

.255 1.931

-35.0

-10.67 2.352

.011 2.337

.269 2.334

-30.0

-9.14 2.747

.023 2.737

.232 2.718

-25.0

-7.62 3.013

.043 3.012

.159 2.970

-20.0

-6.10 3.015

.081 3.012

.273 2.956

-15.0

-4.57 2.689

.150 2.671

.513 2.620

-10.0

-3.05 2.166

.266 2.136

.677 2.098

-5.0

-1.52 1.737

.392 1.726

.709 1.676 35

.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 100.0 150.0 100.0 150.0 0

.00 1.52 3.05 4.57 6.10 7.62 9.14 10.67 12.19 13.72 15.24 30.48 45.72 30.48 45.72 1.601 1.737 2.166 2.689 3.015 3.013 2.747 2.352 1.942 1.575 1.270

.208

.064

.208

.064

.434

.392

.266

.150

.081

.043

.023

.011

.005

.001

.000

.000

.001

.000

.001 1.601 1.726 2.136 2.671 3.012 3.012 2.737 2.337 1.925 1.560 1.257

.207

.064

.207

.064

.692

.709

.677

.513

.273

.159

.232

.269

.255

.219

.178

.020

.004

.020

. 004 1.536 1.676 2.098 2.620 2.956 2.970 2.718 2.334 1.931 1.568 1.265

.208

.064

.208

.064 Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name:.C:\\TLW30\\ACDCLINE\\DATA\\ACSTR75 Date: 12/12/2002 Time: 10: 1 DATE: 12/12/2002 TIME: 10: 1 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS.

0 OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

20.00 365.00 feet AC SHORT CIRCUIT CURRENT -

2.96 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1%

AC VOLTAGE TO GROUND -

50% AC VOLTAGE TO GROUND -

3139. V

.1764. V 261. V 35

Specific Data for 1000+16.20 span =1001+80 - 993+77 = 803 feet sag = 30 feet @ 200 degrees Str 135: 68 feet elevation of conductor connection distance to road is 10016+16 - 993+77 = 639 feet Str 136: 72 feet elevation of conductor connection distance to road is 803 - 639 = 164 feet elevation of ground at road - 18 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductor is'weighted average:

[(68-18)164 + (72-18)639Y803 = 53 feet Sketch:

30 ACDCLINE Run Attached 37

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR135 Date: 12/12/2002 Time: 10: 4 STR135 Brunswick-Jacksonville -

US 17 4**4**.****4**4************44******4*****4***44444*4*4*4*4**44*4444*4***44*

BUNDLE INFORMATION 4*4*4*****44**

  • i*4444444**4*********4*444*4 444******+****4***444*4*4*4*4**

I I

I VOLTAGE I

CURRENT l I I

BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I t I

  1. I (kV) 1(DEG)l (A)

J(DEG)ICONDI (feet) I (feet)j(feet)I I

    • I*2*******************************************

530 301A***

I I 1 1 1 I 230.01 0.1 500.1 0.1 1 1

-18.01 53.01 30.01 A

I 1 2 I 1 1 230.01 240.l 500.1 240.1 1 1

.01 53.01 30.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 53.01 30.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.!

1 I

-19.01 67.81 10.01 GND I 1 5 1 1 -

.01 0.1 0.1 0.1 1 I1 19.01 67.81 10.01 GND I

  • 4********************************************************4***********4***

MINIMUM GROUND CLEARANCE -

23.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter 44 444*********4*44444*****.**44*4*44*44*4*444

  • 4*****4****4*4*

4*44*444*4****

                                      • 4***4*****4*****4*******************4******44***4*4*
    • 4****

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES

                                      • 4************************************4******************

IBNDL I CONDUCTOR I -DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

I I

NAME I (inch)

I (inch)

I (ohm/mile) I (ohm/mile) I (ohmh/ile)l

(****1********************0**********{**********************************

I 1 2

BITTERN 1

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 I

17#10AW I

.310 1

.000 1 3.8100 I 3.8800 1

.7770 1 1 5 I7I1OAW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1

  • 44*444*4*4*44444***
  • 44****4***444444*4****44444*4444*

.4**44*

0 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 164.00 feet
  • LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters). (kV/m)

(ratio)

(kV/m)

(kV/n)

(kV)

-50.0

-15.24 1.180

.003 1.173

.132 1.177

-45.0

-13.72 1.395

.006 1.387

.147 1.389

-40.0

-12.19 1.626

.010 1.619

.151 1.618

-35.0

-10.67 1.850

.017 1.845

.137 1.838

-30.0

-9.14 2.026

.028 2.024

.101 2.008

-25.0

-7.62 2.097

.047 2.097

.098 2.072

-20.0

-6.10 2.015

.076 2.012

.193 1.982

-15.0

-4.57 1.767

.126 1.753

.312 1.726

-10.0

-3.05 1.402

.214 1.377

.400 1.353

-5.0

-1.52 1.033

.373 1.010

.441

.986 38

.0

.00

.844

.535

.844

.450

.816 5.0 1.52 1.033

.373 1.010

.441

.986 10.0 3.05 1.402

.214 1.377

.400 1.353 15.0 4.57 1.767

.126 1.753

.312 1.726 20.0 6.10 2.015

.076 2.012

.193 1.982 25.0 7.62 2.097

.047 2.097

.098 2.072 30.0 9.14 2.026

.028 2.024

.101 2.008 35.0 10.67 1.850

.017 1.845

.137 1.838 40.0 12.19 1.626

.010 1.619

.151 1.618 45.0 13.72 1.395

.006 1.387

.147 1.389 50.0 15.24 1.180

.003 1.173

.132 1.177 100.0 30.48

.237

.000

.236

.021

.237 150.0 45.72

.076

.001

.076

.005

.076 100.0 30.48

.237

.000

.236

.021

.237 150.0 45.72

.076

.001

076

.005

.076 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTRl35 Date: 12/12/2002 Time: 10: 4 0

DATE: 12/12/2002 TIME: 10: 4

  • 4* **

4 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX. (LONG VEHICLE) 4

            • 4*******4***************************4*********

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 164.00 feet AC SHORT CIRCUIT CURRENT -

1.90 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND w 2016. V 1% AC VOLTAGE TO GROUND -

i133. V 50% AC VOLTAGE TO GROUND -

167. V 39

Brunswick Steam Electric Plant Wallace Transmission Line Analysis Data Sources Wallace Plan and Profile Drawing, TD-1 1679, sheets 1-34 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-I Wallace One-Line TD-1l679 - 143 System Phasing Diagram, Wilmington Area, TE-12606, sheets 4 and 5 of 5 General Data length: 54.765 miles [1470+26 restarts survey at 247+06.54]

ROW widths:

Brunswick to 75+88 = CP&L 75+88 to 621+70 = 310' 621+70 to 246+81?= 170' 246+81 to 1707+73 = 170' Conductor 1272 MCM 45/7 ACSR; spaced -18, 0, 18 at equal height OHGW: two 7# 10 AW (3/8"); 14.75' above conductor, +/- 19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. The least clearance low point was selected as a candidate.

2000 Clearance Structure Location Name (feet) 6-7 46+38.37 NCSR 520?

33 16-17 106+79.80 paved road 41 36-37 246+21.09 NCHWY 133 41 72-73 498+67 NCSR1531 32 88-89 615+30.90 NCSR 1518 30 136-137 999+75 US HWY 17 39 152-153 1110+59.14 NCSR41157?

39 154-155 1124+90 US 74/76 47 as labeled 164-165 1190+43 NCSR 1433 41 178-179 1280+74.80 NCSR 1430 44 236-237 473+25.70 US HWY 421 38 259-260 635+11.08 HWY 210 38 301-302 930+97 NCSR 1120 65 314-315 1019+35 NC 53 40 322-323 1076+36 NCST 1216 43 347-348 1251+82 NCSR 1332 43 356-357 1312+99 NCSR 1205 34 363-364 1359+40 NCSR 1333 40 375-376 1441+03 NCSR 1315?

35 391-392 1555+70 NCSR 133 43 40

397-398 1588+87 NCSR 1001 40 403-404 1631+47 NCSR117(likely 39 US 117)__

406-407 1652+40 NCSR 1501 39 53-54 365+80 lowest clearance 24 on line

_I Selection of Locations to Analyze The least clearance location 365+80, is over a marsh.. There is no road there, just a hardwood marsh.

The least clearance road is NCSR 1531 at 615+30.90. These two locations will be analyzed.

Specific Data for 365+80 span = 369+90 -36 1+70 = 820 feet sag = 30 feet @ 200 degrees Str 53: 60 feet elevation of conductor connection distance to point of interest is 820/ 2 410 feet Str 54: 57 feet elevation of conductor connection distance to point of interest is 410 feet elevation of ground at point of interest - 4 feet Surrogate Geometry Use 200 degree sag. Place low point exactly in center span at 410 feet.

Relative height of conductor connections is 24 feet clearance + 30 feet sag = 54 feet.

Relative height of OHGW is 54 + 14.75 68.75 feet.

Sketch:

t

8 ACDCLINE Run Attached 41

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR53-Date: 12/11/2002 Time: 12: 4 STR53-Brunswick-Wallace; lowest point on line, midspan of STR 53-54 BUNDLE INFORMATION I

I I

VOLTAGE I

CURRENT I I I

BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I I

I t I (kV)

I(DEG)l (A)

I(DEG)ICONDI (feet) I (feet)l(feet)l I

        • 320I********************************3
  • 4********************A 1 1 1 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 54.01 30.01 A I I 2 1 1 1 230.01 240.1 500.1 240.1 1 I

.01 54.01 30.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1

-1.01 54.01 30.01 C I I 4 I 2 I

.01 0.1 0.1 0.l 1 I

-19.01 68.81 10.01 GND I 1 5 J 1 1

.01 0.1 0.1 0.l

1. 1 19.0.l 68.81 10.01 GND I MINIMUM GROUND CLEARANCE -

24.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter 4*.***+***************************************************************4*4*4*

                                                                                    • IF*****4d************4**+***4********4*

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I I NAME I (inch)

I (inch).

I (ohm/mile) I (ohm/mile) I (ohm/mile)

  • I* *1**4*******4**4****0***************************
                              • 0*******3 I 1 IBITTERN I

1.350 i

.000 1

.0730 I

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 1

.000 1

.0730 3.0760 1

.3780 1 1 4 17#10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 I

5 I7O1OAW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1

                • 4******************

0 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 4io.00 feet 4

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/rn)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.295

.003 1.279

.200 1.290

-45.0

-13.72 1.645

.001 1.625

.257 1.637

-40.0

-12.19 2.089

.002 2.064

.318 2.076

-35.0

-10.67 2.620

.007 2.595

.362 2.599

-30.0

-9.14 3.182

.018 3.164

.344 3.145

-25.0

-7.62 3.623

.039 3.618

.232 3.565

-20.0

-6.10 3.718

.080 3.716

.318 3.636

-15.0

-4.57 3.335

.161 3.311

.670 3.240

-10.0

-3.05 2.678

.299 2.645

.903 2.598

-5.0

-1.52 2.256

.398 2.252

.908 2.183 42

.0

.00 2.202

.386 2.202

.849 2.103 5.0 1.52 2.256

.398 2.252

.908 2.183 10.0 3.05 2.678

.299 2.645

.903 2.598 15.0 4.57 3.335

.161 3.311

.670 3.240 20.0 6.10 3.718

.060 3.716

.318 3.636 25.0 7.62 3.623

.039 3.618

.232 3.565 30.0 9.14 3.182

.018 3.164

.344 3.145 35.0 10.67 2.620

.007 2.595

.362 2.599 40.0 12.19 2.089

.002 2.064

.318 2.076 45.0 13.72 1.645

.001 1.625

.257 1.637 50.0 15.24 1.295

.003 1:279

.200 1.290 100.0 30.48

.194

.001

.193

.019

.194 150.0 45.72

.059

.001

.058

.004

.059 100.0 30.48

.194

.001

.193

.019

.194 150.0 45.72

.059

.001

.058

.004

.059 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR53-Date: 12/11/2002 Time: 12: 4 0

DATE: 12/11/2002 TIME: 12: 4

    • .k*
  • ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA 2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

20.00 410.00 feet AC SHORT CIRCUIT CURRENT 3.73 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3957.

V 1% AC VOLTAGE TO GROUND -

2224. V 50% AC VOLTAGE TO GROUND -

328. V 43

Specific Data for 615+30.90 span = 617+45 - 609+95 - 750 feet sag = 26 feet @ 200 degrees Str 88:

93 feet elevation of conductor connection distance to road is 615+30.90 - 609+95 = 536 feet Str 89:

90 feet elevation of conductor connection distance to road is 750 - 536 = 214 feet elevation of ground at road - 35 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductors is a weighted average:

[(93-35)214 + (9O-35)536J/750 56 feet Sketch:

-4 A.

R ACDCLINE Ron Attached 44

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR53-Date: 12/11/2002 Time: 12:11 STR53-Brunswick-Wallace; lowest road crossing.at NCSR 1518

  • 4 BUNDLE INFORMATION
      • 4*******4*****~********'*f**********4*********'***+***********'***************

I I

VOLTAGE 1

CURRENT-I I

BUNDLE COORDINATES I

IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I I I I

I (kV)

I(DEG)I (A) ICDEG)ICONDI (feet) I (feet)l(feet)l 1

I 1 1 1 1 230.01 0.1 500.1 0.11 I1

-18.01 56.01 26.01 A

I 1 2 1 -1 1 230.01 240.1 500.1 240.1 1 1

.01 56.01 26.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 56.01 26:01 C

I 1 4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 70.81 10.01 GND.I I

5 1 1 1

.01 0.1 0.1 0.l 1 I1 19.01 70.81 10.01 GND I MINIMUM GROUND CLEARANCE -

30.00 feet POWER SYSTEM FREQUENCY

60.

Hz

-SOIL RESISTIVITY 100.

ohm meter SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I I I NAME I

(inch)

I (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)I I

1 'BITTERN 1.3 50 I

.000 I

.0730 I

.0760 I

.3780 I I 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780.1 1 3 IBITTERN I

1.350 1

.000 I

.0730 1

.0760 1

.3780 1 1 4 II7 AR I

1

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1 5 17#1OAW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 0

            • +**********'**iI.**********

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 214.00 feet
                                    • 4*******+***4'***4' LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet)

(meters)

(kV/m)

(ratio)

(kV/m)

(ky/n)

(kV)

-50.0

-15.24 1.157

.004 1.151

.123 1.153

-45.0

-13.72 1.356

.007 1.349

.135.

1.350

-40.0

-12.19 1.565

.011 1.559

.136 1.557

-35.0

-10.67 1.762

.018 1.759

.119 1.751

-30.0

-9.14 1.910

'.029 1.909

.086 1.893

-25.0

-7.62 1.960

.046 1.960

.092 1.937

-20.0

-6.10 1.871

.075 1.867

.181 1.841

-15.0

-4.57 1.633

.122 1.620

.286 1.596

-10.0

-3.05 1.291

.205 1.266

.365 1.245

-5.0

-1.52

  • .937

.369

.913

.405

.892 45 -

.0

.00

.746

.554

.748

.414

.723 5.0 1.52

.937

.369

.913

.405

.892 10.0 3.05 1.291

.205 1.266

.365 1.245 15.0 4.57 1.633

.122 1.620

.286 1.596 20.0 6.10 1.871

.075 1.867

.181 1.841 25.0 7.62 1.960

.046 1.960

.092 1.937 30.0 9.14 1.910

.029 1.909

.086 1.893 35.0 10.67 1.762

.018 1.759

.119 1.751 40.0 12.19 1.565

.011 1.559

.136 1.557 45.0 13.72 1.356

.007 1.349

.135 1.350 50.0 15.24 1.157

.004 1.151

.123 1.153 100.0 30.48

.242

.000

.241

.021

.242 150.0 45.72

.078

.001

.078

.005

.078 100.0 30.48

.242

.000

.241

.021

.242 150.0 45.72

.078

.001

.078

.005

.078 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR53-Date: 12/11/2002 Time: 12:11 0

DATE: 12/11/2002 TIME: 12:11 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 214.00-feet AC SHORT CIRCUIT CURRENT -

1.78 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1890. V 1% AC VOLTAGE TO GROUND -

1062. V 50% AC VOLTAGE TO GROUND -

157. V.

46

Brunswick Steam Electric Plant Weatherspoon Transmission Line Analysis Data Sources Weatherspoon Plan and Profile Drawing, TD-1 1637, sheets 1-20 Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-I Weatherspoon One-Line TD-1 1637; 135 System Phasing Diagram, Wilmington Area, TE-12606, sheet 4 of 5 General Data length: 77.93 miles ROW widths:

Brunswick to 87+05 = CP&L 87+05 to 232+70 = 310' 232+70 to 1297+94 = 240' 1297+94 to 1642+97 - 170' 1642+97 (27+65) to 1304+00 165-170' Conductor: 1272 MOM 45t7 ACSR spaced-18, 0, 18 at equal height OHGW: one 7#10 AW (3/8"); 14.75' above conductor; +1-19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. The least clearance of these was selected as a candidate.

200° Clearance Structure Location Name (feet) 12-13 87+75 NC HWY 87 51 88-90 603+58 NCSR 1513 36 101 - 101-1

.699+37 US 17 45 109-110 761+75 NCSR 1406 43 206-207 1430+14 SR 1849 35 224-225 1559+29 SR 1824 43 230-231 1594+19 Eastbound US 74/76 39 230-231 1594+95 Westbound US 74176 40 121-122 836+56 representative low 27 point - farm road very close Locations beyond the 1642+99 (STR 239 just west of Delco) were not considered because they pre-existed the plant. Only the analyzed portion was built specifically to connect BSEP to the grid.

Selection of Locations to Analyze Choose representative low point at 836+56 and lowest road clearance at SR 1849, 1430+14.

47

Specific Data for 836+56 span = 840+20 - 832+65 = 755 feet sag = 22 feet @ 200 degrees Str 121:100 feet elevation ofconductor connection distance to point of interest is - 365' Str 122:104 feet elevation of conductor connection distance to point of interest is 755 - 365 = 390 feet elevation of ground at point of interest - 50 feet Surrogate Geometry Use 200 degree sag. Place low point exactly in center span at 378 feet.

Relative height of conductor connections is 27 feet clearance + 22 feet sag 49 feet.

Sketch:

ACDCLINE Run Attached 48

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR121 Date: 12/16/2002 Time:

9: 9 STR121 Brunswick Weatherspoon STR 121, representative low point 4*4*4*4444*4*************4***44****4***4*****4*********44***4****4****4******

BUNDLE INFORMATION VOLTAGE I

CURRENT I I I

BUNDLE COORDINATES IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I I I 4 I (kV)

I(DEG)I (A)

I(DEG)ICONDI (feet)

I (feet)l(feet)l I

44*********************44**************************4*******4***********4*4**

I 1 I 1 1 230.01 0.1 500.1 0.l 1 I1

-18.01 49.01 22.01 A.1 1 2 1 1 1 230.01 240.1 500.1 240.1 1 1

..01 49.01 22.01 B I

1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 49.01 22.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 63.81 10.01 GND I 1 5 1 1 1

.01 0.1 0.1 0.1 1 1 19.01 63.81 10.01 GND I

  • 4*4*d*4*4********44**********4*4**4**********4****4***.********4*******4*4**4 MINIMUM GROUND CLEARANCE -

27.00' feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter 4*4*4*4************4***************44*******4****4*******444****

44*4444444

  • 4*4*444*4**4*4*44******4*44***************4****4*****4***

4*****4*4**4&**44*

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES 4*4*4444 4******************************44************44*****4*4**4**44444****

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

I I

NAME I (inch)

I (inch) 1 (ohm/mile) I (ohm/mile) I (ohm/mile) 1 4*4*4*4*

4*******4****4*******4***444*********4**4******4***********4*4*444**4*

1 1

IBITTERN I

1.35t0

.000 I

.0730 I

.0760 1

.3780 1 I 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780.1 1

3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 I 4. 17I10AW 1

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1 5 17#10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 4*44*4*4

    • 4****************************444*4**444*4*4*444+****44444444*4*****
  • 4**4**4****4**4****4444********4**44***

4 4

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 365.00 feet 4

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet)

(meters)

(kV/m)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.264

.000 1.251

.178 1.260

-45.0

-13.72 1.568

.002 1.553

.218 1.561

-40.0

-12.19 1.934

.005 1.918

.255 1.923

-35.0

-10.67 2.343

.011 2.328

.268 2.325

-30.0

-9.14 2.737

.023 2.728

.232 2.708

-25.0

-7.62 3.003

.043 3.002

.159 2.960

-20.0

-6.10 3.004

.081 3.002

.272 2.946

-15.0

-4.57 2.681

.151 2.662

.511 2.612

-10.0

-3.05 2.160

.266 2.130

.675 2.092

-5.0

-1.52 1.733

.391 1.722

.707 1.672 49

.0

.00 1.598

.437 1.598

.690 1.533 5.0 1.52 1.733

.391 1.722

.707 1.672 10.0 3.05 2.160

.266 2.130

.675 2.092 15.0 4.57 2.681

.151 2.662

.511 2.612 20.0 6.10 3.004

.081 3.002

.272 2.946 25.0 7.62 3.003

.043 3.002

.159 2.960 30.0 9.14 2.737

.023 2.728

.232 2.708 35.0 10.67 2.343

.011 2.328

.268 2.325 40.0 12.19 1.934

.005 1.918

.255 1.923 45.0 13.72 1.568

.002 1.553

.218 1.561 50.0 15.24 1.264

.000 1.251

.17B 1.260 100.0 30.48

.206

.000

.205

.019

.206 150.0 45.72

.063

.001

.063

.004

.063 100.0 30.48

.206

.000

.205

.019

.206 150.0 45.72

.063

.001.

.063

.004

.063 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR121 Date: 12/16/2002 Time:

9: 9 0

DATE: 12/16/2002 TIME:

9: 9 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -2 LONG BOX (LONG VEHICLE)

      • 4*********I**4**********4*,k************~****4****

4,,4

.EQUIVALENT COUPLED OBJECT AREA M

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

.2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 365.00 feet AC SHORT CIRCUIT CURRENT -

2.86 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3037. V 1% AC VOLTAGE TO GROUND -

1707. V 50% AC VOLTAGE TO GROUND -

252. V 50

Specific Data for 1430+14 span =1435+70 - 1428+55 = 715 feet sag - 24 feet @ 200 degrees Str 206:

114 feet elevation of conductor connection distance to road is.1430+14 - 1428f55 159 feet Str 207:

109 feet elevation of conductor connection distance to road is 715 - 159 556 feet elevation of ground at road - 61 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductor is a weighted average:

[(114-61)556 + (109-61)159]J7I5 = 52 feet Sketch:

___I____

ACDCLINE Run Attached 51

0------------------------------------------------

7 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR206 Date: 12/16/2002 Time:

9:13 STR206 Brunswick Weatherspoon STR 206, SR 1849 BUNDLE INFORMATION

                              • ~*,******

I I

I VOLTAGE I

CURRENT I I I

BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

.1 Y

I SAG I PH I

I

$ I I I (kV) 'I(DEG)i (A) I(DEG)ICONDI (feet) I (feet)l(feet)l I

I 1 I 1 I 230.01 0.1 500.1 0.1 1 1

-18.01 52.01 -24.01 A I

1 2 1 1 1 230.01 240.1 500.1240.l 1 1

.01 52.01 24.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 52.01 24.01 C

I 1 4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 66.81 10.01 GND I 1 5 1 1 1

.01 0.1 0.1 0.1 1 1 19.01 66.81 10.01 GND I MINIMUM GROUND CLEARANCE -

28.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

oha meter

                      • +****4*****
                              • .f**************************

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

t I NAME I

(inch)

I (inch)

I (ohm/mile)I (ohm/mile)l (ohm/mile)j 1***3*0***************************0**********0*******************************

I 1 IBITTERN I

1.350 1

.000 1

.0730 l

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1

.000 1

.0730 I

.0760 1

.3780 1 1

3 IBITTERN I

1.350 1

.000 l

.0730 1

.0760 1

.3780 1 I 4 17#10AW I

.310 1

.000 I 3.8100 1 3.8800 1

.7770 1 1 5 17#10AW I

.310 1

.000 1 3.8100 I 3.8800 1

.7770 1

                • 4***************************************************************

O AC ELECTRIC FIELD PROFILE at 3.28 feet above ground longitudinal distance: 159.00. feet

  • +*******+*F**************

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/n)

(ratio)

(kV/m)

(kV/m)

(kV)

-50.0

-15.24 1.137

.004 1.131

.119 1.133

-45.0

-13.72 1.328

.007 1.322

.129 1.323

-40.0

-12.19 1.527

.011 1.522

.129 1.520

-35.0

-10.67 1.713

.018 1.709

.112 1.702

-30.0

-9.14 1.849

.029 1.848

.081 1.833

-25.0

-7.62 1.890

.047 1.890

.090 1.869

-20.0

-6.10 1.800

.074 1.796

.175 1.772

-15.0

-4.57 1.569

.120 1.557

.274 1.533

-10.0

-3.05 1.238

.203 1.214

.349 1.194

-5.0

-1.52

.895

.367

.871

.387

.851 52

.0

.00

.708

.562

.708

.397

.686 5.0 1.52

.895

.367

.871

.387

.851 10.0 3.05 1.238

.203 1.214

.349 1.194

.5.0 4.57 1.569

.120 1.557.

.274 1.533 20.0 6.10 1.800

.074 1.796

.175 1.772 25.0 7.62 1.890

.047 1.890

.090 1.869 30.0 9.14 1.849

.029 1.B48

.081 1.833 35.0 10.67 1.713

.018 1.709

.112 1.702 40.0 12.19 1.527

.011 1.522

.129 1.520 45.0 13.72 1.328

.007 1.322

.129 1.323 50.0 15.24 1.137

.004 1.131..

.119 1.133 100.0 30.48

.241

.000

.240

.021

.241 150.0 45.72.

.078

.001

.078

.005

.078 100.0 30.48

.241

.000

.240

.021

.241 150.0 45.72

.078

.001

.078

.005

.078 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

--- -- -- -- - --- L--

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR206 Date: 12/16/2002 Time:. 9:13 D

DATE: 12/16/2002 TIME:

9:13

  • ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

  • ************4***********,*

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AlP

-ONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 159.00 feet AC.SHORT CIRCUIT CURRENT -

1.67 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1776. V 1% AC VOLTAGE TO GROUND -

998. V 50% AC VOLTAGE TO GROUND -

147. V 53

I Brunswick Steam Electric Plant Whiteville Transmission Line Analysis Data Sources Whiteville Plan and Profile Drawing, TD-1 1680, sheets 1-30A Medium Tangent H-Frame Porcelain Insulator (Steel H-Frame) Drawing CT-00217 230 kV Transmission Lines Suspension Structure (typical 230 kV Wood H-Frame), T3-230 H-1

.Whiteville One-Line TD-11680; 138 System Phasing Diagram, Wilmington Area, TE-12606, sheet 4 of 5 General Data length: 48.3 miles ROWwidths: Brunswickto232+70 =310' 232+70 to Whiteville - mW Conductor: 1272 MCM 45/7 ACSR; spaced -18, 0, 18 at equal height OHGW: two 7#10 AW (3/8'); 14.75' above conductor, +/- 19' from centerline of tower Phasing: ABC looking from plant Candidate Locations to Analyze Ignored dirt roads unless they were identified as State Roads. There are a number of center span (low point) locations with low clearance, but no road. One of the several least clearance locations was selected as a representative.

2000 Clearance 600 Clearance Structure Location Name (feet)

(feet) 13-14 87+56 NC HWY 87 43 46 61-62 421+66 NCSR 1500 41 45 85-86

.590+82 NCSR 1505 42 46 87-88 604+62 NCSR 1504 40 45 117-118 816+53 US'17 35 40 124-125 869+82 NCSR211 42 48 143-144 1003+01 NCSR342??

41 46 145-146 1017+73 NCSR 1007?

42 46 148-149 1037+81 NCSR 1345 37 41 213-214 1486+39 NCSR 1340 43 46 numerous paper company roads crossing and parallel in the ROW 375-376 2617+69

-HWY 748 42 30-31 209+77 representative low 27 *35 point Selection of Locations to Analyze Selected 209+77 as the least clearance location. The least clearance road is US 17 at 816+53. These two locations will be analyzed.

54

Specific Data for 209+77 span = 213+35 -206+20 = 715 feet sag - 23 feet @ 200 degrees and 16 feet at 60 degrees Str 30: 98 feet elevation of conductor connection distance to point of interest is 209+77 -206+20 357 feet Str 31:.98 feet elevation of conductor connection distance to point of interest is 357 feet elevation of ground at point of interest - 48 feet Surrogate Geometry

Use 200 degree sag. Place low point exactly in center span at 367 feet Relative height of conductor connections is 27 feet clearance + 23 feet sag =50 feet.

Relative height of OHGW is 50 + 14.75 - 64.75 feet.

Sketch:

N EC,

ACDCLINE Run Attached

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR30 Date: 12/10/2002 Time: 15:47 STR30 Brunswick Whiteville; Str 30, representative low point

                                              • ,********.**I***********~*********************~****

BUNDLE INFORMATION

      • 4****************
                                                                        • 4************+*******

I I

I VOLTAGE I

CURRENT I

  • I BUNDLE COORDINATES IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I

  1. I
  1. I (kV) -I(DEG)l (A)

I(DEG)ICONDI (feet) I (feet)l(feet)

I

.1 1 1 I1 230.01 0.1 500.1 0.1 1 I

-18.01 50.01 23.01 A I

1 2-1 1 1 230.01 240.1 500.1 240.1 1 1

.01 50.01 23.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 50.01 23.01 C

I 1

4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 64.81 10.01 GND I I 5 I 1 I

.01 0.1 0.1 0.1 1 1 19.01 64.81 10.01 GND I

          • ~*d.*****************,************************~****

MINIMUM GROUND CLEARANCE -

.27.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES

~***~**************************************.f**********************t************

IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

  1. I NAME I (inch)

I (inch)

I (ohm/mile)I (ohm/mile)l (ohm/mile)I I 1 IBITTERN I

1.350 I

.000 I

.0730 1

.0760 I

.3780 1 1

2 IBITTERN 1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1

4 17#10AW 1

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1 5 1710AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 I AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 357.00 feet *
            • 4**************************

LATERAL DISTANCE (feet) (meters)

.- 50.0

-i5.24

-45.0

-13.72

-40.0

-12.19

-35.0

-10.67

-30.0

-9.14

-25.0

-7.62

-20.0

-6.10

-15.0

-4.57

-10.0

-3.05

-5.0

-1.52 MAXIMUM MINOR/MAJOR FIELD ELLIPSE AXES (kV/m) 1.267 1.572 1.939 2.349 2.743 3.010 3.012 2.6B7 2.165 1.737 (ratio)

.000

.001

.005

.011

.023

.043

.081

.151

.266

.392 VERTICAL (kV/m) 1.254 1.557 1.922 2.333 2.734 3.009 3.010 2.669 2.135 1.725 HORIZONTAL (kV/m)

.178

.219

.255

.269

.232

.159

.273

.513

.677

.708 SPACE POTENTIAL (kV) 1.263 1.565 1.928 2.330 2.714 2.967 2.954 2.618 2.0a6 1.676 56

.0

.00 1.601

.435 1.601

.691 1.537 5.0 1.52 1.737

.392 1.725

.708 1.676 10.0 3.05 2.165

.266 2.135

.677 2.096.

15.0 4.57 2.687

.151 2.669

.513 2.618 20.0 6.10 3.012

.081 3.010

.273 2.954 25.0.

7.62 3.010

.043 3.009

.159 2.967 30.0 9.14 2.743

.023 2.734

.232 2.714 35.0 10.67 2.349

.011 2.333

.269 2.330 40.0 12.19 1.939

.005 1.922

.255 1.928 45.0 13.72 1.572

.001 1.557

.219 1.565 50.0 15.24 1.267

.000 1.254

.178 1.263 100.0 30.48

.207

.000

.206

.019

.207 150.0 45.72

.063

.001

.063

.004

.063 100.0 30.48

.207

.000

.206

.019

.207 150.0 45.72

.063

.001

.063

.004

.063 D

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93),for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR30 Date: 12/10/2002 Time: 15:47 0

-DATE: 12/10/2002 TIME: 15:47 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF *6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

          • 4**********

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

25.00 357.00 feet AC SHORT CIRCUIT CURRENT -

2.87 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3041. V 1% AC VOLTAGE TO GROUND -

1709. V 50% AC VOLTAGE TO GROUND -

252. V 57

Specific Data for 816+53 span = 822+3 5 -815+05 =730 feet sag = 25 feet @ 200 degrees and 17 feet at 60 degrees Str 117: 68 feet elevation of conductor connection distance to road is 816+53 - 815+05 = 148 feet Str 118: 74 feet elevation of conductor connection distance to road is 730-148 582 feet elevation of ground at road - 19 feet Surrogate Geometry Use 200 degree sag.

Relative height of conductor is a weighted average:

[(68-19)582 + (74-19)148in30 = 50.2 Relative height of OHGW is 50 +14.75 64.75 feet.

Sketch:

we 72, ACDCLINE Run Attached 58

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR117 Date: 12/10/2002 Time: 15:45 STR117 Brunswick Whiteville; Str 117, US 17 BUNDLE INFORMATION

  • 4****4*******************44****************44******
        • 4*********4***.****

VOLTAGE I

CURRENT I I I BUNDLE COORDINATES.

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

I SAG I PH I

I I

I I I (kV)

I(DEG)l (A)

I(DEG)ICONDI (feet)

I (feet)l(feet)l I

I 1 1 1 1 230.01 0.1 500.1 0.1 1 I

-18.01 50.01 25.01 A I

1 2 i 1 1 230.01 240.1 500.1 240.1 1 1

.01 50.01 25.01 B

I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 50.01 25.01 C

1 1 4 1 1 1

.01 0.1 0.1 0.1 1 1

-19.01 64.81 10.01 GND I

.1 5 1 1 1

.01 0.1 0.1 0.1 1 1 19.01 64.81 10.0lIGND I

  • 44**I**I**
      • 4**I*

MINIMUM GROUND CLEARANCE -

25.00 feet POWER SYSTEM/FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter

                                                    • 4***************4********4******4*********4*********

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

I I NAME I

(inch)

1. (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)I I 1 IBITTERN.

I 1.350 I

.000 I

.0730 I

.0760 I

.3780 I 1

2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1

3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 4 17#10AW I

.310 1

.000 1 3.8100 1 3.8800 1

.7770 1 1

5 17#10AW I

.310.1

.000 1 3.8100 1 3.8800 1

.7770 1

            • 4*4*****4******4***4***44****4*********4*4**4*444
          • 4*******4**********
    • 4*****4***4*******

4****4***4***44**4**

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground

  • longitudinal distance: 148.00 feet
  • 4**4************4********

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)

(kV/n)

(kV)

-50.0

-15.24 1.165

.003 1.158

.129 1.161

-45.0

-13.72 1.375

.006 1.368

.143 1.370

-40.0

-12.19 1.600

.011 1.593

.147 1.592

-35.0

-10.67 1.817

.018 1.812

.132 1.804

-30.0

-9.14 1.984

.029 1.983

.097 1.967

-25.0

-7.62 2.051

.047 2.051

.096 2.027

-20.0

-6.10 1.968

.076 1.964

.189 1.936

-15.0

-4.57 1.724

.125 1.711

.304 1.684

-10.0

-3.05 1.368

.212 1.343

.390 1.320

-5.0

-1.52 1.006

.372

.983

.430

.960 59

.0

.00

.819

.538

.819

.439

.792 5.0 1.52 1.006

.372

.983

.430

.960 10.0 3.05 1.368

.212 1.343

.390 1.320 15.0 4.57 1.724

.125 1.711

.304 1.684 20.0 6.10 1.968

.076 1.964

.189

  • 1.936 25.0 7.62 2.051

.047 2.051

.096 2.027 30.0 9.14 1.984

.029 1.983

.097 1.967 35.0 10.67 1.817

.018 1.812

.132 1.804 40.0 12.19 1.600

.011 1.593

.147 1.592 45.0 13.72 1.375

.006 1.368

.143 1.370 50.0 15.24 1.165

.003 1.158

.129 1.161 100.0 30.48

.236

.000

.235

.021

.235 150.0 45.72

.076

.001

.075

.005

.076 100.0 30.48

.236

.000

.235

.021

.235 150.0 45.72

.076

.001

.075

.005

.076 Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\ACSTR117 Date: 12/10/2002 Time: 15:45 0

DATE: 12/10/2002 TIME: 15:45

  • 4**4************************************4**************4

.4 ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE) 4 f

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER 25.00 148.00 feet AC SHORT CIRCUIT CURRENT -

1.84 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

1952. V 1%

AC VOLTAGE TO GROUND -

1097. V 50% AC VOLTAGE TO GROUND -

162. V 60

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC1LINE Date: 12/10/2002 Time: 13:47 1LINE Generic test of cumulative effect of 3 lines spaced at 75 feet.

BUNDLE INFORMATION I

I I

VOLTAGE I

CURRENT II BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI OF I X

I Y

.I SAG I PH I

I

.1 I I (WkV) I(DEG)I (A) I(DEG)ICONDI (feet) I (feet)j(feet)t

                        • +**************************************************~******

I 1 I 1 1 230.01 0.1 500.1 0.1 1 1

.-18.01 51.01 25.01 A

I 1 2 1 1 1 230.01 240.1 500.1 24D.1 1 1

.01 51.01 25.01 B I I 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 51.01 25.01 C

I MINIMUM GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

Hz SOIL RESISTIVITY 100.

ohm meter

                                  • dr****************************

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT -

I I

I NAME I

(inch)

I (inch)

I (ohm/mile)l (ohm/mile)l (ohm/mile)l I 1 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1

I 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 1

.000. I

.0730 1

.0760 1

.3780 1 0

        • *************+*************

AC ELECTRIC FIELD PROFILE at 3.28 feet above ground i

d*

  • longitudinal distance: 520.00 feet*

LATERAL DISTANCE (feet) (meters)

-150.0

-45.72

-145.0

-44.20

-140.0

-42.67

-135.0

-41.15

.-130.0

-39.62

-125.0

-38.10

-120.0

-36.58

-115.0

-35.05

-110.0

-33.53

-105.0

-32.00

-100.0

-30.48

-95.0

-28.96

-90.0

-27.43

-85.0

-25.91 MAXIMUM I FIELD I

(kV/m)

.076

.084

.093

.103

.115

.12B

.144

.162

.184

.209

.239

.275

.318

.370 MINOR/MAJOR ELLIPSE AXES (ratio)

.001_____

.001

.001

.001

.001

.001

.001

.001

.000

.000

.000

.000

.001

.001

.001 VERTICAL (kV/m)

.076

  • .084

.093

.103

.115

.128

.144

.162

.183

.208.

.238

.274

.316

.368 HORIZONTAL (kV/n)

.005

.005

.006

.007

.008

.010

.011

.013

.015

.018

.021

.026

.031

.038 SPACE POTENTIAL (kV)

.076

.084

.093

.103

.115

.128

.144

.162

.184

.209

.239

.274

.317

.369 61

-80.0

-24.38

.433

.001

.431

.046

.433

-75.0

-22.86

.511

.001

.508

.056

.510

-70.0

-21.34

.606

.001

.602

.069

.605

-65.0

-19.81

.724

.001

.719

.085 723

-60.0

-18.29

.869

.001

.863

.105

.867

-55.0

-16.76 1.048

.000 1.040

.129 1.046

-50.0

-15.24 1.266

.001 1.257

.155 1.262

-45.0

-13.72 1.525

.003 1.514

.181 1.519

-40.0

-12.19 1.817.

.007 1.807

.197 1.808

-35.0

-10.67 2.120

.014 2.112

.191 2.105

-30.0

-9.14 2.382

.026 2.378

.149 2.359

-25.0

-7.62 2.524

.045 2.524

.117 2.492

-20.0

-6.10 2.465

.079 2.462

.230 2.423

-15.0

-4.57 2.179

.136 2.163

.396 2.126

-10.0

-3.05 1.742

.235 1.714

.514 1.683

-5.0

-1.52 1.327

.384 1.307

.556 1.273

.0

.00 1.144

.489 1.144

.559 1.102 5.0 1.52 1.327

.384 1.307

.556 1.273 10.0 3.05 1.742

.235 1.714

.514 1.683 15.0 4.57 2.179

.136 2.163

.396 2.126 20.0 6.10 2.465

.079 2.462

.230 2.423 25.0 7.62 2.524

.045 2.524

.117 2.492 30.0 9.14 2.382

.026 2.378

.149 2.359 35.0 10.67 2.120

.014 2.112

.191 2.105 40.0 12.19 1.817

.007 1.807

.197 1.808 45.0 13.72 1.525

.003 1.514

.181 1.519 50.0 15.24 1.266

.001 1.257

.155 1.262 55.0 16.76 1.048

.000 1.040

.129 1.046 60.0 18.29

.869

.001

.863

.105

.867 65.0 19.81

.724

.001

.719

.085

.723 70.0 21.34

.606

.001

.602

.069

.605 75.0 22.86

.511

.001

.508

.056

.510 80.0 24.38

.433

.001

.431

.046

.433 85.0 25.91 370

.001

.368

.038

.369

.90.0 27.43

.318

.001

.316

031

.317 95.0 28.96

.275

.001

.274

.026

-.274 100.0 30.48

.239

.000

.238

.021

.239 105.0 32.00

.209

.000

.208

.018

.209 110.0 33.53

.184

.000

.183

.015

.184 115.0 35.05

.162

.000

.162

.013

.162 120.0 36.58

.144

.001

.144

.011

.144 125.0 38.10

.128

.001

.i28

.010

.128 130.0 39.62

.115

.001

.115

.008

.115 135.0 41.15

.103

.001

.103

.007

.103 140.0 42.67

.093

.001

.093

.006

.093 145.0 44.20

.084

.001

.084

.005

.084 150.0 45.72

.076

.001

.076

.005

.076 0-

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC1LINE Date: 12/10/2002 Time: 13:47 0

DATE: 12/10/2002 TIME: 13:47

          • I******

ELECTRICAL COUPLING TO.OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE =2 LONG BOX (LONG VEHICLE) 62

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER 25.00 368.00 feet AC SHORT CIRCUIT CURRENT -

3.06 raA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3263. V 1% AC VOLTAGE TO GROUND -

1834. V 50% AC VOLTAGE TO GROUND -

271. V 63

Electric Field Profile 3

II II


I- -

II III Mw a,

.)

IL I

I II II I IoI

-200

-100 0

100 200 Distance ( meters )

c0

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC2LINES Date: 12/10/2002 Time: 13:45 2LINES Generic test of cumulative effect of 2 lines spaced at 75 feet.

BUNDLE -INFORMATION

                  • +***t****************************~*****************&****~&***d******

I VOLTAGE I

CURRENT I t I BUNDLE COORDINATES I

I IBNDLICIRCIVOLTAGEIANGLEI LOAD IANGLEI.OF I X

I *Y I SAG I PH I I f I f I (kV)

I(DEG)

(A) I(DEG)ICONDI (feet)

I (feet)l(feet)l I

                    • II
                        • 2***********************************0********

I 1 1 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 51.01 25.01 A

I 1 2 1 1 1 230.01 240.l 500.1 240.1 1 1

.01 51.0!

25.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 51.01 25.01 C

I

.1 4 1 2 1 230.01 0.1 1000.1 0.l 1 1

-93.01 51.01 25.01 A

I 1 5 1 2 1 230.01 240.1 1000.l 240.1 1 1

-75.01 51.01 25.01 B I 1 6 1 2 1 230.01 120.1 i000.1 120.1 1 1

-57.01 51.01 25.01 C

lI MINIMUM GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

-Hz*

SOIL RESISTIVITY 100.

ohm meter

  • &* *************************************************************~*******~***

SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES

                • 4* ****+**********************************************************&***

IBNiL I CONDUCTOR I DIAMETER I SPACING I DC RESIST I AC RESIST I AC REACT I I

I NAME I (inch)

I (inch)

I (ohm/mile)

(ohm/mile)l (ohm/mile)l

  • *o*****************************************i*******i*l*****************e*.*

I 1 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1.2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 4 IBITTERN

.l 1.350 1

.000 1

.0730 1

.0760 I

.3780 1 I 5 IBITTERN I

1.350 I

.000.

.0730 1

.0760 1

.3780 1 1 6 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1

                                            • .*****************************+***.*****

0

                                              • t***********

AC ELECTRIC FIELD PROFILE-at 3.28 feet above ground longitudinal distance: 520.00 feet LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

(kV/m)

(ratio)

(kV/m)-

(ky/m)

(kV)

-150.0

-45.72

.558

.002

.555

.058

.557

-145.0

-44.20

.657

.002

.653

.072

.656

-140.0

-42.67

.779

.002

.774

.088

.778

-135.0

-41.15

.928

.002

.922

.108

.927

-130.0

-39.62 1.112

.001 1.104

.132 1.109

-125.0

-38.10 1.335

.000 1.325

.159 1.331

-120.0

-36.58 1.598

.003 1.588

.184 1.592

-115.0

-35.05 1.897

.007 1.886

.201 1.887 65

-110.0

-33.53 2.206

.013 2.198'

.195 2.191

-105.0

-32.00 2.476

.024 2.472

.155 2.454

-100.0

-30.48 2.629

.043 2.629

.119 2.598

-95.0

-28.96 2.585

.074 2.583

.222 2.544

-90.0

-27.43

.2.315

.124 2.301

.381 2.266

-85.0

-25.91 1.889

.202 1.863

.490 1.835

-80.0

-24.38 1.449

.307 1.424

.521 1.393

-75.0

-22.86 1.124

.434 1.113

.512 1.073

-70.0

-21.34 1.031

.484 1.030

.502

.991

-65.0

-19.81 1.249

.329 1.231

.459 1.196

-60.0

-18.29 1.544

.199 1.535

.352 1.491

-55.0

-16.76 1.692

.145 1.692

.246 1.643

-50.0

-15.24 1.603

.149 1.598

.273 1.557

-45.0

-13.72 1.329

.224 1.312

.364 1.287

-40.0

-12.19 1.039

.386 1.031

.420 1.020,

-35.0

-10.67 1.039

.386 1.031

.420 1.020

-30.0

-9.14 1.329

.224 1.312

.364 1.287

-25.0

-7.62 1.603

.149 1.598

.273 1.557

-20.0

-6.10 1.692

.145 1.692

.246 1.643

-15.0

-4;57 1.544

.199 1.535

.352 1.491

-10.0

-3.05 1.249

.329 1.231

.459 1.196

-5.0

-1.52 1.031

.484 1.030

.502

.991

.0

.00 1.124

.434 1.113

.512 1.073 5.0 1.52 1.449

.307 1.424

.521 1.393 10.0 3.05 1.889

.202 1.863

.490 1.835 15.0 4.57 2.315

.124 2.301

.381 2.266 20.0 6.10 2.585

.074 2.583

.222 2.544 25.0 7.62 2.629

.043 2.629

.119 2.598 30.0 9.14 2.476

.024 2.472

.155 2.454 35.0 10.67 2.206

.013 2.198

.195 2.191 40.0 12.19 1.897

.007 1.886

.201 1.887 45.0 13.72 1.598

.003 1.588

.184 1.592 50.0 15.24 1.335

.000 1.325

.159 1.331 55.0 16.76 1.112

.001 1.104

.132 1.109 60.0 18.29

.928

.002

.922

.108

.927 65.0 19.81

.779

.002

.774

.088

.778 70.0 21.34

.657

.002

.653

.072

.656 75.0 22.86

.558

.002

.555

.058

.557 80.0 24.38

.477

.002

.475

.048

.477 85.0 25.91

.411

.001

.409

.039

.410 90.0 27.43

.356

.001

.354

.033

.356 95.0 28.96

.310

.001

.309

.027

.310 100.0 30.48

.272

.001

.271'

.023

.272 105.0 32.00

.240

.000

.239

.019

.240 110.0 33.53

.212

.000

.212

.017

.212 115.0 35.05

.189

.000

.188

.014

.189 120.0 36.58

.169

.000

.169

.012

.169 125.0 38.10

.152

.000

.151

.011

.152 130.0 39.62

.137

.001

.136

.009

.137 135.0 41.15

.124

.001

.123

.008

.124 140.0 42.67

.112

.001

.112

.007

.112 145.0 44.20

.102

.001

.102

.006

.102 150.0 45.72

.093

.001

.093

.005

.093.

0 Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93). for:

COUPLING to OBJECTS & SHIELDING by-OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC2LINES Date: 12/10/2002 Time: 13:45 0

DATE: 12/10/2002 TIME: 13:45

      • ELECTRICALCOUPLINGTOE****TS*

ELECTRICAL COUPLING TO OBJECTS 66

INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -

2 LONG BOX (LONG VEHICLE)

        • l*********

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER

-25.00 368.00 feet AC SHORT CIRCUIT CURRENT -

3.15 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3341. V 1% AC VOLTAGE TO GROUND -

1878. V 50% AC VOLTAGE TO GROUND -

277. V 67

I Electric Field Profile 3,-

I I

II I

I I

I--

-I I,

I It I

I A A s I

i:E C.)

.iIs Ill

-200

-100 0

100 200 Distance ( meters )

0, co

0 Results of AC/DCLINE program EFION (EPRI/HVTRC 7-93) for:

ELECTRIC FIELD & IONS WITHOUT SHIELDING OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC3LINES Date: 12/10/2002 Time: 13:45 3LINES Generic test of cumulative effect of 3 lines spaced at 75 feet.

  • 4*******t*****4********4*************4******************
                        • 4***t**

BUNDLE INFORMATION I

I VOLTAGE I

CURRENT f

I BUNDLE COORDINATES IBNDLICIRCIVOLTAGEIANGLE1 LOAD JANGLEI OF I X

l Y

I SAG I PH I

I t I t I (kV)

J(DEG)j (A) I(DEG)ICONDI (feet) l (feet)I(feet)j I

I.1 I 1 1 230.01 0.1 500.1 0.1 1 1

-18.01 51.01 25.01 A

I 1 2 1 1 1 230.01 240.1 500.1 240.1 1 1

.01 51.01 25.01 B I 1 3 1 1 1 230.01 120.1 500.1 120.1 1 1 18.01 51.01 25.01 C I 1 4 1 2 1 230.01 0.1 1000.1 0.l 1 I1

-93.01 51.01 25.01 A I

1 5 1 2 1 230.01 240.1 1000.1 240.1 1 1

-75.0.1.

51.01 25.01 B I 1 6 1 2 1 230.01 120.1 1000.f 120.l 1 1

-57.01 51.01 25.01 C I 1 7 1 3 1 230.01 0.1 1000.1 0.l 1 I1 57.01 51.01 25.01 A I

I 8 1 3 1 230.01240.1 1000.1 240.1 1 1 75.01 51.01 25.01 B I I 9 1 3 1 230.01 120.1 1000.1 120.1 1 1 93.01 51.01 25.01 C

I

  • 4*4********************4****************************************4**********

MINIMUM-GROUND CLEARANCE -

26.00 feet POWER SYSTEM FREQUENCY

60.

Hz

  • SOIL RESISTIVITY 100.

ohm meter

.**************4********************4******************

  • 4**************4**

4**************4*************4*******4****4******4********t*4

        • 4*****&****4
  • SUBCONDUCTOR INFORMATION -

REGULAR BUNDLES IBNDL I CONDUCTOR I DIAMETER l SPACING I DC RESIST I AC RESIST I AC REACT I I i I NAME I

(inch)

I (inch)

I (ohm/mile) I (ohm/mile) I (ohm/mile) I I*

1****0*******

  • 07*********

4*0*4*40*70***4****

                      • 3**7***I******

I 1 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 2 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 I 3 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 4 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 5 IBITTERN I

1.350 1

.000 I

.0730 1

.0760 1

.3780 1 1 6 IBITTERN I

1.350 1

.000 1 *

.0730 1

.0760 1

.3780 1

I 7 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 1 1 8 IBITTERN I

1.350 1

.000 1

.0730 1

.0760 1

.3780 I I 9 IBITTERN I

1.350 1

.000 1

.0730 I

.0760 1

.3780 1

        • 4*************************4**************************************4*****4****

0 AC ELECTRIC FIELD PROFILE at 3.28 feet above ground longitudinal distance: 520.00 feet

  • 4
  • 4*44***********4*4*4444**4**4***4**4**

LATERAL MAXIMUM MINOR/MAJOR SPACE DISTANCE FIELD ELLIPSE AXES VERTICAL HORIZONTAL POTENTIAL (feet) (meters)

MkM/r)

(ratio)

(kV/m)

(kV/n)

(kV)

-150.0

-45.72

.571

.002

.568

.059

.571

-145.0

-44.20

.671

.002

.667

.072

.670 69

-140.0

-42.67

.793

.002

.788

.088

.792

-135.0

-41.15

.943

.002

.937

.109

.942

-130.0

-39.62 1.127

.001 1.120

.132 1.125

-125.0

-38.10 1.350

.000 1.341

.159 1.346

-120.0

-36.58 1.614

.003 1.604

.184 1.608

-115.0

-35.05 1.913

.007 1.902

.201

.1.903

-110.0

-33.53 2.222

.013 2.214

.195 2.208

-105.0

-32.00 2.493

.024 2.489

.155 2.470

-100.0

-30.48 2.646

.043 2.646.

.119 2.614

-95.0

-28.96 2.602

.073 2.599

.222 2.561

-90.0

-27.43 2.332

.123 2.318

.380 2.283

-85.0

-25.91 1.905

.199 1.880

.489' 1.851

-80.0

-24.38 1.462

.302 1.436

.520 1.406

-75.0

-22.86 1.127

.428 1.115

.510 1.075

-70.0

-21.34 1.015

.491 1.014

.500

.975

-65.0

-19.81 1.219

.337 1.202

.458 1.167

-60.0

-18.29 1.510

.204 1.500

.351 1.456

-55.0

-16.76 1.655

.149 1.655

.247 1.606

-50.0

-15.24 1.566

.156 1.560

.277 1.520

-45.0

-13.72 1.296

.238 1.280

.370 1.255

-40.0

-12.19 1.029

.403 1.025

.426 1.013

-35.0

-10.67 1.081

.368 1.070

.426 1.058

-30.0

-9.14 1.403

.210 1.384

.371 1.359

-25.0

-7.62

  • 1.698

.141 1.692

.280 1.652

-20.0

-6.10 1.807

.136 1.807

.245 1.760

-15.0

-4.57 1.680

.179 1.672

.340 1.630

-10.0

-3.05 1.392

.274 1.376

.436 1.342

-5.0

-1.52 1.118

.398 1.109

.467 1.073

.0

.00 1.013

.458 1.013

.464

.970 5.0 1.52 1.118

.398 1.109

.467 1.073 10.0 3.05 1.392

.274 1.376

.436 1.342 15.0 4.57 1.680

.179 1.672

.340 1.630 20.0 6.10 1.807

.136 1.807

.245

.1.760 25.0 7.62 1.698

.141 1.692

.280 1.652 30.0 9.14 1.403

.210 1.384

.371 1.359 35.0 10.67 1.081

.368 1.070

.426 1.058 40.0 12.19 1.029

.403 1.025

.426 1.013 45.0 13.72 1.296

.238 1.280

.370 1.255 50.0 15.24 1.566

.156 1.560

.277 1.520 55.0 16.76 1.655

.149 1.655

.247 1.606 60.0 18.29 1.510

.204 1.500

.351 1.456 65.0 19.81 1.219.

.337 1.202

.458 1.167 70.0 21.34 1.015

.491 1.014

.500

.975 75.0 22.86 1.127

.428 1.115

.510 1.075 80.0 24.38 1.462

.302 1.436

.520 1.406 85.0 25.91 1.905

.199 1.880

.489 1.851 90.0 27.43 2.332

.123 2.318

.380 2.283 95.0 28.96 2.602

.073 2.599

.222 2.561 100.0 30.48 2.646

.043 2.646

.119 2.614 105.0 32.00 2.493

.024 2.489

.155 2.470 110.0 33.53 2.222

.013 2.214

.195 2.208 115.0 35.05 1.913

.007 1.902

.201 1.903 120.0 36.58 1.614

.003 1.604

.184 1.608 125.0 38.10 1.350

.000 1.341

.159 1.346 130.0 39.62 1.127

.001 1.120

.132 1.125 135.0 41.15

.943

.002

.937

.109

.942 140.0 42.67

.793

.002

.788

.088

.792 145.0 44.20

.671

.002

.667

.072

.670 150.0 45.72

.571

.002

.568

.059

.571 0

Results of AC/DCLINE program COUPLE (EPRI/HVTRC 7-93) for:

COUPLING to OBJECTS & SHIELDING by OBJECTS Configuration file name: C:\\TLW30\\ACDCLINE\\DATA\\AC3LIN-S 70

Date: 12/10/2002 Time: 13:45 DATE: 12/10/2002 TIME: 13:45

        • V**4*
  • * ** ** ** * ** ** * *i*

ELECTRICAL COUPLING TO OBJECTS INCLUDING EFFECTS OF 6 SHIELDING OBJECTS OBJECT TYPE -2 LONG BOX (LONG VEHICLE)

      • ****************************~****

EQUIVALENT COUPLED OBJECT AREA -

2890.14 ft**2 CALCULATED CAPACITANCE TO GROUND -

2500. pF CALCULATED RESISTANCE TO GROUND -

.72 kohms (1% RESISTANCE VALUE MEASURED FOR VEHICLES WITH THE SAME CAPACITANCE, IN DIFFERENT WEATHER CONDITIONS AND ON DIFFERENT PAVEMENTS -

NORTHEAST USA)

LATERAL AND LONGITUDINAL DISTANCE TO OBJECT CENTER -

100.00 368.00 feet AC SHORT CIRCUIT CURRENT -

3.16 mA THEORETICAL MAXIMUM AC VOLTAGE TO GROUND -

3357. V 1% AC VOLTAGE TO GROUND -

1887. V 50% AC VOLTAGE TO GROUND -

279. V 71

- z.

I Electric Fietd Profile 3

~ ~ ~ ~ ~

~

~

~

i i

U-0 a)in I

nO

-200

-100 0

Distance ( meters )

100 200

-4 jo