E-mail from Steve Kesler to Thomas Koshy, Subject: Electronic Copy of Palo Verde Switchyard Voltage
ML042960408
Person / Time
Site: Palo Verde  
Issue date: 06/25/2004
From: Kesler S
Arizona Public Service Co
To: Thomas Koshy
Office of Nuclear Reactor Regulation
References
FOIA/PA-2004-0307
Download: ML042960408 (2)


Text

Isye-RE: Electronic Copy of Palo Verde Switchyard Voltages Pagel From:

<SKESLER@apsc.com>

To:

<TXK@nrc.gov>

Date:

Fri, Jun 25, 2004 10:33 AM

Subject:

RE: Electronic Copy of Palo Verde Switchyard Voltage In response to your first request, attached is the voltage plot for the June 14th event. I'm sorry I misunderstood your request. In response to the second subject, APS plans to add phase distance and ground over current detection at each of the lower voltage substation connected to the 500 kV grid in APS system. See the attached e-mail from Baj Agrawal for more detail.

Also, attached are e-mails from Salt River Project and Southern California Edison documenting their reviews that they have do not have single points of failures.

Steve Kesler


Original Message-From: Thomas Koshy [1]

Sent: Friday, June 25, 2004 4:07 AM To: Kesler, Steven L(Z55768)

Subject:

Re: Electronic Copy of Palo Verde Switchyard Voltage

Steve, What I requested was the voltage during the event. Could you get me D

that?

Frequency and the voltage Second subject Any progress on APS decision to install Zone 2 or ground fault protection between 230 and 500kv at West Wing ?

Thomas Koshy, email:txk@ nrc.gov, Tel:(301)415-1176 Electrical Engineering Section Electrical, Instrumentation & Controls Branch Mail Stop 0-4A15A

>>> <SKESLER@apsc.com> 06/22/04 06:02PM >>>

Attached is an electronic version of voltage plot of the 500 KV system at the Palo Verde switchyard, that was previously provided in hard copy.

<<Palo Verde Switchyard Voltage for 6-14-2004.pdf>>>

Steve Kesler CC:

<SKESLER@apsc.com>, <PPARAMIT@ apsc.com>, <HLEAKE @apsc.com>,

\\ jony_~__

RE Elctonc Vev2 Ia!~

rde Switchyardj Vl~tage 2j._L.

1hZ. 72

<DSTRAKA@ apsc.com>, <Bajarang.Agrawalaps.com>