From:

<DSTRAKA@a Pc.com>

To:

<atg@nrc.gov>

PtftV fi_,(QOO '

Date:

6/28/04 2:15PM 0

0

Subject:

RE: Unit 2 tripIEDG 2A loss of voltage Tony:

Please pass along to Chuck Paulk, thank you.

Regards, Don Straka Senior Consultant - Regulatory Affairs dstraka@apsc.com phone: 623.393.5041 pager: 602.509.6240 mobile: 602.509.6240

> -- Original Message-

> From:

Payne, W.Steven (Z99560)

> Sent:

Thursday, June 24, 2004 4:12 PM

> To: Straka, Donald J(Z99942)

> Cc: Steen, Douglas K(Z91197); Radspinner, Mark A(Z76778)

Subject:

Unit 2 trip/EDG 2A loss of voltage

> Don, per my conversation today with Doug Steen and yourself, the

> following is the status of the failed diode that caused EDG 2A to lose

> voltage subsequent to the Unit 2 trip last week.

> Last week, the NRC AIT inspector asked what was the run time of EDG 2A

> (implying what was the hours on the diode). I told him that the diesel

> had run 2325 hours0.0269 days <br />0.646 hours <br />0.00384 weeks <br />8.846625e-4 months <br /> (i.e. the diode was energized for 2325 hours0.0269 days <br />0.646 hours <br />0.00384 weeks <br />8.846625e-4 months <br />). This

> diode is on the installed spare bridge which was just switched to in

> 2R1 1. This diode was energized for only about 75 hours8.680556e-4 days <br />0.0208 hours <br />1.240079e-4 weeks <br />2.85375e-5 months <br /> (root cause not

> determined).

> Thanks,

> Steve Payne

> DG System Engineer

> telephone - 623-393-5157

> email address - wpayneOl@apsc.com CC:

<DKSTEEN@apsc.com>, <MRADSPIN@apsc.com>,

<WPAYNE01 @apsc.com>