May 27, 2004 Mr. David A. Christian Sr. Vice President and Chief Nuclear Officer Dominion Nuclear Connecticut, Inc.
Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711
SUBJECT:
MILLSTONE POWER STATION, UNIT NO. 3 - REVIEW OF PROPOSED REVISION TO THE PREVIOUSLY-APPROVED DEVIATION FROM BRANCH TECHNICAL POSITION CMEB 9.5-1 (TAC NO. MB8731)
Dear Mr. Christian:
By letter dated April 17, 2003, Dominion Nuclear Connecticut, Inc. (DNC) submitted for approval a deviation request to the previously-approved deviation from Branch Technical Position CMEB 9.5-1, Guidelines for Fire Protection for Nuclear Power Plants, Section C.7.c.
In discussions with your staff, DNC was told that a deviation was no longer the process for the Nuclear Regulatory Commission (NRC) staff review and approval of this change. Instead, it was necessary for DNC to submit a proposed license amendment for approval since this change would entail a change in your license condition. As a result of those discussions, DNC formally submitted a proposed amendment for approval by letter dated April 15, 2004. As such, the NRC staffs review of the April 17, 2003 submittal will be discontinued. TAC MB8731 for the review of the April 17, 2003 submittal will be closed, and a new TAC number to cover the review of the April 15, 2004 submittal will be opened. If you have any questions, please contact me at (301) 415-1484.
Sincerely,
/RA/
Victor Nerses, Senior Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-423
Millstone Power Station, Unit No. 3 cc:
Lillilan M. Cuoco, Esquire Senior Counsel Dominion Resources Services, Inc.
Rope Ferry Road Waterford, CT 06385 Edward L. Wilds, Jr., Ph.D.
Director, Division of Radiation Department of Environmental Protection 79 Elm Street Hartford, CT 06106-5127 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 First Selectmen Town of Waterford 15 Rope Ferry Road Waterford, CT 06385 Mr. P. J. Parulis Manager - Nuclear Oversight Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. W. R. Matthews Senior Vice President - Nuclear Operations Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. John Markowicz Co-Chair Nuclear Energy Advisory Council 9 Susan Terrace Waterford, CT 06385 Mr. Evan W. Woollacott Co-Chair Nuclear Energy Advisory Council 128 Terrys Plain Road Simsbury, CT 06070 Senior Resident Inspector Millstone Power Station c/o U.S. Nuclear Regulatory Commission P. O. Box 513 Niantic, CT 06357 Mr. G. D. Hicks Director - Nuclear Station Safety and Licensing Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Ms. Nancy Burton 147 Cross Highway Redding Ridge, CT 00870 Mr. William D. Meinert Nuclear Engineer Massachusetts Municipal Wholesale Electric Company Moody Street P.O. Box 426 Ludlow, MA 01056 Mr. J. Alan Price Site Vice President Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. Chris Funderburk Director, Nuclear Licensing and Operations Support Dominion Resources Services, Inc.
5000 Dominion Boulevard Glen Allen, VA 23060-6711 Mr. David W. Dodson Licensing Supervisor Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385
Millstone Power Station, Unit No. 3 cc:
Mr. S. E. Scace Assistant to the Site Vice President Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. M. J. Wilson Manager - Nuclear Training Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. A. J. Jordan, Jr.
Director - Nuclear Engineering Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385 Mr. S. P. Sarver Director - Nuclear Station Operations and Maintenance Dominion Nuclear Connecticut, Inc.
Rope Ferry Road Waterford, CT 06385
May 27, 2004 Mr. David A. Christian Sr. Vice President and Chief Nuclear Officer Dominion Nuclear Connecticut, Inc.
Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, VA 23060-6711
SUBJECT:
MILLSTONE POWER STATION, UNIT NO. 3 - REVIEW OF PROPOSED REVISION TO THE PREVIOUSLY-APPROVED DEVIATION FROM BRANCH TECHNICAL POSITION CMEB 9.5-1 (TAC NO. MB8731)
Dear Mr. Christian:
By letter dated April 17, 2003, Dominion Nuclear Connecticut, Inc. (DNC) submitted for approval a deviation request to the previously-approved deviation from Branch Technical Position CMEB 9.5-1, Guidelines for Fire Protection for Nuclear Power Plants, Section C.7.c.
In discussions with your staff, DNC was told that a deviation was no longer the process for the Nuclear Regulatory Commission (NRC) staff review and approval of this change. Instead, it was necessary for DNC to submit a proposed license amendment for approval since this change would entail a change in your license condition. As a result of those discussions, DNC formally submitted a proposed amendment for approval by letter dated April 15, 2004. As such, the NRC staffs review of the April 17, 2003 submittal will be discontinued. TAC MB8731 for the review of the April 17, 2003 submittal will be closed, and a new TAC number to cover the review of the April 15, 2004 submittal will be opened. If you have any questions, please contact me at (301) 415-1484.
Sincerely,
/RA/
Victor Nerses, Senior Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-423 DISTRIBUTION:
PUBLIC OGC PDI-2 R/F ACRS CHolden CRaynor CBixler, RI Tech Branch GHill (2)
JClifford VNerses ADAMS Accession Number: ML041400358 OFFICE PDI-2/PM PDI-2/LA PDI-2/SC NAME VNerses CRaynor JClifford DATE 5/20/04 5/19/04 5/20/04 OFFICIAL RECORD COPY