May 4, 2004 Mr. Bryce L. Shriver Senior Vice President and Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Boulevard, NUCSB3 Berwick, PA 18603-0467
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION (RAI) - SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1 AND 2 - REVISED MAIN TURBINE BYPASS SYSTEM REQUIREMENTS (TAC NOS. MC1596 AND MC1597)
Dear Mr. Shriver:
In reviewing your submittal of December 5, 2003, concerning a request to add a requirement to implement linear heat generation rate limits for an inoperable main turbine bypass system, the Nuclear Regulatory Commission staff has determined that additional information contained in the enclosure to this letter is needed to complete its review. This question was discussed with your staff during a teleconference on April 28, 2004. As agreed to by your staff, we request you respond within 30 days of the date of this letter.
If you have any questions, please contact me at 301-415-1030.
Sincerely,
/RA/
Richard V. Guzman, Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-387 and 50-388
Enclosure:
RAI cc w/encl: See next page
May 4, 2004 Mr. Bryce L. Shriver Senior Vice President and Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Boulevard, NUCSB3 Berwick, PA 18603-0467
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION (RAI) - SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1 AND 2 - REVISED MAIN TURBINE BYPASS SYSTEM REQUIREMENTS (TAC NOS. MC1596 AND MC1597)
Dear Mr. Shriver:
In reviewing your submittal of December 5, 2003, concerning a request to add a requirement to implement linear heat generation rate limits for an inoperable main turbine bypass system, the Nuclear Regulatory Commission staff has determined that additional information contained in the enclosure to this letter is needed to complete its review. This question was discussed with your staff during a teleconference on April 28, 2004. As agreed to by your staff, we request you respond within 30 days of the date of this letter.
If you have any questions, please contact me at 301-415-1030.
Sincerely,
/RA/
Richard V. Guzman, Project Manager, Section 1 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-387 and 50-388
Enclosure:
RAI cc w/encl: See next page DISTRIBUTION:
Public OGC CBixler, Rgn-1 RGuzman DLPM DPR PDI-1 R/F RLaufer MOBrien GThomas ACRS FAkstulewicz Accession Number: ML041210001
- See previous concurrence OFFICE PDI-1/PM PDI-2/LA SRXB/SC*
PDI-1/SC NAME RGuzman MOBrien RLandry for FAkstulewicz RLaufer DATE 5/4/04 5/4/04 4/30/04 5/4/04 OFFICIAL RECORD COPY
Enclosure REQUEST FOR ADDITIONAL INFORMATION RELATING TO REVISED MAIN TURBINE BYPASS SYSTEM REQUIREMENTS FOR SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1 AND 2 PPL SUSQUEHANNA, LLC (PPL)
DOCKET NOS. 50-387 AND 50-388 1.
In NUREG-1433, Volume 1, Revision 2, Standard Technical Specifications [STS]
General Electric Plants BWR/4," Section 3.7.7, the average planar linear heat generation rate and the minimum critical power ratio are the applicable thermal limits to allow the limiting condition for operation to be met for an inoperable main turbine bypass system.
PPL proposes to add a requirement to implement the linear heat generation rate thermal limits for an inoperable main turbine bypass system. Please provide the basis for this deviation from the STS.
Susquehanna Steam Electric Station, Unit Nos. 1 and 2 cc:
Richard L. Anderson Vice President - Nuclear Operations PPL Susquehanna, LLC 769 Salem Blvd., NUCSB3 Berwick, PA 18603-0467 Aloysius J. Wrape, III General Manager - Nuclear Assurance PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Terry L. Harpster General Manager - Plant Support PPL Susquehanna, LLC 769 Salem Blvd., NUCSA4 Berwick, PA 18603-0467 Robert A. Saccone General Manager - Nuclear Engineering PPL Susquehanna, LLC 769 Salem Blvd., NUCSB3 Berwick, PA 18603-0467 Rocco R. Sgarro Manager - Nuclear Regulatory Affairs PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Walter E. Morrissey Supervising Engineer Nuclear Regulatory Affairs PPL Susquehanna, LLC 769 Salem Blvd., NUCSA4 Berwick, PA 18603-0467 Michael H. Crowthers Supervising Engineer Nuclear Regulatory Affairs PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Dale F. Roth Manager - Quality Assurance PPL Susquehanna, LLC 769 Salem Blvd., NUCSB2 Berwick, PA 18603-0467 Herbert D. Woodeshick Special Office of the President PPL Susquehanna, LLC 634 Salem Blvd., SSO Berwick, PA 18603-0467 Bryan A. Snapp, Esq Assoc. General Counsel PPL Services Corporation Two North Ninth Street, GENTW3 Allentown, PA 18101-1179 Supervisor - Document Control Services PPL Susquehanna, LLC Two North Ninth Street, GENPL4 Allentown, PA 18101-1179 Richard W. Osborne Allegheny Electric Cooperative, Inc.
212 Locust Street P.O. Box 1266 Harrisburg, PA 17108-1266 Director - Bureau of Radiation Protection Pennsylvania Department of Environmental Protection P.O. Box 8469 Harrisburg, PA 17105-8469 Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 35, NUCSA4 Berwick, PA 18603-0035 Regional Administrator, Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406
Susquehanna Steam Electric Station, Unit Nos. 1 and 2 cc:
Board of Supervisors Salem Township P.O. Box 405 Berwick, PA 18603-0035 Dr. Judith Johnsrud National Energy Committee Sierra Club 443 Orlando Avenue State College, PA 16803