ML041140335

From kanterella
Jump to navigation Jump to search
Part 21 Notification Involving Voltage Monitoring Relays
ML041140335
Person / Time
Site: Beaver Valley, Vogtle, Cook, 07001201  
Issue date: 04/21/2004
From: Starr F
Framatome ANP
To:
Office of Nuclear Reactor Regulation
References
-RFPFR
Download: ML041140335 (6)


Text

0412112004 U.S. Nuclear Regulatory Commission Operations Center Event Report Pare I General Information or Other (PAR)

Event#

40691 Rep Org: AREVA ELECTRICAL PRODUCTS Notification Date I Time: 04/21/2004 13:07 (EDT)

Supplier: AREVA ELECTRICAL PRODUCTS Event Date I Time: 04/21/2004 (EDT)

Last Modification: 04/21/2004 Region: 1 Docket #:

City: CRANBERRY TOWNSHIP Agreement State:

No County:

License #:

State: PA NRC Notified by: FRAN STARR Notifications: DAVID HILLS R3 HQ Ops Officer: JEFF ROTTON VERN HODGE NRR Emergency Class: NON EMERGENCY DAVID SILK RI 10 CFR Section:

TERRANCE REIS NRR 21.21 UNSPECIFIED PARAGRAPH PART 21 NOTIFICATION INVOLVING VOLTAGE MONITORING RELAYS "The following information is provided pursuant to the requirements of 10CFR Part 21 to report a potential safety concern. A potential safety condition may exist with the Eaton Cutler-Hammer D65 Series BI Voltage Monitoring Relay that can cause the unit to bypass the Manual Reset feature. This could result in the D65 relay being energized without an operator manually resetting it resulting in possible personal injury or death or property damage. This condition exists with Eaton Cutler-Hammer D65 Series BI Voltage Monitoring Relays with a manufacturing date between May 12, 2002 and February 20, 2004.

"On March 25, 2004, Framatome/AREVA Electrical Products received the attached Eaton Cutler Hammer Product Safety Warning for D65 Voltage Monitoring Relays, dated March 24, 2004. The Product Safety Warning states that Eaton's Cutler-Hammer D65 Series BI Voltage Monitoring Relays with a manufacturing date identified above may power up without being manually reset even when a NC [Normally closed] switch is wired to activate manual reset mode. This condition is only present when used in applications operating in the manual reset mode. This condition is not present when the device is used in automatic reset mode. This condition may only result when the D65 Series BI is used and will not result if the Al Series is used (as the Al series did not offer the potential for manual reset).

"The supply of Safety Related D65 Voltage Monitoring Relays by Framatome/AREVA Electrical Products is isolated to only one Nuclear Customer (i.e. First Energy - Davis Besse Nuclear Power Plant). The First Energy Davis Besse Nuclear Power Plant was notified by Framatome/AREVA Electrical Products on April 2, 2004."

16 Gf

SPR.-21-2004(WED) 11:59 At AREVA

-ramatome RNP Cranberru PR (FRX)724 779 9844 P.001/005 AREVA-Electrical Products Electrical Products, Pittsburgh 200 West Kensinger Drive, Suite 600 Cranberry Township, Pennsylvania 16066 FAX COVER SHEET Date:

AprIl 21, 2004

  1. of pages:

uhing cowrpage) 5 To:

NRC Operations Center Company:

United States Nuclear Regulatory Commission Telephone #:

(301)- 16-5100 Fax #.

(301).816-5151 From:

Fran Starr - Quality Manager AREVA Electrical Products Company:

Framatome ANP, Electrical Products Telephone

.724-779-9800 EXL 1321_

Fax it:

724-779-9844 COMMENTS:

Subject I OCFR Part 21 NRC Initial Notification Attached please find Framatome ANP, Inc. - AREVA Electrical Products, Letter No.

LTA 04117 which identifies a potential safety concern associated with Eaton Cutler-Hammer D65 Voltage Monitoring Relays.

Should you have any questions, please Contact me at (724) 779-9800, ext 1321.

Thank You, Fran Starr Quality, Manager - AREVA Electrical Products THtS MESSAO! IS INTENDED ONIY FOR THE UsS OF THE INMDrOUAL OR ENTrTY TO WHICH IT IS ADDRESSED, ANO MAY CONTAIN INFORMAllON THAT IS PRIVLSOGED AND/OR CONFIDENTIAL AND PROPRIETARY TO FRAMATOME ANP, I=c It you arO not tho Intandad roedplent,.or an omployan or gont razpanzblhc for dolivering the mmcioe to the Intended rceieont, you arm hereby notified that any dlzzxrinatlon, dstlibution, or copying of this communication Is strictly prohibited. It you have recelved this communication In error. please notify us ImmedIately by tWlaphonc and return the original messgo to us by mall. Thank you.

04/21/2004 WED 13:02

[TI/RX NO 5923] 0 001

APR-21-2004(WED) 11:59 Framatome RNP Cranberry PR (FAX)724 779 9844 P.002/005 At ARE VA April 21, 2004 LTR 04117 Document Control Desk United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Director, Office of Inspection and Enforcement Subject Potential Safety Condition for Eaton Cutler-Harnmer D65 Voltage Monitoring Relays The following Information is provided pursuant to the requirements of 1 OCFR Part 21 to report a potential safety concern. A potential safety condition may exist with the Eaton Cutler-Hammer D65 Series Bi Voltage Monitoring Relay that can cause the unit to bypass the Manual Reset feature. This could result in the D65 relay being energized without an operator manually resetting It resulting in possible personal Injury or death or property damage. This condition exists with Eaton Cutler-Hlammer D65 Series 81 Voltage Monitoring Relays with a manufacturing date between May 12, 2003 and February 20, 2004.

On March 25, 2004, Framatome/AREVA Electrical Products received the attached Eaton Cutler-Hammer Product Safety Warning for D65 Voltage Monitoring Relays, dated March 24,2004.

The Product Safety Warning states that Eaton's Cutler-Hammer DBS Series 81 Voltage Monitoring Relays with a manufacturing date Identified above may power up without being manually reset even when a NC switch Is wired to activate manual reset mode. This condition Is only present when used In applications operating In the manual reset mode. This condition is not present when the device is used in automatic reset mode. This condition may only result when the D55 Series Si Is used and will not result I the Al Series Is used (as the Al series did not offer the potential for manual reset).

The logic board of the relay is being powered by two of the three phases. It is Phases B and C for the surface mount units (style numbers beginning with D65VMLS) and Phases A and C for the plug-in units (style numbers beginning with D6SVMLP). If either of the phases being used to power the logic board Is lost, the logic board configurations are lost and the unit will go into Power Up mode upon clearing of the fault The unit will not operate as If It is wired for Manual Reset Mode.

ONLY the style numbers identified below are affected:

DS5VMLS4BD-Bl D65VMLS120-B1 DSSVMLSSOO-81

  • D65VMLP480-B1
  • D6SVMLPI2O-81 D65VMLP120-Bl FRAMATOME ANP, INC.

200 West Konsingar Drive. Sulto BOO Cranberry Township, Ponneylvania 10060 Phone: 724-779-9800 / Fax: 724-770.98144 www.areva.comn 04/21/2004 WED 13:02

[TX/RX NO 5923] Ri002

RPR-21-2004(WED) 11:59 Framatome RNP Cranberry PR (FAX)724 779 9844 P. 003/005 Document Control Desk LTR 04117 Director, Office of Inspection and Enforcement Page 2 of 2 ONLY date codes between 0320 and 0408 are affected. The date code of the unit can be determined by finding the four-digit numerical code on th6 lower left side of the product label located on the left side of the unit. The right side of the unit has a label to identify the type of fault which has occurred based upon LED status. The date code is on the label on the opposite side of the unit The first two digits of the date code represent the year of manufacturer while the second two digits represent the month of manufacture.

If a D65 Series BI Voltage Monitoring Relays with a Manufacturing Date Code between 0320 and 0408 Is being utilized and the application requires manual reset, replacement of the unit Is required. If the automatic reset mode is being utilized, the unit will operate properly and Is not subject to the condition identified in the attached Eaton Cutler-Hammer Product Safety Warning, however, replacement of the unit is suggested by Eaton Cutler-Hammer. If the unit Is not replaced for any reason, the units must be labeled to explain to any future user not to use the unit In the manual reset mode.

The supply of Safety Related D65 Voltage Monitoring Relays by Framatome/AREVA Electrical Products Is Isolated to only one Nuclear Customer (i.e. First Energy - Davis Besse Nuclear Power Plant). The First Energy Davis Besse Nuclear Power Plant was notified by Framatome/AREVA Electrical Products on April 2,2004.

Frarnatome/ARIEVA Electrical Products recommends the replacement of all D65 Series B8 Voltage Monitoring Relays with a manufacturing Date Code between May 12,2003 and February 20, 2004. For additional information regarding product replacement, please contact Laurence Patterson, Project Management - AREVA Electrical Products at (724) 779-9800 ext.

1317.

Sincerely, AREVA Electrical Products Fran Starr Quality Manager Attachment Eaton Cutler-Hammer Product Safety Warning, D65 Monitoring Relays, dated 3124104 cc Gary Gibson - ELP Laurence Patterson - ELP Dan Mikow - ELP Joe Beene - ELP Dan Livermore - ELP W[lliam Orga - ELP Jim Mallay-FANP Emily A. Mayhew - FANP Tarm W. Werner - FANP FRAMATOME ANP, INC.

200 Wost Kensinger Drive, Suite 600 Cranberry Township, Pennsylvanhi 16050 Phone: 724-779-9800 I Fax: 724-.779.9044 www.arova.com 04/21/2004 WED 13:02

[TI/RX NO 5923]

aO03

RPR-21-2004(WED) 11:59 Framatome ANP Cranberry PA (FAX)724 779 9844 P.004/005 Cutier-Hammer 401 N.

SL E X.W*

oN MUWdUkae.WE 3215 184 (414) 49460 I= (414) 497a19 March 24,2004 To: Valued Eaton Customer Product Safety Warning D65 Voltage Monitoring Relays For Applications Using Manual Reset Mode Eaton Corporation has identified a quality Issue with our D65 Series B1 Voltage Monitoring Relay that can cause the unit to bypass the Manual Reset feature. This could result In the D65 relay being energized without an operator manually resetting It resulting In possible personal injury or death or property damage. This document describes which products and what applications are affected, and the corrective actions required.

If you are using a D65 relay with the Manual Reset feature, the unit must be replaced. As part of our standard warranty process, Eaton will arrange to send you replacement devices In advance to facilitate easier replacement The replacement D65 products are Identified as Series 82 devices.

A modification has been made to the Software for this device that will permanently eliminate any potential for this condition occurring In the future. When In the manual reset mode, the reset button must be opened on power up and after a fault has been cleared to allow the unit to operate normally.

In addition, the adjustable time delay (1-300 seconds) now applies both on power up and on restart after a fault has been cleared. All other features of the product remain the same-Description Eaton's Cutler-Hammer D65 Series B1 Voltage Monitoring Relays with a Manufacturing Date between May 12, 2003 and Februay20,2004 may power up without being manually reset-even when a NC switch Is wired to activate manual reset mode. This could result In personal Injury, 'equipment damage, or death. This condition Is only present when used in applications operating In the.

manual reset mode. This condition is not present when the deVice Is used in automatlC ret mode. This condition may only result when the D65 Series 81 is used end will not result if the Al Series Is used (as the Al series did not offer the potential for manual reset). A list of affected style numbers is found later in this document.

The logic board of the relay Is being powered by two of the three phases. It is Phases B and C for the surface mount units (style numbers beginning with D65VMLS) and Phases A and C forthe plug-in units (style numbers beginning with D65VMLP). If either of the phases being used to power the logic board Is lost, the logic board configurations are lost and the unit will go Into Power Up mode upon clearing of the fault. The unit wil not operate as If It Is wired for Manual Reset Mode.

Page 1 of 2 04/21/2004 WED 13:02

[TX/RI NO 59231 lM004

APRL21-2004(WED) 11:59 Frawatome RNP Cranberry PR (FAX)724 779 9844 P. 005/005 Corrective Actions If you are using a D65 Series B1 Voltage Monitoring Relay with a Manufacturing Date Code between 0320 and 0408 and your application requires manual reset, we require you to return the device for a no-charge replacement unit using standard warranty procedures.

If you are using automatic reset mode, the unit will operate properly and Is not subject to the condition described In this document. However, we suggest that you return the unit for a replacement device through standard warranty procedures. If you decide not to replace the unit for any reason, you must apply the enclosed sUcker somewhere visible on the unit to explain to any future user not to use the unit In the manual reset mode.

Product Identification ONLYthe style numbers listed below are affected:

DG5MWLS480-B1 D65VMLSI120-B1 De5VMLS600-B1 DS5VMLP480-B1 D65VMLP120-Bl P ONLY date codes between 0320 and 0408 are affected. You can determine the date code of your unit by finding the four-digit numerical code on the lower left side of the product label located on the left side of the unit. The right side of the unit has a label to Identify the type of fault which has occurred based upon LED status -the date code Is on the label on the opposite side of the unit The first two digits of the date code represent the year of manufacture while the second two digits represent the month of manufacture. Date codes 0320 through 0408 are affected.

Help In filing a warranty claim is available by calling the local distributor who sold the unit If you can not identify where the unit was purchased from, please call Eaton at (800) 410-2910 to get a replacement Please call Betty Robinson in our Warranty Department at 828-651-0942 for other questions regarding this Product Warning. Eaton continuously strives to produce the highest quality products. We apologize for any Inconvenience that this may have caused you.

Sincerely, Kerry J. Tingley Product Manager Industrial Controls Division Page 2 of 2 04/21/2004 WED 13:02

[1TX/RX NO 59231 21005