Indiana Michigan Power Company 500 Circle Drive Buchanan, MI 49107 1395 INDIANA MICHIGAN POWER February 10, 2004 AEP:NRC:2691-39 Docket Nos.

50-315 50-316 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop O-P1-17 Washington, DC 20555-0001 Donald C. Cook Nuclear Plant Units I and 2 MONTHLY OPERATING REPORT Pursuant to the requirements of Donald C. Cook Nuclear Plant Unit 1 and Unit 2 Technical Specification 6.9.1.8, the attached Monthly Operating Report for January 2004 is submitted.

Additionally, the Unit 1 NRC Operating Data Report and the Unit 1 Average Daily Power Level for June 2003 are being resubmitted due to a data entry error. The error affected the Unit 1 auxiliary power generation. The total auxiliary power was revised for the month of June 2003 prior to preparing the July 2003 NRC Monthly Operating Report. Therefore, this error did not affect subsequent NRC Monthly Operating Reports.

There are no new commitments associated with this submittal.

Should you have any questions, please contact Mr. Toby K. Woods, Compliance Supervisor, at (269) 466-2798.

Sincerely, John i. Zwolinski Director of Design Engineering and Regulatory Affairs JEN/jen Attachment

.A

U. S. Nuclear Regulatory Commission AEP:NRC:2691-39 Page 2 c: R. Aben - Department of Consumers and Industry Services ANI Nuclear Engineering Department L. Brandon - MDEQ - WHMD/HWRPS M. J. Finissi G. T. Gaffney - Canton INPO Records Center J. N. Jensen J.T.King-MPSC B. Lewis - McGraw-Hill Companies D. H. Malin K. L. Matheny M. K. Nazar NRC Project Manager - NRR NRC Region m NRC Resident Inspector D. W. Paul - Columbus T. C. Pham W. H. Schalk J. A. Zwolinski

N.R.C. OPERATING DATA REPORT DOCKET NO.

50-315 DATE 2/3/2004 COMPLETED BY R. Harris TELEPHONE 269-465-5901 OPERATING STATUS

1. Unit Name D. C. Cook Unit I Notes:
2. Reporting Period Jan-04
3. Licensed Thermal Power (MWt) 3304
4. Name Plate Rating (Gross MWe) 1152
5. Design Electrical Rating (Net MWe) 1020
6. Maximum Dependable Capacity(GROSS MWe) 1056
7. Maximum Dependable Capacity (Net MWe) 1000
8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons
9. Power Level To Which Restricted. If Any (Net MWe)
10. Reasons For Restrictions.

This Mo.

Yr. to Date

11. Hours in Reporting Period 744.0 744.0
12. No. of Hrs. Reactor Was Critical 744.0 744.0
13. Reactor Reserve Shutdown Hours 0.0 0.0
14. Hours Generator on Line 744.0 744.0
15. Unit Reserve Shutdown Hours 0.0 0.0
16. Gross Therm. Energy Gen. (MWH) 2456463.2 2456463.2
17. Gross Elect. Energy Gen. (MWH) 799520.0 799520.0
18. Net Elect. Energy Gen. (MWH) 773280.0 773280.0
19. Unit Service Factor 100.0 100.0
20. Unit Availability Factor 100.0 100.0
21. Unit Capacity Factor (MDC Net) 103.9 103.9
22. Unit Capacity Factor (DER Net) 101.9 101.9
23. Unit Forced Outage Rate 0.0 0.0
24. Shutdowns Scheduled over Next Six Months (Type,Date,and Duration):

Cumm.

254952.0 174645.3 463.0 171923.6 321.0 513824990.7 166841323.0 160618563.9 67.9 67.9 64.4 63.2 19.0

25. If Shut Down At End of Report Period, Est'd Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

UNIT DATE COMPLETED BY TELEPHONE 50-315 ONE 03-Feb-04 R. Harris 269-465-5901 MONTH Jan-04 AVERAGE DAILY POWER LEVEL AVERAGE DAILY POWER LEVEL DAY DAY 1/1/2004 1/2/2004 1/3/2004 1/4/2004 1/5/2004 1/6/2004 1/7/2004 1/8/2004 1/9/2004 1/10/2004 1/11/2004 1/12/2004 1/13/2004 1/14/2004 1/15/2004 1/16/2004 1039 1043 1042 1035 1040 1040 1038 1037 1039 1038 1036 1037 1041 1038 1038 1042 1117/2004 1/18/2004 1/19/2004 1/20/2004 1/21/2004 1/22/2004 1/23/2004 1/24/2004 1/25/2004 1/26/2004 1/27/2004 1/28/2004 1/29/2004 1/30/2004 1/31/2004 1040 1042 1038 1039 1041 1039 1042 1035 1040 1039 1040 1042 1038 1041 1040

DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE PAGE 50-315 D.C. Cook Unit I February 4, 2004 J. Newmiller 269-465-5901 1 of 1 UNIT SHUTDOWNS AND POWER REDUCTIONS - January 2004 METHOD OF SHUTTING LICENSEE DURATION DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION NO.

DATE TYPE' HOURS REASON2 REACTOR3 REPORT NO.

CODE 4 CODE5 TO PREVENT RECURRENCE None 1 TYPE:

F: Forced S: Scheduled 2 REASON:

A: Equipment Failure (Explain)

B: Maintenance or Test C: Refueling D: Regulatory Restriction E: Operator Training and License Examination F: Administrative G: Operational Error (Explain)

H: Other (Explain) 3 METHOD:

1: Manual 2: Manual Scram 3: Automatic Scram 4: Other (Explain) 4 SYSTEM:

Exhibit G - Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5 COMPONENT:

Exhibit I: Same Source

N.R.C. OPERATING DATA REPORT DOCKET NO.

50-316 DATE 213/2004 COMPLETED BY R. Harris TELEPHONE 269-465-5901 OPERATING STATUS

1. Unit Name D. C. Cook Unit 2 Notes:
2. Reporting Period Jan-04
3. Licensed Thermal Power (MWt) 3468
4. Name Plate Rating (Gross MWe) 1133
5. Design Electrical Rating (Net MWe) 1090
6. Maximum Dependable Capacity(GROSS MWe) 1100
7. Maximum Dependable Capacity (Net MWe) 1060
8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons
9. Power Level To Which Restricted. If Any (Net MWe)
10. Reasons For Restrictions.

This Mo.

Yr. to Date Cumm.

11. Hours in Reporting Period 744.0 744.0 229098.0
12. No. of Hrs. Reactor Was Critical 670.6 670.6 148953.9
13. Reactor Reserve Shutdown Hours 0.0 0.0 0.0
14. Hours Generator on Line 665.1 665.1 145019.3
15. Unit Reserve Shutdown Hours 0.0 0.0 0.0
16. Gross Therm. Energy Gen. (MWH) 2277302.4 2277302.4 455953161.9
17. Gross Elect. Energy Gen. (MWH) 754080.0 754080.0 147868110.0
18. Net Elect. Energy Gen. (MWH) 730226.8 730226.8 142595133.4
19. Unit Service Factor 89.4 89.4 63.9
20. Unit Availability Factor 89.4 89.4 63.9
21. Unit Capacity Factor (MDC Net) 92.6 92.6 59.9
22. Unit Capacity Factor (DER Net) 90.0 90.0 58.2
23. Unit Forced Outage Rate 10.6 10.6 23.3
24. Shutdowns Scheduled over Next Six Months (Type,Date,and Duration):
25. If Shut Down At End of Report Period, Estd Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

UNIT DATE COMPLETED BY TELEPHONE 50-316 TWO 3-Feb-04 R. Harris 269-465-5901 MONTH Jan-04 AVERAGE DAILY POWER LEVEL AVERAGE DAILY POWER LEVEL DAY DAY 1/1/2004 1/2/2004 1/3/2004 1/4/2004 1/5/2004 1/6/2004 117/2004 1/8/2004 1/9/2004 1/10/2004 1/11/2004 1/12/2004 1/13/2004 1/14/2004 1/15/2004 1/16/2004 0

0 0

339 1088 1112 1114 1111 1115 1113 1112 1110 1111 1115 1101 1118 1/17/2004 1/18/2004 1/19/2004 1/20/2004 1/21/2004 1/22/2004 1/23/2004 1/24/2004 1/25/2004 1/26/2004 1/27/2004 1/28/2004 1/29/2004 1/30/2004 1/31/2004 1120 1120 1120 1118 1118 1121 1115 1122 1117 1113 1115 1116 1117 1116 1117

DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE PAGE 50-316 D.C. Cook Unit 2 February 4, 2004 J. Newmiller 269-465-5901 1 of 1 UNIT SHUTDOWNS AND POWER REDUCTIONS - January 2004 METHOD OF SHUTTING LICENSEE DURATION DOWN EVENT SYSTEM COMPONENT CAUSE AND CORRECTIVE ACTION NO.

DATE TYPE1 HOURS REASON 2 REACTOR 3 REPORT NO.

CODE 4 CODE5 TO PREVENT RECURRENCE 216 031230 F

78.9 H

3 316/2003-005 EF BU Unit 2 Reactor automatically tripped from 100% power due to a low steam generator level coincident with feed flow less than steam flow, which occurred during maintenance activities.

I TYPE:

F: Forced S: Scheduled 2 REASON:

A: Equipment Failure (Explain)

B: Maintenance or Test C: Refueling D: Regulatory Restriction E: OperatorTraining and License Examination F: Administrative G: Operational Error (Explain)

H: Other (Explain) 3 METHOD:

1: Manual 2: Manual Scram 3: Automatic Scram 4: Other (Explain) 4 SYSTEM:

Exhibit G - Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 0161) 5 COMPONENT:

Exhibit l: Same Source

N.R.C. OPERATING DATA REPORT DOCKET NO.

50-315 DATE 1/21/2004 COMPLETED BY T. Pham TELEPHONE 269-465-5901 OPERATING STATUS

1. Unit Name D. C. Cook Unit 1 Notes:
2. Reporting Period Jun-03
3. Licensed Thermal Power (MWt) 3304
4. Name Plate Rating (Gross MWe) 1152
5. Design Electrical Rating (Net MWe) 1020
6. Maximum Dependable Capacity(GROSS MWe) 1056
7. Maximum Dependable Capacity (Net MWe) 1000
8. If Changes Occur in Capacity Ratings (Items no. 3 through 7) Since Last Report Give Reasons
9. Power Level To Which Restricted. If Any (Net MWe)
10. Reasons For Restrictions.

This Mo.

11. Hours in Reporting Period 720.0
12. No. of Hrs. Reactor Was Critical 720.0
13. Reactor Reserve Shutdown Hours 0.0
14. Hours Generator on Line 720.0
15. Unit Reserve Shutdown Hours 0.0
16. Gross Therm. Energy Gen. (MWH) 2377289.8
17. Gross Elect. Energy Gen. (MWH) 770667.0
18. Net Elect. Energy Gen. (MWH) 745175.0
19. Unit Service Factor 100.0
20. Unit Availability Factor 100.0-
21. Unit Capacity Factor (MDC Net) 103.5
22. Unit Capacity Factor (DER Net) 101.5
23. Unit Forced Outage Rate 0.0
24. Shutdowns Scheduled over Next Six Months (Type,Dateand Duration):

Yr. to Date 4343.0 3065.9 0.0 3030.5 0.0 9892795.1 3204963.0 3098451.7 69.8 69.8 71.3 69.9 30.2 Cumm.

249791.0 170414.5 463.0 167719.4 321.0 500161869.7 162447393.0 156373648.2 67.6 67.6 64.0 62.8 19.4 l

I

25. If Shut Down At End of Report Period, Est'd Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forecast Achieved INITIAL CRITICALITY INITIAL ELECTRICITY COMMERCIAL OPERATION

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

UNIT DATE COMPLETED BY TELEPHONE 50-315 ONE 21-Jan-04 T. Pham 269-465-5901 MONTH Jun-03 AVERAGE DAILY POWER LEVEL AVERAGE DAILY POWER LEVEL DAY DAY 6/1/2003 6/2/2003 6/3/2003 6/4/2003 6/5/2003 6/6/2003 6/7/2003 6/8/2003 6/9/2003 6/10/2003 6/11/2003 6/12/2003 6/13/2003 6/14/2003 6/15/2003 6/16/2003 1024 1026 1041 1028 1043 1038 1039 1040 1040 1040 1038 1046 1032 1035 1045 1039 6/17/2003 6/18/2003 6/19/2003 6/20/2003 6/21/2003 6/22J2003 6/23/2003

  • 6/24/2003 6/25/2003
  • 6/26/2003 6/27/2003 6/28/2003 6/29/2003 6/30/2003 1034 1020 1025 1036 1039 1033 1033 1032 1028 1027 1028 1027 1041 1051 I