November 21, 2003 Mr. James Scarola, Vice President Shearon Harris Nuclear Power Plant Carolina Power & Light Company Post Office Box 165, Mail Code: Zone 1 New Hill, North Carolina 27562-0165
SUBJECT:
SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 - FINAL ACCIDENT SEQUENCE PRECURSOR ANALYSIS OF SEPTEMBER 2000 OPERATIONAL EVENT
Dear Mr. Scarola:
The Nuclear Regulatory Commission (NRC) staff conducted a preliminary Accident Sequence Precursor (ASP) analysis of an operational event that occurred at the Shearon Harris Nuclear Power Plant, Unit 1 in September 2000. This condition was documented in Licensee Event Report (LER) 400/2000-007-02, event date September 4, 2000. You did not provide comments on the preliminary ASP analysis. However, on April 22, 2003, during a telephone conversation, you informed the NRC staff that further analysis by the pump vendor determined that the pump was operable during the period in question. With the new information provided on the pump operability, the final ASP program position is to reject the operating condition as a potential precursor because the change in core damage probability is less than 10-6.
Please contact me at 301-415-3025 if you have any questions regarding the enclosure.
Sincerely,
/RA/
Chandu P. Patel, Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-400 cc: See next page
November 21, 2003 Mr. James Scarola, Vice President Shearon Harris Nuclear Power Plant Carolina Power & Light Company Post Office Box 165, Mail Code: Zone 1 New Hill, North Carolina 27562-0165
SUBJECT:
SHEARON HARRIS NUCLEAR POWER PLANT, UNIT 1 - FINAL ACCIDENT SEQUENCE PRECURSOR ANALYSIS OF SEPTEMBER 2000 OPERATIONAL EVENT
Dear Mr. Scarola:
The Nuclear Regulatory Commission (NRC) staff conducted a preliminary Accident Sequence Precursor (ASP) analysis of an operational event that occurred at the Shearon Harris Nuclear Power Plant, Unit 1in September 2000. This condition was documented in Licensee Event Report (LER) 400/2000-007-02, event date September 4, 2000. You did not provide comments on the preliminary ASP analysis. However, on April 22, 2003, during a telephone conversation, you informed the NRC staff that further analysis by the pump vendor determined that the pump was operable during the period in question. With the new information provided on the pump operability, the final ASP program position is to reject the operating condition as a potential precursor because the change in core damage probability is less than 10-6.
Please contact me at 301-415-3025 if you have any questions regarding the enclosure.
Sincerely,
/RA/
Chandu P. Patel, Project Manager, Section 2 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-400 cc: See next page Distribution:
PUBLIC PDII-2 Reading AHowe CPatel EDunnington OGC ACRS PFredrickson POReilly JGolla MHarper, RES Document Name: G:\\PDII-2\\Shearon Harris\\ASP09042000.wpd ADAMS ACCESSION NO. ML033250189 OFFICE PDII-2/PM PDII-2/LA PDII-2/SC NAME CPatel EDunnington AHowe DATE 11/19/2003 11/19/2003 11/20/2003 OFFICIAL RECORD COPY
Mr. James Scarola Shearon Harris Nuclear Power Plant Carolina Power & Light Company Unit 1 cc:
Steven R. Carr Associate General Counsel - Legal Department Progress Energy Service Company, LLC Post Office Box 1551 Raleigh, North Carolina 27602-1551 Resident Inspector/ Harris NPS c/o U. S. Nuclear Regulatory Commission 5421 Shearon Harris Road New Hill, North Carolina 27562-9998 Ms. Margaret A. Force Assistant Attorney General State of North Carolina Post Office Box 629 Raleigh, North Carolina 27602 Public Service Commission State of South Carolina Post Office Drawer 11649 Columbia, South Carolina 29211 Ms. Beverly Hall, Section Chief Division of Radiation Protection N.C. Department of Environment and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721 Mr. James W. Holt Manager Performance Evaluation and Regulatory Affairs PEB 7 Progress Energy Post Office Box 1551 Raleigh, North Carolina 27602-1551 Mr. Benjamin C. Waldrep Plant General Manager - Harris Plant Carolina Power & Light Company Shearon Harris Nuclear Power Plant P. O. Box 165, Mail Zone 3 New Hill, North Carolina 27562-0165 Mr. John H. ONeill, Jr.
Shaw, Pittman, Potts & Trowbridge 2300 N Street, NW.
Washington, DC 20037-1128 Mr. Robert J. Duncan II Director of Site Operations Carolina Power & Light Company Shearon Harris Nuclear Power Plant Post Office Box 165, Mail Zone 1 New Hill, North Carolina 27562-0165 Mr. Robert P. Gruber Executive Director Public Staff NCUC 4326 Mail Service Center Raleigh, North Carolina 27699-4326 Chairman of the North Carolina Utilities Commission Post Office Box 29510 Raleigh, North Carolina 27626-0510 Mr. Herb Council, Chair Board of County Commissioners of Wake County P. O. Box 550 Raleigh, North Carolina 27602 Mr. Tommy Emerson, Chair Board of County Commissioners of Chatham County P. O. Box 87 Pittsboro, North Carolina 27312 Mr. Terry C. Morton, Manager Support Services Carolina Power & Light Company Shearon Harris Nuclear Power Plant P. O. Box 165, Mail Zone 1 New Hill, North Carolina 27562-0165 Mr. John R. Caves, Supervisor Licensing/Regulatory Programs Carolina Power & Light Company Shearon Harris Nuclear Power Plant P. O. Box 165, Mail Zone 1 New Hill, NC 27562-0165