ML033010435
| ML033010435 | |
| Person / Time | |
|---|---|
| Site: | Surry, North Anna (DPR-032, DPR-037, NPF-004, NPF-007) |
| Issue date: | 10/28/2003 |
| From: | John Nakoski NRC/NRR/DLPM/LPD2 |
| To: | Christian D Virginia Electric & Power Co (VEPCO) |
| Monarque S, NRR/DLPM, 415-1544 | |
| References | |
| TAC MB8787, TAC MB8788, TAC MB8914, TAC MB9529 | |
| Download: ML033010435 (8) | |
Text
October 28, 2003 Mr. David A. Christian Sr. Vice President and Chief Nuclear Officer Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Blvd.
Glen Allen, Virginia 23060-6711
SUBJECT:
NORTH ANNA AND SURRY POWER STATIONS, UNITS 1 AND 2 - REQUEST TO USE SUBSEQUENT EDITION AND ADDENDA OF ASME SECTION XI FOR QUALIFICATION OF EXAMINATION PERSONNEL (TAC NOS. MB8787, MB8788, MB8914, AND MB9529)
Dear Mr. Christian:
By letter dated May 6, 2003, as supplemented by letter dated June 12, 2003, Virginia Electric and Power Company requested approval to use the 1998 Edition through the 2000 Addenda of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, subsection IWA-2300 (including references to the 1995 Edition of CP-189-1995, entitled ASNT Standard for Qualification and Certification of Nondestructive Testing Personnel), Appendices VI and VII of the ASME Code, and any rule modification and limitation, in order to establish examiner qualification requirements for the containment programs at North Anna Power Station, Units 1 and 2 (NAPS) and Surry Power Station, Units 1 and 2 (SPS).
Our evaluation and conclusion are contained in the enclosed Safety Evaluation. The Nuclear Regulatory Commission staff has concluded that your proposal to use the 1998 Edition through the 2000 Addenda of ASME Code,Section XI, subsection IWA-2300 (including references to the 1995 Edition of CP-189-1995), Appendices VI and VII of the ASME Code, and any rule modification and limitation, in order to establish examiner qualification requirements for the containment programs is approved pursuant to Title 10 of the Code of Federal Regulations Section 50.55a(g)(4)(iv) for the 1992 Edition and the 1992 Addenda of ASME Section XI containment programs at NAPS and SPS. This approval applies to the first interval IWE and second interval IWL inservice inspection intervals at NAPS and SPS.
TAC Nos. MB8787, MB8788, MB8914, and MB9529 will remain open and will be closed after disposition of your request to use the portions of a later ASME Code and Addenda associated with the qualification of nondestructive examination personnel for ASME Code Class 1, 2, and 3 components.
Sincerely,
/RA/
John A. Nakoski, Chief, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-280, 50-281, 50-338, and 50-339
Enclosure:
As stated cc w/encl: See next page TAC Nos. MB8787, MB8788, MB8914, and MB9529 will remain open and will be closed after disposition of your request to use the portions of a later ASME Code and Addenda associated with the qualification of nondestructive examination personnel for ASME Code Class 1, 2, and 3 components.
Sincerely,
/RA/
John A. Nakoski, Chief, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-280, 50-281, 50-338, and 50-339
Enclosure:
As stated cc w/encl: See next page Distribution PUBLIC CGratton EDunnington (paper copy)
RidsNrrDlpmLpdii GHill (2)
SMonarque RidsOgcRp ACRS RidsRgn2MailCenter PDII-1 R/F DTerao ADAMS ACCESSION NO. ML033010435
- See previous concurrence OFFICE PM:PDII/S1 PM:PDII/S1 LA:PDII/S2 SC/EMEB*
OGC*
SC/PDII-1 NAME CGratton SMonarque EDunnington DTerao SUttal JNakoski DATE 10/21/03 10/20/03 10/2103 9/16/03 9 /28/03 10/24/03 OFFICIAL RECORD COPY
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION UPDATED REFERENCED ASME CODE EDITION AND ADDENDA CONTAINMENT PROGRAMS SURRY POWER STATION, UNITS 1 AND 2 NORTH ANNA POWER STATION, UNITS 1 AND 2 VIRGINIA ELECTRIC AND POWER COMPANY DOCKET NOS. 50-280, 50-281, 50-338, AND 50-339
1.0 INTRODUCTION
By letter dated May 6, 2003, as supplemented by letter dated June 12, 2003, Virginia Electric and Power Company (the licensee) requested approval to use the 1998 Edition through the 2000 Addenda (98-2000) of American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code (Code),Section XI, subsection IWA-2300 (including references to the 1995 Edition of CP-189-1995, entitled ASNT Standard for Qualification and Certification of Nondestructive Testing Personnel), Appendices VI and VII of the ASME Code, and any rule modification and limitation, in order to establish examiner qualification requirements for the inservice inspection (ISI) interval and containment programs at North Anna Power Stations, Units 1 and 2 (NAPS) and Surry Power Stations, Units 1 and 2 (SPS). NAPS and SPS are currently on the first interval IWE and second interval IWL ISI intervals.
The U.S. Nuclear Regulatory Commission (NRC) staff is currently reviewing the licensees request for the ISI programs at NAPS and SPS; as such, this safety evaluation will only address the licensees request for the containment programs. The NRC staff will provide its evaluation of the ISI programs under separate correspondence.
2.0 REGULATORY EVALUATION
In the Federal Register dated August 8, 1996, the Commission amended Title 10 of the Code of Federal Regulations (10 CFR) Section 50.55a to incorporate by reference the 1992 Edition through the 1992 Addenda of the ASME Code,Section XI, Subsections IWE and IWL.
Subsection IWE provides the requirements for ISI of Class MC (metallic containment components) and the metallic liner of Class CC (concrete containment programs). Subsection IWL provides the requirements for ISI of Class CC components. The Code of record for NAPS and SPS is the 1992 Edition with the 1992 Addenda.
Enclosure
3.0 TECHNICAL EVALUATION
By letter dated May 6, 2003, as supplemented by letter dated June 12, 2003, the licensee requested that the NRC approve the use of a portion of a more recent edition and addenda of the ASME Code,Section XI. Specifically, the licensee requested approval to use the 98-2000 ASME Code,Section XI, subsection IWA-2300, including references to the 1995 Edition of CP-189-1995, Appendices VI and VII of the ASME Code, and any rule modification and limitation in order to establish the ISI examiner qualification requirements for the containment programs at NAPS and SPS. Subsection IWA-2300 is used to establish the qualification requirements for nondestructive examination personnel. However, the licensee proposed to maintain the VT-1, VT-2, and VT-3 examination requirements, not the General Visual and Detailed Visual requirements for IWE specified in the 98-2000 ASME Code, so that common examiner qualification requirements could be used to aid in resource flexibility and examiner qualification tracking.
10 CFR 50.55a(g)(4)(iv) states that inservice examination of components and system pressure tests may meet the requirements set forth in subsequent editions and addenda that are incorporated by reference in 10 CFR 50.55a(b), subject to the limitations and modifications listed therein, and subject to NRC staff approval. Furthermore, 10 CFR 50.55a(g)(4)(iv) states that portions of editions or addenda may be used provided that all related requirements of the respective editions and addenda are met. The requirements contained in the 98-2000 ASME Code,Section XI were incorporated by reference in 10 CFR 50.55a(b) on September 26, 2002 (67 FR 60520). The specific limitations and modifications placed on subsection IWA-2300 are described in 10 CFR 50.55a(b)(2)(xviii) and must be followed by the licensee.
The licensees use of VT-1, VT-2, and VT-3 examination requirements, in lieu of the General Visual and Detailed Visual requirements for IWE as specified in the 98-2000 ASME Code, is acceptable because these examination requirements are part of the current Code of record.
During the transition to the next ISI program interval pursuant to 10 CFR 50.55a(g)(4)(ii), it is anticipated that the 98-2000 ASME Code,Section XI will be adopted as the basis for the ISI program. In order to continue using the VT-1, VT-2, and VT-3 examination requirements in lieu of the General Visual and Detailed Visual requirements that are specified in the 98-2000 ASME Code, the licensee will again be required to submit the aforementioned alternate examination requirements for NRC staff approval pursuant to 10 CFR 50.55a(a)(3).
4.0 CONCLUSION
Based upon the incorporation by reference of the 98-2000 ASME Code and the licensee meeting all related requirements including applicable limitations of and modifications to IWA-2300, the licensees request to use the 98-2000 ASME Code,Section XI, subsection IWA-2300 (including references to the 1995 Edition of CP-189-1995), Appendices VI and VII of the ASME Code, and any rule modification and limitation, in order to establish examiner qualification requirements for the containment programs at SPS and NAPS is approved pursuant to 10 CFR 50.55a(g)(4)(iv). This approval applies to the first interval IWE and second interval IWL ISI intervals at NAPS and SPS.
Principal Contributor: G. Klein, EMEB Date: October 28, 2003
Mr. David A. Christian Virginia Electric and Power Company cc:
Ms. Lillian M. Cuoco, Esq.
Senior Counsel Dominion Resources Services, Inc.
Millstone Power Station Building 475, 5th Floor Rope Ferry Road Rt. 156 Waterford, Connecticut 06385 Mr. Richard H. Blount, II Site Vice President Surry Power Station Virginia Electric and Power Company 5570 Hog Island Road Surry, Virginia 23883-0315 Senior Resident Inspector Surry Power Station U. S. Nuclear Regulatory Commission 5850 Hog Island Road Surry, Virginia 23883 Chairman Board of Supervisors of Surry County Surry County Courthouse Surry, Virginia 23683 Dr. W. T. Lough Virginia State Corporation Commission Division of Energy Regulation P. O. Box 1197 Richmond, Virginia 23218 Robert B. Strobe, M.D., M.P.H.
State Health Commissioner Office of the Commissioner Virginia Department of Health P.O. Box 2448 Richmond, Virginia 23218 North Anna and Surry Office of the Attorney General Commonwealth of Virginia 900 East Main Street Richmond, Virginia 23219 Mr. Chris L. Funderburk, Director Nuclear Licensing & Operations Support Innsbrook Technical Center Virginia Electric and Power Company 5000 Dominion Blvd.
Glen Allen, Virginia 23060-6711 Mr. David A. Heacock Site Vice President North Anna Power Station Virginia Electric and Power Company P. O. Box 402 Mineral, Virginia 23117-0402 Mr. C. Lee Lintecum County Administrator Louisa County P.O. Box 160 Louisa, Virginia 23093 Old Dominion Electric Cooperative 4201 Dominion Blvd.
Glen Allen, Virginia 23060 Senior Resident Inspector North Anna Power Station U.S. Nuclear Regulatory Commission 1024 Haley Drive Mineral, Virginia 23117 Mr. William R. Matthews Vice President - Nuclear Operations Virginia Electric and Power Company Innsbrook Technical Center 5000 Dominion Boulevard Glen Allen, Virginia 23060-6711