MR-4-2003-0012 Nebraska Public Power District, Cooper, Fire on 345 Kv Tower (Event 40281)
ML033010371
Person / Time
Site: Cooper 
(DPR-046)
Issue date: 10/28/2003
From:
NRC Region 4
To:
References
MR-4-2003-0012
Download: ML033010371 (1)


Text

PRIORITY ATTENTION REQUIRED MORNING REPORT -

REGION IV October 28, 2003 050-00298 Licensee/Facility:

Dockets:

[1] GE-4 Notification:

MR Number: 4-2003-0012 Date:

10/28/2003 Call from Resident Inspector License No:

Columbus, Nebraska Cooper NEBRASKA PUBLIC POWER DISTRICT

Subject:

Fire on 345 kV Tower (Event 40281)

Discussion:

On October 28, 2003, the Cooper Nuclear Station was operating at approximately 100 percent power. At 1:30 a.m.

(CST) the licensee observed a small fire on the cross-arm of a wood tower supporting the transmission lines from the main power transformer to the 345 kV switchyard. At 1:47 a.m. the operating crew entered the emergency shutdown procedure and power was rapidly lowered to 75 percent. At 2 a.m. a manual SCRAM of the reactor was initiated when operators observed a portion of the cross-member fall from the tower. All control rods inserted as expected in response to the original SCRAM. At 3:17 a.m. the Auburn Fire Department responded to the site and contained the fire on the ground until the fire was out. The plant is currently stable and a cooldown has been initiated. Offsite power sources to the plant were not affected by the fire. At the time of the event, one of the onsite emergency diesel generators was out of service for preplanned maintenance.

REGIONAL ACTION:

The Senior Resident Inspector responded to the site and monitored the licensee's response to the event. Followup inspection will be performed to review the licensee's root cause evaluation, corrective actions, and response to the event.