A, Xs DC Sources -Shutdown 3.8.5 3.8 ELECTRICAL POWER SYSTEMS 3.8.5 DC Sources-Shutdown LCO 3.8.5 APPLICABILITY:
The Train A or Train B DC electrical power subsystem shall be OPERABLE to support one train of the DC electrical power distribution subsystems required by LCO 3.8.10, "Distribution Systems-Shutdown."
MODES 5 and 6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. Required DC electrical A.1 Declare affected required Immediately power subsystems feature(s) Inoperable.
OR A.2.1 Suspend CORE Immediately ALTERATIONS.
AND A.2.2 Suspend movement of Immediately irradiated fuel assemblies.
AND A.2.3 Suspend operations Immediately involving positive reactivity additions that could result in loss of required SDM or boron concentration.
AND (continued)
COMANCHE PEAK - UNITS I AND 2 3.8-28 Amendment No. 105
0 Inverters-Shutdown 3.8.8 3.8 ELECTRICAL POWER SYSTEMS 3.8.8 Inverters -Shutdown LCO 3.8.8 APPLICABILITY:
The Train A or Train B inverters shall be OPERABLE to support one train of the onsite Class 1 E AC vital bus electrical power distribution subsystems required by LCO 3.8.10, *Distribution Systems -Shutdown."
MODES 5 and 6 ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A. One or more required A.1 Declare affected required Immediately inverters inoperable.
feature(s) Inoperable.
OR A.2.1 Suspend CORE Immediately ALTERATIONS.
AND A.2.2 Suspend movement of Immediately irradiated fuel assemblies.
AND A.2.3 Suspend operations Immediately involving positive reactivity additions that could result in loss of required SDM or boron concentration.
AND (continued)
COMANCHE PEAK - UNITS I AND 2 3.8-36 Amendment No. 105