June 5, 2003 Mr. Clay C. Warren Vice President of Nuclear Energy Nebraska Public Power District P.O. Box 98 Brownville, NE 68321
SUBJECT:
COOPER NUCLEAR STATION - ISSUANCE OF AMENDMENT RE: FIRE PROTECTION (TAC NO. MB5794)
Dear Mr. Warren:
The U. S. Nuclear Regulatory Commission (the Commission) has issued the enclosed Amendment No. 199 to Facility Operating License (FOL) No. DPR-46 for the Cooper Nuclear Station. The amendment consists of changes to the FOL in response to your application dated July 10, 2002, as supplemented by letter dated April 16, 2003.
The amendment replaces the fire protection requirements contained in FOL Section 2.C.(4) with the standard fire protection FOL condition recommended by Generic Letter 86-10, Section F, adapted to the Cooper Nuclear Station.
A copy of our related Safety Evaluation is also enclosed. The Notice of Issuance will be included in the Commissions next biweekly Federal Register notice.
Sincerely,
/RA/
Mohan C. Thadani, Senior Project Manager, Section 1 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-298
Enclosures:
- 1. Amendment No. 199 to DPR-46
- 2. Safety Evaluation cc w/encls: See next page
- NLO w/Changes & Comments NRR-058 OFFICE PDIV-1P/M PDIV-1/PM PDIV-1/LA SPLB/SC OGC PDIV-1/SC NAME DJaffe:sab MThadani MMcAllister EWeiss SHom*
RGramm DATE 4/28/03 6/03/03 4/28/03 5/12/03 6/03/03 6/04/04
NEBRASKA PUBLIC POWER DISTRICT DOCKET NO. 50-298 COOPER NUCLEAR STATION AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 199 License No. DPR-46 1.
The U. S. Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Nebraska Public Power District (the licensee) dated July 10, 2002, as supplemented by letter dated April 16, 2003, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commissions rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commissions regulations; D.
The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commissions regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to Paragraph 2.C.(4) of Facility Operating License No. DPR-46 as indicated in the attachment to this license amendment.
3.
The license amendment is effective as of its date of issuance and shall be implemented within 60 days from the date of issuance.
FOR THE NUCLEAR REGULATORY COMMISSION
/RA/
Robert A. Gramm, Chief, Section 1 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation
Attachment:
Changes to the Facility Operating License Date of Issuance: June 5, 2003
ATTACHMENT TO LICENSE AMENDMENT NO. 199 FACILITY OPERATING LICENSE NO. DPR-46 DOCKET NO. 50-298 Replace the following page of the Facility Operating License No. DPR-46 with the enclosed revised page.
REMOVE INSERT 4
4
Amendment No. 190, 196, 199 2.C.(4) Fire Protection The licensee shall implement and maintain in effect all provisions of the approved fire protection program as described in the Cooper Nuclear Station (CNS) Updated Safety Analysis Report and as approved in the Safety Evaluations dated November 29, 1977; May 23, 1979; November 21, 1980; April 29, 1983; April 16, 1984; June 1, 1984; January 3, 1985; August 21, 1985; April 10, 1986; September 9, 1986; November 7, 1988; February 3, 1989; August 15, 1995; and July 31, 1998, subject to the following provision:
The licensee may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
C(5)
Additional Conditions The Additional Conditions contained in Appendix C, as revised through Amendment No. 178, are hereby incorporated into this license. Nebraska Public Power District shall operate the facility in accordance with the Additional Conditions.
C(6)
Upon receiving NRC approval of the licensees seismic evaluation of the main steam isolation valve leakage pathway to the main turbine condenser, the main turbine condenser, and the turbine building, the licensee shall fully implement the approved request, including the associated modifications, prior to restart from refueling outage
- 22. Until implementation is completed, potassium iodide will continue to be made available to Control Room personnel during a loss-of-coolant accident with core damage.
D (Not used)
SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 199 TO FACILITY OPERATING LICENSE NO. DPR-46 NEBRASKA PUBLIC POWER DISTRICT COOPER NUCLEAR STATION DOCKET NO. 50-298
1.0 INTRODUCTION
By application to the U. S. Nuclear Regulatory Commission (the Commission, NRC) dated July 10, 2002, as supplemented by letter dated April 16, 2003, Nebraska Public Power District (the licensee), requested an amendment to Facility Operating License (FOL) No. DPR-46 for Cooper Nuclear Station (CNS). The supplement dated April 16, 2003, provided additional information that clarified the application, did not expand the scope of the application as originally noticed, and did not change the staffs original proposed no significant hazards consideration determination as published in the Federal Register on January 7, 2003 (68 FR 808).
The proposed changes would replace the fire protection (FP) requirements contained in FOL No. DPR-46, Section 2.C.(4). Specifically, the proposed changes would delete the current condition which calls for completion of certain FP modifications with the standard FP condition recommended by Generic Letter (GL) 86-10, Implementation of Fire Protection Requirements, Section F, adapted to CNS.
2.0 REGULATORY EVALUATION
The staff finds that the licensee in Section 4.0 of its July 10, 2002, submittal identified the applicable regulatory requirements. The regulatory requirements for which the NRC staff based its acceptance are contained in Title 10, Code of Federal Regulations (10 CFR) Part 50, Section 50.48, Fire protection and Appendix R to Part 50, Fire Protection Program for Nuclear Power Facilities Operating Prior to January 1, 1979. As stated in GL 86-10, This package represents recent staff assessment...and provides guidance as to acceptable methods of satisfying Commission regulatory requirements.
3.0 TECHNICAL EVALUATION
The staff has reviewed the licensee's regulatory and technical analyses in support of its proposed license amendment which are described in Sections 4.0 and 6.0 of the licensee's July 10, 2002, submittal. The detailed evaluation below supports the conclusion that: (1) there 1 Cooper - Operating License DPR-46 Amendment 56 supported by FPSER issued May 23, 1979 Amendment 66 supported by Supplement 1 to FPSER issued November 21, 1980 is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commissions regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
3.1 Current License Condition Concerning Fire Protection The current license condition concerning fire protection for CNS is contained in FOL No. DPR-46, Section 2.C.(4) which states:
The licensee may proceed with and is required to complete the modifications identified in Paragraphs 3.1 through 3.37 of the NRCs Fire Protection Safety Evaluation (SE),
dated May 23, 1979, for the facility. These modifications will be completed prior to July 1, 1980.
In addition, the licensee shall submit the additional information in Table 3.1 of this SE in accordance with the schedule contained therein. In the event these dates for submittal cannot be met, the licensee shall submit a report, explaining the circumstances, together with a revised schedule.
The licensee is required to implement the administrative controls identified in Section 6 of the SE. The administrative controls shall be in effect by November 1, 1979.
With regard to the above-described modifications, the May 4, 1982, Exemption issued to CNS, concerning fire protection, states:
The FPSER [Fire Protection Safety Evaluation Report] and its supplement supported issuance of amendments to the operating licensee [license] of Cooper Nuclear Station1 which required modifications to be made to plant physical features, systems, and administrative controls to meet the criteria of Appendix A to BTP [Branch Technical Position] 9.5-1. All of these modifications have been completed.
Since the subject modifications have been completed, the U.S. Nuclear Regulatory Commission (NRC) staff concludes that FOL No. DPR-46, Section 2.C.(4) should be replaced as requested by the licensee.
3.2 Proposed License Condition Concerning Fire Protection Section F of GL 86-10 contains a sample license condition for use by licensees in proposing an amendment to the operating license to amend any current license conditions and substitute a standard condition. The standard condition (1) requires the licensee to implement and maintain in effect an approved fire protection program as described in the Final Safety Analysis Report, (2) provides a list of references for the FPSER and supplements, and (3) provides a system of making changes to the approved fire protection program. In the licensees supplement dated April 16, 2003, the licensee submitted a proposed license condition to replace FOL No. DPR-46, Section 2.C.(4). The proposed license condition, based upon the guidance contained in GL 86-10, Section F, states the following:
The licensee shall implement and maintain in effect all provisions of the approved fire protection program as described in the Cooper Nuclear Station (CNS) Updated Safety Analysis Report and as approved in the Safety Evaluations dated November 29, 1977; May 23, 1979; November 21, 1980; April 29, 1983; April 16, 1984; June 1, 1984; January 3, 1985; August 21, 1985; April 10, 1986; September 9, 1986; November 7, 1988; February 3, 1989; August 15, 1995; and July 31, 1998, subject to the following provision:
The licensee may make changes to the approved fire protection program without prior approval of the Commission only if those changes would not adversely affect the ability to achieve and maintain safe shutdown in the event of a fire.
The NRC staff has reviewed the licensees proposed license condition and concludes that it conforms to the guidance contained in GL 86-10, Section F, and is acceptable.
4.0 STATE CONSULTATION
In accordance with the Commission's regulations, the Nebraska State official was notified of the proposed issuance of the amendment. The State official had no comments.
5.0 ENVIRONMENTAL CONSIDERATION
The amendment changes a requirement with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20. The NRC staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration, and there has been no public comment on such finding (68 FR 808 dated January 7, 2003). Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendments.
6.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendments will not be inimical to the common defense and security or to the health and safety of the public.
Principal Contributor: D. H. Jaffe Date: June 5, 2003
January 2003 Cooper Nuclear Station cc:
Mr. William J. Fehrman President and Chief Executive Officer Nebraska Public Power District 1414 15th Street Columbus, NE 68601 Mr. Michael T. Coyle Site Vice President Nebraska Public Power District P. O. Box 98 Brownville, NE 68321 Mr. John R. McPhail, General Counsel Nebraska Public Power District P. O. Box 499 Columbus, NE 68602-0499 Mr. Paul V. Fleming, Licensing Manager Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 Mr. Michael J. Linder, Director Nebraska Department of Environmental Quality P. O. Box 98922 Lincoln, NE 68509-8922 Chairman Nemaha County Board of Commissioners Nemaha County Courthouse 1824 N Street Auburn, NE 68305 Ms. Cheryl K. Rogers, Program Manager Nebraska Health & Human Services System Division of Public Health Assurance Consumer Services Section 301 Centennial Mall, South P. O. Box 95007 Lincoln, NE 68509-5007 Mr. Ronald A. Kucera, Director of Intergovernmental Cooperation Department of Natural Resources P.O. Box 176 Jefferson City, MO 65102 Senior Resident Inspector U.S. Nuclear Regulatory Commission P. O. Box 218 Brownville, NE 68321 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, TX 76011 Jerry Uhlmann, Director State Emergency Management Agency P. O. Box 116 Jefferson City, MO 65101 Chief, Radiation Control Program, RCP Kansas Department of Health and Environment Bureau of Air and Radiation 1000 SW Jackson Suite 310 Topeka, KS 66612-1366 Mr. Daniel K. McGhee Bureau of Radiological Health Iowa Department of Public Health 401 SW 7th Street Suite D Des Moines, IA 50309 Mr. Scott Clardy, Director Section for Environmental Public Health P.O. Box 570 Jefferson City, MO 65102-0570