Nuclear Operating Company South Tas Pof/cCttCtr/c GueratinS aa BOx8 29 fds ortfth Teas 7783 May 15, 2003 NOC-AE-03001533 1 OCFR50.55a U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 South Texas Project Units 1 and 2 Docket Nos. STN 50-498 and STN 50-499 Request for Approval of ASME Section IX Code Cases 2142-1 and 2143-1 for the Second Ten-Year Inspection Interval (Relief Request RR-ENG-2-31)

Pursuant to 10CFR50.55a(a)(3)(i), STP Nuclear Operating Company (STPNOC) hereby requests NRC approval of ASME Section IX Code Cases 2142-1 and 2143-1 for use during the second ten-year inspection interval at the South Texas Project. These Code Cases were previously approved for use on the replacement steam generators at the South Texas Project. The details of the 1 OCFR50.55a request are attached.

STPNOC requests approval on an expedited basis by June 9, 2003, based on the schedule for repairing bottom mounted instrument nozzles in the Unit 1 reactor pressure vessel during the current forced outage.

If there are any questions regarding this request, please contact Michael S. Lashley at (361) 972-7523 orme at (361) 972-7902.

Jordan Vice President Engineering & Technical Services jtc

Attachment:

10CFR50.55a ReliefRequest RR-ENG-2-31 STI: 31607502

NOC-AE-03001533 Page 2 of 2 cc:

(paper copy)

(electronic copy)

Ellis W. Merschoff Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, Texas 76011-8064 U. S. Nuclear Regulatory Commission Attention: Document Control Desk One White Flint North 11555 Rockville Pike Rockville, MD 20852 Richard A. Ratliff Bureau of Radiation Control Texas Department of Health 1100 West 49th Street Austin, TX 78756-3189 Cornelius F. O'Keefe U. S. Nuclear Regulatory Commission P. 0. Box 289, Mail Code: MN1 16 Wadsworth, TX 77483 A. H. Gutterman, Esquire Morgan, Lewis & Bockius LLP L. D. Blaylock City Public Service Mohan C. Thadani U. S. Nuclear Regulatory Commission R. L. Balcom Texas Genco, LP A. Ramirez City of Austin C. A. Johnson AEP Texas Central Company Jon C. Wood Matthews & Branscomb C. M. Canady City of Austin Electric Utility Department 721 Barton Springs Road Austin, TX 78704

NOC-AE-03001533 Attachment Pagel of2 10CFR50.55a Relief Request RR-ENG-2-31 Proposed Alternative in Accordance with 10 CFR 50.55a(a)(3)(i)

-- Alternative Provides Acceptable Level of Quality and Safety--

1.

ASME Code Components Affected Components, component supports, or other items fabricated from Alloy 690 material and requiring the use of UNS N06052 filler metal or UNS W86152 electrodes for welding operations.

2.

Applicable Code Edition and Addenda

American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,Section XI, 1989 Edition with no Addenda.

3.

Applicable Code Requirement

IWA-4000 of the South Texas Project (STP)Section XI Code of record requires that repair welds and installation welds for replacement items meet the requirements of the original construction codes, or later approved code, including materials requirements.

The ASME Section III codes applied to the original construction and the corresponding Section II material codes for most STP components do not address the welding materials specified in Code Cases 2142-1 and 2143-1.

4.

Reason for the Request STP Nuclear Operating Company (STPNOC) requests relief to employ the alternative welding materials of ASME Section IX Code Cases 2142-1 and 2143-1 as necessary during the second ten-year inservice inspection interval of South Texas Project Units 1 and 2. The immediate need for these Code Cases is for repairing the bottom mounted instrument nozzles in the Unit 1 reactor vessel.

5.

Proposed Alternative and Basis for Use Industry studies have demonstrated that Alloy 690 weld materials possess a high resistance to primary water corrosion. The use of Alloy 690 weld materials has been previously approved for other applications at several operating nuclear power plants (refer to Section 7 below.)

NOC-AE-03001533 Attachment Page 2 of 2 Code Cases 2142-1 and 2143-1 introduce and classify nickel-based weld materials that closely match and are intended for welding Alloy 690. Code Case 2142-1 establishes welding classifications and other requirements for bare filler metal. Code Case 2143-1 establishes welding classifications and other requirements for coated electrodes. The Code Cases were approved by ASME on June 5, 1995, and published in the 1995 Edition of the ASME Boiler and Pressure Vessel Code, Code Cases Supplement No. 1.

Code Case 2142-1 lists the American Welding Society (AWS) specification A5.14 and Universal Numbering System (UNS) designation N06052 for a filler metal conforming to Inco 52 (Inconel 52). It establishes this weld metal as F-No. 43 for both procedure and perfornance qualification purposes. Code Case 2143-1 lists appropriate AWS specification A5.11 and UNS specification W86152 for a coated electrode conforming to Inco 152 (Inconel 152) and establishes F-No. 43 for this material for welding purposes.

By this set of specifications and F-No. assignments, the materials are completely described for welding purposes as similar in their welding characteristics to many other Code nickel-based weld metals. These materials are similar in composition and mechanical and thermal properties to approved metals; thus, existing welding procedures may be used with the Inco 52 or 152 (Inconel 52/152) type weld metals.

STPNOC has determined that the proposed alternative to employ the alternative welding materials of Code Cases 2142-1 and 2143-1 provides an acceptable level of quality and safety.

6.

Duration of Proposed Alternative This relief request will be implemented during the second ten-year inservice inspection interval of South Texas Project Units 1 and 2.

7.

Precedents Catawba Nuclear Station Unit 2 Three Mile Island Nuclear Station Unit I Docket No. 50-414 Docket No. 50-289 TAC No. MB3003 TAC No. MB2323 January 18, 2002 November 7, 2001 Oconee Nuclear Station Units 1 & 3 Oconee Nuclear Station Unit 2 Docket Nos. 50-269 and 50-287 Docket No. 50-270 TAC No. MB2681 and MB2682 TAC No. MB1918 September 6, 2001 May 23, 2001 South Texas Project Units I & 2 Docket Nos. 50-498 and 50-499 TAC Nos. MA2250 and MA2251 December 15, 1998