SFPEVS 3.7.11 3.7 PLANT SYSTEMS 3.7.11 Spent Fuel Pool Exhaust Ventilation System (SFPEVS)

LCO 3.7.11 APPLICABILITY:

The SFPEVS shall be OPERABLE and in operation.

During movement of recently irradiated fuel assemblies in the I Auxiliary Building.

ACTIONS CONDITION REQUIRED ACTION COMPLETION TIME A.

One SFPEVS charcoal A.1 Verify OPERABLE SFPEVS Immediately adsorber bank train is in operation.

inoperable.

OR OR A.2 Suspend movement of Immediately One SFPEVS exhaust recently irradiated fan inoperable.

fuel assemblies in the Auxiliary Building.

OR One SFPEVS charcoal adsorber bank and one SFPEVS exhaust fan inoperable.

B. No OPERABLE SFPEVS B.1 Suspend movement of Immediately train.

recently irradiated fuel assemblies in the OR Auxiliary Building.

No OPERABLE SFPEVS train in operation.

Il CALVERT CLIFFS - UNIT 1 CALVERT CLIFFS - UNIT 2 3.7.11-1 Amendment No.

Amendment No.

257 234